Product Data WeatherMaker Single Packaged Rooftop - Carrier

Transcription

Product DataWeatherMaker Single Packaged Rooftop5 Nominal Tons (18.17 kW)50FC 07 Electric Cooling Rooftop Units with Optional Electric Heatwith Puron Refrigerant (R-410A) 50 Hz 2020 Carrier CorporationForm 50FC-7-C01PD

Features/BenefitsThe New CarrierWeatherMaker rooftop units(RTU) with EcoBlue Technology were designedby customers for customersand integrate new technologyto provide value addedbenefits never seen in thistype of equipment before.New major design features include: Patent pending, industry’s first efficient indoor fan system using VaneAxial fan with electric commutatedvariable speed motor Upgraded unit control board withintuitive indoor fan adjustment Reliable copper tube/aluminum fincondenser coil with 5/16-in. tubingto help reduce refrigerant chargeversus prior designs New outdoor fan system with rugged — lightweight high impact composite fan bladeWeatherMaker 50FC 5 ton units arespecifically designed to fit on Carrierroof curbs that were installed back to1989, which makes replacement easyand eliminates the need for curb adapters or changing utility connections.All models are capable of either verticalor horizontal airflow.The Carrier rooftop unit (RTU) wasdesigned by customers for customers.With “no-strip” screw collars, handledaccess panels, and more, the unit iseasy to install, easy to maintain, andeasy to use. Your new 5 ton CarrierWeatherMaker rooftop unit (RTU) provides optimum comfort and controlfrom a packaged rooftop.Value-added features include: Puron refrigerant (R-410A) Single point electrical connections RTU Open controller for BACnet1,LonWorks2, Modbus3 and JohnsonControls N2 Scroll compressors with internalline-break overload protection Units come with an easy accesstool-less filter door. Filter track tiltsout for filter removal and replacement. All filters are the same size ineach unitInstallation easeAll WeatherMaker units are fieldconvertible to horizontal airflow, whichmakes it easy to adjust to unexpectedjob-site complications. Lighter unitsmake for easy replace. Simple, fastplug-in connections to the standard1. BACnet is a registered trademark ofASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers).2. LonWorks is a registered trademark ofEchelon Corporation.3. Modbus is a registered trademark ofSchneider Electric.Table of contentsPageFeatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Fan Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342integrated unit control board (UCB).Clearly labeled connections points toreduce installation time. Also, a largecontrol box provides room to work androom to mount Carrier accessorycontrols.Easy to maintainWith the new EcoBlue Vane Axial fansystem and direct drive ECM motor,there is no longer a need to adjust beltsor pulleys as in past designs. This freesup maintenance and installation time.Easy access handles by Carrier providequick and easy access to all normallyserviced components. Our “no-strip”screw system has superior holdingpower and guides screws into positionwhile preventing the screw from stripping the unit’s metal.Sloped, corrosion resistant compositedrain pan sheds water; and won’t rust.Easy to useThe new Unit Control Board by Carrierputs all connections and troubleshooting points in one convenient place.Most low voltage connections aremade to the same board for easyaccess. Setting up the fan is simplewith an intuitive switch and rotary dialarrangement. Carrier rooftops havehigh and low pressure switches, a filterdrier, and 2-in. filters standard.

