PROFIBUS-PA - Fieldbus Components For PROFIBUS-PA

Transcription

FIELDBUSCOMPONENTSFORPROFIBUS-PAF1026/01

FIELDBUS COMPONENTS FORPROFIBUS-PAFieldbus systems in processautomationFieldbus systems have become prevalentin the field of process automation inaddition to decentral peripheral systems.PROFIBUS-PA and FOUNDATION fieldbus fieldbus systems are now the established fieldbuses in this field (for furtherinformation about the TURCK-productportfolio and in particular FOUNDATIONfieldbus products, please see catalogueD301024).The advantages of both of these systemsare the process adapted specification andthe real interoperability of field devicesfrom various manufacturers and theircompatibility with external host systems.Both the FOUNDATION fieldbus andPROFIBUS-PA fieldbus fulfil the demandsof the chemical, pharmaceutical andpetrochemical industries. The mostimportant features are : standardised user profile suited for use in explosionhazardous areas bus supply and fieldbuscommunication via shielded andtwisted pair cables online device exchange withoutaffecting system processesComprehensive tests performed by theindustry, interest groups and committeesconfirm the unlimited suitability of both bussystems for use in process engineering.TURCK fieldbus componentsWith TURCK products you are not tieddown to company-specific fieldbustechnologies, but can choose the mostsuitable bus product for your applicationfrom a comprehensive product spectrum.TURCK offers the complete range for allconventional industrial fieldbus systems infactory and process automation, no matterwhether you require junction modules,connection products or even completesystems.Junction modules in IP67(1, 4 and 6 channels) Device versions for use in:– zone 1– zone 2– Non-Ex area Adjustable current limitation Switch-in terminating resistors Housing material: powder-coatedaluminium die-cast (4 and 6-channeltypes) or encapsulated Polyurethane(PUR) for the single channel versions. Connection technology: cable glandsor flange connectionsin 7/8“ or M12 1, stainless steelMultibarriers in IP66 (4 channels) Installation in explosion hazardousareas (zone 1) Galvanic isolation between the EEx ioutputs and the EEx e main cableas well as between the individualEEx i outputs Fieldbus power supply according to enhanced safety EEx e Four intrinsically safe EEx iaoutputs, 4 40 mA, short-circuitprotected and non-interacting FISCO and Entity conform outputs(IEC TS 60079-27) Short-circuit indication via LEDs(inside housing) Integrated terminating resistors(switch-in)Junction modules in IP20(4, 6, 8 and 12 channels) Device versions for use in:– zone 1– zone 2– Non-Ex area Adjustable current limitation Switch-in terminating resistors Housing material: aluminium Connection technology: cage clampterminals or removeable connectorsStainless steel housing for IP20junction boxes Plastic or stainless steel cable glands l Degree of protection IP67 Pressure compensation element Isolated shielding busTURCK fieldbus components are specially designed for the harsh industrialenvironment. The extensive product linefor diverse applications fulfils all demandsand provides Plug & Play connectivity toensure fast and easy connection of thefield device to the control system.Fieldbus cables and cordsets in variousfieldbus standards and materials and withdifferent connector types are available fordata transfer and voltage supply of thestations.2 /0407Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

Temperature transmitters Automatic protocol conversion Ex-approval (EEx ia and EEx n) DIN type B connector Linear resistance, compensatorand bipolar mV measurementsFieldbus cable available as bulk cableor prefabricated For indoor and outdoor use For connection to field-wireableM12 1 or 7/8” connectors, PG9or M16/M20 cable glands Simple installation via Fast-Assembly technology Just-In-Time delivery by the TURCKJIT-5D-programme: Delivery of allavaliable premoulded cable lenghtswithin 5 daysTerminating resistors Versions for intrinsically-safe andnon-intrinsically safe circuits M12 1 or 7/8“ Plug-and-Play technology Connector pin assignment conform toCENELEC standard EN 50044Connectors Connector size: M12 1 or 7/8“,type: straight or angled(angled M12 1 only) Plug-and-Play technology Load capacity: 7/8“ with 9 A,M12 1 with 4 A Connector pin assignment conform toCENELEC standard EN 50044Field device overvoltage protection Aluminium die-cast housings Connection to potential equalisationvia M5 1 bolt on housing Degree of protection: IP67 and IP20The data sheets are available underwww.turck.comSpecial accessories Stripping tool, stripping of round(shielded) data conductors from2.5.8 mm Ø (also forFastConnect /Fast Assembly ) Special tool for cable glands onmultibarrier and junction modules Closure caps and feed-throughsin 7/8“ and M12 1Flange connections Field-wireable or prefabricated Connector size: M12 1 or 7/8“ Solderable and screw-type versions Standard installation thread Stainless steel housingsHans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com3 /04071

