Product Data - Climaproyectos S.A. De C.V.

Transcription

50TCSingle Package RooftopCooling OnlyHorizontal Air Flow Unitwith Puronr (R --- 410A) Refrigerant15, 17.5, 20, 25 Tons --- (Sizes 18, 21, 25, 29)Product DataC12590(Unit shown with economizer and power exhaust.)the environmentally sound refrigerant

TABLE OF CONTENTSPAGEPAGEFEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . 3APPLICATION/SELECTION DATA . . . . . . . . . . . . . . 23MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . 4COOLING CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . 25FACTORY OPTIONS & ACCESSORIES . . . . . . . . . . . 5STATIC PRESSURE ADDERS . . . . . . . . . . . . . . . . . . 33AHRI RATING TABLE . . . . . . . . . . . . . . . . . . . . . . . . . 9DAMPER, BAROMETRIC RELIEF & PE PERF . . . . 34MIN-- MAX AIRFLOWS CLG & ELECT HEAT . . . . . . 9FAN PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . 35SOUND PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . 9ELECTRICAL INFORMATION . . . . . . . . . . . . . . . . . 39PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . 53DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . 56OPTIONS & ACCESSORIES WEIGHT ADDERS . . . 23The 15 to 25 ton WeatherMaker Carrier rooftop unit (RTU) was designed by customers for customers. With a newlydesigned cabinet that integrates “no-- strip” screw collars, handled access panels, and more, we’ve made your unit easy toinstall, easy to maintain and easy to use and reliable.Easy to install:These WeatherMaker units are designed for dedicated factory supplied horizontal air flow duct configurations. No specialfield kits are required. Designed to fit on pre-- installed curbs by other another manufacturer, these units also fit on pastdesigned Carrier installed curbs with a new certified and authorized adapter curb. This cabinet design also integrates alarge control box that gives you room to work and room to mount Carrier accessory controls.Easy to maintain:Easy access handles by Carrier provide quick and easy access to all major, normally serviced components. Our “no-- strip”screw system has superior holding power and guides screws into position while preventing the screw from stripping theunit’s metal. Take accurate pressure readings by reading condenser pressure with panels in place as compressors arestrategically located to eliminate any air bypass.Easy to use:The newly designed, central terminal board by Carrier puts all your connections and troubleshooting points in oneconvenient place, standard. Most low voltage connections are made to the same board and make it easy to find what you’relooking for and easy to access it. Carrier rooftops have high and low pressure switches, a filter drier, and 2-- in (51mm)filters standard.Reliable:Each unit comes with precision sized and tested scroll compressor that is internally protected from over temperature andpressures. In addition, each refrigerant circuit is further protected with a high pressure and low pressure switch as well ascontaining a liquid line filter drier. Each unit is factory tested prior to shipment to help ensure units operation onceproperly installed.2

FEATURES AND BENEFITSS 2-- stage cooling capacity with independent circuits and control.S High performance copper tube / aluminum plate (RTPF) fin condenser and evaporator coils with optional coating.S EER’s up to 11.0S IEER’s up to 11.2 with single speed indoor fan motor and up to 12.9 with 2-- speed/VFD indoor fan motorS Dedicated horizontal air flow duct configuration models. No field kits required.S Utility connections through the side or bottom. Bottom connections are also in an enclosed environment to help preventwater entry. Field supplied couplings are required.S Standardized components and control box layout. Standardized components and controls make stocking parts and serviceeasier.S Scroll compressors on all units. This makes service, stocking parts, replacement, and trouble-- shooting easier.S Proven TXV refrigerant metering system.S Easy-- adjust, belt-- drive motor available. Motor assembly also contains a fan belt break protection system on all modelsand reliable pillow block bearing system that allows lubrication thru front of the unit.S Capable of thru-- the-- base electrical routing.S Full range of electric heaters and single point electric kits – pre-- engineered and approved for field installation.S Single-- point electrical connection.S Sloped, composite drain pan sheds water; and won’t rust.S Standardized controls and control box layout. Standardized components and controls make stocking parts and serviceeasier.S Clean, large, easy to use control box.S Color-- coded wiring.S Large, laminated wiring and power wiring drawings which are affixed to unit make troubleshooting easy.S Single, central terminal board for test and wiring connections.S Fast-- access, handled, panels for easy access on normally accessed service panels.S “No-- strip” screw system guides screws into the panel and captures them tightly without stripping the screw, the panel, orthe unit.S Mechanical cooling (115 F to 35 F / 46 C to 2 C) standard on all models. Low ambient controller allows operationdown to - 20 F / - 29 C.S 2-- in (51mm) disposable filters on all units, with 4-- in (102mm) filter track - field installed.S Refrigerant filter-- drier on each circuit.S High and low pressure switches. Added reliability with high pressure switch and low pressure switch.S Many factory-- installed options ranging from air management economizers, 2 position dampers, manual outdoor airdampers, plus convenience outlets, disconnect switch and smoke detectors.S Factory-- installed Humidi-- MiZerR adaptive dehumidification system.S Standard Parts Warranty: 10 year aluminized heat exchanger, 5 year compressor, condenser coil, 1 year others.S Optional Staged Air Volume (SAV) system utilizes a Variable Frequency Drive (VFD) to automatically adjust the indoorfan motor speed between cooling stages. Available on 2-- stage cooling models with electromechanical controls or RTUOpen.3

