Knauf Data SheetSonic XP Duct Liner with ECOSE TechnologyCI-DLS-DS 04-14

Sonic XP Duct Liner with ECOSE TechnologyDescriptionKnauf Insulation Sonic XP Duct Liner is a flexible,mat-faced insulation bonded with ECOSE Technology. It is faced with a tightly bonded matto give the airstream a smooth, tough surface,resisting damage during installation and operation.The encapsulant edge coating eliminates airstreamflaring.ECOSE TechnologyECOSE Technology is a revolutionary binderchemistry that makes Knauf Insulation productseven more sustainable than ever. It features rapidlyrenewable bio-based materials rather than nonrenewable petroleum-based chemicals traditionallyused in glass mineral wool insulation products.ECOSE Technology reduces binder embodiedenergy and does not contain phenol, acrylics orartificial colors.ApplicationSpecifically designed as an interior insulation materialfor sheet metal ducts used in heating, ventilating andair conditioning. Provides an optimum combination ofefficient sound absorption, low thermal conductivityand minimal airstream surface friction.Features and Benefits Low thermal conductivity Fire-resistant, non-corrosive, durable and resilient Tough, tightly bonded mat facing Excellent sound absorption Energy conservation Better temperature control I f necessary, can be cleaned in accordance withNAIMA’s “Cleaning Fibrous Glass Insulated AirDuct Systems Recommended Practices.”Technical Data Knauf Insulation achieved UL GREENGUARDGold Certification. Products are certified to ULGREENGUARD standards for low chemicalemissions into indoor air during productusage. Knauf Insulation has achieved a ULEnvironment claim validation for minimum 50%post-consumer recycled glass content in ourinsulation products. UL GREENGUARD CertifiedSustainabilityAir Velocity (ASTM C 1071) Carbon negative: meaning Knauf Insulationproducts used for thermal insulating purposesrecover the energy that it took to make themin just hours or a few days, depending onthe application. Once installed, the productcontinues to save energy and reduce carbongeneration as long as it is in place. Maximum 6000 fpm (1829 mpm) Glass mineral wool insulation with ECOSETechnology contains three primary ingredients: Sand, one of the world’s most abundantand renewable resources A minimum 50% recycled post-consumerglass content and UL Environmentverification every 6 months ECOSE Technology which reduces binderembodied energy by up to 70% UL GREENGUARD GOLD Certified Does not exceed 25 Flame Spread, 50 SmokeDeveloped when tested in accordance with UL723, ASTM E 84, UL/ULC S102-M88 and NFPA255.Temperature Range (ASTM C 411) Up to 250 F (121 C) Tested to 15,000 fpm (4572 mpm)Corrosiveness (ASTM C 665) Does not accelerate corrosion on steel,copper or aluminumCorrosion (ASTM C 1617) T he corrosion rate in mils/yr will not exceed thatof the 1 ppm chloride solution.Water Vapor Sorption (ASTM C 1104) Less than 3% by weightWater Repellency (INDA IST 80.6-92) 4Microbial Growth (ASTM C 1338) Airstream surface mat facing is treated with anEPA-registered anti-microbial agent to aid in theprevention of fungal and bacterial growth.Specification ComplianceIn U.S.: Does not promote or support the growth of mold,fungi or bacteria. ASTM C 1071; Type IMicrobial Resistance T his product does not contain polybrominateddiphenyl ethers (PBDE) such as Penta-BDE,Octa-BDE, or Deca-BDE. Lowers operating costs ASTM G 21 Greatly reduces noise from fans and mechanicalequipment as well as cross-talk and airmovementIn Canada: CAN/ULC S102-M88 W ithstands damage from normal handling andshop abuseSurface Burning Characteristics UL/ULC classified NFPA 90A and 90B CAN/CGSB-51.11-92 T ested and certified to meet all the requirementsof EUCEB.Application & Specification GuidelinesStorage Inside storage is recommended.Fabrication and Application F abricate in compliance with the latest edition ofNAIMA’s Fibrous Glass Duct Liner Standard.

Mechanical Fastener LocationSound Absorption Coefficients (ASTM C 423, Type A Mounting)Octave Band Center Frequency (cycles/sec.)Type125250500100020004000NRC1.5 PCF1" (24 kg/m3 25 mm).18.36.59.86.95.90.701.5 PCF1.5" (24 kg/m3 38 mm).35.51.83.93.97.96.801.5 PCF2"(24 kg/m3 51 mm).34.64.961.031.001.03.902.0 PCF.5"(32 kg/m3 13 mm).09.14.40.60.73.82.452.0 PCF1"(32 kg/m3 25 mm).25.35.69.89.961.01.702.0 PCF1.5"(24 kg/m3 38 mm).27.55.87.991.00.98.85Coefficients determined per ASTM E 795 Type A Mounting.NOTE: ASHRAE Handbook for HVAC Applications – Sound and Vibration Control contains insertion loss values for lined sheet metal 15000(12.725.4)A From cornersof duct4"(102 mm)4"(102 mm)B From transverseof duct3"(76 mm)3"(76 mm)C Across width ofduct, on centers(min. 1/side)12"(305 mm)6"(152 mm)D Across length ofduct, on centers(min. 1/side)18"(457 mm)16"(406 mm)Friction Loss (Inches of water per 100')(HD Hydraulic Diameter)f (in. of H2O per 100 ft.)10.0001.0000.1000.010Liner Interior Width0.001100100010000VELOCITY (FPM)FPMHydraulic 867.422.283No. PinsInches(mm)0 8 35989-1002261-2540

