Product Selector - 1SXP210003C0201 ABB Molded Case

Transcription

Product Selector - 1SXP210003C0201ABB Molded Case Circuit BreakersFormula, Tmax XT & Tmax T ranges

Index1Table of contents2Formula ranges3Tmax XT ranges4Tmax T rangesABB catalog 1SXP210003C0201

Table of contentsFormula ranges2/1General InformationIntroduction2/2Circuit breakers for power distribution2/3Catalog number explanation2/4Ordering detailsA1, 100A2/5A2, 250A2/6Accessories2/7Tmax XT ranges3/1General InformationIntroduction3/2Circuit breakers for power distribution3/4Catalog number explanation3/6Ordering detailsXT1, 125A, 600Y/347VAC3/10XT1 Accessories3/12XT2, 125A, 600VAC3/19XT2 Accessories3/24XT3, 225A, 600Y/347VAC3/34XT3 Accessories3/36XT4, 250A, 600VAC3/43XT4 Accessories3/52Tmax T ranges4/1General InformationIntroduction4/2Circuit breakers for power distribution4/4Catalog number explanation4/6Ordering detailsT5, 300/400/600A, 600VAC4/13T6, 600/800A, 600VAC4/15Accessories4/17T7, 1000/1200A, 600VAC4/24T7M, 1000/1200A, 600VAC4/27Accessories4/30T8, 1600/2000/2500/3000A, 600VAC4/36Accessories4/39ABB catalog 1SXP210003C0201 1/11

Formula rangesFormula ranges2/1General InformationIntroduction2/2Circuit breakers for power distribution2/3Catalog number explanation2/4Ordering detailsA1, 100A2/5A2, 250A2/6Accessories2/7ABB catalog 1SXP210003C0201 2/12

Formula rangesIntroductionThe FORMULA circuit breakers from 15A to 250A consist of the interruption part together with the trip unit and can be installed: Directly on the back plate of cubicles On a DIN rail2They are characterized by: Fixed version Polarity: 1 pole, 2 poles, 3 poles Maximum breaking capacity of 25kA at 240V AC Fixed thermomagnetic trip unit (TMF) for protection of networks in alternating current A single depth of 2.36” Standard front terminalsFORMULA A11 pole2 pole3 poleFORMULA A22 pole2/21SXP210003C0201 ABB catalog3 pole

Formula rangesCircuit breakers for power distributionMolded case circuit breakers (MCCB)A1A2Frame Size[A]100250Rated Current[A]15.100125.250Poles[No.]1,2,32,3(AC) 50-60Hz[V]240240(DC)[V]250 (2p,3p)250 (2p,3p)Rated voltage2VersionsFixedInterrupting 3p]10101825–10–255–10–10–25240 V (AC)[kA]250 V (DC) 3 poles in seriesWeightTotal opening timeAN[kA]–[No. Operations]8500100001 pole[mm]/[in][25.4 x 60 x 130] / [1 x 2.36 x 5.12]–2 poles[mm]/[in][50.8 x 60 x 130] / [2 x 2.36 x 5.12][70 x 60 x 150] / [2.76 x 2.36 x 5.91]3 poles[mm]/[in][76.2 x 60 x 130] / [3 x 2.36 x 5.12][105 x 60 x 150] / [4.13 x 2.36 x 5.91]1 pole[kg]/[lbs][0.245] / [0.54]–2 poles[kg]/[lbs][0.470] / [1.04][0.73] / [1.61]3 poles[kg]/[lbs][0.700] / [1.54][1.1] / [2.43]CB with SOR[ms]1515CB with UVR[ms]1515 Mechanical lifeDimensions - Fixed(Width x Depth x Height)FixedNTrip units for power distributionTMFABB catalog 1SXP210003C0201 2/3