MODEL NUMBER NOMENCLATUREPosition:123456789 10 11 12 13 14 15 16 17 18Example:50TC-D25A5A5-0AA0Unit Heat Type50 - Electric HeatPackaged Rooftop0Packaging & Seismic Complience0 StandardElectrical OptionsA NoneC Non-Fused DisconnectG 2-Speed Indoor Fan (VFD) Controller(Standard on 29 size models)J 2 Speed Fan Controller (VFD) &Non-Fused DisconnectModel Series - WeatherMakerTMTC - Standard EfficiencyHeat Options– Standard, No Electric HeatRefrig. Systems OptionsD Two stage cooling modelE Two stage cooling models with Humidi-MiZerService Options0 None1 Unpowered Convenience Outlet2 Powered Convenience Outlet3 Hinged Panels4 Hinged Panels andUnpowered Convenience Outlet5 Hinged Panels andPowered Convenience OutletCooling Tons18 15 tons21 17.5 tons25 20 tons29 25 tonsSensor OptionsA NoneB RA Smoke DetectorC SA Smoke DetectorD RA SA Smoke DetectorE CO2F RA Smoke Detector and CO2G SA Smoke Detector and CO2H RA SA Smoke Detector and CO2Intake / Exhaust OptionsA NoneB Temperature Economizer w/ Barometric ReliefF Enthalpy Economizer w/ Barometric ReliefK 2-Position DamperU Temp Ultra Low Leak Economizer w/ Baro ReliefW Enthalpy Ultra Low Leak Economizer w/ Baro ReliefBase Unit Controls0 Electro mechanical controls. Can be used withW7212 EconoMi er IV (Non-Fault Detection &diagnostic)1 PremierLink Controller2 RTU Open Multi-Protocol Controller6 Electro mechanical controls. Can be used withW7220 EconoMi er X ( with Fault Detection &Diagnostic)Indoor Fan Options & Air Flow Configuration5 Standard Static/Horizontal Supply, Return Air Flow6 Medium Static/Horizontal Supply, Return Air Flow7 High Static/Horizontal Supply, Return Air FlowF Medium Static High Efficiency Motor/HorizontalSupply,Return Air FlowG High Static High Efficiency Motor/Horizontal Supply,Return Air FlowDesign Revision- Factory Design RevisionCoil Options – RTPF (Outdoor - Indoor - Hail Guard)A Al/Cu - Al/CuB Precoat Al/Cu - Al/CuC E-coat Al/Cu - Al/CuD E-coat Al/Cu - E-coat Al/CuE Cu/Cu - Al/CuF Cu/Cu - Cu/CuM Al/Cu -Al/Cu — Louvered Hail GuardN Precoat Al/Cu - Al/Cu — Louvered Hail GuardP E-coat Al/Cu - Al/Cu — Louvered Hail GuardQ E-coat Al/Cu - E-coat Al/Cu — Louvered Hail GuardR Cu/Cu - Al/Cu — Louvered Hail GuardS Cu/Cu - Cu/Cu — Louvered Hail GuardVoltage1 575/3/605 208-230/3/606 460/3/60Fig. 1 - Model Number Nomenclature (Example)4C13798C

