Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsB8512G IP control panel, 8 areas, 99 pointsG Seriesu Fully integrated intrusion, fire, and accesscontrol allows users to interface with onesystem instead of threeu Provides up to 99 points using a combination ofhardwired or wireless devices for installationflexibility, and up to 8 areas and 8 doors for upto 500 usersu On-board Ethernet port for Conettix IP alarmcommunication and remote programming,compatible with modern IP networks includingIPv6/IPv4, Auto-IP, and Universal Plug and Playu Installer-friendly features for simple installationand communications, including plug-in PSTNand cellular communication modulesThe B9512G Control Panel and the B8512G ControlPanel are the new premier commercial control panelsfrom Bosch. B8512G control panels integrateintrusion, fire, and access control providing onesimple user interface for all systems.With the ability to adapt to large and smallapplications, the B8512G provides up to 99individually identified points that can be split into 8areas.The control panel communicates via the built-inEthernet port or via compatible plug-in modules thatcan send events over the public switched telephonenetwork (PSTN) or over cellular networkcommunications.For users, programmable keypad shortcuts, situationsensitive on-screen help, and a bilingual user interfacemake system operation simple and easy.With the B8512G, you can: Monitor alarm points for intruder, gas, or firealarms. Program all system functions local or remote usingRemote Programming Software (RPS) or by usingbasic programming through the keypad. Add up to 8 doors of access control using theoptional B901 Access Control Module or D9210CAccess Control Interface Module.The B8512G is a direct replacement for previouscontrol panel models D7412GV4, D7412GV3,D7412GV2, and D7412G.FunctionsProgrammable outputs Four alarm-output patterns Programmable bell testOutput ProfilesOutput Profiles support custom programming andprovide a way for outputs to operate based on uniqueapplication requirements.Once an Output Profile is created, it can be reusedand assigned to multiple outputs enabling quickoutput programming.You can create Output Profiles that define how anoutput operates when specific events occur. OutputProfiles provide a way to assign and use consistentoutput effects throughout the system.Point response Selectable point response time Selectable EOL values and configuration Cross point capability Fire alarm verification Dangerous gas indicator includes carbon monoxide Watch mode Selectable point response timeUser interface Supervision of up to 32 keypads

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 points Custom keypad text is fully programmable throughRPS Full function menu including customizable shortcuts Authority by area and 32 character name for eachuser 14 custom authority levels to restrict systemfeatures that each user can access Programmable primary and secondary language byuser and keypad 12 available languages (any two can be concurrentlyused)User interface languagesThe following table shows the available languages perkeypad type.B915/B915IB920/B925F/B926F /B926M B921CB930 B940W/B942/B942WEnglish Chinese Dutch French German Greek Hungarian Italian Polish Portuguese Spanish Swedish Area configurationsLink multiple areas to a shared area such as a lobby orcommon entryway. The shared area then automaticallyturns On (arms) when all associate areas are armedand turns Off (disarms) when any one associate areais disarmed. For higher security applications, the AreaRe-Arm feature guarantees that areas are alwaysrearmed, and are disarmed for no longer than aspecific, configurable, amount of time (for example,service time).Custom functionsFor added convenience, the installer can programcustom functions that allow customers to completecomplex tasks with one simple action. For example, acustom function can bypass a group of points and arm2 11the system, allowing the user to perform thesefunctions with one easy command. Users can activatecustom functions with a keypad, keyfob, token, orcard, or the control panel can activate a function inreaction to a faulted point, or automatically through ascheduled event (SKED).Passcode security Two-man rule. Requires two people with two uniquepasscodes to be present at the time of opening. Early ambush. Allows users to verify that the facilityis safe by requiring two passcodes. The controlpanel sends a duress event if the user does notenter the passcode a second time after inspectingthe premises. Dual authentication. Requires two forms ofidentification before processing certain systemcommands, including turning off the system andopening doors. A standard system user must have apasscode, a credential (token or card), andappropriate command authority permissions.Door controlUsing the B901 Access Control Module or D9210CAccess Control Interface Module, the control panelprovides a fully supervised access control solution.The solution offers 14 programmable levels of accessauthority. Authority for door access is controlled bythe user level, the group of the user, the time of day,the door state, and the area armed (On/Off) state.Easy exit controlThe control panel changes from one On (armed) stateto another without turning off (disarming) the system.For example, if you change