PLC Connection Guide - Cermate

Transcription

Technical DocumentRevision 1.0March, 2009PLC Connection GuideTN512DCommunication settings betweenSiemens S7-200 PPI and PanelMaster HMI Revision RecordRevisionDateContentOwnerwww.cermate.com

TND512-E0PrefaceThis tech note introduces how to connect Siemens S7-200 PPI Port with PanelMasterHMI. S7-200 CPU PPI Port (Port0 & Port1)(1) PLC Parameter setting:Execute the “STEP 7 MicroWIN” software to link with the S7-200 PLC via PPI Adapter program cable.Page 2 of 9www.cermate.com

TND512-E0Create a new project and select the CPU to set its communication format from “System Block”.NOTE: The standard format is 9600, 8, Even, 1 and the PLC Address is “2”Execute “Set PG/PC Interafce” --- “PC/PPI cable(PPI)” option to select the correct communication porton PC side.Page 3 of 9www.cermate.com

TND512-E0Execute “Communication” option, it can find out the PLC automatically.Page 4 of 9www.cermate.com

TND512-E0If the communication port is correct, you can execute the download/upload function to change the “PLCAddress”/”Baud Rate” etc.Connection Cable diagramHMI SidePLC Cable SideCOM1 9-PIN MalePPI Port 9-PIN Male (RS485)485 13485 485 -68485-SG55SGHMI SidePLC Cable SideCOM2 T.B. 5-PINPPI Port 9-PIN Male (RS485)485 TX 13485 485 TX-48485-SG55SGPage 5 of 9www.cermate.com

TND512-E0(1)HMI setting:(a) S7-200 (PPI; 1-to-1) Setting: (Without Token Command)Select【Device/Server:Siemens AG Simatic S7-200 (PPI; 1-to-1)】NOTE: Driver Name --- C39001.dll / C39001.modSet the HMI link port parameter identical with PLC communication parameterPage 6 of 9www.cermate.com

TND512-E0(b) S7-200 (PPI; Network) Setting: (With Token Command)Select 【Device/Server: Siemens AG Simatic S7-200 (PPI; Network)】NOTE: Driver Name --- C39011.dll / C39011.modSet the HMI link port parameter identical with PLC communication parameterNote: The network driver is using token command to link with PLC and HMI, it can be usedto link with different devices that support PPI Network protocol.Page 7 of 9www.cermate.com

TND512-E0(3) PLC Memory AddressBit Devices (PPI; 1-to-1 & Network)Word Devices (PPI; 1-to-1 & Network)NOTE: Device named DBWn specified same as VWn. Thank You Page 8 of 9www.cermate.com

TND512-E0Technical Support Information中國大陸 QQ 專線 : 800014850www.panelmaster.com.cn / www.cermate.com資料下載專區 ftp:://mail.cermate.com User name Password 線: China: 0910011916 / 86-13823788405 sunny@cermate.comTaiwan: 886-910011915Kevin@cermate.comWorldwide: 886-910011914Linda@cermate.comCermate Technologies (Shanghai) Inc. 屏通科技(上海)有限公司Phone: 86-21-51758590 2FAX : 86-21-51758589E-mail: service01.sh@cermate.comShenzhen Cermate Technologies Inc. 屏通科技(深圳)有限公司Phone: 86-755-83562179,FAX : 86-755-83562294E-mail: sa-cermate@cermate.comCermate Technologies Inc. (台湾) 屏通科技股份有限公司7F-1, No. 168, Lien-Cheng Road, Chung-Ho City, Taipei, Taiwan 235 R.O.C.Phone: 886-2-22437000FAX : 886-2-22499933E-mail: service@cermate.comPage 9 of 9www.cermate.com

Execute the "STEP 7 MicroWIN" software to link with the S7-200 PLC via PPI Adapter program cable. PPI Port (Port0 & Port1) TND512-E0 Page 3 of 9 www.cermate.com Create a new project and select the CPU to set its communication format from "System Block".