Table 1 – FACTORY-- INSTALLED OPTIONS AND FIELD-- INSTALLED ACCESSORIESCATEGORYCabinetCoil OptionsHumidity ControlCondenser ProtectionControlsEconomizers& Outdoor AirDampersFACTORYINSTALLEDOPTIONITEMHinged Access PanelsCu/Cu indoor & outdoor coilsXXE ---coated indoor & outdoor coilsXPre ---coated outdoor coilsXHumidi ---MiZer Adaptive Dehumidification SystemCondenser coil hail guard (louvered design)Thermostats, temperature sensors, and subbasesXXPremierLink DDC communicating controllerXRTU Open protocol controllerXSmoke detector (supply and/or return air)XXEconoMi er IV for electro---mechanical controls --- Non FDD(Standard air leak damper models)6XXEconoMi er2 for DDC controls, complies with FDD (Standard and Ultra Low Leak air damper models)6,7XXMotorized 2 position outdoor ---air damperXXManual outdoor ---air damper (25%)BarometricXrelief1XXBarometric hood (Horizontal economizer)XEconoMi er X for electro---mechanical controls, complieswith FDD. (Standard and Ultra Low Leak air damper models)6XXDifferential dry bulb temperatureXsensors2XXSingle enthalpy sensors2XDifferential enthalpy sensors2XXmounted)2XElectric Resistance HeatersXXSingle Point KitXMultiple motor and drive packagesXIndoor Motor& DriveStaged Air Vol (SAV) system w/VFD controller (2---stage coolonly with electrical mechanical and RTU Open controls)Display Kit for SAV system with VFDLow AmbientControlWinter start kit3Roof CurbsXPhase MonitorCO2 sensor (wall, duct, or unitPowerOptionsXXSingle dry bulb temperature sensors2Electric HeatXXTime Guard II compressor delay control circuitPower exhaustEconomizer Sensors &IAQ DevicesFIELDINSTALLEDACCESSORYXXXMotorMaster head pressure controller to ---20 F(---29 C)3XConvenience outlet (powered)XConvenience outlet (unpowered)XNon ---fused disconnect4XRoof curb 14---in (356mm)XRoof curb 24---in (610mm)XNOTES:1. Included with economizer.2. Sensors for optimizing economizer.3. See application data for assistance.4. Non--- fused disconnect switch cannot be used when FLA electrical rating exceeds 100 amps at 460/575 volt and 200 amps at 208/230volt. Carrier RTUBuilder selects this automatically.5. Not for 48TJE028--- 028 models using 48DP900041, 48DP900051 or 48DP900061 roofcurbs.6. FDD --- (Fault Detection and Diagnostic) capability per California Title 24 section 120.2.7. Models with RTU Open DDC controls comply with California Title 24 Fault Detection and Diagnostic (FDD). PremierLink is non FDD.5