the state from Part On(Perimeter Arm) to All On (Master Arm), the controlpanel complies and reports the change. Easy exitcontrol reduces the number of keystrokes, simplifyingsystem operation.Programmable passcode-controlled menu listPasscode-controlled shortcuts provide users only withthe options and information pertinent to them,simplifying system operation.Flexible controlThe system provides the flexibility to choose addedconvenience or high security. For example, you canrestrict to a keypad's immediate local area turning on(arming) and turning off (disarming) the system with apasscode, even if the user has access to other areas.This is particularly useful for high security areas,where a user may have access to the area, but wouldprefer to only turn off (disarm) the area individuallyrather than with the rest of the system.Monitor Delay/Delayed ResponseCreate a special point profile that delays the reactionof a point for a specified time (up to 1 hour in minutesand seconds). This delay provides time for thespecified condition to reset before activating anyannunciation. The system can annunciate locally andsend a report, if desired. When the system is armed,

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsthe point can respond like a normal point - providingdual functionality. Use this feature to ensure thatperimeter doors have not been propped open, or tomonitor critical areas such as computer rooms andsafes, for example.System usersThe system supports up to 500 users. Each user canhave a personalized passcode, a wireless keyfob, andan access credential to control the system. You canassign passcodes to one of 14 customized authoritylevels in each area that can be restricted to operateonly during certain times. You can program a primaryand secondary language for each user and by keypad(select from English, Chinese, French, Greek,Hungarian, Italian, Polish, Portuguese, and Spanish).The keypad changes to the user’s programmedlanguage when the user enters his passcode or holdsthe Help key.Route groups and destinationsThe control panel can send reports to four differentroute groups using one primary and up to threebackup destination devices for each route group.Reporting capabilitiesThe control panel has flexible communications formost central station receivers with reportingcapabilities such as: Individual point numbers Opening or closing reports by user and area number Remote programming attempts Diagnostic reportsDestination testIt is possible to send test reports to each and alldestinations within each route group.Communication formatsThe control panel sends reports in these formats: Contact ID (PSTN) Modem4 (PSTN) Conettix Modem4 Conettix ANSI-SIA Contact ID ANSI-SIA DC-09iNoticeUL and ULC LISTED applicationsANSI-SIA DC-09 format is not available for ULand ULC LISTED applications.IP communicationThe control panel can use IP to communicate with aConettix D6600 or a Conettix D6100IPv6communications receiver/gateway. Use one of thefollowing for IP: The on-board Ethernet connection Ethernet Communication Module: B426 Plug-in cellular communicator: B442/B443/B444-A/B444-V3 11Conettix IP communication provides a secure paththat includes anti-replay/anti-substitution features,and enhanced security with up to AES 256-bitencryption (using Cipher Block Chaining (CBC)).The control panel supports Domain Name System(DNS) for both remote programming and centralstation communication. DNS provides ease of use,eliminating the need to use static IP addresses as yourreporting destination, and accommodates a simplesolution for central station disaster recovery. Thecontrol panel supports both IPv6 and IPv4 networks.Communication pathsThe control panel accommodates up to four separatephone and four separate network paths to the centralstation receiver. When resetting alarms or turning asystem on and off, the user is identified by name andnumber.Personal notificationThe control panel can send text messages and emailsfor personal notification over Ethernet or using acellular communicator. You can configure up to 32destinations using a combination of cellular phonenumbers and email addresses. The control panelsends notifications in the user’s programmed primarylanguage.Firmware updatesRemote firmware updates are available.A wide variety of input optionsEach point: Single 1 kΩ, single 2 kΩ, dual 1 kΩ (1 kΩ 1 kΩ),and No EOL (end-of-line) (EOL) resistor options (foron-board and B208 inputs) Programmable for Fire, Intrusion, Access, Gas, andSupervisory devices Supports hardwired and wireless devices Supports IP cameras by Bosch as point and outputdevicesIP camera supportThe control panel can integrate directly with Bosch IPcameras, using them as fully supervised points andoutputs.Integration of cameras allows the camera’s videomotion detection to activate points on the controlpanel. The IP Camera Point Source now includes twowired inputs of an IP camera. The control panel’svirtual outputs (IP camera output source) can beconfigured to trigger camera actions, includingsending video snapshots via email.Security and fire detectionThe control panel provides eight on-board points, andup to 91 additional off-board points (depending onmodel and expansion interfaces). You can programindividual points to monitor some types of burglaralarms, fire alarms, and supervision devices.

