DeltaV Distributed Control SystemProduct Data SheetSeptember 2018S-series Virtual I/O Module 2 Non-intrusive DeltaV I/O simulation Powerful integration solution Easy to use Modular, flexible packagingThe S-series Virtual I/O Module 2 provides DeltaV I/O simulationand a high speed Ethernet I/O device integration platform.IntroductionBenefitsThe DeltaV S-series Virtual I/O Module 2 (VIM2) providesnonintrusive simulation of the DeltaV S-series I/O Cards anddigital bus field devices for process simulation when used withEmerson’s Mimic Simulation Software. DeltaV control strategiesand system configurations can be fully tested with this powerfulsimulation interface.Non-Intrusive DeltaV I/O simulation. Use the VIM2 inconjunction with Emerson’s Mimic Simulation Software tosimulate your DeltaV S-series I/O and digital bus field devices.The VIM2 also provides an interface to Ethernet I/O networksand devices that use the Modbus TCP or EtherNet/IP protocoldrivers. DeltaV S-series controllers can read and write signalsfrom plant floor devices connected to Ethernet I/O networkssuch as PLC’s, Motor Control Centers, and Weigh Scales. Supports DeltaV I/O modules. Provides completely nonintrusive simulation of all DeltaV S-series I/O Modules.Supports autosensing of I/O and accurate testing of controllerloading. DeltaV configuration can be fully tested withoutmodifying the control strategies. Digital bus support. Provides simulation of all DeltaV DigitalBusses and Foundation Fieldbus function blocks. SupportsFoundation Fieldbus control in the field configuration testing. Powerful simulation solution. Provides full simulation of upto 64 DeltaV I/O modules per controller. Simulation executionis fast and efficient; the DeltaV controller thinks it’s talkingwith real I/O.

S-series Virtual I/O Module 2Powerful integration solution. Use the VIM2 in conjunctionwith the Ethernet I/O drivers to integrate your DeltaV systemwith your Ethernet I/O device networks. Large device capacity. Each VIM2 emulates four DeltaVSerial Cards and supports up to 128 Serial Card Datasets ofinformation from up to 128 network devices in simplex andup to 256 in dual simplex installations as well as 16 devices inredundant installations. Communication over the EthernetI/O device network is fast and efficient.Flexible networking. User configurable IP addressingallows the VIM2 to be used in almost any plant environmentregardless of networking scheme. The VIM2 and the EthernetI/O devices must be on the same IP subnet to communicate.1:1 Redundancy. Redundancy can be achieved by adding asecond VIM2 and configuring the two cards as a redundantpair - when supported by the protocol. The VIM2 appearsas four redundant DeltaV Serial Card pairs. Automaticswitchover of primary to standby cards is handled like theDeltaV Serial Card. The operator is given clear notificationof a switchover at the operator display. Manual switchovercan be controlled in DeltaV Diagnostics.September 2018 Configured in DeltaV Explorer. When serial datasetconfiguration is used for the Ethernet I/O integration, it isdone in the DeltaV Explorer in the same manner as a DeltaVSerial Card. Ethernet I/O signals can be used in DeltaV ControlModules, displayed on DeltaV Operate graphics, and stored inthe DeltaV Continuous Historian. Intuitive setup. The VIMNet Explorer application providesplug-n-play capability making setup of the VIM2 easy andintuitive. Graphical drag-n-drop functionality makes settingup multiple VIM2s almost effortless. VIMNet Explorer isintegrated with DeltaV Explorer to make setup of the VIM2easy and intuitive.Modular, flexible packaging. The VIM2 mounts in the samemanner as the DeltaV controller. It mounts in the controller slotof a DeltaV 2-wide horizontal carrier and uses a standard DeltaVSystem Power Supply. The advanced design of the VIM2 willprovide years of uninterrupted use.Easy to use. The VIM2 is easy to use and well integrated intothe DeltaV system. Specific ease of use features include: Automatic updates. Simulation I/O driver updates for theVIM2 are included with the Mimic software releases.Updates are quick and easy over the simulation network. Seamless Ethernet I/O integration. When used with theEthernet I/O drivers, the VIM2 is seen by the DeltaV S-seriescontroller as four DeltaV Serial Cards. Commissioned VIM2sare then auto-sensed by the DeltaV controller as DeltaVSerial Cards.S-series System Power supply and VIM2.www.emerson.com/deltav2