FACTORY OPTIONS AND/OR ACCESSORIESEconomizer (dry--bulb or enthalpy)Non--Fused DisconnectEconomizers save energy, money and improve comfortlevels in the conditioned space. They bring in fresh,outside air for ventilation; and provide cool outside air tocool your building. This also is the preferred method oflow ambient cooling. When integrated with CO2 sensors,economizers can provide even more savings by couplingthe ventilation air to only that amount required based onspace occupancy. Economizers are available, installed andtested by the factory, with either enthalpy or temperaturedry-- bulb inputs. There are also models forelectromechanical, direct digital controllers and singlespeed fan or 2-- speed indoor fan motors. Additionalsensors are available as accessories to optimize theeconomizer. Economizers include gravity controlledbarometric relief that helps equalize building pressure andambient air pressures. This can be a cost effective solutionto prevent building pressurization. Economizers areavailable in Ultra Low Leak and standard low leakversions.This OSHA-- compliant, factory-- installed, safety switchallows a service technician to locally secure power to therooftop.CO2 SensorRTU Open Protocol ControllerImproves productivity and saves money by working withthe economizer to intake only the correct amount ofoutside air for ventilation. As occupants fill your building,the CO2 sensor detects their presence through increasingCO2 levels, and opens the economizer appropriately.Connect the rooftop to an existing BAS without needingcomplicated translators or adapter modules using the RTUOpen controller. This new controller speaks the 4 mostcommon building automation system languages (Bacnet,Modbus, N2, and Lonworks). Use this controller whenyou have an existing BAS.When the occupants leave, the CO2 levels decrease, andthe sensor appropriately closes the economizer. Thisintelligent control of the ventilation air, called DemandControl Ventilation (DCV) reduces the overall load on therooftop, saving money.Smoke DetectorsTrust the experts. Smoke detectors make your applicationsafer and your job easier. Carrier smoke detectorsimmediately shut down the rooftop unit when smoke isdetected. They are available, installed by the factory, forsupply air, return air, or both.Louvered Hail GuardsSleek, louvered panels protect the condenser coil fromhail damage, foreign objects, and incidental contact.Convenience Outlet (powered or un--powered)Reduce service and/or installation costs by including aconvenience outlet in your specification. Carrier willinstall this service feature at our factory. Provides aconvenient, 15 amp, 115v GFCI receptacle with “Wet inUse” cover. The “powered” option allows the installer topower the outlet from the line side of the disconnect asrequired by code. The “unpowered” option is to bepowered from a separate 115/120v power source.Power Exhaust with Barometric ReliefSuperior internal building pressure control. Thisfield-- installed accessory or factory-- installed option mayeliminate the need for costly, external pressure controlfans.PremierLink, DDC ControllerThis CCN controller regulates your rooftop’s performanceto tighter tolerances and expanded limits, as well asfacilitates zoning systems and digital accessories. It alsounites your Carrier HVAC equipment together on one,coherent CCN network. The PremierLink can befactory-- installed, or easily field-- installed. Not availablewith 2-- speed indoor fan motor.Time Guard II Control CircuitThis accessory protects your compressor by preventingshort-- cycling in the event of some other failure, preventsthe compressor from restarting for 30 seconds afterstopping. Not required with PremierLinkr, RTU Open, orauthorized commercial thermostats.Filter or Fan Status SwitchesUse these differential pressure switches to detect a filterclog or indoor fan motor failure. When used inconjunction with a compatible unit controller/thermostat,the switches will activate an alarm to warn the appropriatepersonnel.Motorized 2--Position DamperThe new Carrier 2-- position, motorized outdoor air damperadmits up to 100% outside air. Using reliable, gear-- driventechnology, the 2-- position damper opens to allowventilation air and closes when the rooftop stops, stoppingunwanted infiltration.Manual OA DamperManual outdoor air dampers are an economical way tobring in ventilation air. The dampers are available in 25%versions.6

