Product Data SheetPS-00838, Rev. FFebruary 2022Micro MotionTM MVDTM Direct ConnectTMCoriolis Meters with MVDTM TechnologyThe Micro Motion MVD Direct Connect solution combines the accuracy, reliability, andperformance of Micro Motion Coriolis meters withthe simplicity of a direct Modbus interface. TheMVD Direct Connect I.S. barrier option enablesinstallation of the meter into hazardous areas andprovides the same power conditioning benefits thata transmitter offers. Unique MVD Direct Connect architecturesimplifies installation and reduces cost andcomplexity through direct integration into aModbus host Complete solution provides access to allMicro Motion process variables, embeddeddiagnostics, and full sensor configuration Optional compact DIN rail barrier allowshazardous-area installation and provides powerconditioning

MVD Direct Connect Coriolis Meters with MVD TechnologyFebruary 2022Micro Motion MVD Direct Connect Coriolis Meterswith MVD TechnologyMicro Motion Coriolis meters from Emerson meet a vast range of application needs, ranging from extremelow-flow up to high-flow, high-capacity lines. Cryogenic, hygienic, high-temperature, and high-pressure —Micro Motion meters can handle them all. Micro Motion meters are available with a variety of wetted partsto ensure the best material compatibilityMVD technology makes your Micro Motion meter work smarter Front end signal processing gives faster responsetime and dramatically reduces signal noise Provides reduced wiring costs through use ofstandard 4-wire instrument cable On-board signal processing results in thecleanest, most accurate signal delivered, evenwith tough measurement conditions such asentrained gasMicro Motion MVD Direct ConnectCoriolis metersThe unique architecture of Micro Motion MVDtechnology lowers the power requirements anddistributes safe DC power to the sensor,dramatically lowering installed costs compared totraditional analog meters. The MVD Direct ConnectI.S. barrier conditions the power and providesintrinsically safe DC power and Modbuscommunications to the sensor in the field.In a typical Micro Motion MVD meter, the coreprocessor performs the Coriolis signal processingfunctions. The transmitter then transduces thedigital data to traditional analog or frequencyoutputs for use by the control system. Without thetransmitter, you still have all the sensor and flowrate data, plus management controls such asevents, two-phase flow limits, and totalizers —accessible via Modbus communications.2Micro Motion MVD Direct Connect meters are theideal solution for systems integrators and OEMslooking for the most efficient and cost-effective wayto provide MVD technology to their customers for avariety of fluids including toothpaste, vegetableoils, vinegar, ketchup, mayonnaise, and additives, inapplications like: Material blending skids Juice blending CNG dispensers Remote flow monitoringAccess information when you need itwith asset tagsNewly shipped devices include a unique QR code asset tag thatenables you to access serialized information directly from thedevice. With this capability, you can: Access device drawings, diagrams, technicaldocumentation, and troubleshootinginformation in your MyEmerson account Improve mean time to repair and maintainefficiency Ensure confidence that you have located thecorrect device Eliminate the time-comsuming process oflocating and transcribing nameplates to viewasset informationwww.emerson.com

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologyMVD Direct Connect architectureMVD Direct Connect I.S. barrier(recommended)Barriers installed in safe areasminimize wiring and groundloop issues.reaeaSafaareusdozarHaMVD Direct Connect I.S. barrierEasy on spaceEasy on cablingMVD Direct Connect architecture eliminates transmitters,interface cards, wiring, and cabinet space.Use 4-wire cable between the core processor and the barrier,and use standard RS-485 cable between the barrier and thehost.The MVD Direct Connect barrier snaps onto a 35 mm DIN rail,and measures less than 5 x 5 x 1 inches (105 x 110 x 25 mm).Easy on installationStreamlined installation procedures make it easy to put yourMicro Motion meter in your pipeline and integrate it with yourcontrol system.www.emerson.com3

MVD Direct Connect Coriolis Meters with MVD TechnologyFebruary 2022Micro Motion meters and the MVD Direct ConnectsolutionMicro Motion leads the industry with the widest selection ofmeter types and sizes available. Match the meter to yourrequirements: sanitary, improved surface finish, hazardousarea, high temperature, secondary containment, explosionproof, and more.MVD Direct solutions can be installed with any Micro Motionmeter that accepts an integral core processor.For meters that cannot accept an integral core processor, theMVD Direct Connect solution can be installed with a remotecore processor, as long as hazardous area approvals are notrequired.Micro Motion is continually expanding its meter line. Forinformation on a specific meter, consult the meter product datasheet or contact Micro Motion.Modbus communications and MVD Direct ConnectProLink III softwareCustom softwareFor configuration, management, and viewing process variables,Micro Motion offers ProLink III, a Windows-based softwareprogram.Your custom software can perform the same functions and thentranslate process data into process control. Using industrystandard Modbus protocol, you can read flow rates and totals,start and stop batches, and respond to process fluctuations anderror conditions.ProLink III automatically recognizes the meter it is connected to,retrieves process data, reports status and alarms, and providesdata logging and meter fingerprinting capabilities.ProLink III provides full support for MVD Direct Connectinstallations with or without the barrier.4Micro Motion has published its Modbus interface, providingcomplete access to meter functionality.www.emerson.com