Thermal Conductance “C”* and Resistance “R”† (ASTN C 177)Mean Temperature 75 F (24 C)ProductConductance “C”Resistance “R”1.5 PCF1"(24 kg/m 25 mm).24(1.42)4.2(.74)1.5 PCF1.5"(24 kg/m3 38 mm).17(.97)6.0(1.06)1.5 PCF2"(24 kg/m3 51 mm).13(.74)8.0(1.41)2.0 PCF.5"(32 kg/m3 13 mm).48(2.73)2.1(.37)2.0 PCF1"3(32 kg/m 25 mm).24(1.36)4.2(.74)2.0 PCF1.5"(32 kg/m3 38 mm).16(.91)6.3(1.11)“C” Units:3BTUft² hr FWm² C* The lower the value, the better the performance.†“R” Units:ft² hr FBTUThe higher the value, the better the ’(15.24 m)(30.48 m)(42.67 m)(60.96 m)1.5 PCF1"1.5 PCF1.5"46" - 48"(1168 mm - 1219 mm)50'90’(15.24 m)(27.43 m)1.5 PCF2"56" - 72"(1422 mm - 1829 mm)50'100'(15.24 m)(30.48 m)2.0 PCF.5"100’(30.48 m)2.0 PCF1”50’100’(15.24 m)(30.48 m)34"- 36"*(864 mm - 915 mm) Liner should be adhered to the duct with90% minimum area coverage of an adhesivewhich conforms to ASTM C 916. Mechanical fasteners should not compressthe insulation more than ⅛" (3 mm), andshall be installed perpendicular to the ductsurface. All fasteners should comply withthe guidelines of NAIMA’s Fibrous GlassDuct Liner Standard and the MechanicalFastener’s Standard MF-1-1975.m² CWForms AvailableDensity Liner shall be folded and compressed in thecorners of rectangular duct sections or shallbe cut and fit to assure lapped, compressedjoints. Longitudinal joints in duct liner shouldnot occur except at the corner of ducts.Longitudinal joints in liner shall be coatedwith adhesive. All damaged areas of the airstream surface shall be repaired with anadhesive which conforms to ASTM C 916.*Widths of 34″-36″ not available with edge coating.**Non-standard widths for all .5″, 1″, 1.5″, and 2″ products from 34″-36″, 46″-48″ and 56″-72″ are available in 25″ (6.35 mm) increments ofminimum order quantity. Metal nosings shall be securely installed overtransversely oriented liner edges facing theairstream at fan discharge, at access doorsand at any interval of lined duct precededby unlined duct. In addition, where velocitiesexceed 4000 fpm (1219 mpm), metal nosingsmall be used on upstream edges of liner atevery transverse joint (See illustration)Limitations Knauf Sonic XP Duct Liner with ECOSETechnology should not be used in systemsoperating at velocities exceeding 6000 fpm(1829 mpm) or at temperatures above 250 F(121 C).Glass Mineral Wool and MoldGlass mineral wool insulation will not sustain moldgrowth. However, mold can grow on almost anymaterial when it becomes wet and contaminated.Carefully inspect any insulation that has beenexposed to water. If it shows any sign of mold,it must be discarded. If the material is wet butshows no evidence of mold, it should be driedrapidly and thoroughly. If it shows signs of facingdegradation from wetting, it should be replaced.Air handling insulation used in the air stream mustbe discarded if exposed to water.For more information call (800) 825-4434, ext. 8283or visit us online at www.knaufinsulation.us

Consistent blanket thicknessand uniform glass mineralwool distribution providesefficient and hassle-freecutting and pinning on allfabrication processes. Ultra-fast Roto Zipprocessessing speedwith Knauf Sonic XP Duct Liner. Stands up to abuse—Sonic XP Duct Liner’stough mat facing is durableenough to withstand shopand job site wear and tear. The encapsulant edgecoating eliminatesairstream flaring. The natural brown baseblanket with ECOSE Technology binder has noadded phenol, formaldehyde,acrylics or artificial colors.Facts at a glance Excellent sound absorption reduces noise from fans,mechanical equipment, cross-talk and air movement. NRC rating of .70 (1.5 PCF, 1”). More cost-effective than alternative closed cell duct liners. Certified for indoor air quality as a low emitting product byUL Environment. ECOSE Technology is a revolutionary binder based on rapidly renewable bio-basedmaterials rather than non-renewable petroleum-based chemicals such as phenol,formaldehyde, acrylics or artificial colors.

Knauf Insulation GmbHOne Knauf DriveShelbyville, IN 46176Sales(800) 825-4434, ext. 8283Technical Support(800) 825-4434, ext. 8512Fax(317) itewww.knaufinsulation.us 2014 Knauf Insulation GmbH.leed Eligible ProductUse of this product may helpbuilding projects meet green buildingstandards as set by the Leadershipin Energy and Environmental Design(LEED) Green Building Rating System.This product has beentested and is certifiedto meet the EUCEBrequirements.LEED V 4 - Credit MR 3 - Regional MaterialsLEED V 4 - Credit MR 4 - Recycled ContentGREENGUARD GoldKnauf Insulation Sonic XP Duct Liner with ECOSE Technology iscertified by UL GREENGUARD for indoor air quality as low emittingproducts, have achieved UL GREENGUARD Gold certification.Post-Consumer Recycled Glass ContentKnauf Insulation has achieved a UL Environment claim validation forminimum 50% post-consumer recycled glass content in our insulationproducts.

Duct Liner Standard and the Mechanical Fastener's Standard MF-1-1975. Metal nosings shall be securely installed over transversely oriented liner edges facing the airstream at fan discharge, at access doors and at any interval of lined duct preceded by unlined duct. In addition, where velocities exceed 4000 fpm (1219 mpm), metal nosing