FACTORY OPTIONS AND/OR ACCESSORIES (cont.)Optional Humidi--MiZer AdaptiveDehumidification SystemCarrier’s Humidi-- MiZer adaptive dehumidificationsystem is an all-- inclusive factory installed option that canbe ordered with any WeatherMaker 50TC18-- 29 rooftopunit.This system expands the envelope of operation ofCarrier’s WeatherMaker rooftop products to provideunprecedented flexibility to meet year round comfortconditions.The Humidi-- MiZer adaptive dehumidification system hasthe industry’s only dual dehumidification mode setting.The Humidi-- MiZer system includes two new modes ofoperation.The WeatherMaker 50TC18-- 29 rooftop coupled with theHumidi-- MiZer system is capable of operating in normaldesign cooling mode, subcooling mode, and hot gas reheatmode. Normal design cooling mode is when the unit willoperate under its normal sequence of operation by cyclingcompressors to maintain comfort conditions.Subcooling mode will operate to satisfy part load typeconditions when the space requires combined sensible anda higher proportion of latent load control. Hot Gas Reheatmode will operate when outdoor temperatures diminishand the need for latent capacity is required for solehumidity control. Hot Gas Reheat mode will provideneutral air for maximum dehumidification operation.Staged Air Volume (SAV) Indoor Fan SpeedSystemCarrier’s Staged Air Volume (SAV) system saves energyand installation time by utilizing a Variable FrequencyDrive (VFD) to automatically adjust the indoor fan motorspeed in sequence with the units cooling operation. PerASHRAE 90.1 2010 standard section 6.4.3.10.b, duringthe first stage of cooling operation the VFD will adjust thefan motor to provide 2/3rd of the total cfm established forthe unit. When a call for the second stage of cooling isrequired, the VFD will allow the total cfm for the unitestablished (100%). During the heating mode the VFDwill allow total design cfm (100%) operation and duringthe ventilation mode the VFD will allow operation to2/3rd of total cfm.Compared to single speed indoor fan motor systems,Carrier’s SAV system can save substantial energy, 25% *,versus single speed indoor fan motor systems.The VFD used in Carrier’s SAV system has soft startcapabilities to slowly ramp up the speeds, thus eliminatingany high inrush air volume during initial start-- up. It alsohas internal over current protection for the fan motor anda field installed display kit that allows adjustment and indepth diagnostics of the VFD.This SAV system is available on models with 2-- stagecooling operation with electrical mechanical or RTUOpen, Multi Protocol controls. Both space sensor andconventional thermostats controls can be used to provideaccurate control in any application.The SAV system is very flexible for initial fanperformance set up and adjustment. The standard factoryshipped VFD is pre-- programmed to automatically stagethe fan speed between the first and second stage ofcooling. The unit fan performance static pressure and cfmcan be easily adjusted using the traditional means ofpulley adjustments. The other means to adjust the unitstatic and cfm performance is to utilize the field installedDisplay Kit and adjust the frequency and voltage in theVFD to required performance requirements. In either case,once set up, the VFD will automatically adjust the speedbetween the cooling stage operations.*Data based on .10 ( /kWh) in an office applicationutilizing Carrier’s HAP 4.6 simulation software programMotormaster Head Pressure ControllerThe Motormaster motor controller is a low ambient, headpressure controller kit that is designed to maintain theunit’s condenser head pressure during periods of lowambient cooling operation. This device should be used asan alternative to economizer free cooling not wheneconomizer usage is either not appropriate or desired. TheMotormaster will either cycle the outdoor-- fan motors oroperate them at reduced speed to maintain the unitoperation, depending on the model.MotorMaster allows cooling operation down to - 20 F(-- 29 C) ambient conditions.Winter Start KitThe winter start kit by Carrier extends the low ambientlimit of your rooftop to 25 F (-- 4 C). The kit bypasses thelow pressure switch, preventing nuisance tripping of thelow pressure switch. Other low ambient precautions maystill be prudent.Alternate Motors and DrivesSome applications need larger horsepower motors, someneed more airflow, and some need both. Regardless of thecase, your Carrier expert has a factory installedcombination to meet your application. A wide selection ofmotors and pulleys (drives) are available, factoryinstalled, to handle nearly any application.Thru--the--Base ConnectionsThru-- the-- base provisions/connection points are availableas standard with every unit. When bottom connections arerequired, field furnished couplings are required.7

FACTORY OPTIONS AND/OR ACCESSORIES (cont.)Hinged Access PanelsAllows access to unit’s major components withspecifically designed hinged access panels. Panels are:filter, control box and fan motor.Electric Heaters / Single Point KitCarrier offers a full-- line of field-- installed accessoryheaters and single point kits when required. The heatersare very easy to use, install and are all pre-- engineered andcertified.Carrier Energy Demand System(EDS)The Energy Demand System is as easy to install asthermostats, and requires no special training. Everycontroller has a built-- in self-- configuring wirelessnetwork. The controllers work together to establish awireless network, eliminating the need for expensivewiring. The secure web portal allows property managersto easily access multiple sites from any internetconnection to monitor building performance andreconfigure controllers for demand response or thescheduling of loads.S Simple, affordable, wireless electrical demandmanagementCarrier’s wireless automated demand management anddemand response controllers can be easily installed ontoany packaged rooftop unit. Once installed, the controllerswork together like a swarm of bees, intelligentlycommunicating and managing the duty cycles of the unitsbeing controlled.S Automated demand response, including Open matically reduce peak electrical demand by up to 30percent in commercial and light industrial properties andallow for effective scheduling of overnight and weekendloads. This platform can easily be installed when a fullbuilding automation system is not required.S Electrical demand reductionsS Energy consumption reduction through efficientschedule-- based controlS Intelligent, adaptive energy managementS Web-- based interfaceS Reduce energy costs, not comfortBarometric HoodFor Horizontal Economizer applications where reliefdamper is installed in duct work. This kit provides theneeded protection.8