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsEvent logThe event log stores up to 2048 local and reportedevents. The event log includes time, date, event, area,point, and user. View the event log from a keypad oruse RPS to remotely retrieve event information. Whenthe event log reaches a programmed threshold ofstored events, it can send an optional report to areceiver.Scheduled events (SKEDs)The internal clock and calendar start individuallyscheduled events (SKEDs). SKEDs perform severalfunctions such as turn on or off, relay control, or pointbypassing.The control panel offers: 40 scheduled events with up to 31 differentfunctions 8 opening windows and 8 closing windows 8 user group windows Day-of-week, date-of-month, or holiday onlyschedules 4 holiday schedules of 366 days (leap year)Dual bus and SDI keypad retrofitsThe dual SDI2 device bus design provides greaterinstallation flexibility, such as bus isolation forIntrusion and Fire. To use popular SDI keypads (forexample D1255 and D1260), program one of the twoSDI2 buses for SDI operation.ZONEX and POPEX retrofitsTo retrofit legacy Bosch control panels that useZONEX and POPEX devices, the control panel iscompatible with the B600 Retrofit (ZONEX) Module.The B600 adds two ZONEX buses to the control panelwhich can connect to existing legacy point bus(POPEX) devices (for example, the D8125).ProgrammingInstallers can perform limited programming on-sitewith a keypad (critical parameters; such as accountIDs, central station and RPS IP addresses and phonenumbers, reporting formats, and more). They can alsodo full programming on-site or remotely (attended orunattended) with RPS. A programmable systempasscode prevents unauthorized remoteprogramming.The following table shows the available languages forRPSRPS programmingEnglish RPS custom text* Dutch French German Hungarian 4 11RPS programmingRPS custom text*Italian Portuguese Spanish Swedish * RPS custom text is text, that can be entered in RPSand which will then be displayed on keypads and onthe mobile app.DiagnosticsKeypads and RPS offer diagnostic help for monitoringand troubleshooting. The diagnostics features allowyou to view the status of the wired and wirelessdevices. The features provide the status of the controlpanel and its connected devices, such as firmwareversion, power, and missing conditions. View thestatus of each area.3rd Party IntegrationsThe control panel provides options for integrationwith software applications and solutions. Dependingon the application, options include a Bosch SDK, RPSAPI, Bosch proprietary MODE 2 or OPC interface. TheOPC interface enables key DA (Data Access) and AE(Alarms & Events) to integrate with the Bosch BISsolution or 3rd party OPC Classic systems.Bosch Video Management System integrationWith Bosch Video Management System (Bosch VMS)and an intrusion system, the VMS operator has asingle user interface to monitor and control theintrusion system combined with video surveillance.With Bosch VMS and a control panel, the operatorcan, for example: View videos triggered by intrusion events, includingall relevant information such as areas, point, anduser show in the display with the event. View areas, points, outputs, and doors - with theirstatuses - on the Bosch VMS map, providing theexact location in the system. Turn on (arm) and turn off (disarm) areas. Bypass and unbypass points. Lock and unlock doors (Bosch VMS 6.0 and higher).Requirements to integrate Bosch VMS with a controlpanel: A licensed Bosch VMS system using ProfessionalEditions v5.5 or higher or Bosch VMS EnterpriseEdition v5.5 or higher. Expansion license to integrate the intrusion controlpanel. One license needed per control panel. Ordernumber MBX-XINT-xx for the expansion licenseadded to a Bosch VMS base license. Refer to theBosch Video Management Software product pageon the Bosch website, www.boschsecurity.com. Access to the control panel account and RemoteProgramming Software (RPS).

