University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302Table of ContentsSECTION I: FACILITY INFORMATION . 4SECTION II: INTRODUCTION . 5Summary of Permit Activity . 5Process Description . 5Regulations . 6Emission Summary . 6SECTION III: PERMIT HISTORY . 17SECTION IV: SPECIFIC CONDITIONS . 18SN- 01 through SN-05 . 18SN- 10A, SN-10B and SN-10C . 23SN-12 through SN-33 . 25SN-34 through SN-39, SN-54 and SN-55. 32SN-40, SN-43 through SN-47, SN-52 and SN-56 . 41SN-57 . 43SECTION V: COMPLIANCE PLAN AND SCHEDULE . 53SECTION VI: PLANTWIDE CONDITIONS . 54SECTION VII: INSIGNIFICANT ACTIVITIES. 55SECTION VIII: GENERAL PROVISIONS . 58APPENDIX A . 64NSPS, 40 CFR Part 60, Subpart Dc - Standards of Performance for Small Industrial Commercial - Institutional Steam Generating Units . 64APPENDIX B . 88NSPS, 40 CFR Part 60, Subpart IIII - Standards of Performance for Stationary CompressionIgnition Internal Combustion Engines . 88APPENDIX C . 124APPENDIX D . 312NESHAP, 40 CFR Part 63, Subpart ZZZZ—National Emissions Standards for Hazardous AirPollutants for Stationary Reciprocating Internal Combustion Engines . 312APPENDIX E . 396NSPS, 40 CFR Part 60, Subpart JJJJ— Standards of Performance for Stationary SparkIgnition Internal Combustion Engines . 3962

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302List of Acronyms and AbbreviationsA.C.A.Arkansas Code AnnotatedAFINADEQ Facility Identification NumberCFRCode of Federal RegulationsCOCarbon MonoxideHAPHazardous Air Pollutantlb/hrPound Per HourMVACMotor Vehicle Air ConditionerNo.NumberNOxNitrogen OxidePMParticulate MatterPM10Particulate Matter Smaller Than Ten MicronsSNAPSignificant New Alternatives Program (SNAP)SO2Sulfur DioxideSSMStartup, Shutdown, and Malfunction PlanTpyTons Per YearUTMUniversal Transverse MercatorVOCVolatile Organic Compound3

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302SECTION I: FACILITY INFORMATIONPERMITTEE:University of Arkansas for Medical Sciences (UAMS)AFIN:60 00302PERMIT NUMBER:2125-AOP-R3FACILITY ADDRESS:4301 West Markham St.Little Rock, AR 72205MAILING ADDRESS:4301 West Markham Street - Mail Slot 617Little Rock, AR 72205-7199COUNTY:Pulaski CountyCONTACT NAME:John RyalsCONTACT POSITION:Chemical Hygiene Officer, Fire & Life Safety OfficerTELEPHONE NUMBER:(501) 686-5299REVIEWING ENGINEER: Christopher RileyUTM North South (Y):Zone 15: 3845464.29 mUTM East West (X):Zone 15: 562077.55 m4

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302SECTION II: INTRODUCTIONSummary of Permit ActivityThe University of Arkansas for Medical Sciences (UAMS) operates a General Medical andSurgical Hospital (NAICS 62211 and 622110) in Little Rock, Arkansas. The purpose of thismodification is to: Replace SN-03 (MCEP boiler #3) with a 700 bhp boiler (down from 750 bhp currently)Remove SN-26, a 2C Diesel Generator, from the permitThe emissions will change as follows: PM -0.4 tpy, PM10 -0.4 tpy, NOX -0.4 tpy, SO2 0.1 tpy, CO -0.1 tpy, VOC -0.1 tpy , benzene -0.02 tpy, formaldehyde -0.01 tpy, POM 0.01 tpy, and hexane -0.06 tpy.Process DescriptionThe facility operates four (4) 31.5 million Btu per hour (MMBtu/hr) boilers (SN-01, SN-02, SN04 and SN-05) and one (1) 29.4 MMBtu/hr boiler (SN-03) for steam production. The boilers usenatural gas as their primary fuel and are capable of using fuel oil as a backup. The facility alsooperates two (2) 4.2 MMBtu/hr boilers (SN-06 and SN-07), which burn only natural gas and areused in the Center on Aging building for steam production, and two (2) 0.2 MMBtu/hr boilers(SN-08 and SN-09), which burn only natural gas and are used in the J.T. Stephens building forhot water production. The facility plans to install two (2) new 25.2 million Btu per hour boilers(SN-10A, SN-10B and SN-10C) in their proposed power plant for steam production. These newboilers will burn natural gas only.UAMS currently has thirty (30) diesel generators, SN-12 through SN-39 (SN-26-27 removed),SN-54, SN-55 and SN-57 on site for the production of back-up electricity. These generators willprovide back-up electricity and may also be used during peak demand times for electricitygeneration. The facility maintains eight (8) chillers (SN-40 through SN-47) with a total of fortythree (43) bays of non-contact cooling towers that are used for facility cooling with a total flowcapacity of 69,446 gpm. There are two (2) additional chillers (SN-48 and SN-49) with a total offour (4) cooling tower bays located at the Center on Aging, with a total flow capacity of 3,000gpm, and two (2) additional chillers (SN-50 and SN-51) with a total of four (4) cooling towerbays located at the J.T. Stephens Institute, with a total flow capacity of 6,000 gpm.5

