Tranquility 16 COMPACT (TC) Series - Files.climatemaster

Transcription

Tranquility 16COMPACT (TC) SeriesTable of ContentsMODELS TCH/V 006 - 6060 HZ - HFC-410AINSTALLATION, OPERATION& MAINTENANCE97B0075N07Revised: July 7, 2020Model Nomenclature – General OverviewGeneral InformationUnit Physical DataHorizontal InstallationField Conversion of Air DischargeHorizontal InstallationVertical InstallationPiping InstallationWater-Loop Heat Pump ApplicationsGround-Loop Heat Pump ApplicationsGround-Water Heat Pump ApplicationsWater Quality StandardsTC - Horizontal – Dimensional DataTCH with WSE – Dimensional DataTC - Horizontal Service AccessTC - Vertical Upflow – Dimensional DataTCV with WSE – Dimensional DataTC - Vertical Service AccessElectrical Data – Standard UnitElectrical Data – High Static BlowerElectrical Data – Constant Torque ECMElectrical Data – Constant Volume ECMElectrical – Line VoltageEletctical – Power & Low Voltage WiringElectrical – Low Voltage WiringElectrical – Thermostat WiringBlower Performance Data – TC006Blower Performance Data – TC009Blower Performance Data – TC012Blower Performance Data – TC015Blower Performance Data – TC018Blower Performance Data – TC024Blower Performance Data – TC030Blower Performance Data – TC036Blower Performance Data – TC041Blower Performance Data – TC042Blower Performance Data – TC048Blower Performance Data – TC060Constant Volume ECM ControlWiring Diagram MatrixDIP Setting TableCXM ControlsDXM2 ControlsSafety Features – CXM and DXM2 ControlsUnit Starting and Operating ConditionsPiping System Cleaning and FlushingTC with Waterside Economizer 637383940414243444546474849505253545560626364

CLIMATEMASTER WATER-SOURCE HEAT PUMPSTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0Table of Contents, Cont’d.Unit and System CheckoutUnit Start-Up ProcedureUnit Operating ConditionsPreventive MaintenanceFunctional TroubleshootingPerformance TroubleshootingStart-Up Log SheetFunctional TroubleshootingWarranty (U.S & Canada)Warranty (International)Revision History26667697475767778798084C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

THE SMART SOLUTION FOR ENERGY EFFICIENCYTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0Model Nomenclature – General Overview1 2TC3H4 5 60367A8G9C1011312013A14L15BSMODEL TYPESUPPLY AIR OPTIONSTC TRANQUILITY COMPACT R410AOptionTBSV1Y1Z1K2P2W2122232CONFIGURATIONH HORIZONTALV VERTICALS STANDARDUNIT SIZE006 - E,G009 - E,G012 - E,G015 - E,G018 - E,G024 - E,F,G,H030 - E,FG,H036 - E,FG,H041 - F,G,H,N (TCV ONLY)042 - F,G,H,N048 - F,G,H,N060 - F,G,H,N12L LEFT RETURNR RIGHT RETURNF FRONT RETURN and VERTICAL 009 - 030 AND 041 ONLYV LEFT RETURN S.S. DRAIN PANW RIGHT RETURN S.S. DRAIN PANZ FRONT RETURN S.S. DRAIN PAN and VERTICAL 009-030 AND 041 ONLYA CURRENT REVISION FOR ALL SIZESHEAT EXCHANGER OPTIONSVOLTAGECOPPERCUPRO-NICKELOPTION WATER COILWATER COILAYESNOCJYESNONG 208/230/60/1E 265/60/1H 208/230/60/3F 460/60/3N 575/60/31234CONTROLS{Not available for sizes 006, 009, 012, 041Not available for size 041RETURN AIR OPTIONSREVISION LEVELw/DISCONNECTSupply CTopTCVPSC Hi StaticPSC Hi StaticTCHBackPSC Hi HC CXMD DXM2L CXM w/LONM DXM2 w/LONN CXM w/MPCP DXM2 w/MPCYESNONOYESTIN PLATEDAIR COILYESNOYESNOYESE-COATEDECON COILN/AN/AN/AN/AYESNOYESNONOYESNOWATER SIDEECONOMIZERNOYESFUTURE USE0 NONECABINET INSULATIONOPTION RANGEA CXMB DXM2E CXM w/LONK DXM2 w/LONR CXM w/MPCS DXM2 w/MPC1AJK2CLM3ENP4GRSULTRAQUIETNOYESNOYES1” FILTER 2” FILTER 1” FILTER 2” ONOYESNONOYESYESNONONote: Above model nomenclature is a general reference. Not all configurations are available on all models. Consult selection software for detailed information.climatemaster.com3