S-series Virtual I/O Module 2Product DescriptionThe VIM2 may be used for either DeltaV I/O simulation orEthernet I/O device integration. The VIM2 mounts on a 2-widecarrier on either side of the DeltaV controller. A dedicatedDeltaV system power supply is required.IO Simulation. When used with Mimic Simulation Software,the VIM2 supports I/O simulation for all DeltaV S-series I/Ocards including classic IO, Foundation Fieldbus, ProfibusDP,DeviceNet, ASi-bus and Serial.Mimic Simulation Software provide dynamic simulation forDeltaV system software acceptance testing and operatortraining. The Mimic software works by simulating the DeltaVI/O. It also simulates field devices using Foundation Fieldbus,ProfibusDP, DeviceNet and AS-i bus. In order for Mimic to dothis, the real I/O cards are disconnected from the controlsystem. The Mimic driver writes to the I/O subsystem of theDeltaV controller. Process models in Mimic simulate realisticprocess reactions to control system output signals.The I/O simulation driver is provided with the VIM2 hardware,pre-loaded in the VIM2. Mimic Simulation Software must bepurchased separately. Technical support for Mimic SimulationSoftware and the I/O simulation driver is available.Ethernet I/O integration. When used with the Ethernet I/Odrivers, the VIM2 can communicate with high- speed Ethernetnetworks over Modbus TCP or Ethernet/IP. Depending on whichEtherNet I/O driver is used to configure the VIM2, the DeltaVController auto-senses a commissioned VIM2 as four or eightDeltaV Serial Cards or DeviceNet Cards.Ethernet I/O integration. When used with the MYNAHEthernet I/O drivers, the VIM2 can communicate with highspeed Ethernet networks over Modbus TCP or Ethernet/IP.Depending on which EtherNet I/O driver is used to configure theVIM2, the DeltaV Controller auto-senses a commissioned VIM2as four or eight DeltaV Serial Cards or DeviceNet Cards. In simplex installations these cards will be sensed in slots57-60 or 61-64. In dual simplex installations these cards will be sensed inslots 57 to 64.September 2018VIMNet Explorer. The VIMNet Explorer utility allows theuser to commission the VIM2, setup primary, secondary, and/or redundant VIM2s, and the Ethernet I/O network. The useris able to specify the IP address, Subnet Mask, and Gatewayof each VIM2 and set the node address and names of eachEthernet I/O device that is used by the VIM2. The VIMNetExplorer is also used to flash upgrade a VIM2 from one versionof a driver to another or to replace an existing driver type withanother. Only one Ethernet I/O driver may be loaded in theVIM2 at one time.The VIMNet Explorer application must run on a workstation thathas network connectivity to the Ethernet I/O network. This maybe a DeltaV workstation with the third network interface card(NIC) connected to the Ethernet I/O network or may be a nonDeltaV workstation. Connection to the VIM2 is done throughthe RJ-45 Network Connection on the bottom of the VIM2.The VIMNet Explorer software installation file for the VIM2is available on a DeltaV v12 and later workstation and on theDeltaV v12 and later software installation DVD. The VIMNetExplorer software installation file is also provided with thepurchase of an Ethernet I/O driver.VIM2 dual simplex or redundant setups. Two VIM2scan either be setup as a dual simplex or redundant pair forinstallations that either consist of a lot of slaves or requiresbackup Ethernet I/O networks. Each VIM2 will be installed on itsown 2-wide carrier, with its own system power supply to the leftside of simplex or redundant DeltaV Controllers.If they are setup for dual simplex operation, both VIM2s willwork as standalone units, therefore no need for the redundancylink cable. If they are setup for redundant operation, the activeand standby VIM2s monitor each other with a continuousstatus command using the redundancy link cable supplied witheach redundant pair. The active VIM2 communicates over thenetwork to the Industrial Ethernet device and the standby sendsan intermittent signal to the device to maintain communicationintegrity. The Ethernet I/O drivers are not provided with theVIM2 hardware; they must be purchased. Technical support forthe Ethernet I/O drivers is available.In redundant installations the redundant pairs will be sensedin slots 57 to 64. Configuration of the I/O signals from thecommissioned VIM2 is done in the DeltaV Explorer in the samemanner as either for a DeltaV Serial or DeviceNet Card.www.emerson.com/deltav3