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302RegulationsThe following table contains the regulations applicable to this permit.RegulationsArkansas Air Pollution Control Code, Regulation 18, effective June 18, 2010Regulations of the Arkansas Plan of Implementation for Air Pollution Control,Regulation 19, effective September 13, 2014Regulations of the Arkansas Operating Air Permit Program, Regulation 26, effectiveNovember 18, 2012NSPS, 40 CFR Part 60, Subpart Dc, Standards of Performance for Small Industrial Commercial - Institutional Steam Generating UnitsNSPS, 40 CFR Part 60, Subpart IIII - Standards of Performance for StationaryCompression Ignition Internal Combustion Engines40 CFR Part 89 – Control of Emissions From New and In-use Non-road Compression –Ignition EnginesNESHAP, 40 CFR Part 63, Subpart ZZZZ—National Emissions Standards for HazardousAir Pollutants for Stationary Reciprocating Internal Combustion EnginesNSPS, 40 CFR Part 60, Subpart JJJJ— Standards of Performance for Stationary SparkIgnition Internal Combustion EnginesEmission SummaryThe following table is a summary of emissions from the facility. This table, in itself, is not anenforceable condition of the permit.EMISSION SUMMARYEmission RatesSourceNumberDescriptionPollutantTotal Allowable um**Chromium0.4510.0080.0081.590.0060.006

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberSN-01SN-02SN-03Emission lentMCEP 750 hp Boiler#1MCEP 750 hp Boiler#2MCEP 700 hp 0010.010.010.80.811.713.90.10.80.190.010.01

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberSN-04SN-05SN-10ASN-10BEmission hromium,hexavalentPM/PM10CONOXSO2VOCMCEP 750 hp Boiler#4MCEP 750 hp Boiler#5WCEP 600 hpBoiler #1WCEP 600 hpBoiler 10.22.22.60.10.2

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberSN-10CEmission ydePOMWCEP 600 hpBoiler #3SN-12MCEP DieselGenerator #1SN-13MCEP DieselGenerator #2SN-14MCEP DieselGenerator 010.010.010.10.62.10.10.10.010.010.010.01

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberEmission RatesDescriptionSN-15Biomedical DieselGeneratorSN-16CI Diesel Generator#1SN-17CI Diesel Generator#2SN-18JEI Diesel GeneratorSN-19OPC/Carti .010.010.10.30.90.1

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberEmission RatesDescriptionSN-20COPH DieselGeneratorSN-21Sim. Lab DieselGeneratorSN-227A Diesel GeneratorSN-23EDII DieselGenerator 0.10.50.10.10.010.010.01

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberEmission RatesDescriptionSN-24EDII DieselGenerator #2SN-25OPC DieselGeneratorSN-28Bioventures DieselGeneratorSN-29Distribution DieselGeneratorSN-30RIOA 10.10.2

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberEmission RatesDescriptionSN-31JTS DieselGeneratorSN-32MRI DieselGeneratorSN-33FMC DieselGeneratorSN-34WCEP DieselGenerator 10.10.01

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberEmission RatesDescriptionSN-35WCEP DieselGenerator #2SN-36WCEP DieselGenerator #3SN-37WCEP DieselGenerator #4SN-38WCEP DieselGenerator .010.010.010.01

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberSN-39Emission RatesDescriptionPollutantWCEP DieselGenerator #6MCEP CoolingTower #1MCEPCoolingSN-43 A/BTower #4SN-44MCEP CoolingA/B/C/D/E/F/G/H/I/JTower #6SN-45MCEP CoolingA/B/C/D/E/F/G/H/I/JTower #7SN-46MCEP CoolingA/B/C/DTower #8SN-47MCEP CoolingA/B/C/DTower #9SN-48COA Cooling TowerA/B#1SN-49COA Cooling TowerA/B#2SN-50JTS Cooling TowerA/B#1SN-51JTS Cooling TowerA/B#2SN-52WCEP CoolingA/BTowersSN-40 A/B/CSN-54CI #3 GeneratorSN-55PDC 10.10.010.010.010.010.10.32.30.10.1