CLIMATEMASTER WATER-SOURCE HEAT PUMPSTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0General InformationSafetyWarnings, cautions, and notices appear throughout thismanual. Read these items carefully before attempting anyinstallation, service, or troubleshooting of the equipment.DANGER: Indicates an immediate hazardous situation,which if not avoided will result in death or serious injury.DANGER labels on unit access panels must be observed.WARNING: Indicates a potentially hazardous situation,which if not avoided could result in death or serious injury.CAUTION: Indicates a potentially hazardous situation oran unsafe practice, which if not avoided could result inminor or moderate injury or product or property damage.NOTICE: Notification of installation, operation, ormaintenance information, which is important, but which isnot hazard-related. WARNING! WARNING! The EarthPure Application and Service Manualshould be read and understood before attempting to servicerefrigerant circuits with HFC-410A. WARNING! WARNING! To avoid the release of refrigerant into theatmosphere, the refrigerant circuit of this unit must beserviced only by technicians who meet local, state, andfederal proficiency requirements. CAUTION! CAUTION! To avoid equipment damage, DO NOT usethese units as a source of heating or cooling during theconstruction process. The mechanical components and filterscan quickly become clogged with construction dirt and debris,which may cause system damage and void product warranty. WARNING! WARNING! The installation of water-source heat pumps andall associated components, parts, and accessories whichmake up the installation shall be in accordance with theregulations of ALL authorities having jurisdiction and MUSTconform to all applicable codes. It is the responsibility ofthe installing contractor to determine and comply with ALLapplicable codes and regulations.4 WARNING! WARNING! All refrigerant discharged from this unit mustbe recovered WITHOUT EXCEPTION. Technicians mustfollow industry accepted guidelines and all local, state, andfederal statutes for the recovery and disposal of refrigerants.If a compressor is removed from this unit, refrigerant circuitoil will remain in the compressor. To avoid leakage ofcompressor oil, refrigerant lines of the compressor must besealed after it is removed.Inspection - Upon receipt of the equipment, carefullycheck the shipment against the bill of lading. Make sureall units have been received. Inspect the packaging ofeach unit, and inspect each unit for damage. Ensure thatthe carrier makes proper notation of any shortages ordamage on all copies of the freight bill and completes acommon carrier inspection report. Concealed damagenot discovered during unloading must be reported to thecarrier within 15 days of receipt of shipment. If not filedwithin 15 days, the freight company can deny the claimwithout recourse.Note: It is the responsibility of the purchaser to fileall necessary claims with the carrier. Notify yourequipment supplier of all damage within fifteen (15)days of shipment.Storage - Equipment should be stored in its originalpackaging in a clean, dry area. Store units in an uprightposition at all times. Stack units a maximum of 3 unitshigh.Unit Protection - Cover units on the job site witheither the original packaging or an equivalent protectivecovering. Cap the open ends of pipes stored on thejob site. In areas where painting, plastering, and/orspraying has not been completed, all due precautionsmust be taken to avoid physical damage to the units andcontamination by foreign material. Physical damage andcontamination may prevent proper start-up and mayresult in costly equipment clean-up.C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s

THE SMART SOLUTION FOR ENERGY EFFICIENCYTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0General Information, Cont’d.Examine all pipes, fittings, and valves before installingany of the system components. Remove any dirt or debrisfound in or on these components.Pre-Installation - Installation, Operation, andMaintenance instructions are provided with eachunit. Horizontal equipment is designed for installationabove false ceiling or in a ceiling plenum. Other unitconfigurations are typically installed in a mechanical room.The installation site chosen should include adequateservice clearance around the unit. Before unit start-up,read all manuals and become familiar with the unit and itsoperation. Thoroughly check the system before operation.Prepare units for installation as follows:1. Compare the electrical data on the unit nameplate withordering and shipping information to verify that thecorrect unit has been shipped.2. Keep the cabinet covered with the original packaginguntil installation is complete and all plastering, painting,etc. is finished.3. Verify refrigerant tubing is free of kinks or dents andthat it does not touch other unit components.4. Inspect all electrical connections. Connections must beclean and tight at the terminals.5. Remove any blower support packaging (water-to-airunits only).6. Loosen compressor bolts and remove compressorbracket on TC sizes 06, 09, and 12 units equippedwith compressor spring vibration isolation until thecompressor rides freely on the springs. Removeshipping restraints. (No action is required forcompressors with rubber grommets.)7. Some airflow patterns are field convertible (horizontalunits only). Locate the airflow conversion section ofthis IOM.8. Locate and verify any hot water generator (HWG),hanger, or other accessory kit located in thecompressor section or blower section. CAUTION! CAUTION! All three phase scroll compressors must havedirection of rotation verified at start-up. Verification isachieved by checking compressor Amp draw. Amp drawwill be substantially lower compared to nameplate values.Additionally, reverse rotation results in an elevated soundlevel compared to correct rotation. Reverse rotation will resultin compressor internal overload trip within several minutes.Verify compressor type before proceeding. CAUTION! CAUTION! DO NOT store or install units in corrosiveenvironments or in locations subject to temperature orhumidity extremes (e.g., attics, garages, rooftops, etc.).Corrosive conditions and high temperature or humidity cansignificantly reduce performance, reliability, and service life.Always move and store units in an upright position. Tiltingunits on their sides may cause equipment damage. CAUTION! CAUTION! CUT HAZARD - Failure to follow this caution mayresult in personal injury. Sheet metal parts may have sharpedges or burrs. Use care and wear appropriate protectiveclothing, safety glasses and gloves when handling parts andservicing heat pumps.NOTICE! Failure to remove shipping brackets fromspring-mounted compressors will cause excessivenoise, and could cause component failure due toadded vibration.climatemaster.com5