Formula rangesCatalog number explanation2A1N015TW-21,234,5,67891,2 - Formula prefixA1A2Formula A1 - up to 100A, 240Vac Thermal magnetic protectionFormula A2 - from 125A to 250A, 240Vac Thermal magnetic and electronic protection3 - Breaking capacity at 240VacA (Adequate)N (Normal)A1(1p) 10kA, (2,3p) 10kA(1P) 18kA, (2,3p) 25kA4,5,6 - 20022525015A (Formula A1 only)20A (Formula A1 only)25A (Formula A1 only)30A (Formula A1 only)40A (Formula A1 only)50A (Formula A1 only)60A (Formula A1 only)70A (Formula A1 only)80A (Formula A1 only)90A (Formula A1 only)100A (Formula A1 only)125A (Formula A2 only)150A (Formula A2 only)175A (Formula A2 only)200A (Formula A2 only)225A (Formula A2 only)250A (Formula A2 only)7 - Protection trip unitTThermal-Magnetic protection with fixed threshold8 - ConnectionWWithout lugs9 - Number of poles-1-2Blank2/41 pole version2 pole version3 pole version1SXP210003C0201 ABB catalogA2(2,3p) 10kA(2,3p) 25kA

Formula rangesOrdering details Formula A1A1 100A TMF - Fixed (F) - 1 pole - Front terminals (F) - UL/CSA - Thermal-Magnetic (TMF) 240VacThermal magnetic trip unitTypeTMFInI3IC Rating(240V)A10kAPart numberN18kAPart 90TW-11001000A1A100TW-1A1N100TW-12A1 100A TMF - Fixed (F) - 2 pole - Front terminals (F) - UL/CSA - Thermal-Magnetic (TMF) 240VacThermal magnetic trip unitTypeTMFInI3IC Rating(240V)A10kAPart numberN18kAPart 90TW-21001000A1A100TW-2A1N100TW-2A1 100A TMF - Fixed (F) - 3 pole - Front terminals (F) - UL/CSA - Thermal-Magnetic (TMF) 240VacThermal magnetic trip unitTypeTMFInI3IC Rating(240V)A10kAPart numberN18kAPart A1A090TWA1N090TW1001000A1A100TWA1N100TWABB catalog 1SXP210003C0201 2/5

Formula rangesOrdering details Formula A2A2 250A TMF - Fixed (F) - 2 pole - Front terminals (F) - UL/CSA - Thermal-Magnetic (TMF) 240VacThermal magnetic trip unitType2TMFInI3IC Rating(240V)A10kAPart numberN18kAPart A250TW-2A2N250TW-2A2 250A TMF - Fixed (F) - 3 pole - Front terminals (F) - UL/CSA - Thermal-Magnetic (TMF) 240VacThermal magnetic trip unitTypeTMF2/61SXP210003C0201 ABB catalogInI3IC Rating(240V)A10kAPart numberN18kAPart 52250A2A225TWA2N225TW2502500A2A250TWA2N250TW

Formula rangesOrdering details accessoriesTerminalsType1 pcsPart number2 pcsPart number3 pcsPart number4 pcsPart number6 pcsPart -2KA2F-3KA2F-4KA2F-6A1KA1EF-1FC CuAl 80AFC CuAl 100AFC CuAl 250A Cu cables and 225A Al 080-6KA1100-6KA2225-6FC CuAl 80AA2KA2250-1KA2250-2KA2250-3KA2250-4KA2250-6F Front terminalsEF terminalEF Extended front terminals (1)ES Extended spread terminalsFCCu terminal(1)(1)2IEC rated only.Terminals coversTypeTerminal coversA1A2HTC, 3p (2pcs)KA1HTC-3KA2HTC-3LTC, 3p (2pcs)Sealable screws for terminal coversSealable screws for W-FSealable screwPhase SeperatorsTypePB 50mmA1(2 pcs)(4 pcs)A2(2 pcs)(4 pcs)KA1PBL-2KA1PBL-3--PB 80mm--KA2PBL-2KA2PBL-3PB 100mmKA2PBH-2KA2PBH-3KA2PBH-2KA2PBH-3Phase barriersDIN rail adaptorTypeA1 - A2Part numberBracket for 1p, 2p, 3p versionsKA2DINBracket for DIN railABB catalog 1SXP210003C0201 2/7