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsBosch Security Manager Mobile AppThe Bosch Security Manager app allows users tocontrol their security systems remotely from theirsmart devices. Users can: Easily view their system's status at a glance via theadvanced and colorful design of the app Turn the security system On or Off (either the entiresystem or specific areas) Receive and filter event-driven push notifications View full event history for their system Add, edit, and delete users in their system Control outputs and doors View live video from Bosch IP cameras Access their panels from any device just by logginginto the app with a Bosch ID (panels are now linkedto an account and not a device)Full functionality requires panel firmware 3.10 orhigher and integration with the new Installer ServicesPortal. App users must have a valid email account andmust be invited to the app by their Bosch certifieddealer.For those without access to the Installer ServicesPortal, Remote Security Control will remain available.RegionInstaller Services Portal (North America)The Installer Services Portal offers secure and easyaccess for managing Bosch cloud and cellularcommunication services for remote programming andalarm reporting. The Bosch Cloud Remote Connectservice eliminates the need to change local routersettings, firewall rules or to use Domain Name Service(DNS). In addition to seamless integration with RPSfor remote programming, the Remote Connect servicefully supports the Bosch Security Manager mobileapp.Regulatory informationRegionRegulatory compliance/quality marksUSAANSI-SIAAustralia5 11Regulatory compliance/quality marksULUL 636 - Holdup Alarm Units and SystemsULUL 864 - Standard for Control Units andAccessories for Fire Alarm Systems (10thedition)ULUL 985 - Household Fire Warning SystemUnits (6th edition)ULUL 1023 - Household Burglar Alarm SystemUnitsULUL 1076 - Proprietary Burglar Alarm Unitsand SystemsULUL 1610 - Central Station Burglar AlarmUnitsULUL 1635 - Standard for Digital AlarmCommunicator System UnitsULUL 2572 - Standard for Mass NotificationSystemsFMCentral StationFMLocal Protective SignalingFMRemote StationCSFMCalifornia State Fire MarshalFCCPart 15 Class BFDNY-CoA Fire Department of New York City[B9512G, B8512G]CanadaCP-01-2010-Control Panel Standard Features for False Alarm ReductionULCUnderwriters Laboratories of CanadaULCCAN/ULC S303 - Local Burglar Alarm Unitsand SystemsULCCAN/ULC S304 - Standard for SignalReceiving Center and Premise BurglarAlarmULCCAN/ULC S545 - Residential Fire WarningSystem Control UnitsULCCAN/ULC S559 - Fire Signal ReceivingCentres and SystemsULCULC-ORD C1023 - Household BurglarAlarm System UnitsRCMRegulatory Compliance MarkRCMRegulatory Compliance MarkRCMACMAEuropeCEEMC, LVD, RoHSUSAULUnderwriters LaboratoriesULUL 294 - Standard for Access Control Unitsand SystemsULCULC-ORD C1076 - Proprietary BurglarAlarm Units and SystemsULUL 365 - Police Station Connected BurglarAlarm UnitsICICES-003 - Information TechnologyEquipment (ITE)ULUL 609 - Standard for Local Burglar AlarmUnits and SystemsANATEL04450-16-01855 [B9512G, B8512Gwhen used with B430 or B442]Brazil

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsInstallation/configuration notesiNoticeNot all products and features are available in allregions. Consult your local Bosch representativefor availability details.Compatible productsKeypadsB940W Touch screen KP, White (SDI2)B942/B942W Touch Screen Keypad (SDI2)B930 ATM Style Alphanumeric Keypad (SDI2)B926F Fire Keypad (SDI2)B925F Fire Keypad (SDI2)6 11D8108A-CE Attack Resistant Enclosure with Built-in TransformerD8109 Fire EnclosureAccessoriesB56 Keypad Surface Mount BoxB96 Keypad Trim BezelB99 USB Direct Connect CableB501-10 Interconnect wiring cables (pack of 10)D161 Dual Modular Telephone Cord (7 f)D162 Modular Telephone