S-series Virtual I/O Module 2September 2018The DeltaV system with S-series VIM2 and Ethernet I/O integration (simplex VIM2 and DeltaV controller shown).Supported IndustrialEthernet Protocols Code 8 - Diagnostic Loop Back Test Code 15 - Force Multiple CoilsModbus TCP. The VIM2 with the Modbus TCP Master Driversupports the following Modbus communications protocolfunction codes to read and write values to and from a Modbusslave device, as specified by the Modbus Application ProtocolSpecification from Modbus-IDA.org. Code 16 - Preset Multiple RegistersThe VIM2 Modbus TCP/IP Driver supports the followingModbus function codes: Code 1 - Read Coil Status Code 2 - Read Input Status Code 3 - Read Holding Registers Code 4 - Read Input Registers Code 5 - Force Single Coil Code 6 - Preset Single Registerwww.emerson.com/deltavThe VIM2 can function as both a Modbus TCP master and slavesimultaneously. Master or slave mode is set at the virtual portlevel. In master-only mode, this driver can communicate witha maximum of 96 slave devices in a simplex and with 192 slavedevices in dual simplex setups. Systems that use both masterand slave mode can communicate with a maximum of 32slaves and 32 masters at the same time. The master and slavecapability is available in simplex implementations only.In redundant applications, only master mode is supported.4

S-series Virtual I/O Module 2Ethernet/IP. The VIM2 with the EtherNet/IP Scanner Driverprovides the following compatible functions using theCommon Industrial Protocol (CIP) as defined in the EtherNet/IP Specification from Open DeviceNet Vendor Association andControlNet International.September 2018The VIM2 ODVA EtherNet/IP Driver provides: I/O Scanner (Transport Class 1 originator, using connectedimplicit messaging) I/O Adapter (Transport Class 1 target, using connectedimplicit messaging) Unconnected explicit (UCMM) messaging client Connected explicit (Transport Class 3 originator)messaging clientThe VIM2 EtherNet/IP Scanner Driver provides: IO Adapter (Transport Class 1 target, using connectedimplicit messaging)Unconnected explicit (UCMM) messaging client- Embedded DF1 (PCCC)Embedded DF1 is supported in simplex, dual simplex, andredundant configurations. IO Adapter messaging is supportedonly in simplex and dual simplex configurations.This driver can communicate with a maximum of 32 slavedevices in a simplex and with 64 slave devices in dualsimplex setups. In redundant applications, only 16 slavedevices are supported.FMC722 Subsea. The VIM2 with the FMC722 Driver supportscommunications with FMC Technologies Topside ProcessingUnit (TPU) using the FMC722 (TPC) protocol.A maximum of 32/64 slave devices is supported with theFMC722 Subsea driver.This driver can only communicate in a simplex or dualsimplex setup. A maximum of 128 slave devices in a simplexand 256 slave devices in dual simplex setups is supported.PROFINET. The VIM2 with the PROFINET Driver acts as an I/OController in a PROFINET network, exchanging data with I/ODevices using Real-Time (RT) messaging. Isochronous realtime (IRT) communication is not supported. It supports thePROFINET v2.2 specification.Field device communications comprise I/O data, alarms anddiagnostics. Other aspects of field data, e.g. data records andlogbook information, are not supported. Alarm and diagnosticinformation is reported to PC based VIMNet Explorer tools.Only I/O data and corresponding status are reported to theDeltaV controller.ODVA EtherNet/IP. The VIM2 with the ODVA EtherNet/IPScanner Driver provides the following compatible functionsusing the Common Industrial Protocol (CIP) as defined inthe EtherNet/IP Specification from Open DeviceNet VendorAssociation and ControlNet International. The driver canemulate Programmable Serial cards or DeviceNet cards on theDeltaV I/O Bus.www.emerson.com/deltav5