Formula rangesOrdering details accessoriesRotary Handle Component2Direct rotary handleTypeA1 - A2Part numberRHD (direct standard)KA2RHDRHD EM (direct Emergency colour)KA2RHDEMRHE (returned standard)KA2RHERHE EM (returned emergency colour)KA2RHEEMRHE B (rotary mechanism only)KA2RHE-BRHE S (Rod only)KA2RHE-SRHE-H (standard handle only)KA2RHE-HRHE EM (emergency colour handle only)KA2RHE-HEMPistol handle NEMA 1,3R,12 blackOHB65J10BPistol handle NEMA 4,4X blackOHB65L10BShaft for pistol handle 500mmOXP10X500Extended rotary handlePadlocks for lever operating mechanism (PLL)TypeA1 - A2Part numberRemovable in open positionKA2LDORFixed in open positionKA2LDOFixed in open and closed positionKA2LDFixed padlock in open position(PLL)Fixed padlock in open and closedposition (PLL)Removable padlock in open position (PLL)Keylock on handle and operating mechansim (IEC only)Key lock for direct handleTypeA1 - A2Part numberRHL-D Open position, different keysKA2RHLORHL-S Open position, same keys type AKA2RHLO-ARHL-S Open position, same keys type BKA2RHLO-BRHL-S Open position, same keys type CKA2RHLO-CRHL-S Open position, same keys type DKA2RHLO-DRHL-D Open/Closed position, different keysKA2RHLKey lock for extended handle2/81SXP210003C0201 ABB catalog

Formula rangesOrdering details accessoriesShunt Opening Release (cabled) - SOR-CCabled service releaseSOR-C and UVR-CTypeA1 - A2Part numberSOR-C 12 VdcKA2S9SOR-C 24-30V ac/dcKA2S8SOR-C 48-60V ac/dcKA2S7SOR-C 110-127V ac/dcKA2S4SOR-C 220-240Vac, 220-250VdcKA2S22Undervoltage Release (cabled) - UVR-CTypeA1 - A2Part numberUVR-C 12 VdcKA2U9UVR-C 24-30V ac/dcKA2U8UVR-C 48V ac/dcKA2U7UVR-C 60V ac/dcKA2U5UVR-C 110-127Vac, 110-125VdcKA2U4UVR-C 220-240Vac, 220-250VdcKA2U2Auxiliary contacts (cabled version with numbered cables) - AUX-CTypeA1, 2pPart numberA1, 3pPart numberA2, 2pPart numberA2, 3pPart numberKA2ASAUX-C, 1Q 1SY, 250V ac/dcKA2AS-2KA2AS-AUX-C, 2Q 1SY, 250V ac/dc-KA2AS2KA2AS2-2KA2AS2AUX-C, 1Q 1SY, 24VdcKA2ASAU-2KA2ASAU-KA2ASAUAUX-C, 2Q 1SY, 24Vdc-KA2AS2AUKA2AS2AU-2KA2AS2AUAuxiliary contacts (cabled version spare parts IEC only)Cabled auxiliary contactTypeA1 - A2AUX-C, 250V, 1 CONT.Part numberKA2ASSPEarly auxiliary contacts (IEC only) - AUE-CTypeA1 - A2AUE-CPart numberKA2RH-EMEarly auxiliary contactABB catalog 1SXP210003C0201 2/9

Tmax XT rangesTmax XT ranges3/1General InformationIntroduction3/2Circuit breakers for power distribution3/4Catalog number explanation3/6Ordering detailsXT1, 125A, 600Y/347VAC3/10XT1 Accessories3/12XT2, 125A, 600VAC3/19XT2 Accessories3/24XT3, 225A, 600Y/347VAC3/34XT3 Accessories3/36XT4, 250A, 600VAC3/43XT4 Accessories3/52ABB catalog 1SXP210003C0201 3/13