Cord (2 ft)D166 Telephone Jack (RJ31X)B926M Mass Notification Keypad (SDI2)DetectorsB921C Two-line Capacitive Keypad (SDI2)D7050 Series Addressable Photoelectric Smoke and Smoke Heat DetectorHeadsB920 Two-line Alphanumeric Keypad (SDI2)F220-B6PM/S 12/24 VDC Addressable Detector Bases with POPITsB915/B915I Basic Keypad (SDI2)F220‑B6 12/24 VDC Two‑wire BaseD1255 Series KeypadsF220‑B6R Standard 12/24 VDC Four‑wire Base)D1260 Series KeypadsF220‑P Photoelectric Smoke DetectorD1256RB Fire KeypadD1257RB Remote Fire Alarm AnnunciatorPowerD1640 16.5 VAC 40 VA TransformerDE-45-18 TransformerD126 Standby Battery (12 V, 7 Ah)D1218 Battery (12 V, 18 Ah)D122 Dual Battery HarnessD122L Dual Battery Harness with Long LeadsF220‑PTH Photoelectric Smoke Detector with 135 F ( 57 C) HeatSensorF220‑PTH Photoelectric Smoke Detector with 135 F ( 57 C) HeatSensor and Carbon Monoxide SensorsF220‑B6C 12/24 VDC Four‑wire Base with Auxiliary Form C RelayFCC-380 Carbon Monoxide DetectorFCH-T320 Heat DetectorFCP-OT320 Multisensor Detector Optical/ThermalFCP-O320 Optical Smoke DetectorMX775i Addressable PIR DetectorEnclosuresMX794i Long Range Multiplex PIR DetectorB8103 Universal Enclosure (White)MX934i Addressable PIR DetectorD8103 Universal Enclosure (Gray)MX938i Addressable PIR DetectorD8108A Attack Resistant EnclosureZX776Z PIR Detector

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsZX794Z Long Range PIR DetectorD132A Smoke Detector Reversing Relay ModuleZX835 TriTech Microwave/PIR DetectorD133 Single Relay ModuleZX935Z PIR DetectorD134 Dual Relay ModuleZX938Z PIR DetectorD185 Reverse Polarity Signaling ModuleZX970 PIR/Microwave DetectorD192G Class “B”, Style Y Bell Circuit SupervisionBosch conventional detectors, including Professional Series, Blue LineGen2, Blue Line, Classic Line, Commercial Line, and Ceiling Mount motiondetectors, as well as glass break, seismic, request-to-exit, photoelectric,heat, and smoke detectors.D1218 Battery (12 V, 18 Ah)7 11D8125 Addressable Expansion ModuleD8125MUX Multiplex Bus InterfaceModulesD8128D OctoPOPIT Eight‑point ExpanderB208 Octo-input ModuleD8129 Octo‑relay ModuleB299 POPEX ModuleD8130 Door Release ModuleB308 Octo-output ModuleD9127U/T POPIT ModuleB426 Conettix Ethernet Communication ModuleDS7461i Single‑zone Input ModuleB430 Plug-in Telephone CommunicatorDS7465i Input‑output ModuleB440 Conettix Plug-in Cellular CommunicatorsD9210C Access Control Interface ModuleB442 Conettix Plug-in Cellular Communicator (using GPRS)ICP-EZTS Cover and Wall Tamper SwitchB443 Conettix Plug-in Cellular Communicator (using HSPA )ICP-SDI-9114 SDI SplitterB444 Conettix Plug-in Cellular CommunicatorApplicationsB444-A Plug-in cell module, AT&T LTERemote Programming Software (RPS or RPS‑LITE) v6.03 and higherB444-V Plug-in cell module, Verizon LTEBosch Video Management System v5.5 and higherB450 Conettix Plug-in Communicator InterfaceRemote Security ControlB520 Auxiliary Power Supply ModuleB600 Retrofit (ZONEX) ModuleB810 wireless receiver (RADION)B820 SDI2 Inovonics Interface ModuleConettix receivers(Managed and configured with Conettix D6200 Programming/Administration Software v2.10)Conettix D6600 Communications Receiver/Gateway (with only D6641 linecards installed) with CPU version 01.10.00B901 Access Control ModuleD113 Battery Lead Supervision ModuleD125B Dual Class B Initiating ModuleConettix D6100IPv6 Communications Receiver/Gateway with CPU version61.10.00Conettix D6100i Communications Receiver/Gateway with CPU version61.10.00D126 Standby Battery (12 V, 7 Ah)D129 Class A Initiating ModuleRADION wireless from BoschD130 Auxiliary Relay ModuleB810 wireless receiver (RADION)

