Click Plus Plc

Transcription

For the latest prices, please check AutomationDirect.com.CLICK PLUS Option Slot Module SpecificationsC2-08AR-6V4 AC Input / 4 Relay Output4 Analog Voltage Input2 Analog Voltage OutputOption Slot I/O ModuleNOTE: Use this module and a CLICK PLUS CPUas a comparable replacement for the existingC0-12ARE-2-D PLC.Wiring DiagramC2-08AR-6V100–120 VACIN 100-120VC1210mA34OUT 6-27VC2121A / 6-240V 1A34AD2VIN 0-10VAD1VSee Discrete I/O SpecificationsInputs (X1 – X4)6–27 VDC6–240 VACLLLTransmitter P/STransmitter 0-10VTransmitter 0-10VAD3VTransmitter 0-10VAD4VTransmitter 0-10VACOMDA2VOUT 0-10VDA1VSee Discrete I/O SpecificationsOutputs (Y1 – Y4)L 1See Analog I/O Specifications VoltageInputs (AD1V – AD4V)See Analog I/O Specifications VoltageOutputs (DA1V – DA2V)ACOMNOTE: There are no ZIPLink pre-wired PLCconnection cables and modules for the Analog OptionSlot Modules (cannot mix discrete I/O and analog I/Osignals in a ZIPLink cable).General Specifications100mA max(All Points On)Current Consumption at 24VDCTerminal Block Replacement Part No.WeightC0-16TB58gCLICK PLCstCLP-65

For the latest prices, please check AutomationDirect.com.CLICK PLUS Option Slot Module SpecificationsC2-08AR-6V (cont’d)X1 - X4Equivalent Discrete Input CircuitDiscrete I/O Specifications - InputsOperating Voltage Range47–63 HzInput CurrentTyp 8.5 mA @ 100VAC (50Hz)Typ 10mA @100VAC (60Hz)16mA @ 144VACInput Impedance15kΩ @ 50Hz12kΩ @ 60HzON Voltage Level 60VACOFF Voltage Level 20VACMinimum ON CurrentMaximum OFF CurrentOFF to ON ResponseON to OFF ResponseStatus IndicatorsCommons3.3 V100–120 VACAC FrequencyMax. Input CurrentInternal Module Circuitry4INPUTX1-X4100-120 VACC1COMC2-08AR-6V Temperature Derating Chart5mA42mA 40ms 40msLogic Side (4 points, green LED)Inputs3PointsInputs per Module211 (4 points/common)003210502068308550 55 C122 131 F40104Surrounding Air Temperature ( C/ F)Y1 - Y4Equivalent Discrete Output CircuitDiscrete I/O Specifications - OutputsOperating Voltage RangeOutput TypeAC FrequencyMaximum CurrentMinimum Load CurrentMaximum Inrush CurrentOFF to ON ResponseON to OFF ResponseStatus IndicatorsCommons per Module46–27 VDC, 6–240 VACLRelay, form A (SPST)24VOUTPUTY1-Y447–63 Hz1A/point (resistive)COM5mA @ 5VDCC23A for 10ms 15ms 15msLogic Side (4 points, red LED)1 (4 points/common)Typical Relay Life (Operations)at Room TemperatureVoltage & Load TypeLoad Current: 1 A30VDC Resistive200,000 cycles*30VDC Inductive100,000 cycles*250VAC Resistive200,000 cycles*250VAC Inductive50,000 cycles**ON to OFF 1 cycleInternal Module Circuitry6-27 VDC6-240 VACC2-08AR-6V Temperature Derating Chart4Outputs3PointsOutputs per Module2100321050206830854010450 55 C122 131 FSurrounding Air Temperature ( C/ F)CLICK PLCstCLP-66