Tmax XT rangesIntroduction3The new SACE Tmax XT go everywhere and fear no tests because they are made to respond successfully to all plantengineering requirements, from the standard to the most technologically advanced, thanks to the extraordinary fullness of theirrange. They provide a complete offering up to 250A for distribution, for energy metering, for motor protection, for generatorprotection, as switch-disconnectors and for any other needs. In addition, a new range of both thermomagnetic and electronicprotection trip units, interchangeable right from the smallest frames, has been created. This is to say nothing of the new andvast line of dedicated accessories available, even for special applications.All that remains is making a simple selection: XT1 and XT3, with ABB SACE’s unquestioned reliability and safety, for standardinstallations, or XT2 and XT4, with top of the market performance, for technologically advanced installations. The new SACETmax XT: simply extraordinary, for any choice.Ekip trip units are interchangeable and guarantee absolute tripping reliability and precision. Apart from the continuous greenLED, which indicates correct operation of the protection trip unit, all the Ekip trip units also have an LED to signal interventionof all the protection functions.To allow the Ekip units to communicate and exchange information with the other devices, the Ekip Com module can be insertedinside the circuit breaker, freeing space inside the electric panel.All the Ekip trip units can be fitted with a vast range of dedicated accessories. The main accessories include:– the Ekip Display, to be applied onto the front of the electronic trip unit for simpler setting and for better reading ofinformation;– the Ekip LED Meter, a device to be installed on the front of the trip unit to simplify current readings;– the Ekip TT, the new trip test unit;– the Ekip T&P, the extraordinary testing and programming unit.Finally, for the first time an integrated energy metering function is available on the 250A frame Ekip: isn’t all this simplyXTraordinary?3/21SXP210003C0201 ABB catalog

Tmax XT rangesIntroductionThere are the 4 new SACE Tmax XT UL/CSA vailableavailableupupupuptotototo125A125A with 600Vac ratings225A250A with 600Vac ratings3600Y/347VAC, 480VACXT1 - 125AXT3 - 225AXT2 - 125AXT4 - 250A600VACABB catalog 1SXP210003C0201 3/3

Tmax XT rangesCircuit breakers for power distributionMolded case circuit breakers (MCCB)XT1Frame Size[A]125Rated80% rated 100% rated TMup to 100APolesRated voltage100% rated Ekip-[No.]3, 4(AC) 50-60Hz[V]600Y/347(DC)[V]500Versions3Fixed, Plug-inInterrupting ratingsNSH240 V (AC)[kA]5065100480 V (AC)[kA]253565600Y/347 V (AC)[kA]182225600 V (AC)[kA]–––250 V (DC) 2 poles in series[kA]354250500 V (DC) 3 poles in series[kA]–––500 V (DC) 4 poles in series[kA]355050600 V (DC) 3 poles in series[kA]–––[No. Operations]25000Mechanical life[No. Hourly operations]240Dimensions - Fixed(Width x Depth x Height)3 poles[mm]/[in][76,2 x 70 x 130] / [3 x 2.75 x 5.12]4 poles[mm]/[in][101,6 x 70 x 130] / [4 x 2.75 x 5.12]WeightFixed 3/4 poles[kg]/[lbs][1,1 - 2.43] / [1,4 - 3.07]Plug-in (EF) 3/4 poles[kg]/[lbs][2,21 - 4.87] / [2,82 - 6.22]Withdrawable (EF) 3/4 poles[kg]/[lbs]–CB with SOR[ms]15CB with UVR[ms]15Total opening timeTrip units for power distributionTMF TMA–Ekip LS/I–Ekip I–Ekip LSI–Ekip LSIG–Ekip E-LSIG–Interchangeable protection trip units(1)(2)(3)(4)–Current Limiting circuit breaker in 480V AC and 600V AC2-poles version available only as complete circuit breaker with TMF, trip units interchangeable; 4-poles version available only as complete circuit breaker from In 80 to In 250 with TMF, trip units interchangeableWith F, EF, ES, FCCuAl installation100kA up to 150A, 65kA from 175A up to 250AMotor protection (1)XT1Frame Size[A]Poles[No.]3(AC) 50-60Hz[V]600Y/347(DC)[V]Rated service voltage125500VersionsFixed, Plug-inRating levelHTrip units for motor protection(1)MA (MCP) Ekip M-LIU (MPCB)–Available only as complete circuit breakerMolded case disconnect switches (MCS)XT1Frame Size[A]Poles[No.]3, 4(AC) 50-60Hz[V]600Y/347(DC)[V]Rated voltageVersions3/41SXP210003C0201 ABB catalog500 4p series / 3p CB up to 250V DC 2p seriesFixed, Plug-inRating levelMagnetic Override125N[A]1250SH