THE TURCK PRODUCT DATA BASEIN THE WORLD WIDE WEBYour are looking for a customised solutionconcerning your application or searchingfor a particular product? You want to orderor download catalogues, data sheets,manuals, software or configuration files?For comprehensive information, please goto www.turck.com4 /0407Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

FIELDBUS COMPONENTS FORPROFIBUS-PAFeldbus systems – basicsPROFIBUS-PA – bus physicsPROFIBUS-PA – topologyOverview – application of TURCK’s fieldbus components in the explosionhazardous and non-explosion hazardous areasPage6719Active componentsMultibarrier MBD48-T415/Ex – basics and application benefitsMultibarrier MBD48-T415/ExDigital Display FD-48-T317/ExTemperature transmitters KMU-40Ex.111214162Junction boxesJunction boxes by TURCKJunction boxes in IP67 with short-circuit protectionJunction boxes in IP67 without short-circuit protectionJunction boxes in IP20 with short-circuit protectionJunction boxes in IP20 without short-circuit protection21224670783Fieldbus cablesCable technology– basicsCable FBY-./SD.Cable FBY-BK/LD.Cable FBH-YE.Cable FBA-YE.Cable 482A./Cable 482BA.Cable FB4910-BK.868889909192934Premoulded cablesJust in time delivery: the TURCK JIT-5D-Programme– M12 1 with cable FBY48.– 7/8“ with cable FBY48.7/8“ with armoured cables 482A. or 482BA.949595965Flange connectors7/8“ connectorM12 1 connector981046Field wireable connectors7/8“ connectorM12 1 connector1101167Bus termination resistors7/8“ connectorM12 1 connector12312481269AccessoriesStainless steel housingsStripping tool, special tool for cable glands,closure caps, feed-through receptaclesType index13013610Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com5 /0407

PROFIBUS-PABasicsPROFIBUS-PA – bus physicsWith the publication of the internationalstandard IEC 61158-2 in October 1994,a suitable transmission technology wasdetermined and internationally specifiedfor the application areas of PROFIBUS-PAand FOUNDATION fieldbus . This waslater integrated into the European standards as EN 61158-2.Both systems comply with IEC 61158-2and operate on the voltage mode with atransmission speed of 31.25 kBit/s. In thisway the data packages are modulatedonto the supply voltage for the fieldbusstation and transmitted via a shielded twowire cable (see Fig. 1).bus voltagefieldbus data signal0,75.1,0 VSS9.32 VtFig. 1Transmission of data packages to IEC 61158-2These bus physics offer a decisiveadvantage: fieldbus communication andpower supply of the bus station can beimplemented using a single cable. Thesebus physics lead to enhanced operationalsafety and lower costs compared with theconventional fieldbus solution used up tothis point with its additional wiring effort.Characteristic features of the IEC 61158-2 transmission physicsData transmissiondigital, bit synchronous, Manchester codingTransmission speed31.25 kBit/s, voltage modeData securitypreamble, fault protected start and end delimiterCableshielded and twisted 2-wire cableRemote supply of the stationsoptionally via signal cablesProtection classesintrinsically safe (Ex ia/ib or Ex nL), increased safe (Ex e or Ex nA) andexplosion protected (EEx d/m/p/q)Topologyspur and tree topologies; also in combinationNumber of stationsup to 32 stations per cable segmentRepeatercan be extended with a maximum of 4 repeaters6 /0407Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

PROFIBUS PA – topologyHostSystem integration with PROFIBUS-PAis implemented via a DP/PA segmentcoupler originating from the PROFIBUSDP fieldbus. The segment coupler adaptsthe RS485 transmission physics to thetransmission physics determined in IEC61158-2. If the DP segment operateswith a higher speed, an additional link isrequired.1PCPROFIBUS-DP RS485DP/PALink/CouplerEExi outputPTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 Xexcom Junction box JBBS-48.The segment coupler for non-explosionhazardous applications provides enoughpower for a sufficient number of fieldbusstations (Fig. 2).PROFIBUS-PAFieldbus NodeFig. 2A coupler with an intrinsically-safe outputis necessary for use in explosion-hazardous areas. This, however, reduces theoutput power and the number of connectable bus stations. Only a few stationscan be powered (Fig. 3) due to the currentconsumption of the bus stations.Topology – PROFIBUS PA in the non-explosion hazardous area withDP/PA couplerHostPCPROFIBUS-DP RS485DP/PALink/CouplerEExi outputJunction boxJBBS-48./ExPTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 Xexcom PROFIBUS-PAFieldbus NodeFig. 3Topology – PROFIBUS-PA in the explosion hazardous area withDP/PA couplers with intrinsically safe outputsHans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com7 /0407