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 points8 11RFBT-A/RFBT bill trapEN1235D Beltclip Pendant Transmitter (Double-button)RFDL-11-A/RFDL-11 TriTech motion detectorEN1235DF Fixed-location Transmitter (Double-button)RFDW-RM-A/RFDW-RM recessed mount door/window contactEN1235S Beltclip Pendant Transmitter (Single-button)RFDW-SM-A/RFDW-SM surface mount door/window contactEN1235SF Fixed-location Transmitter (Single-button)RFGB-A/RFGB glass break detectorEN1247 Glass-break Detector TransmitterRFKF-A/RFKF two-button keyfobEN1249 Bill Trap TransmitterRFKF-FBS-A/RFKF-FBS four-button keyfobEN1242 Smoke Detector TransmitterRFKF-TBS-A/RFKF-TBS two-button keyfobEN1260 Wall Mount Motion DetectorRFPB-SB-A/ RFPB-SB single-button panicEN1261HT High Traffic Motion DetectorRFPB-TB-A/RFPB-TB two-button panicEN1262 Motion Detector with Pet ImmunityRFRP-A/RFRP repeaterEN1265 360 Ceiling Mount Motion DetectorRFHT-A Wireless heat detectorEN4200 Serial ReceiverRFSM2-A Wireless smoke detectorEN5040-T High Power Repeater with TransformerRFCO-A Wireless CO detectorParts includedRFPR-12-A/RFPR-12 PIR motion detectorQuantityComponentRFPR-C12-A/RFPR-C12 PIR curtain motion detector1Control panelRFUN-A/RFUN universal transmitter1Hardware pack1Literature packInovonics WirelessB820 SDI2 Inovonics Interface ModuleENKIT-SDI2 SDI2 Inovonics Interface and Receiver Kit. Includes B820 andEN4200EN1210 Universal Transmitter (Single-input)EN1210EOL Universal Transmitter with EOL Resistor1 UL Installation Guide ULC Installation Guide Owner’s Manual Release Notes SIA Quick Reference GuideLiterature CD containing product literatureEN1210W Door-Window Transmitter with Reed SwitchTechnical specificationsEN1215EOL Universal Transmitter with Wall Tamper, Reed Switch, andEOL ResistorCapacityEN1223D Water‑resistant Pendant Transmitter (Double-button)Number of points99EN1223S Water‑resistant Pendant Transmitter (Single-button)Number of areas8EN1224-ON Multiple-Condition Pendant TransmitterNumber of events2048EN1233D Necklace Pendant Transmitter (Double-button)Number of users501EN1233S Necklace Pendant Transmitter (Single-button)Number of outputs93

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsNumber of on-board outputs3Number of custom functions8Number of SKEDs40Number of IP cameras8ElectricalCurrent consumption (mA)180 mA – 260 mAInput voltage (VAC)16.50 VAC – 18 VACMaximum auxiliary output current(mA)1400 mANominal voltage (VDC)12 VDCOutput current (A)0A–2AEnvironmental9 11AccessoriesB520 Auxiliary power supply module, 2A 12VProvides auxiliary power to 12 VDC devices or to SDI2modules.Order number B520 F.01U.172.941B208 SDI2 8-Input Expansion ModuleProvides 8 programmable inputs.Order number B208 F.01U.385.671 F.01U.397.024F.01U.323.801B308 SDI2 8-Output Expansion ModuleProvides 8 programmable relays.Order number B308 F.01U.385.672 F.01U.397.025F.01U.323.802B901 Door ControllerFully supervised, addressable SDI2/SDI bus device thatallows access control integration for Bosch G and BSeries Control Panels.Order number B901 F.01U.323.803 F.01U.386.908B810 Wireless SDI2 bus interfaceReceives RF signals from RADION transmitters,repeaters, and glassbreaks. Operates at 433.42 MHz. Foruse with compatible SDI2 bus control panels.Order number B810 F.01U.323.799 F.01U.383.394Operating temperature ( C)0 C – 49 COperating temperature ( F)32 F – 120 FOperating relative humidity, noncondensing (%)5% – 93%D122 Dual battery harnessHarness with circuit breaker. Connects two batteries (inparallel) to a compatible control panel.Order number D122 4.998.800.378ColorBlackD122L Dual battery harness, longHarness with circuit breaker and leads measuring 35 in.