Tmax XT rangesCircuit breakers for power distributionXT2XT3125225XT4250 up to 100Afixed version onlyup to 250A (3) 3, 4-up to 250A (3)3, 42 (for N version) 3, 4600600Y/347600500500600Fixed, Plug-in, WithdrawableFixed, Plug-inFixed, Plug-in, WithdrawableNSH (1)L (1)V(1)XNSNSH (1)L 02500025000240240240[90 x 82,5 x 130] / [3.54 x 3.25 x 5.12][105 x 70 x 150] / [4.13 x 2.75 x 5.90][105 x 82,5 x 160] - [4.13 x 3.25 x 6.3][120 x 82,5 x 130] / [4.72 x 3.25 x 5.12][140 x 70 x 150] / [5.51 x 2.75 x 5.90][140 x 82,5 x 160] - [5.51 x 3.25 x 6.3][1,2 - 2.65] / [1,6 - 3.53][1,7 - 3.37] / [2,1 - 4.63][2,5 - 5.51] / [3,5 - 7.72][2,54 - 5.60] / [3,27 - 7.21][3,24 - 7.14] / [4,1 - 9.04]1515151515 – – – – – –– – XT2XT3XT4125225250333600600Y/347600500500600Fixed, Plug-in, WithdrawableFixed, Plug-inFixed, Plug-in, WithdrawableHSH – XT2XT3XT41252252503, 43, 43, 4600600Y/347600500 3p series500 3p series600 3p seriesFixed, Plug-in, WithdrawableFixed, Plug-in1250(4)[5 - 11.02] / [6,76 - 14.90]15H3[4,19 - 9.24] / [5,52 - 12.17][3,32 - 7.32] / [4,04 - 8.91]NXLVN2250Fixed, Plug-in, WithdrawableSNSHLV2500ABB catalog 1SXP210003C0201 3/5

Tmax XT rangesCatalog number explanationTmax XT Part number 4151617181,2 - Tmax XT prefix, XT3 - Frame size31234XT1 - to 125A, 600Y/347V (UL)) - Thermal magnetic protectionXT2 - to 125A, 600V (UL) - Thermal magnetic and electronic protectionXT3 - to 225A, 600Y/347V (UL) - Thermal magnetic protectionXT4 - to 250A, 600V (UL) - Thermal magnetic and electronic protection4 - Breaking CapacityXT118kA @ 600Y/347Vac22kA @ 600Y/347Vac25kA @ 600Y/347Vac-NSHLVX(1)XT218kA @ 600Vac22kA @ 600Vac25kA @ 600Vac35kA @ 600Vac42kA @ 600Vac45kA @ 600VacXT310kA @ 600Y/347Vac10kA @ 600Y/347Vac-XT418 @ 600Vac22 @ 600Vac25 @ 600Vac50 @ 600Vac65 @ 600Vac100kA @ 600Vac (1)100kA up to 150A. 65kA from 175A up to 250A5 - StandardUQUL standard versionUL 100% rated version6 - Number of poles2342 poles (XT4N UL version only)3 poles4 poles, 100% neutral7,8,9 - Nominal current 7A15A30A50A70A80A100A125A-MCSXT2TMF/125A-TMA 0A80A100A125A-LIU25A60A100A-MCS125A-(1)XT2 TMF FIXED treshold up to 70A, TMA adjustable for 80A and higher.(2)XT4 2p version with TMF version only. XT4 3p TMF version up to 70A, TMA adjustable for 80A and higher. XT4 4p TMA version only3/61SXP210003C0201 ABB F/225A-TMA 40A60A100A150A-250A