S-series Virtual I/O Module 2September 2018DeltaV Licensing GuidelinesDeltaV Software Licensing Requirements (DST count) willbe used with the ODVA EtherNet/IP driver when DeviceNetCard-based Data mapping is selected as for any other v12 andlater DeviceNet device. The number of DSTs per connectedDeviceNet device will be one DST in most cases. The DST typecounted will be the most valuable type used to reference asignal for each device. If references are made to more than 16signals from a device, additional signal references beyond the16th reference will each count as a DST. A motor starter, forexample, with 4 to 5 signal references, will consume one DST(typically an AI or DO DST). A remote I/O island will consumeone DST for the first 16 signal references, and one DST for eachadditional signal reference beyond the 16th signal reference.For DeltaV versions prior to v12, each signal referenced from aconnected Ethernet device will count as one DST each.Using all other drivers and options, the DST count will beimpacted by DeltaV Module configuration by using registers, inthe same way as Serial Card registers. The following guidelinescan be applied: A DeltaV Serial Card data set can contain up to 100 values(a value can be any Boolean, 8-bit or 16-bit number), andup to16 data sets are supported by each of the 2 ports onthe serial card. If the data set registers are configured asfloating point or 32-bit values, then the maximum value is 50.However, the serial device, in general, limits the total capacityof the interface. Each data set counts as one DST as long as a single modulereferences all values in the data set. If multiple modulesreference values in a data set, then the DST count for thedata set is equal to the number of modules referencingthe data set. S-series system power supply and VIM2 details.Values used in modules containing control function blockswill be counted as Control DSTs.www.emerson.com/deltav6

S-series Virtual I/O Module 2September 2018Hardware SpecificationsSpecifications for the S-series Virtual I/O Module 2Power RequirementSupplied by System Power Supply through 2-wide Power/Controller CarrierMaximum Current1.4A at 5 V DCFuse Protection (Internal)3.0A, non-replaceable fusesPower Dissipation5.0W typical, 7.0W maximumUser Memory48 MBMountingOn right slot of power/controller carrierSize Dimensions4.1 cm w x 19.9 cm h x 14.0 cm dEnvironmental specificationsOperating Temperature*-40 C to 60 C (-40 F to 140 F)Storage Temperature-40 C to 85 C (-40 F to 185 F)Relative Humidity5 to 95%, non-condensingAirborne ContaminantsISA-S71.04-1985 Airborne Contaminants Class G2Shock (Normal Operating Conditions)10 g ½-sine wave for 11 msVibration (Operative Limit)1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 HzLED Indicators – On StatusGreen – PowerIndicates DC power is applied.Red – ErrorIndicates an error condition.Green – ActiveIndicates that the VIM2 is commissioned and active.Green – StandbyIndicates that the VIM2 is redundant and in standby mode.Yellow Flashing – NetworkSolid - Indicates valid network communication.Yellow, Flashing – Ctlr I/OIndicates valid DeltaV I/O Bus communication.All except Power flashing, alternating evenand oddVisual ID of controller initiated from user interface software by ping commandExternal connectionsPlant Ethernet NetworkTwo 100BaseTX RJ-45 connectors (simplex mode only)Plant Ethernet Networkand Redundancy LinkOne 100BaseTX RJ-45 connector (redundant mode)One 100BaseTX RJ-45 connector (cable supplied with redundant modules)*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.www.emerson.com/deltav7