Table 2 – AHRI COOLING RATING TABLE 2-- STAGE .0282.0LEGENDAHRI--- Air Conditioning, Heating and RefrigerationInstitute Test StandardASHRAE --- American Society of Heating, Refrigeratingand Air Conditioning, Inc.EER--- Energy Efficiency RatioIEER--- Integrated Energy Efficiency Ratio*--- Model only available with 2--- Speed indoor Fan MotorUse of the AHRI CertifiedTM Mark indicates amanufacturer’sparticipation in theprogram For verificationof certification for individualproducts, go towww.ahridirectory.org.TOTALPOWER (kW)EER15.818.421.128.211.011.011.010.0IEER WITHSINGLE SPEEDINDOORMOTOR11.211.211.2N/A*IEER WITH2---SPEEDINDOORMOTOR12.912.912.911.2NOTES1. Rated and certified under AHRI Standard 340/360, as appropriate.2. Ratings are based on:Cooling Standard: 80 F (27 C) db, 67 F (19 C) wb indoor airtemp and 95 F db outdoor air temp.IEER Standard: A measure that expresses cooling part--- loadEER efficiency for commercial unitary air conditioning and heatpump equipment on the basis of weighted operation at variousload capacities.3. All 50TC units comply with ASHRAE 90.1 Energy Standard forminimum EER and IEER requirements.4. Where appropriate, 50TC units comply with US Energy PolicyAct. Refer to state and local codes or visit the following website:http://bcap --- energy. org to determine if compliance with thisstandard pertains to your state, territory, or municipality.Table 3 – MINIMUM - MAXIMUM AIRFLOWS (CFM) COOLING AND ELECTRIC HEATNominalkWModel SizeMinimumSingle SpeedFan mMinimum2---Speed Fan2---Speed FanMotorMotor(at high speed)(at low speed)ELECTRIC 0075008450557712500700012500Table 4 – SOUND PERFORMANCE TABLEOUTDOOR SOUND (dB)MODELSIZECLGSTAGES182125292222LEGENDdB --- DecibelA TES:1. Outdoor sound data is measure in accordance with AHRIstandard 270--- 2008.2. Measurements are expressed in terms of sound power. Donot compare these values to sound pressure values becausesound pressure depends on specific environmental factorswhich normally do not match individual applications. Soundpower values are independent of the environment and therefore more accurate.3. A--- weighted sound ratings filter out very high and very lowfrequencies, to better approximate the response of “average”human ear. A--- weighted measurements for Carrier units aretaken in accordance with AHRI standard 270--- 2008.9

Table 5 – PHYSICAL DATARTPF (Round Tube/Plate Fin Coil Design)(COOLING)15-- 25 TONS50TC ---D1850TC ---E1850TC ---D2150TC ---E212 / 2 / Scroll17/16.4TXV630 / 50554 / 1172 / 2 / Scroll24.5/25.7TXV630 / 50527 / 442 / 2 / Scroll17.5/16.8TXV630 / 50554 / 1172 / 2 / Scroll25.5/25.5TXV630 / 50527 / 44Cu / Al3/8” RTPF4 / 15223/4”Cu / Al3/8” RTPF4 / 15223/4”Cu / Al3/8” RTPF4 / 15223/4”Cu / Al3/8” RTPF4 / 15223/4”n/an/an/an/aCu / Al3/8” RTPF1 / 1722n/an/an/an/aCu / Al3/8” RTPF1 / 1722StandardStaticMotor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt2.2514--- 680562 / Centrifugal18 x 15/15 X 111/1/ Belt2.2514--- 680562 / Centrifugal18 x 15/15 X 111/1/ Belt3.3622--- 822562 / Centrifugal18 x 15/15 X 111/1/ Belt3.3622--- 822562 / Centrifugal18 x 15/15 X 11MediumStaticMotor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt3.3614--- 780562 / Centrifugal18 x 15/15 X 111/1/ Belt3.3614--- 780562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9713--- 879562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9713--- 879562 / Centrifugal18 x 15/15 X 11HighStaticMotor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt4.9746--- 912562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9746--- 912562 / Centrifugal18 x 15/15 X High EffMotor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)n/an/an/an/an/an/an/an/an/an/an/an/a1/1/ Belt6.5/ 6.9/ 7.0/ 8.3882--- 1078184T2 / Centrifugal18 x 15/15 X 111/1/ Belt6.5/ 6.9/ 7.0/ 8.3882--- 1078184T2 / Centrifugal18 x 15/15 X 11Refrigeration System# Circuits / # Comp. / TypeR--- 410a charge A/B (lbs)Metering deviceHigh--- press. Trip / Reset (psig)Low--- press. Trip / Reset (psig)MaterialTube DiameterRows / FPItotal face area (ft2)Condensate drain conn. sizeHumidimizer CoilMaterialTube DiameterRows / FPItotal face area (ft2)Evap. fan and motor10