Tmax XT rangesCatalog number explanation10 - Trip unitAThermal magnetic fixed (TMF)BThermal magnetic adjustable (TMD/TMA)DMolded case switch disconnector (MCS)EEkip LS/I (Electronic, LS/I protection)FEkip LSI (Electronic, LSI protection)GEkip LSIG (Electronic, LSIG protection)HEkip E-LSIG (Electronic, LSIG plus measurements)JEkip I (Electronic, Instantaneous trip only)LEkip M-LIU (Electronic Motor Protector with integrated overload and phase loss detection)MMotor circuit protector (MCP - magnetic only (MA)311 - Line side termination (top)FF Front terminals, no lugs installedAFC Cu Terminals for Cu cables (Saddle Clamps)BFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 110A (UL XT2)(1)GFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 100A (UL XT3, UL XT4)(2)HFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 100A, Control Tap Included (UL XT3, UL XT4)(1)(2)JFC CuAl Terminals for CuAl cables, 4 AWG-300 kcmil, 225A (UL XT3, UL XT4)(2)KFC CuAl Terminals for CuAl cables, 4 AWG-300 kcmil, 225A, Control Tap Included (UL XT3, UL XT4)(1)(2)LFC CuAL Terminals for CuAl Cables, 250-350 kcmil, 250A (UL XT4)(1)(2)ZMC Multi-cable terminals for Cu (6 wire)1EF Extended front terminals2ES Extended spread terminals3FB Terminals for flexible busbar (IEC only)4R Rear terminals (IEC only)5Panel board Adapter(1)6Plug-in kit (Must also use 6 for load side)7Withdrawable kit - XT2 & XT4 only (Must also use 7 for the load side)(1)Contact ABB for availability.(2)Not available for XT4 X version to 150A.Note: Additional terminal options are available as loose accessories for IEC versions. Please see the IEC catalog for more details.12 - Load side termination (bottom)FF Front terminals, no lugs installedAFC Cu Terminals for Cu cables (Saddle Clamps)BFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 110A (UL XT2)(1)GFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 100A (UL XT3, UL XT4)(2)HFC CuAl Terminals for CuAl cables, 14-1/0 AWG, 100A, Control Tap Included (UL XT3, UL XT4)(1)(2)JFC CuAl Terminals for CuAl cables, 4 AWG-300 kcmil, 225A (UL XT3, UL XT4)(2)KFC CuAl Terminals for CuAl cables, 4 AWG-300 kcmil, 225A, Control Tap Included (UL XT3, UL XT4)(1)(2)LFC CuAL Terminals for CuAl Cables, 250-350 kcmil, 250A (UL XT4)(1)(2)ZMC Multi-cable terminals for Cu (6 wire)1EF Extended front terminals2ES Extended spread terminals3FB Terminals for flexible busbar (IEC only)4R Rear terminals (IEC only)6Plug-in kit (Must also use 6 for line side)7Withdrawable kit - XT2 & XT4 only (Must also use 7 for the line side)(1)Contact ABB for availability.(2)Not available for XT4 X version to 150A.Note: Additional terminal options are available as loose accessories for IEC versions. Please see the IEC catalog for more details.ABB catalog 1SXP210003C0201 3/7