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologySpecifications.MVD Direct Connect I.S. BarrierElectricalSupply voltage24 VDC 20%Maximum consumption3.5 WProtectionPolarityIsolation test voltageSupply to safe side: 500 VACI.S to supply/safe side: 3750 VACCommunicationsSensor supply voltage15.3 V nominalSensor current limit145 mA nominalLEDsPowerRS-485PhysicalEnvironmentalBaud half-duplex1200 to 38,400ProtocolTIA/EIA-485 (RS-485)Dimensions (H x W x D)4.29” x 0.93” x 4.10” (109 x 23.5 x 104 mm)Weight0.34 lb (152 g)Ingress protection enclosureIP50Ingress protection terminalsIP20Screw terminal torsion0.5 N-mTemperature–40 to 140 F (–40 to 60 C)Relative humidity 95% (non-condensing)EMC EffectsComplies with EMC directive 2004/108/EC based on EN-61326IndustrialComplies with NAMUR NE-21 (09.05.2012).Meter systemCableCore processor to host orbarrierMicro Motion recommendsusing Micro Motion 4-wirecablewww.emerson.comCable typeWire sizeMax length2Signal wire (RS-485)22 AWG (0.35 mm ) or larger500 ft (150 meters)Power wire – must be sized toprovide a minimum of 15 V atthe core processor. See theinstallation manual for details22 AWG (0.35 mm2)20 AWG (0.5 mm2)18 AWG (0.8 mm2)300 feet (90 meters)500 feet (150 meters)500 feet (150 meters)5

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologyMeter systemCableCable typeWire sizeMax lengthBarrier to hostSignal wire (RS-485)22 to 18 AWG1000 feet (300 meters)(0.35 to 0.8 mm2)Barrier to power supplyPower wire22 AWG (0,35 mm2)500 feet (150 meters)2500 feet (150 meters)20 AWG (0,5 mm )18 AWG (0,8 mm )Communications300 feet (90 meters)2Autodetects incoming signal and switches to matchProtocolModbus RTU (8-bit)Modbus ASCII (7-bit)Baud1200 to 38,400ParityEven, odd, noneStop bits1, 2PhysicalSee product data sheet for selected sensorEnvironmentalSee product data sheet for selected sensorHazardous area classificationsATEXBVS 11 ATEX E 039 XII (2) G [Ex ib Gb] IIC (Device must be installed in a safe area, but has an intrinsic safeoutput to a sensor that is installed in Zone 1).II 3 (2) G Ex nA [ib Gb] IIC T4 Gc (For installation in areas where category 3G equipmentis required, the module must be mounted in an enclosure in accordance with EN60079-15).IECExIECEx BVS 07.0024 X[Ex ib Gb] IIC (Device must be installed in a safe area, but has an intrinsic safe output to a sensorthat is installed in Zone 1).Ex nA [ib Gb] IIC T4 Gc (For installation in Zone 2, the module must be mounted in an enclosurein accordance with IEC 60079-15).CSASuitable for installation in:Class I, Division 2, Groups A, B, C, DProviding intrisically safe outputs Class I, Division 1, Groups C, D andfor:Class II, Division 1, Groups E, F, G6www.emerson.com

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologyULSuitable for installation in:Class I, Division 2, Groups A, B, C, DProviding intrisically safe outputs Class I, Division 1, Groups C, D andfor:Class II, Division 1, Groups E, F, GNEPSIGYJ12.1554[Ex ib Gb] IICGYJ12.1555UEx nA [ib Gb] IIC T4 GcThe MVD Direct Connect I.S. barrier must be installed in IP 54 (GB4208-1993) housing to be used in a hazardous location. Thehousing should observe the requirements of GB3836.1-2010 and GB3836.4-2010.Provisions shall be made to prevent the rated voltage being exceeded by transient disturbances of more than 40%.End users are not permitted to change any components inside. For installation, use, and maintenance of the MVD Direct ConnectI.S. barrier, observe the instruction manual and the following standards: GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres. Part 13: Repair and overhaul for apparatus used inexplosive gas atmospheres”GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres. Part 15: Electrical installations in hazardous area (otherthan mines)”GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres. Part 16: Inspection and maintenance of electricalinstallation (other than mines)”GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electricalequipment installation engineering”www.emerson.com7