EcoBlue TechnologyDirect drive EcoBlue Technologyindoor fan system uses Vane Axial fandesign and electrically commutatedmotors.This new Vane Axial design over pastbelt drive systems has 75% fewer moving parts, uses up to 40% less energyand has no fan belts, blower bearingsand shaft.Streamlined control andintegrationCarrier controllers make connectingWeatherMaker rooftops into existingbuilding automation systems easy. Theunits are compatible with conventionalthermostat controls.Operating efficiency andflexibilityThe 50FC rooftop units meet ASHRAE(American Society of Heating, Refrigerating, and Air-Conditioning Engineers)High Efficiency Outdoor Fan– Non-corrosive blade– Balanced blade– Efficient airflow collar1. IECC is a registered trademark of the International Code Council, Inc.Vane Axial Indoor Fan– Direct drive ECM– Slow ramp up– Phase loss protection– No belts or pulleysUnit controls– Base unit controllerSwitch/dial fan settingLarge terminalconnections– RTU Open optionMulti-protocol controllerEfficient Coils– Round tube/plate fin– Copper/Aluminum– Special coating available– New ⁵/ -in. (7.9 mm)condenser tube90.1-2016, IECC1 (International EnergyConservation Code) IECC-2018 minimum efficiency requirements.Field convertible airflowAll WeatherMaker 5 ton units are fieldconvertible to horizontal airflow, whichmakes it easy to adjust to unexpectedjob-site.Heating– Electric HeatingMultiple sizes availableSingle point powerCompression– Fully hermitic scroll– Internally protected– Two-stageCabinet Design– Heavy gage base rails– Large handled access panels– Tool-less filter access door– Replacement “original” fit design3

Model number nomenclature50FC MODEL NUMBER NOMENCLATUREPosition:12345678910 11 12 13 14 15 16 17 18Example:50FC-M07A2A9-0A0Electrical OptionsA NoneC Non-Fused DisconnectD Thru-The-Base Connections (TTB)F Non-Fused Disconnect andThru-The-Base ConnectionsN Phase Monitor/ProtectionQ Phase Monitor/Protection andNon-Fused DisconnectR Phase Monitor/Protection and TTBT Phase Monitor/Protection,Non-Fused Disconnect, TTBModel Series - WeatherMaker FC – 14.0 SEER Standard EfficiencyHeat Size- No heatRefrig. Systems OptionsM Single Circuit, Two Stage CoolingCooling Tons07 18.17 kW (5 ton)Indoor Fan Options1 Direct Drive – EcoBlue – Standard Static2 Direct Drive – EcoBlue – Medium Static3 Direct Drive – EcoBlue – High StaticCoil Options (Outdoor – Indoor – Hail Guard)A Al/Cu – Al/CuB Precoat Al/Cu – Al/CuC E-coat Al/Cu – Al/CuD E-coat Al/Cu – E-coat Al/CuE Cu/Cu – Al/CuF Cu/Cu – Cu/CuM Al/Cu – Al/Cu – Louvered Hail GuardN Precoat Al/Cu – Al/Cu – Louvered Hail GuardP E-coat Al/Cu – Al/Cu – Louvered Hail GuardQ E-coat Al/Cu – E-coat Al/Cu – Louvered Hail GuardR Cu/Cu – Al/Cu – Louvered Hail GuardS Cu/Cu – Cu/Cu – Louvered Hail Guard40Packaging & Seismic Compliance0 StandardUnit Heat Type50 – Electric Heat Packaged RooftopSensor OptionsA NoneB Return Air (RA) Smoke DetectorC Supply Air (SA) Smoke DetectorD RA SA Smoke DetectorE CO2 SensorF RA Smoke Detector and CO2 SensorG SA Smoke Detector and CO2 SensorH RA SA Smoke Detector and CO2 SensorJ Condensate Overflow SwitchK Condensate Overflow Switch and RA Smoke DetectorL Condensate Overflow Switch and RA and SA Smoke DetectorsM Condensate Overflow Switch and SA Smoke DetectorAService Options0 None3 Hinged Access Panels6 MERV-8 High Efficiency Filters9 Hinged Access Panels and MERV-8 FiltersIntake / Exhaust OptionsA NoneB Temperature Economizer w/ Barometric ReliefF Enthalpy Economizer w/ Barometric ReliefK Two-Position DamperU Temperature Ultra Low Leak Economizerw/ Barometric ReliefW Enthalpy Ultra Low Leak Economizerw/ Barometric ReliefBase Unit Controls0 Electro-mechanical Controls – can be used withfield-installed W7212 EconoMi er IV(Non-Fault Detection and Diagnostic)2 RTU Open Multi-Protocol Controller6 Electro-mechanical Controls – can be used with W7220EconoMi er X (with Fault Detection and Diagnostic)Design Revision- Factory Design RevisionVoltage9 400/3/50