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302EMISSION SUMMARYSourceNumberSN-56Emission dePOMPM/PM10MCEP CoolingTower /PM100.10.1CO0.10.1NOx0.10.1SO20.10.1VOC0.10.1RIOA GeneratorSN-57Hexane1.42E-037.11E-05(310 HP)Cadmium8.69E-074.35E-08Chromium Ps included in the VOC totals. Other HAPs are not included in any other totals unlessspecifically stated.**Air Contaminants such as ammonia, acetone, and certain halogenated solvents are not VOCsor HAPs.16

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302SECTION III: PERMIT HISTORYPermit 2125-AOP-R0 was issued on July 16, 2007 and was the initial permit for the facility. Thefacility had actual emissions below permitting thresholds (25 tpy NOX) and planned to installthree (3) new natural gas fired boilers and six (6) new diesel generator sets. The proposedemission rates were significantly greater than the projected actual emissions in order to allowmaximum flexibility, and to account for an anticipated increase in natural gas usage due toincreased electricity cost.Permit #2125-AOP-R1 was issued on December 4, 2009. In this modification, the facility madethe following changes to the permit:1.2.3.4.5.Installed 2 New Generators (SN-54) and (SN-55),Relocated and reactivated a previously deactivated generator (SN-27),Changed the exhaust stacks from horizontal to vertical on generators SN-34through SN-39,Incorporated NSPS IIII compliance conditions into the permit, andAdded one 500-gallon and two 1500-gallon new diesel storage tanks to theInsignificant Activities listPermit 2125-AOP-R2 was issued on June 6, 2014 as a modification. The purpose of thismodification is to renew the Title V Operating Permit in accordance with General Provision 3 ofthe permit and ADEQ Regulation §26.406. The facility also requested the following changes tothe permit:1.2.3.4.5.6.7.8.Construction of a new non-contact water cooling tower (SN-56),Removal of cooling towers SN-41 and SN-42,Installation of a new 0.79 MMBtu/hr backup generator (SN-57),Removal of instrument sterilizer (SN-53),Removal of IOA-Computer Room Generator (SN-27),Increase the maximum allowable operating hours from 500 to 580 for SN-34through SN-39,Reduce the maximum allowable operating hours from 200 to 100 hours for SN-12through SN-33 and SN-54, andReduce the maximum allowable sulfur content from 0.1% to 0.0015% for SN-01through SN-05, SN-12 through SN-39, SN-54 and SN-55.There was an overall reduction in permitted emissions with the most significant changes being areduction of 7.0 tpy PM/PM10, 5.6 tpy SO2, 1.2 tpy VOC, 4.4 tpy CO and 11.5 tpy NOx.17

University of Arkansas for Medical Sciences (UAMS)Permit #: 2125-AOP-R3AFIN: 60 00302SECTION IV: SPECIFIC CONDITIONSSN- 01 through SN-05MCEP BoilersSource DescriptionThe five (5) 31.5 MMBtu/hr Boiler house boilers are capable of using either pipeline qualitynatural gas or distillate oil (diesel fuel) as a fuel source. The boilers are permitted to operate8,760 hours per year on natural gas with the option of running 200 hours each on diesel fuel.Due to an installation/modification date (1988) prior to the applicability date of June 9, 1989,SN-01 is not subject to NSPS Subpart Dc - Standards of Performance for Small Industrial Commercial - Institutional Steam Generating Units. SN-02, SN-03, SN-04 and SN05 are subjectto Subpart Dc due to installation dates (1996, 2015, 1995 and 1995, respectively) after theapplicability date. SN-01 through SN-05 all meet the definition of a gas fired boiler as seen in 40CFR Part 63 JJJJJJ §63.11237 and are therefore exempt per §63.11195 so long as they are incompliance with SC #16.Specific Conditions1.The permittee shall not exceed the emission rates set forth in the following table. Thepermittee will demonstrate compliance with this condition by compliance with SpecificConditions 6 and 8. [Regulation 19, §19.501 et seq., and 40 CFR P

UAMS currently has thirty (30) diesel generators, SN-12 through SN-39 (SN-26-27 removed), SN-54, SN-55 and SN-57 on site for the production of back-up electricity. These generators will provide back-up electricity and may also be