(89 cm). Connects two batteries (in parallel) to acompatible control panel in a separate enclosure.Order number D122L 4.998.140.606Dimension (H x W x D) (cm)26.99 cm x 19.69 cm x 4.76 cmDimension (H x W x D) (in)10.6250 in. x 7.75 in. x 1.8750 in.Dimension (H x W x D) (mm)269.90 mm x 196.90 mm x 47.60mmWeight (g)880 gWeight (kg)0.88 kgWeight (lb)1.95 lbMechanicalNetworkEthernet type10/100BASE-TOrdering informationB8512G IP control panel, 8 areas, 99 pointsSupports up to 99 points, 3 on-board outputs, and 8areas for intrusion, commercial fire. On-board Ethernet.Order number B8512G F.01U.296.327 F.01U.396.919F.01U.390.775D126 Battery, 12V 7AhA rechargeable sealed lead‑acid power supply used as asecondary power supply or in auxiliary or ancillaryfunctions.Order number D126 4.998.125.825D1218 Battery, 12V 18AhThe D1218 is a 12 V 18 Ah sealed lead‑acid battery withtwo bolt-fastened terminals. It is used for standby andauxiliary power. It connects to a compatible controlpanel using a D122 or D122L Dual battery harness.Order number D1218 4.998.125.820D137 Accessory mounting bracket for enclosureUsed to mount accessory modules in B8103, D8108A,and D8109 enclosures.Order number D137 F.01U.020.521D1640 Transformer plug-in, 16V 40VASystem transformer rated at 16.5 VAC, 40 VA.Order number D1640 4.998.125.832D1640-CA Transformer, plug-in, 16V 40VA, CanadaFor use in Canada. System transformer rated at16.5 VAC, 40 VA.Order number D1640-CA F.01U.270.316 F.01U.026.408

Intrusion Alarm Systems - B8512G IP control panel, 8 areas, 99 pointsD9002-5 Mounting plate, 6 location 3-hole, 5 pcs5 pack of mounting skirts for B8103, D8103, D8108A,and D8109 enclosures. Each skirt can hold up to sixstandard 3-hole mounting modules.Order number D9002-5 F.01U.217.699D101 Enclosure lock and key setShort-body lock set with one key supplied. Uses theD102 (#1358) replacement key.Order number D101 4.998.800.200D110 Tamper switch for enclosure, 2pcsScrew‑on tamper switch that fits all enclosures. Shippedin packages of two.Order number D110 F.01U.246.707 4.998.137.947ICP-EZTS Dual tamper switchCombination tamper switch with a wire loop foradditional tamper outputs.Order number ICP-EZTS F.01U.217.038 F.01U.003.526B8103 Universal enclosure, whiteWhite steel enclosure measuring 41 cm x 41 cm x 9 cm(16 in. x 16 in. x 3.5 in.).Order number B8103 F.01U.300.149D8108A Attack resistant enclosure, large, greyGrey steel enclosure measuring 41.5 cm x 41.5 cm x9 cm (16 in. x 16 in. x 3.5 in.).UL Listed. Includes a lock and key set.Order number D8108A 4.998.125.920D8109 Fire enclosure, 16x16x3.5", redRed enclosure, 16in. x 16in. x 3.5in. (41cm x 41cm x9cm), 16 gauge (1.5mm) cold-rolled steel, full‑lengthhinge, D101F lock and 2 D102F keys, UL Listed forcommercial fire/burglary applications.Order number D8109 4.998.800.205D8004 Transformer enclosure kit, greyFor applications that might require a remote transformerin an enclosure. Can be used with B Series controlpanels and D9412GV4/D7412GV4 control panels.Order number D8004 4.998.140.404BATB-40 Battery box/enclosure, 22x21x7.25"22 x 20.75 x 7.25" (56 x 53 x 18.5 cm). Holds two dry orwet cell batteries. Optional BATB-SHELF battery shelfincreases number of batteries. Suitable for residential/commercial fire or burglary applications.Order number BATB-40 4.998.137.930BATB-80 Battery box/enclosure, 22x21x7.25"22 in. x 20.75 in. x 7.25 in. (55.9 cm x 52.7 cm x 18.4cm). Battery box/enclosure with shelf holds up to fourdry or wet cell batteries. Suitable for residential/comercial fire or burglary applications.Order number BATB-80 4.998.137.931B99 USB direct connect cableMale A to Male A USB cable for local programming ofcontrol panels with on-board USB ports.Order number B99 F.01U.278.853B915 Basic KeypadTwo-line alphanumeric basic keypad with languagefunction keys.Available languages: English, Chinese, Dutch

Output Profiles support custom programming and provide a way for outputs to operate based on unique application requirements. Once an Output Profile is created, it can be reused . ZONEX and POPEX retrofits To retrofit legacy Bosch control panels that use ZONEX and POPEX devices, the control panel is compatible with the B600 Retrofit (ZONEX .