Input Module, Input/output Module - Zrelektronik

Transcription

Sinteso / Cerberus PROInput module, input/output moduleFDCI221, FDCIO221Input module and input/output module for the automatically addressed detectorline FDnet/C-NETInput module FDCI221:– Monitorable contact input for reporting technical statuses or activating analarmInput/output module FDCIO221:– Control output with potential-free relay contact for activation of alarmingdevices, fans, air conditioning systems, lift controls, etc.– Monitorable contact input for reporting technical statuses or activating analarm– Use as a monitored output with a separate power supply, e.g., for operatingacoustic signal transmittersLED indicator for input/output statuses and for fault, test, localizationPower supply and communication via FDnet/C-NET (addressed individually)Address automatically issued during commissioningTwo-wire installation for all cable typesA6V10202196 k en -2018-06-15Building TechnologiesControl Products and Systems

PropertiesFeaturesTransparent housing, ensuring that indicators are easy to seeProtected electronicsIntegrated line separatorChronological status monitoringSupply via FDnet/C-NET, auxiliary supply only required if the output is configured asmonitored (FDCIO221)Microprocessor-controlled signal processingDifferent mounting optionsFor dry areasIn humid environments, use additional housing FDCH221Eco-friendlyEnvironmentally friendly processingReusable materialsElectronic parts and synthetic materials can be easily separatedFunctionsFDCI221 input moduleInput for potential-free detector contactMonitoring the input line for open line and short-circuit with terminating resistorsThe input for status or alarm messages can be configured using the fire control panel.Status indicator by means of LEDFields of application:– To activate a potential-free normally open or normally closed contact in order toreport technical statuses (e.g., door or fan control) or to activate an alarm (e.g.,sprinkler alarm)21FDnet/C-NETFDnet/C-NET32Building TechnologiesFire Safety1Potential-free detector contact2Connections for the input3Connections for the detector lineA6V10202196 k en -2018-06-15

FDCIO221 input/output moduleInput for potential-free detector contactMonitoring the input line for open line and short-circuit with terminating resistorsThe input for status or alarm messages can be configured using the fire control panel.Output which can be configured via jumper:– Not monitorable: Potential-free relay contact (AC 22 V, 2 A or DC 30 V, 2 A)– Monitorable: Relay contact (DC 30 V, 2 A)Status indicator by means of LEDFields of application:– To activate a potential-free normally open or normally closed contact in order toreport technical statuses (e.g., fan control) or to activate an alarm (e.g., sprinkleralarm)– For decentralized activation of alarming devices, fans, air conditioning systems, liftcontrols, etc.214FDnet/C-NETFDnet/C-NET3Building TechnologiesFire Safety1Potential-free detector contact3Connections for the detector line2Connections for the input4Connections for the output3A6V10202196 k en -2018-06-15

Type OverviewTypeDesignationOrder numberWeight [kg]FDCI221Input module incl. 2 resistors, 2 mountingfeetS54312-F1-A10.060FDCIO221Input/output module incl. 2 resistors,2 mounting feetS54312-F2-A10.066Accessories for input module FDCI221, input/output module FDCIO221TypeDesignationOrder numberWeight [kg]FDCH221Housing with cover, seal, and screwsS54312-F3-A10.282–M20 x 1.5 metal cable glandA5Q000044780.036–M20 metal counter 5 2.5mm2(3-pin) connection terminalReplacement material for input module FDCI221, input/output module FDCIO221TypeDesignationOrder numberWeight [kg]FDCM291Mounting footA5Q000038550.001Product documentationDocument IDName008164Equipment overview Sinteso Detector system FD20008331List of compatibility (for 'Sinteso ' product line)A6V10229261List of compatibility (for 'Cerberus PRO' product line)A6V10211122Technical Manual Input module FDCI221, input/output module FDCIO221A6V10212086Installation Input module FDCI221, Input/Output module FDCIO221, Housing FDCH221Related documents such as environmental declarations, CE declarations, etc., can bedownloaded at the following Internet address:http://siemens.com/bt/download4Building TechnologiesFire SafetyA6V10202196 k en -2018-06-15