PROFIBUS-PABasicsThis situation can be remedied by a topology which is based on the use of mainline (trunk line) featuring “enhanced safety”and intrinsically safe outputs.This is where the multibarrier is employed,permitting a current of up to 10 A in thetrunk line area, and when connected inseries, supplying up to intrinsically safe32 stations in the explosion-hazardousarea.PCPROFIBUS-DP RS485DP/PACouplerPTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 X PTB 00 ATEX 0000 Xexcom Segment outPROFIBUS-PAFig. 4 shows the typical configuration ofa PROFIBUS-PA network with TURCKmultibarriers. The number of multibarrierswhich can be switched in and the maximum cable lengths depend on the outputpower of the DP/PA coupler and on thecable type.MBD48-T415/ExZone 1TURCK recommends the long-distancecable FBY./LD (see page 89) for thetrunk line; for the outputs the standardcable FBY./SD is recommended (seepage 88).EEx eMBD48-T415/ExEEx eMBD48-T415/ExTrunk inTrunk outMultibarrierüïïý 120 mïïþZone 0Fig. 48 /0407HostTopology – PROFIBUS-PA in the explosion-hazardous area with multibarriersHans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

Overview – application of TURCK’s fieldbus components in the explosion hazardous and non-explosion hazardous areasApplication inEEx i circuitsconform to FISCOApplication inEEx i circuitsconform to EN 50020Application inEx nLcircuitsconform toEEx iaEEx iaEEx ibEEx ibZone 0 Zone 1 Zone 2 Zone 0 Zone 1 Zone 2 FNICOEntityInstallationinInstallationin theNon-ExareaZone 0 Zone 1 Zone 2Junction boxes withoutshort-circuit ��——————————— ——— Junction boxes withshort-circuit ��—————————————— —————— Ex junction boxes withoutshort-circuit protectionJBBS.M./ExJBBS.E./ExJBBS.T./Ex ——— Ex junction boxes withshort-circuit protectionJBBS.SC.M./ExJBBS.SC.E./ExJBBS.SC.T./Ex ——— Ex junction boxes forDIN hat-rail mountingJRBS.1) — MultibarriersMBD.2) — TemperatureKMU-40Ex/1GDKMU-40Ex/3G — — — — — — — — Terminating resistorsRS.-TR——————————— Ex terminating resiatorsRS.-TR/Ex Passive equippmentwithout electronics (cable,connectors, flanges .3) transmitters1) Use possible— Use not possible1)Use only permitted when installed in an additional housing (minimum IP54 degree of protection)Equipment with differing protection classes – only the EEx i outputs haveintrinsically safe circuits3) Taking consideration of the EN 50014, EN 50020 and EN 60079-14 standards2)CAUTIONIntrinsically safe equipment,which has been used in nonintrinsically safe applications,may not subsequently be usedin intrinsically safe applications.Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com9 /04071