Tmax XT rangesCatalog number explanation13 - Internal accessories - left of mechanism30NoneASOR Shunt trip 12V DCBSOR Shunt trip 24-30V AC/DCCSOR Shunt trip 48-60V AC/DCDSOR Shunt trip 110-127V AC / 110-125V DCESOR Shunt trip 220-240V AC / 220-250V DCFSOR Shunt trip 380-440V ACGSOR Shunt trip 480-525V ACZAUX 3Q 250V AC/DC (not available for withdrawable)1UVR Undervoltage release 24-30V AC/DC2UVR Undervoltage release 48V AC/DC3UVR Undervoltage release 60V AC/DC4UVR Undervoltage release 110-127V AC 110-125V DC5UVR Undervoltage release 220-240V AC 220-250V DC6UVR Undervoltage release 380-440V AC7UVR Undervoltage release 480-525V ACNote: A second option for the left side of the mechanism is available on a 4-pole circuit breaker as a loose accessory.14 - Internal accessories - right of mechanism0NoneAAUX 1Q, 1SY 250V AC/DCBAUX 2Q, 1SY 250V AC/DC (not available for withdrawable)CAUX 3Q, 1SY 250V AC/DC (not available for XT1)DAUX 3Q, 2SY 250V AC/DC (XT2, XT4)EAUX 2Q, 2SY, 1 S51 250V AC/DC (XT2, XT4)FAUX 1 S51 250V AC/DC (XT2, XT4)GAUX 1Q, 1SY 24V DCHAUX 3Q, 1SY 24V DC (not available for XT1)JAUX 1 S51 24V DC (XT2, XT4)KAUX 1Q, 1SY 400V AC (XT2, XT4 not compatible with other right side AUX)LAUX 2Q 400V AC (XT2, XT4 not compatible with other right side AUX)1Ekip Com (XT2, XT4, not compatible with other right side AUX)2Ekip Com Aux 1S51 24V DC (XT2, XT4, not compatible with other right side AUX)3Ekip Com Aux 1S51 250V AC/DC (XT2, XT4, not compatible with other right side AUX)3/81SXP210003C0201 ABB catalog

Tmax XT rangesCatalog number explanation15 - Front accessories0NoneAMotor operator 24V DCBMotor operator 48-60V DCCMotor operator 110-125V AC/DCDMotor operator 220-250V AC/DCEMotor operator 380-440V ACFMotor operator 480 - 525V ACGPLL Fixed padlock device in open/closed positionHPLL Fixed padlock device in open positionJPLL Removable padlock device in open position (XT1, XT3)KFLD Front for locking operating lever mechanism (XT2, XT4)LRHD Normal direct handleMRHD Emergency direct handleNRHE Variable depth mechanism, standardPRHE Variable depth mechanism, with padlockQRHD Normal direct handle Early Aux contact, openingRRHD Emergency direct handle Early Aux contact, openingSRHE Variable depth mechanism, standard Early Aux contact, openingTRHE Variable depth mechanism, with padlock Early Aux Contact, openingURHD Normal direct handle Early Aux contact, closingVRHD Emergency direct handle Early Aux contact, closingWRHE Variable depth mechanism, standard Early Aux contact, closingXRHE Variable depth mechanism, with padlock Early Aux Contact, closing1Motor operator for use with Modbus 24V DC (IEC only)2Motor operator for use with Modbus 48-60V DC (IEC only)3Motor operator for use with Modbus 110-125V AC/DC (IEC only)4Motor operator for use with Modbus 220-250V AC/DC (IEC only)5Motor operator for use with Modbus 380-440V AC (IEC only)6Motor operator for use with Modbus 480 - 525V AC (IEC only)316 - Key locksXNoneARonis key lock, open position- A typeBRonis key lock, open position - B typeCRonis key lock, open position - C typeDRonis key lock, open position - D typeERonis key lock, open position - different keysFRonis key lock, open/closed - different keys (not available for motors)Note: Key locks are available for placement on the circuit breaker, on rotary handle mechanisms or on motors. Key locks for motors are IEC only.17 - For future useXNone18 - Additional certificationsXNone3yr warranty4yr warranty5yr warranty345Test certificate provided (in English)EABCTest certificate provided (in French)FGHJTest certificate provided (in Spanish)SKLMNote: Extended warranty options require additional paperwork to be completed per order.ABB catalog 1SXP210003C0201 3/9