Table 5 PHYSICAL DATA (cont.)RTPF (Round Tube/Plate Fin Coil Design)(COOLING)15-- 25 TONS50TC ---D2550TC ---E2550TC ---D2950TC ---E292 / 2 / Scroll23.8/23.1TXV630 / 50554 / 1172 / 2 / Scroll30.0/30.7TXV630 / 50527 / 442 / 2 / Scroll24.9/27.7TXV630 / 50554 / 1172 / 2 / Scroll35.1/35.4TXV630 / 50527 / 44Cu / Al3/8” RTPF4 / 15263/4”Cu / Al3/8” RTPF4 / 15263/4”Cu / Al3/8” RTPF4 / 15263/4”Cu / Al3/8” RTPF4 / 15263/4”n/an/an/an/aCu / Al3/8” RTPF1 / 1726n/an/an/an/aCu / Al3/8” RTPF1 / 1726Standard StaticMotor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt4.9690--- 863562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9690--- 863562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9647--- 791562 / Centrifugal18 x 15/15 X 111/1/ Belt4.9647--- 791562 / Centrifugal18 x 15/15 X 11Medium Static--- High Eff.Motor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt6.5/ 6.9/ 7.0/ 8.3835--- 1021184T2 / Centrifugal18 x 15/15 X 111/1/ Belt6.5/ 6.9/ 7.0/ 8.3835--- 1021184T2 / Centrifugal18 x 15/15 X 111/1/ Belt6.5/ 6.9/ 7.0/ 8.3755--- 923184T2 / Centrifugal18 x 15/15 X 111/1/ Belt6.5/ 6.9/ 7.0/ 8.3755--- 923184T2 / Centrifugal18 x 15/15 X 11High Static--High Eff.Motor Qty / Belt Qty / Driver TypeMax BHPRPM rangemotor frame sizeFan Qty / TypeFan Diameter (in)1/1/ Belt10.5/11.9/11.9/11941--- 1176213T2 / Centrifugal18 x 15/15 X 111/1/ Belt10.5/11.9/11.9/11941--- 1176213T2 / Centrifugal18 x 15/15 X 111/1/ Belt10.5/11.9/11.9/11827--- 1010213T2 / Centrifugal18 x 15/15 X 111/1/ Belt10.5/11.9/11.9/11827--- 1010213T2 / Centrifugal18 x 15/15 X 11Refrigeration System# Circuits / # Comp. / TypeR--- 410a charge A/B (lbs)Metering deviceHigh--- press. Trip / Reset (psig)Low--- press. Trip / Reset (psig)MaterialTube DiameterRows / FPItotal face area (ft2)Condensate drain conn. sizeHumidimizer CoilMaterialTube DiameterRows / FPItotal face area (ft2)Evap. fan and motor11

Table 5 PHYSICAL DATA (cont.)RTPF (Round Tube/Plate Fin Coil Design)(COOLING)15-- 25 TONS50TC --- D1850TC --- E1850TC --- D2150TC --- E2150TC --- D2550TC --- E2550TC --- D2950TC --- E29Cond. Coil (Circuit A)RTPFRTPFRTPFRTPFRTPFRTPFRTPFRTPFCoil Length (in)Coil type7070727282829595Coil Height (in)4444444452525252Rows / FPI2 /172 /172 /172 /172 /172 /172 /172 /17total face area (ft2)21.421.422.022.029.629.634.334.3Cond. Coil (Circuit B)RTPFRTPFRTPFRTPFRTPFRTPFRTPFRTPFCoil Length (in)Coil type7070646480809595Coil Height (in)4444444452525252Rows / FPI2 /172 /172 /172 /172 /172 /172 /172 /17total face area (ft2)21.421.419.519.529.629.634.334.3Cond. fan / motorQty / Motor drive type3 / direct3 / direct4 / direct4 / direct4/ direct4/ direct6 / direct6 / directMotor HP / RPM1/4 / 11001/4 / 11001/4 / 11001/4 / 11001/4 / 11001/4 / 11001/4 / 11001/4 / 1100Fan diameter (in)22222222222

with Puronr (R---410A) Refrigerant 15, 17.5, 20, . The 15 to 25 ton WeatherMaker Carrier rooftop unit (RTU) was designed by customers for customers. With a newly . G High Static High Efficiency Motor/Horizontal Supply, Return Air Flow Refrig. Systems Opt ions D Two stage cooling model