Capacity ratings50FC AHRI RATINGS50FC UNITCOOLINGSTAGESNOMINALCAPACITY(TONS)NET COOLINGCAPACITY(MBH) [kW]TOTAL POWER(kW)SEER1EER250FC*M072559.0 [17.3]5.015.011.8LEGENDAHRI —EER —IEER —SEER —IEER2 WITH2-SPEEDINDOOR FANMOTOR18.8efficiency for commercial unitary air-conditioning equipment on thebasis of weighted operation at various load capacities.4. 50FC units comply with ASHRAE 90.1-2016 (American Society ofHeating, Refrigerating, and Air-Conditioning Engineers) and DOE2018 (Department of Energy) Energy Standard for minimumSEER, IEER, and EER requirements.Air-Conditioning, Heating and Refrigeration InstituteEnergy Efficiency RatioIntegrated Energy Efficiency RatioIntegrated Energy Efficiency RatioNOTES:1. Units tested under AHRI 210/240 standard conditions.2. Units tested under AHRI 340/360 standard conditions.3. Test conditions are based on:Cooling Standard: 27 C (80 F) db, 19 C (67 F) wb indoor airtemperature and 35 C (95 F) db outdoor air temperature.IEER Standard: A measure that expresses cooling part-load EERSOUND RATINGS TABLE50FC 7OUTDOOR SOUND LEGENDdB— DecibelNOTES:1. Outdoor sound data is measured in accordance with AHRI Standard 270.2. Measurements are expressed in terms of sound power. Do notcompare these values to sound pressure values because soundpressure depends on specific environmental factors which normally do not match individual applications. Sound power valuesare independent of the environment and therefore more accurate.3. A-weighted sound ratings filter out very high and very low frequencies, to better approximate the response of “average” human ear.A-weighted measurements for Carrier units are taken in accordance with AHRI Standard 270.MINIMUM - MAXIMUM AIRFLOW RATINGS (CFM) — COOLING UNITS AND ACCESSORY ELECTRIC HEATCOOLING50FC UNITMINIMUMAIRFLOW CFM(CFM [L/s])MINIMUM2-SPEED AIRFLOWLOW SPEED(CFM [L/s])50FC*M071800 [846]1200 [564]ELECTRIC HEAT*MINIMUM2-SPEEDAIRFLOWHIGH SPEED(CFM [L/s])1800 [846]MAXIMUMAIRFLOW CFM(CFM [L/s])MINIMUMAIRFLOW CFM(CFM [L/s])MAXIMUMAIRFLOW CFM(CFM [L/s])3000 [1410]1800 [846]3000 [1410]* Electric heat modules are available as field-installed accessories for 50FC units.5

Physical data50FC 5 TON PHYSICAL DATA50FC UNITNOMINAL TONSREFRIGERATION SYSTEMNo. Circuits/No. Compressors/TypePuron (R-410A) charge A/B (lbs-oz) [kg]Metering deviceHigh-Pressure Trip/Reset (psig)Low-Pressure Trip/Reset (psig)EVAPORATOR COILMaterial (Tube/Fin)Coil TypeRows/FPITotal Face Area (ft2) [m2]Condensate Drain Connection SizeCONDENSER COILMaterialCoil TypeRows/FPITotal Face Area (ft2) [m2]Standard Static 3 PhaseMotor Qty/Drive TypeMax Cont BHPRPM [r/s] RangeFan Qty/TypeFan Diameter (in.) [mm]Medium Static 3 PhaseMotor Qty/Drive TypeMax Cont BHPRPM RangeFan Qty/TypeFan Diameter (in.) [mm]High Static 3 PhaseMotor Qty/Drive TypeMax Cont BHPRPM RangeFan Qty/TypeFan Diameter (in.) [mm]CONDENSER FAN AND MOTORQty / Motor Drive TypeMotor HP/RPM [Motor kW / r/s]Fan Diameter (in.) [mm]FILTERSRA Filter Qty / Size (in.)OA Inlet Screen Qty / Size (in.)650FC*M07 (English)51 / 1 / 2-Stage Scroll10-0 [4.5]TXV630/50554/117Cu/Al[10 mm] RTPF4/157.3 [0.67]3/ -in. [19 mm]43/ -in.8Cu/Al[7 mm] RTPF2/1815.0 [1.4]5/ -in.161/Direct1.31230-2300 [3.8-38.3]1/Vane Axial16.6 [421.6]1/Direct1.76253-2530 [4.2-42.2]1/Vane Axial16.6 [421.6]1/Direct2.43284-2836 [4.7-47.3]1/Vane Axial16.6 [421.6]1/41 / Direct/ 1100 [0.186 / 18]23 [584.2]4 / 16x16x2 [4 / 406x406x51]1 / 20x24x1 [1 / 508x610x25]