For the latest prices, please check AutomationDirect.com.CLICK PLUS Option Slot Module SpecificationsC2-08AR-6V (cont’d)AD1V - AD4VAnalog Voltage Input CircuitAnalog Specifications - Voltage InputInputs per Module4 (voltage)Input Range0–10 VDCResolution12-bitConversion Time50msInput ImpedanceInput StabilityFull-Scale Calibration ErrorOffset Calibration ErrorAccuracy vs. Temperature ErrorInternal Module A/DConverter 2 LSB maximumTransmitterP/S 2% maximum 25mV maximum 100ppm / C maximumDA1V - DA2VAnalog Specifications - Voltage OutputOutputs per Module2 (voltage)Output Range0–10 VDCResolution1msLoad Impedance4kΩ minimum (output current 2.5 mAmaximum)Offset Calibration ErrorAccuracy vs. Temperature ErrorInternal Module Circuitry12-bitConversion TimeFull-Scale Calibration ErrorAnalog Voltage Output CircuitDAxVLoad4kΩ minimum0VD/AConverterACOM 2% maximum 25mV maximum 100ppm / C maximumINSULATIONBasic insulation is provided between AC input terminal andRelay output terminal. In order to comply with IEC/UL 61010-2201, please externally provide an isolation with basic insulationin front of the AC input terminal.Basic insulation requires a clearance distance of 1.5 mm ormore, a creepage distance of 2.5 mm or more, and dielectricvoltage withstand of 1500Vrms.AC inputRelay outputAnalog inputAnalog outputInternal circuit: No insulation: Basic insulation: Reinforced insulationCLICK PLCstCLP-67

For the latest prices, please check AutomationDirect.com.CLICK PLUS Option Slot Module SpecificationsGeneral SpecificationsFor All CLICK PLUSOption Slot ModulesThese general specifications apply toall CLICK PLUS Option Slot Modules.Please refer to the appropriate I/Otemperature derating charts under theOption Slot module and Stackable I/Omodule specifications to determinebest operating conditions based on theambient temperature of your particularapplication.Option Slot Module General SpecificationsOperating TemperatureStorage Temperature32 F to 131 F (0 C to 55 C)–4 F to 158 F (–20 C to 70 C)IEC 60068-2-1 (Test Ab, Cold)IEC 60068-2-2 (Test Bb, Dry Heat)IEC 60068-2-14 (Test Na, Thermal Shock)Ambient Humidity30% to 95% relative humidity (non–condensing)Environmental AirNo corrosive gases. Environmental pollution level is 2 (UL840)EnvironmentFor Indoor Use OnlyVibrationIEC60068-2-6 (Test Fc)5–9Hz:3.5mm amplitude, 9–150Hz 1.0G10 sweep cycles per axis on each of 3 mutually perpendicular axes.ShockIEC60068-2-27 (Test Ea)15G peak, 11ms duration, 3 shocks in each direction per axis, on 3mutually perpendicular axes.Noise ImmunityEmissionsAgency ApprovalsOther EN61131-2 EN61000-4-2 (ESD)EN61000-4-3 (RFI)EN61000-4-4 (FTB)EN61000-4-6 (Conducted)EN61000-4-8 (Power frequency magnetic field immunity) Local Test Impulse Immunity : 1000V @ 1uS pulseEN55011 Class A (Radiated RF emission)UL61010 (File No. E157382, E316037); CE (EN61131-2);CUL Canadian C22.2RoHS 2011/65/EU Amendment (EU)2015/863CLICK PLCstCLP-23

For the latest prices, please check AutomationDirect.com.CLICK PLUS PLC SpecificationsCLICK PLUS PLC Hardware/Software CompatibilityThe table below shows the minimum software and hardware versions required for the CLICK PLUS PLCs andOption Slot Modules. The CLICK PLUS PLC can also utilize the CLICK Stackable I/O Modules, as any software andhardware version compatible with CLICK PLUS is also compatible with the CLICK Stackable I/O Modules.CLICK PLUS PLC Features Software CompatibilityMinimum CLICK Software VersionDevice TypePart NumberHardwareHigh-Speed Inputsv3.00v3.00C2-01CPUCLICK PLUS CPUC2-02CPUEtherNet/IPPID, DHCP, DNS, C2-08D1-4VCC2-08D2-4VCC2-08DR-4VCOption SlotI/O 2-6VC2-08DR-6VC2-08AR-6Vv3.00v3.00N/ACLICK PLCstCLP-22