Tmax XT rangesOrdering details XT1XT1 125A TMF - Fixed (F) - 3 poles - Front terminals (F) - UL/CSAThermal magnetic trip unitTypeInI3TMF155003IC Rating(600Y/347V)N18kAPart numberXT1NU3015AFF000XXXS22kAPart numberXT1SU3015AFF000XXXH25kAPart 000XXXSQ22kAPart numberXT1SQ3015AFF000XXXHQ25kAPart numberXT1HQ3015AFF000XXXXT1 125A TMF - Fixed (F) - 3 poles - Front terminals (F) - 100% rated UL/CSAThermal magnetic trip unitTypeInI3IC Rating(600Y/347V)TMF15500NQ18kAPart 1SQ3100AFF000XXXXT1HQ3100AFF000XXXN18kAPart numberS22kAPart numberH25kAPart numberXT1HU4015AFF000XXXXT1 125A TMF - Fixed (F) - 4 poles - Front terminals (F) - UL/CSAThermal magnetic trip unitIC 00XXX1SXP210003C0201 ABB catalog

Tmax XT rangesOrdering details XT1XT1 125A TMF - Fixed (F) - 4 poles - Front terminals (F) - 100% rated UL/CSAThermal magnetic trip unitNQ18kAPart numberSQ22kAPart numberHQ25kAPart AFF000XXXXT1HQ4025AFF000XXXTypeInI3TMF152025IC AFF000XXX3XT1 125A MCP (MA) Fixed (F) - 3 poles - Front terminals (F) - UL/CSAMagnetic trip unitIC Rating(600Y/347V)H25kAPart numberXT1HU3003MFF000XXXTypeInI3MCP39 33721 77XT1HU3007MFF000XXX1545 165XT1HU3015MFF000XXX3090 330XT1HU3030MFF000XXX50150 550XT1HU3050MFF000XXX70210 770XT1HU3070MFF000XXX80240 880XT1HU3080MFF000XXX100300 1100XT1HU3100MFF000XXX125375 1375XT1HU3125MFF000XXXXT1 125A Switch - Fixed (F) - 3 poles - Front terminals (F) - UL/CSANo Trip UnitTypeInMag. OverrideD1251250IC Rating(600Y/347V)N18kAPart numberS22kAPart numberH25kAPart 5DFF000XXXS22 kAPart numberXT1SU4125DFF000XXXH25kPart numberXT1HU4125DFF000XXXXT1 125A Switch - Fixed (F) - 4 poles - Front terminals (F) - UL/CSANo Trip UnitTypeInMag. OverrideD1251250IC Rating(600Y/347V)N18kAPart numberXT1NU4125DFF000XXXABB catalog 1SXP210003C0201 3/11

Tmax XT rangesXT1 AccessoriesFixed parts, conversion kits and accessories for fixed partsFixed part of plug-in (P)Type34pPart numberKit P FP EFKXT1PFPEF-3KXT1PFPEF-4Kit P FP HR/VR(1)KXT1EPFPHR-3KXT1EPFPHR-4(1)Fixed part of plug-in3pPart numberIEC rated only. The terminals are factory-mounted in the horizontal position (HR).Terminals for the fixed parts(1)Type3pPart number4pPart numberEF - Front extended terminalsKXT1EEFFP-3KXT1EEFFP-4R - Rear terminals HR/VRKXT1ERFP-3KXT1ERFP-4PS - Rear phase separators 90mm/3.54inKXTAEPB90-3KXTAEPB90-4(1)IEC rated only.Conversion kit of the circuit breaker from fixed into moving part of plug-inType3pPart number4pPart numberP MP kitKXT1PMP-3KXT1PMP-4Conversion kitAdapter for mounting the terminals of the fixed circuit breaker on the fixed partFixed part adapter3/121SXP210003C0201 ABB catalogType3pPart number4pPart numberADP adapter for fixed part (2 pieces)KXT1ADP-3KXT1ADP-4Note: When using ADP with ES/MC terminals, also order “Kit F Front Terminals”.

Tmax XT rangesXT1 AccessoriesService releasesShunt Trip - SORTypePart numberUncabled versionSOR uncabledSOR 12V DCKXTASORASOR 24-30V AC/DCKXTASORBSOR 48-60V AC/DCKXTASORCSOR 110.127V AC / 110.125V DCKXTASORDSOR 220.240V AC /

Product Selector - 1SXP210003C0201 ABB Molded C