Options and accessoriesITEMELECTRIC HEATElectric resistance heatersSingle point kitsCABINETThru-the-base electrical connectionsHinged access panelsMERV-8 filtersCOIL OPTIONSCu/Cu indoor and/or outdoor coilsPre-coated outdoor coilsPremium, E-coated outdoor coilsCONDENSER PROTECTIONCondenser coil hail guard (louvereddesign)CONTROLSThermostats, temperature sensors,and subbasesSmoke detector (supply and/orreturn air)Horn strobe annunciator1Time guard II compressor delaycontrol circuitPhase monitorCondensate overflow TION*ECONOMIZERS AND OUTDOOR AIR DAMPERSEconoMi er IV for electro-mechanicalcontrols - Non FDD (Low air leakXdamper models)2EconoMi er2 for DDC controls (LowXLeak and Ultra Low Leak air dampermodels)3EconoMi er X for electro-mechanicalcontrols, complies with FDD (LowXLeak and Ultra Low Leak dampermodels)2Motorized 2-position outdoor-airXdamperManual outdoor-air damper (25% and50%)XBarometric relief4Power exhaust - prop designECONOMIZER SENSORS AND IAQ DEVICESXSingle dry bulb temperature sensors5Differential dry bulb temperaturesensors5XSingle enthalpy sensors5Differential enthalpy sensors5CO2 sensor (wall, duct, or unitXmounted)5INDOOR MOTOR AND DRIVEMultiple motor and drive packagesXLOW AMBIENT CONTROLWinter start kit6Low ambient controller to -20 F(-29 C)6POWER OPTIONSXNon-fused disconnect7ROOF CURBSRoof curb 14-in. (356 mm)Roof curb 24-in. (610 mm)ACCESSORY†XXXXXXXXXXXXXXXX*Factory-installed option†Field-installed accessoryNOTES:1. Requires a field-supplied 24V transformer for each application.See price pages for details.2. FDD (Fault Detection and Diagnostic) capability per California Title24 section 120.2.3. Models RTU Open DDC controls comply with California Title 24Fault Detection and Diagnostic (FDD).4. Included with economizer.5. Sensors used to optimize economizer performance.6. See application data for assistance.7. Non-fused disconnect switch cannot be used when unit electricalrating exceeds: 80 amps (FLA).Carrier RTUBuilder automatically selects the amp limitations.7