For the latest prices, please check AutomationDirect.com.AccessoriesC2-USER-MCLICK PLUS PLC Hardware User ManualManual covers all CLICK PLUS PLCand I/O module installation andwiring, specifications, error codes andtroubleshooting guide. The CLICK PLUSPLC Hardware User Manual can bedownloaded free at the AutomationDirectWeb site;EA-MG-PGM-CBLPC to Panel Programming CableAssembly for C-more Micro-GraphicPanels and CLICK/CLICK PLUS PLCsThe 6ft cable assembly connects apersonal computer to any C-more MicroGraphic panel, CLICK PLC, or select CLICKPLUS PLC for setup and programming.Note: This cable assembly uses the PC’s USB port andconverts the signals to serial transmissions. The USB portsupplies 5VDC to the Micro-Graphic panel for configurationoperations.Assembly includes standard USB A-typeconnector to B-type connector cable,custom converter, and a RS232C cablewith RJ12 modular connector on eachend.C0-USER-MCLICK PLC Hardware User ManualManual covers all CLICK PLC andI/O module installation and wiring,specifications, error codes andtroubleshooting guide. The CLICKPLC Hardware User Manual can bedownloaded free at the AutomationDirectWeb site;USB-CBL-AMICB6USB A to USB micro B ProgrammingCable Assembly (CLICK PLUS Only)Programming Cable, USB A to USB microB, 6ft. (1.83 m) length. For use with CLICKPLUS PLCs and most USB devices. TheUSB port supplies 5VDC to the CLICKPLUS CPU for programming.C0-PGMSWProgramming Software CD-ROMThe programming software can bedownloaded free at the AutomationDirectWeb site, or the CD can be purchasedfrom the AutomationDirect online Webstore.D2-DSCBLProgramming Cable for CLICK/CLICKPLUS and DirectLOGIC PLCs12ft. (3.66 m) RS232 shielded PCprogramming cable for CLICK, selectCLICK PLUS PLCs, DL05, DL06, DL105,DL205, D3-350, D4-450, D4-454, andDo-more H2 and T1H series CPUs. 9-pinD-shell female connector to an RJ12 6P6Cconnector.C0-3TBSpare 3-Pole Terminal BlockReplacement 3-pole terminal block for the3-wire RS-485 Port 3 on CLICK Standardand Analog PLCs as well as the CLICKPLUS C2-03CPU. Sold in packs of 2.C0-4TBSpare 24VDC Power Terminal BlockReplacement terminal block for the24VDC supply power to the PLC. Sold inpacks of 2.C0-8TBSpare 8-Point I/OTerminal BlockReplacement terminalblock for the 8-pointI/O modules. Sold inpacks of 2.C0-8TB-1Spare 13-Point I/O TerminalBlockReplacement terminal block for the8-point I/O relay modules. Sold in packsof 2.C0-16TBSpare 16-Point I/O Terminal BlockReplacement terminal block for the16-point I/O modules andPLC built-in I/O. Sold inpacks of 2.Note: If your PC has a USB port but does not have a serial port,you must use programming cable EA-MG-PGM-CBL to connectto CLICK PLCs. For CLICK PLUS PLCs, you may also useUSB-CBL-AMICB6CLICK PLCstCLP-157

CLICK PLUS PLCs, DL05, DL06, DL105, DL205, D3-350, D4-450, D4-454, and Do-more H2 and T1H series CPUs. 9-pin D-shell female connector to an RJ12 6P6C connector. Note: If your PC has a USB port but does not have a serial port, you must use programming cable EA-MG-PGM-CBL to connect to CLICK PLCs. For CLICK PLUS PLCs, you may also use USB-CBL-AMICB6