CLIMATEMASTER WATER-SOURCE HEAT PUMPSTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0Unit Physical DataTranquility 16 (TC) Series (60 Hz)TC SeriesCompressor (1 Each)Factory ChargeHFC-410A (oz)ECM Fan Motor & BlowerBlower Wheel Size(Dia x w)PSC Fan Motor & BlowerFan Motor Type/SpeedsBlower Wheel Size(Dia x w)Water Connection SizeFPTCoax Volume (gallons)VerticalAir Coil Dimensions(H x W)Filter Standard - 1"ThrowawayWeight - Operating (lbs.)Weight - Packaged (lbs.)HorizontalAir Coil Dimensions(H x W)Filter Standard - 1"ThrowawayWeight - Operating (lbs.)Weight - Packaged 815816317417918218720x17.25 20x17.25 20x17.25 20x17.25 24x21.75 20x17.25 24x21.76 24x28.25 24x28.25Notes:All units have TXV expansion device, and 1/2” & 3/4” electrical knockouts.FPT Female Pipe ThreadCondensate Drain Connection is 3/4” FPT.575 volt fan motors are two speed.Models 006, 009, 012 compressor are mounted on springs. Installer must loosen bolts and remove shipping bracket.Unit Maximum Water Working PressureMax Pressure PSIG[kPa]Base Unit500 [3447]WSE Option300 [2068]6C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s20x28 01-14x24,1-18x2427828520x2520x3520x3520x28 4278285

THE SMART SOLUTION FOR ENERGY EFFICIENCYTranquility Compact ( TC) SeriesR ev. : J u l y 7 , 2 0 2 0Horizontal InstallationHorizontal Unit LocationUnits are not designed for outdoor installation. Locatethe unit in an INDOOR area that allows enough space forservice personnel to perform typical maintenance or repairswithout removing unit from the ceiling. Horizontal unitsare typically installed above a false ceiling or in a ceilingplenum. Never install units in areas subject to freezing orwhere humidity levels could cause cabinet condensation(such as unconditioned spaces subject to 100% outsideair). Consideration should be given to access for easyremoval of the filter and access panels. Provide sufficientroom to make water, electrical, and duct connection(s).Mounting Horizontal UnitsHorizontal units have 4 hanger brackets partially attachedat the factory, one at each corner. Enclosed within the unitthere is a hanger kit hardware bag containing vibrationisolation grommets, washers, screws and a hangerinstallation instruction page. One additional screw fromthe hardware bag must be added to each hanger bracketbefore unit installation.Tighten each screw to 75 in-lbs(8.5 Nm). See Figure 1. Refer to the hanger installatio

CLIMATEMASTER WATER-SOURCE HEAT PUMPS Tranquility Compact (TC) Series Rev.: July 7, 2020 Unit Physical Data Tranquility 16 (TC) Series (60 Hz) TC Series 006 009 012 015 018 024 030 036 041 042 048 060 Compressor (1 Each) Rotary Scroll Factory Charge HFC-410A (oz) 19 20 23 35 43 40 48 50 70 70 74 82 ECM Fan Motor & Blower Blower Wheel Size .File Size: 1MBPage Count: 64Explore furtherClimateMaster - Homewww.climatemaster.comTranquility 16 Compact Single-Stage (TC) Serieswww.climatemaster.comHome ended to you based on what's popular Feedback