Options and accessories (cont)Factory-installed optionsEconomizer (dry-bulb or enthalpy)Economizers save money. They bring in fresh, outside airfor ventilation; and provide cool, outside air to cool yourbuilding. This is the preferred method of low-ambient cooling. When coupled to CO2 sensors, economizers can provide even more savings by coupling the ventilation air toonly that amount required.Economizers are available, installed and tested by the factory, with either enthalpy or dry-bulb temperature inputs.Additional sensors are available as accessories to optimizethe economizers. Economizers include a powered exhaustsystem to help equalize building pressures.Economizers include gravity controlled barometric reliefthat helps equalize building pressure and ambient air pressures. This can be a cost effective solution to prevent building pressurization. Economizers are available in ultra lowleak and low leak versions. Economizers can be factoryinstalled or easily field-installed.Unit mounted CO2 sensorThe CO2 sensor works with the economizer to intake onlythe correct amount of outside air for ventilation. As occupants fill your building, the CO2 sensor detects their presence through increasing CO2 levels, and opens theeconomizer appropriately. When the occupants leave, theCO2 levels decrease, and the sensor appropriately closesthe economizer. This intelligent control of the ventilationair, called demand controlled ventilation (DCV), reducesthe overall load on the rooftop, saving money. It is alsoavailable as a field-installed accessory.Smoke detector (supply and/or return air)Trust the experts. Smoke detectors make your applicationsafer and your job easier. Carrier smoke detectors immediately shut down the rooftop unit when smoke is detected.They are available, installed by the factory, for supply air,return air, or both.Thru-the-base connectionsThru-the-base connections, available as a factory option,are necessary to ensure proper connection and seal whenrouting wire and piping through the rooftop’s basepan andcurb. These couplings eliminate roof penetration andshould be considered for main power lines, as well as control power.Hinged access panelsAllows access to unit’s major components with specificallydesigned hinged access panels. Panels are filter, controlbox access indoor fan motor access.8Cu/Cu (indoor) coilsCopper fins and copper tubes are mechanically bonded tocopper tubes and copper tube sheets. A polymer strip prevents coil assembly from contacting the sheet metal coilpan to minimize potential for galvanic corrosion betweencoil and pan.E-coated (outdoor and indoor) coilsA flexible epoxy polymer coating uniformly applied to allcoil surface areas without material bridging between fins.Coating process shall ensure complete coil encapsulationof tubes, fins and headers.Pre-coated outdoor coilsA durable epoxy-phenolic coating to provide protection inmildly corrosive coastal environments. The coating minimizes galvanic action between dissimilar metals. Coating isapplied to the aluminum fin stock prior to the fin stampingprocess to create an inert barrier between the aluminum finand copper tube.Condenser coil hail guardSleek, louvered panels protect the condenser coil from haildamage, foreign objects, and incidental contact.Single enthalpy sensorPrevents the wheel from rotating if the outside air conditions are acceptable for free cooling. Both exhaust andsupply blowers will remain on.Non-fused disconnectThis OSHA-compliant, factory-installed, safety switchallows a service technician to locally secure power to therooftop. When selecting a factory-installed non-fused disconnect, note they are sized for the unit as ordered fromthe factory. The sizing of these do not accommodate fieldinstalled items such as power exhaust devices, etc. If fieldinstalling electric heat with factory-installed non-fused disconnect switch, a single point kit may or may not berequired.MERV-8 return air filtersThis factory option upgrades the return air filters fromstandard unit filters to high efficiency MERV-8 filters. Nonwoven MERV-8 filter media with high strength, moistureresistant frame. Filter media is securely fasted inside the filter frame on all four sides.