S-series Virtual I/O Module 2September 2018Software SpecificationsEthernet I/O CapacityMax VIM2 per DeltaV Controller2Max. Emulated DeltaV Cards4 simplex in simplex setup8 simplex in dual simplex setup4 redundant in redundant setupAmount of Slaves for Serial Data DriversEthernet/IP32 in simplex setup / 64 in dual simplex setup16 in redundant setupModbus TCP96 in simplex setup / 192 in dual simplex setup32 in redundant setupFMC722 Subsea32 in simplex setup / 64 in dual simplex setupODVA Ethernet/IP128 in simplex setup / 256 in dual simplex setupAmount of Slaves for Bus Card DriversODVA Ethernet/IP128 in simplex setup / 256 in dual simplex setupPROFINET128 in simplex setup / 256 in dual simplex setupMax. Data Sets for Serial Data DriversModbus TCP, Ethernet/IP128 in simplex setup / 256 in dual simplex setup128 in redundant setupFMC722 Subsea128 in simplex setup / 256 in dual simplex setupODVA Ethernet/IP128 in simplex setup / 256 in dual simplex setupMax. Data for Bus Card DriversODVA Ethernet/IPDeviceNet Card max limitsPROFINETPROFIBUS DP Card max limitsCertificationsThe following certifications are available for S-series Virtual I/O Module 2: CE:- EMC-EN 61326-1 FM:- FM 3600- FM 3611ATEX:- EN60079-0- EN60079-15 CSA:- CSA C22.2 No. 213-M1987- CSA C22.2 No. 1010-1IEC-Ex:- IEC60079-0- IEC60079-15 Marine Certifications: IACS E10- ABS Certificate of Design Assessment.- DNV-GL Marine Certificate.www.emerson.com/deltav8

S-series Virtual I/O Module 2Hazardous Area/LocationS-series Virtual I/O Module 2 can be installed and usedbased on the following Standards: FM (USA):Class I, Division 2, Groups A, B, C, D, T4 cFM (Canada):September 2018 ATEX:II 3G Ex nA IIC Gc IEC-Ex:II 3G Ex nA IIC GcRegarding the Installation instructions please refer to the following Documents: Class 1 Division2 Installation Instructions DeltaV S-series 12P5402 and Zone 2 Installation Instructions DeltaVS-series 12P5404Class I, Division 2, Groups A, B, C, D, T4Ordering InformationDescriptionModel NumberS-series Virtual I/O Module 2SE4026Redundant S-series Virtual I/O Module 2(Includes two VIM2s and one redundancy link cable)SE4027Mimic Simulation SoftwareMM3-11xxModbus TCP/IP Master DriverIOD-4111EtherNet/IP Scanner DriverIOD-4112FMC722 Ethernet Protocol DriverIOD-4115ODVA EtherNet/IP Protocol DriverIOD-4116PROFINET Protocol DriverIOD-4117Related Products VIMNet Explorer. Used to commission and flash upgrade the VIM2 and to configure the Ethernet I/O network. Provided with theDeltaV v12 and later software.www.emerson.com/deltav9

S-series Virtual I/O Module 2September 2018PrerequisitesSystem Compatibility One power/controller carrier per VIM2. Please refer to theS-series Horizontal Carriers product data sheet for details. S-series VIM can physically be replaced with S-series VIM2back to v11.3.1. One dedicated system power supply per VIM2. Please refer tothe S-series Power Supplies product data sheet for details. To use for I/O Simulation with Mimic Simulation Software, aMimic base license and DeltaV Railbus Driver Pack must bepurchased. Technical support for Mimic Simulation Softwareand the I/O simulation driver is available.Existing Drivers from S-series VIMs will not work with theS-series VIM2 and need to be converted before they canbe reused. To use for Ethernet I/O integration, an Ethernet I/O drivermust be purchased. Te

Updates are quick and easy over the simulation network. Seamless Ethernet I/O integration. When used with the Ethernet I/O drivers, the VIM2 is seen by the DeltaV S-series controller as four DeltaV Serial Cards. Commissioned VIM2s are then auto-sensed by the DeltaV controll