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologyOrdering InformationTo order an MVD Direct Connect meter, specify the appropriate “direct host connection” electronics interface (code W, D, Y, E, 6, 7,8, or 9) when ordering the sensor.To order the MVD Direct Connect I.S. barrier with the meter, specify electronics interface code W, D, Y, E, 6, 7, 8, or 9, incombination with approval code U, C, A, Z, I, P, 6, 7, 8, or G.Example model number: CMF050M313NWBAEZZZBase model, process connection, case optionsRefer to the sensor PDS.Electronics interfaceCodeMVD Direct Connect electronics interface optionsWPolyurethane-painted aluminum integral core processor for MVD Direct Connect installationDStainless steel integral core processor for MVD Direct Connect installationYExtended-mount polyurethane-painted aluminum integral core processor for MVD Direct Connect installationE6Extended-mount stainless steel integral core processor for MVD Direct Connect installation(1)Polyurethane-painted aluminum integral enhanced core processor for MVD Direct Connect installation7 (1)8Stainless steel integral enhanced core processor for MVD Direct Connect installation(1)Extended-mount polyurethane-painted aluminum integral enhanced core processor for MVD Direct Connectinstallation9 (1)(1)Extended-mount stainless steel integral enhanced core processor for MVD Direct Connect installationAvailable only with sensors that are equipped with an enhanced core processor.ApprovalsCode(1)UMVD Direct Connect approval optionsULCCSA (Canada only)ACSA C-US (U.S.A. and Canada)ZATEXI(1)IECEx Zone 1P (1)NEPSI (Only available in China)6ATEX - Equipment Category 2 (Zone 1 - IIC modified) / PED compliant - 2607IECEx Zone 1 IIC modified8NEPSI IIC modified2CSA (US and Canada): Class I, Division 2, Groups A,B,C,DGCountry Specific Approval – Requires a selection from the Approvals section of the ‘Certificate, Tests, Calibrations andServices’ model code option(1)Available only for certain product configurations. Consult factory for detailed information.Measurement application softwareCodeAZ(1)8(1)MVD Direct Connect measurement application software optionsPetroleum measurement softwareNo measurement application softwareAvailable only with CMF, F-Series, and T-Series sensors.www.emerson.com

February 2022MVD Direct Connect Coriolis Meters with MVD TechnologyCountry specific approvalsSelect one from the following if approval code G is selected.CodeFactory optionR1EAC Zone 1 – Hazardous Area ApprovalR2EAC Zone 1 - IIC modified - Hazardous Area ApprovalR3EAC Zone 2 – Hazardous Area ApprovalB1INMETRO Zone 1 - Hazardous Area ApprovalB2INMETRO Zone 1 - IIC modified - Hazardous Area ApprovalB3INMETRO Zone 2 – Hazardous Area Approvalwww.emerson.com9

MVD Direct Connect Coriolis Meters with MVD TechnologyPS-00838, Rev. F)RU PRUH LQIRUPDWLRQ ZZZ HPHUVRQ FRP 0LFUR 0RWLRQ ,QF OO ULJKWV UHVHUYHG 7KH (PHUVRQ ORJR LV D WUDGHPDUN DQG VHUYLFH PDUN RI (PHUVRQ(OHFWULF &R 0LFUR 0RWLRQ (/,7( 3UR/LQN 09' DQG 09' 'LUHFW&RQQHFW PDUNV DUH PDUNV RI RQH RI WKH (PHUVRQ XWRPDWLRQ6ROXWLRQV IDPLO\ RI FRPSDQLHV OO RWKHU PDUNV DUH SURSHUW\ RIWKHLU UHVSHFWLYH RZQHUV Product Data SheetFebruary 2022

6 www.emerson.com MVD Direct Connect Coriolis Meters with MVD Technology February 2022 Hazardous area classifications Barrier to host Signal wire (RS-485) 22 to 18 AWG (0.35 to 0.8 mm2) 1000 feet (300 meters) Barrier to power supply Power wire 22 AWG (0,35 mm2) 20 AWG (0,5 mm2) 18 AWG (0,8 mm2) 300 feet (90 meters)