CORE HOLE APPLICATIONS WITHIN: MASONRY BLOCK OR HEBEL 2HR 100mm Thick .

Transcription

INTUMASTIC HP26iCORE HOLE APPLICATIONS WITHIN:RTBAHDPE PIPESPEX WATER PIPESARMAFLEX AIRCON BUNDLESFICLPE AIRCON BUNDLESEFLYMASONRY BLOCK OR HEBEL2HR 100mm Thick WallsCPVC SPRINKLER PIPESPHONE: (07) 5411 4209OR (02) 8004 3333 (Option 2)SIMPLY SQUIRT THEINTUMASTIC HP INTO THEANNULAR GAP BETWEEN THEOUTSIDE OF THE SERVICEPENETRATION AND THEINSIDE OF THE HOLE. FILL TOTHE FULL DEPTH OF THESUBSTRATE.NBN CAT 5 CABLESIN CONDUITNBN CAT 6 CABLESIN CONDUITWEBSITE: tbafirefly.com.auEMAIL: sales@tbafirefly.com.au

Bundle of up to 12 TPS Electrical CablesProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 40mm)and sealed to the full depth of the substrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:EFLYV9aBundle of up to 12 Red Fire Alarm CablesProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 40mm)and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:RV9bTBAFIUp to 48mm OD CPVC Sprinkler PipeProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 40mm)and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V17a25mm Copper Pipe lagged in 25mm ArmaflexProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 40mm)and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V18

Up to 43mm PEX PipeProtected with TBA Firefly Intumastic HPin the annular gap (Min 10mm Max40mm) and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:RIR 23671Specific ID No:EFLYV19aUp to 43mm OD PEX-AL Gas PipeRProtected with TBA Firefly Intumastic HPin the annular gap (Min 10mm Max40mm) and sealed to the full depth of thesubstrate.TBAFIUp to 40mm OD HDPE PipeProtected with TBA Firefly Intumastic HPin the annular gap (Min 10mm Max40mm) and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:RIR 23671Specific ID No:V20bFRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V2122mm OD uPVC PipeProtected with TBA Firefly Intumastic HPin the annular gap (Min 10mm Max40mm) and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V22

Up to 6 x 13mm Copper Pipes Lagged in9mm Armaflex up to 6 TPS CablesWarringtonfireReport No:FAS190236 RIRSpecific ID No:V27EFLYProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 30mm)and sealed to the full depth of thesubstrate. Finished with a 40mm fillet toboth sides.FRL -/120/12025mm PVC Pipe filled with up to 8 TPS CablesProtected with TBA Firefly Intumastic HP inthe annular gap (Min 10mm Max 30mm) andsealed to a minimum depth of 26mm fromboth faces of the wall.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:RV28bTBAFIUp to 9 x 13mm Copper Pipes Lagged in9mm Armaflex up to 20 x TPS Cables with or without 16mm Flexi-drain or SteelCable TrayProtected with TBA Firefly Intumastic HP inthe annular gap and sealed to the fulldepth of the substrate. Then wrapped out300mm to either side of the Intubatt withTBA Firefly Penowrap.Bundle of 1 x Armaflex Pair Coil and 2 xTPS Cables with or without 18mmPVC Flexi Drain HoseWithin a 70mm Core Hole: Protected withTBA Firefly Intumastic HP in the annulargap and sealed to the full depth of thesubstrate.FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V30FRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V119b

Aircon CLPE Foam Pair-coil 2 TPS Cables& with or without 18mm PVC Flexi DrainHoseWarringtonfireReport No:FAS190236 RIRSpecific ID No:V118aEFLY70mm Core Hole. The annular gaparound the service is to be filled tothe full depth of the substrate usingTBA Firefly Intumastic HPFRL -/120/120Up to 26mm PVC CONDUIT FILLED WITHup to 14 x Cat 5 NBN CABLESFRL -/120/12046mm Core Hole. The annular gap aroundthe service is to be filled to the full depthof the substrate using TBA FireflyIntumastic HPWarringtonfireReport No:FAS190236 RIRSpecific ID No:RV123TBAFIUp to 26mm PVC CONDUIT FILLED WITHup to 10 x Cat 6 NBN CABLES46mm Core Hole. The annular gaparound the service is to be filled to thefull depth of the substrate using TBAFirefly Intumastic HPFRL -/120/120WarringtonfireReport No:FAS190236 RIRSpecific ID No:V124All service penetrations must be treated in strict accordance with the conciseconstruction details contained within the referenced compliance Reports. TheseReports meet Specification A2.3 of NCC2016 Amendment 1 (Including priorversions) & Schedule 5 of NCC2019 (Including amendment 1) for determination ofan FRL.

masonry block or hebel 2hr 100mm thick walls clpe aircon bundles armaflex aircon bundles pex water pipes hdpe pipes cpvc sprinkler pipes nbn cat 5 cables in conduit nbn cat 6 cables in conduit simply squirt the intumastic hp into the annular gap between the outside of the service penetration and the inside of the hole. fill to the full depth of the