Field-installed accessoriesFilter maintenance indicatorWhen the optional factory-installed filter maintenance indicator is used, a factory-installed differential pressure switchmeasures pressure drop across the outside air filter andactivates a field-supplied dry contact indicator when thepressure differential exceeds the adjustable switch setpoint.Condenser coil hail guardSleek, louvered panels protect the condenser coil from haildamage, foreign objects, and incidental contact. This canbe purchased as a factory-installed option or as a fieldinstalled accessory.Differential enthalpy sensorThe differential enthalpy sensor is comprised of an outdoorand return air enthalpy sensors to provide differentialenthalpy control. The sensor allows the unit to determine ifoutside air is suitable for free cooling.Wall or duct mounted CO2 sensorThe IAQ sensor shall be available in duct or wall mount.The sensor provides demand ventilation indoor air quality(IAQ) control.Phase monitor protectionThe Phase Monitor Control will monitor the sequence ofthree phase electrical system to provide a phase reversalprotection; and monitor the three phase voltage inputs toprovide a phase loss protection for the three phase device.It will work on either a Delta or Wye power connection.Winter start kitThe winter start kit by Carrier extends the low ambientlimit of your rooftop to 25 F (–4 C). The kit bypasses thelow pressure switch, preventing nuisance tripping of thelow pressure switch. Other low ambient precautions maystill be prudent.Low ambient controllerThe low ambient controller is a head pressure controller kitthat is designed to maintain the unit’s condenser headpressure during periods of low ambient cooling operation.This device should be used as an alternative to economizerfree cooling when economizer usage is either notappropriate or desired. The low ambient controller willeither cycle the outdoor fan motors or operate them atreduced speed to maintain the unit operation, dependingon the model. This controller allows cooling operationdown to –20 F (–29 C) ambient conditions.Roof curb 14-in. (356 mm) or 24-in. (610 mm)Full perimeter roof curb with exhaust capability providesseparate air streams for energy recovery from the exhaustair without supply air contamination.Filter status indicator accessoryMonitors static pressure across supply and exhaust filtersand provides indication when filters become clogged.Power exhaustSuperior internal building pressure control. This fieldinstalled accessory may eliminate the need for costly, external pressure control fans.Manual OA DamperManual outdoor air dampers are an economical way tobring in ventilation air. The dampers are available in 25%and 50% versions.NOTE: See application tip “ROOFTOP-18-01” prior touse of this damper on 07 size models.Motorized 2-Position DamperThe Carrier 2-position, motorized outdoor air damperadmits up to 100% outside air. Using reliable, gear-driventechnology, the 2-position damper opens to allowventilation air and closes when the rooftop stops, stoppingunwanted infiltration.NOTE: See application tip “ROOFTOP-18-01” prior touse of this damper on 07 size models.Electric HeatersCarrier offers a full-line of field-installed accessory heaters.The heaters are very easy to use, install and are all preengineered and certified.Time Guard II control circuitThis accessory protects your compressor by preventingshort-cycling in the event of some other failure, preventsthe compressor from restarting for 30 seconds after stopping. Not required with RTU Open controller, or authorized commercial thermostats.Power exhaust with barometric reliefSuperior internal building pressure control. This fieldinstalled accessory may eliminate the need for costly, external pressure control fans.9

Options and accessories (cont)OPTIONS AND ACCESSORY WEIGHTS50FC UNIT WEIGHT07OPTION / ACCESSORY NAMEPower Exhaust - VerticalPower Exhaust - HorizontalEconoMi er (X, IV or 2)2-Position DamperManual DamperHail Guard (louvered)Cu/Cu Condenser CoilCu/Cu Condenser and Evaporator CoilsRoof Curb (14-in. curb)Roof Curb (24-in. curb)CO2 SensorOptional Indoor Motor/DriveLow Ambient ControllerWinter Start KitReturn Air Smoke DetectorSupply Air Smoke DetectorFan Filter SwitchNon-Fused DisconnectEnthalpy SensorDifferential Enthalpy SensorNOTE: Where multiple variations are available, the heaviest combination is 3162688437543681742331711

50FC**07 BASE UNIT DIMENSIONSBase unit dimensions11

50FC**07 BASE UNIT DIMENSIONS (cont)Base unit dimensions (cont)12

1350FC**07 BASE UNIT DIMENSIONS (cont)