NotesMountingMounting optionsDirectly on the mounting surfaceSeries mounting on a U-rail TS35Surface-mounted or recess-mounted cable entryIn housing FDCH221 (accessory) with cover, seal, and screws for wet areas1321 Series mounting using mounting feetsupplied, on U-rail TS353 Use auxiliary terminals DBZ1190-AB forshielded cables2 Mounting in housing FDCH221(accessory)DisposalThe device is considered an electronic device for disposal in accordancewith the European Guidelines and may not be disposed of as domesticgarbage.Dispose of the device through channels provided for this purpose.Comply with all local and currently applicable laws and regulations.Building TechnologiesFire Safety5A6V10202196 k en -2018-06-15

Technical dataFDCI221FDCIO221Operating voltageDC 12 33 VOperating current (quiescent)Max. 0.3 mARelay output (ohmic)Max. 0.4 mA-AC 22 V, 2 A, max. 44 VADC 30 V, 2 A, max. 60 WLine resistance (input)Max. 20Operating temperature-25 70 CStorage temperature-30 75 CAir humidity (non-condensing)95 % rel.Communication protocolFDnet/C-NETConnection terminals0.2 2.5 mm²ColorHousingCoverHousing FDCH221 RAL 9010, pure whiteTransparent matt RAL 9010, pure whiteProtection category (IEC 60529)When mounted on a U-rail in a fire control panelWith housing FDCH221IP30IP65StandardsEN 54-17, EN 54-18ApprovalsVdSLPCBFMG209066531h/013038448DNV GL (Marine)MEDB00003UUSystem FS20FS720FDCI221Siemens Schweiz AG; Theilerstrasse 1aCH-6300 ZugTechnical data: see doc. A6V10211122FDCI221 - Input/output device incl. short-circuit isolator for use in fire detection and fire alarm systems installed in buildings.305/2011/EU (CPR): EN 54-17 / EN 54-18 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which isobtainable via the Customer Support Center: Tel. 49 89 9221-8000 or https://siemens.com/bt/downloadDoP No.: 0786-CPR-20709; DoC No.: CED-FDCI221100786FDCIO221Siemens Schweiz AG; Theilerstrasse 1aCH-6300 ZugTechnical data: see doc. A6V10211122FDCIO221 -Iinput/output device incl. short-circuit isolator for use in fire detection and fire alarm systems installed in buildings.305/2011/EU (CPR): EN 54-17 / EN 54-18 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which isobtainable via the Customer Support Center: Tel. 49 89 9221-8000 or https://siemens.com/bt/downloadDoP No.: 0786-CPR-20710; DoC No.: CED-FDCIO2216Building TechnologiesFire SafetyA6V10202196 k en -2018-06-15

Dimensional drawingsInput module FDCI22124957191Input/output module FDCIO22124957191Housing FDCH22150207119Building TechnologiesFire Safety7A6V10202196 k en -2018-06-15

Issued bySiemens Switzerland LtdBuilding Technologies DivisionInternational HeadquartersTheilerstrasse 1aCH-6300 ZugTel. 41 58 724 2424www.siemens.com/buildingtechnologies8Building TechnologiesFire SafetyDocument IDA6V10202196 k en -Edition2018-06-15 Siemens Switzerland Ltd, 2009Technical specifications and availability subject to change without notice.A6V10202196 k en -2018-06-15Manual FD20/FD720Register 5

- M20 x 1.5 metal cable gland A5Q00004478 0.036 - M20 metal counter nut A5Q00004479 0.006 DBZ1190-AB 0.5 2.5 mm2 (3-pin) connection terminal BPZ:4942340001 0.001 Replacement material for input module FDCI221, input/output module FDCIO221 Type Designation Order number Weight [kg] FDCM291 Mounting foot A5Q00003855 0.001 Product documentation