144 355.6]15.19"[385.8]4.96"[126.0]21.74"[552.2]SUPPLY AIR20.41"[518.3]40.69"[1033.5]SUPPLY [356]ROOF CURBACCESSORY #RETURN AIR3.00"[76.2]13.78"[350.0]16.03"[407.2]ERETURN AIROPENINGE32.19"[817.6]70.87"[1800.2]REVAREVISION RECORD"A"DATE04/22/13BYMMCROOFING MATERIAL(FIELD SUPPLIED)CANT STRIP(FIELD SUPPLIED)ROOFING FELT(FIELD SUPPLIED)COUNTER FLASHING(FIELD SUPPLIED)TYPICAL (4) SIDESE-ECHK'D-"A"APP'D-8 9/16"[217.5] WIDEINSULATED DECK PANELSUPPLY AIRECN NO.1067898-SURFACE FINISHPURCHMFG/PURCHT-005, Y-002WEIGHT:1-3/4"[44.5]RETURN AIR1' 4-13/16"[427] INSIDE3/4" [19] NPTPOWER WIRINGFITTING-3 DEC- --ANGMODEL (INTERNAL USE ONLY)CHECKER--CURB ASY, ROOF-N/ASCALEBREVMMCDISTRIBUTIONSHEET 5 OF 548TC4004271-3/4"[44.4]SEE NOTE #21/2" [12.7] NPTACCESSORY CONVENIENCEOUTLET WIRING CONNECTORDRAWING NUMBERNEXT DRAWINGDSIZETITLE5' 7-3/8"[1711.3]2-3/8"[61]1/2" [12.7] NPTCONTROL WIRINGFITTINGMANUFACTURING104173806/17/11 -DRAFTERMMC--2 DECAUTHORIZATION NUMBERENGINEERING-1 DECUNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHESTOLERANCES ON:PRODUCTIONCERTIFIED DRAWINGENGINEERING REQUIREMENTS-MATERIALTHIRD ANGLEPROJECTIONDRAWING RELEASE LEVEL:SEE VIEW "B"3'-1 3/16"[944.6]1/2" [12.7] NPT3/4" [19] NPTGAS FITTING11 3/4"[298.5] WIDEINSULATED DECK PANELSTHRU THE BOTTOMTHRU THE CURBGAS CONNECTION TYPEGAS SERVICE PLATETHRU THE CURBDRILL HOLE2" [50.8] @ASSEMBLY (IFREQUIRED)(SEE NOTE #8)1.00"[25.4]1-3/4"[44.4]SECTIONSCALE CTOR PKG. ACC.NAIL (FIELD SUPPLIED)RIGID INSULATION(FIELD SUPPLIED)7/16"[11]UNITOVERALL DIM. 5'-7 3/8" WAS 5'-7 7/8; 18GAMATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WASWITH CURBDUCT(FIELD SUPPLIED)GASKET(SUPPLIED WITH CURB)CORNER DETAILVIEW "B"NOTES:1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED.2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY.3. DIMENSIONS IN [ ] ARE IN MILLIMETERS.4. ROOFCURB: 18 GAGE STEEL.5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB).6. SERVICE CLEARANCE 4 FEET ON EACH SIDE.7.DIRECTION OF AIR FLOW.8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPEPACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS.ROOF CURB DIMENSIONS — 50FC 07Accessory dimensions

Performance data50FC**07 HIGH STAGE COOLING CAPACITIES50FC**07581500 Cfm62EAT(wb)677276581750 Cfm62EAT(wb)677276582000 Cfm62EAT(wb)677276582250 Cfm62EAT(wb)677276582500 Cfm62EAT(wb)677276LEGEND——Cfm—EAT (db) —EAT (wb) 459.648.763.539.069.826.7——85EAT 95EAT .328.0AMBIENT TEMPERATURE ( F)105EAT 48.722.871.3—67.467.4—40.5—26.739.1—115EAT 125EAT 58.436.0NOTE: See minimum-maximum airflow ratings on page 5.Do Not OperateCubic Feet Per Minute (Supply Air)Entering Air Temperature (dry bulb)Entering Air Temperature (wet bulb)Sensible Heat Capacity (1000 Btuh) GrossTotal Capacity (1000 Btuh) Gross15

Performance data (cont)50FC**07 HIGH STAGE COOLING CAPACITIES (SI)50FC**0714708 L/s17EAT(wb)19222414826 L/s17EAT(wb)19222414944 L/s17EAT(wb)192224141062 L/s17EAT(wb)192224141180 L/s17EAT(wb)192224LEGEND——EAT (db) —EAT (wb) 15.117.514.318.611.420.57.8——29EAT .016

ged — lightweight high impact com-posite fan blade WeatherMaker 50FC 5 ton units are specifically designed to fit on Carrier roof curbs that were installed back to 1989, which makes replacement easy and eliminates the need for curb adapt-ers or changing utility connections. All models are capable of either vertical or horizontal airflow.