PROFIBUS-PA10 /0407Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

PROFIBUS-PAMultibarrier MBD48-T415/Ex –Basics and application benefitsThe operating principle of the MBD48T415/Ex multibarrier is physically basedon IEC 61158-2. The use of multibarriersincreases the number of fieldbus stationsin the PROFIBUS-PA network to a maximum of 32 field devices.This high number of stations is achievedby enhanced safety of the fieldbus supplywhich can be looped through from multibarrier to multibarrier. The fieldbus stationsin zone 0 are supplied with power viathe four intrinsically safe outputs of eachmultibarrier device.User benefitsThe user can expect substantial cost advantages due to the possibility of cascading the multibarriers in a single segmentin the explosion hazardous area, thus fullyexploiting the entire function range of thebus systems.All fieldbus devices can be operated ina single fieldbus segment in the explosion hazard area. Thus, the costs for anadditional bus coupler or a segment cardas well as their integration and parameterdefinition are eliminated. An additionaltrunk line and the wiring material is alsospared.The supply of power to the multibarriersis implemented via the bus which meansthat an additional power cable is notrequired.Installation in the explosion hazardous areaThe area of application to ATEX isII 2 (1 GD) G EEx m e [ia] IIC T4.Due to its EEx e protection rating, theMBD48-T415/Ex multibarrier can beinstalled in zone 1 (II 2 G) according to94/9/EC (ATEX 95a).Use in explosion hazardous areas withexplosion protection group IIC – in conjunction with temperature class T4 – is thestandard in the process industry.Within zone 1, the MBD48-T415/Ex isconnected via a cable and connectionswith enhanced safety (EEx e) to the mainline (trunk line) of a fieldbus conform toIEC 61158-2. This offers the advantagethat the connection to the bus can beimplemented using a loop isolator withoutEX approval, but with a sufficiently highcapacity.Intrinsic safety and galvanic isolationbetween all outputsFor safety reasons, galvanic isolation ofsignals plays a decisive role in the Ex area.The multibarrier provides four intrinsicallysafe and galvanically isolated outputs. Thecomplete galvanic isolation exists betweenthe main bus cable (trunk line) and the output circuits as well as between all of thefour individual output circuits.Galvanic isolation of intrinsically safe circuits, as demanded by the industry,particularly for zone 0, is thus provided.Potential transfers and potential equalization currents are thus reduced and safedata transmission is guaranteed.Operational safetyOperational safety of the bus system mustbe guaranteed should a bus station failor malfunction. The four outputs of themultibarrier each supply an output currentof max. 40 mA.If a short-circuit occurs on a fieldbus station, the integrated short-circuit protectioncomes into play. Only the affected outputwill be shut down, the main line and theother outputs of the fieldbus segmentremain operational. The short-circuit isindicated for each channel by a red LEDinside the housing.Industrially suitable housingIndustrial environmental conditions are frequently harsh and aggressive. Therefore,a housing suitable for these conditions isnecessary. The enhanced IP66 degree ofprotection and the special housing material (die-cast aluminium) – in conjunctionwith the encapsulated module electronics– meet these demands and provide a highlevel of operational safety. Direct installation of a multibarrier in the system is thusunproblematic.The EEx e cable glands guarantee safeand quick connection technology inconjunction with the high-quality cageclamps.Functions which supplement thestandard FISCO conformityThe FISCO model has been developedfor the supply of power to fieldbusstations in the Ex area by the PTB incooperation with renownedmanufacturers. FISCO stands forFieldbus Intrinsically Safe Concept.It is intended to simplify the verificationof intrinsic safety of fieldbus systems.Intrinsically safe networks can beconfigured without highly complexcalculations, and also expanded andoperated without system certification.The outputs of the multibarrier conformto the demands of an Ex current supplyand also conform to FISCO. Switch-in terminating resistorsData transmission on bus cables isfrequently influenced by signal reflection,which can occur when the bus ends arenot terminated. The fieldbus must beprovided with a terminating resistor atboth ends in order to avoid signalreflection. The multibarrier is providedwith an integrated terminating resistor,which should be activated, when themultibarrier is connected as the lastdevice on the main bus line (trunk line). Climatic compensationIn regions subject to large temperatureand air-humidity variations, it is possiblethat formation of condensation or abuild-up of water within the housing ispossible during operation. In order toavoid this, the multibarrier is fitted onthe cable connection end with apressure equalisation element to avoidthe build-up of condensation.The pressure equalisation elementfeatures IP67 degree of protection andguarantees continuous and reliableventilation and venting of themultibarriers. The ePTFE diaphragm inthe centre of the gland features a veryhigh water ingress pressure and repelsoil. Even 100 % of salt crystals are keptout.Shield terminals are capacitively connected to the housing potential in order todivert possible interference voltages onthe cable shield. The riveted ground boltconnects the housing to the main potential equalisation.Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com11 /04072

ñ Edition:Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.comPROFIBUS-PAMultibarrier, 4-channelMBD48-T415/EX1 S2 S3 S4 SRD1 nF Trunk InSRD1 nFS1RD1 nF1 nF Trunk OutSRD1 nFThe four-channel multibarrier MBD48-T415/ outputs to the field devices feature intrinsicsafety, type EEx i.EX is designed to connect a large numberof field devices to the PROFIBUS-PA (acc.The multibarrier is equipped with a selecto IEC 61158-2).table bus terminating resistor. The switch isThe number of connectable field devices to integrated in the housing on the board.the multibarrier depends on the currentThe multibarrier is equipped with four LEDsconsumption of the individual devices. Upto 32 EEx i field devices can be connected located on the printed circuit board insidethe housing to provide short-circuit indicato the bus. This extension capacity istions separately for each channel.achieved by means of the EEx e fieldbussupply which is fed through from multiDue to complete galvanic isolation, trunkbarrier to multibarrier.line to EEx i-outputs and between EEx iThe inputs and outputs of the trunk line fea- outputs, a safe operation is guaranteed.ture increased safety (EEx e) whereas the12 /0407GEntity and FISCO compliance acc.to IEC TS 60079-27GGalvanic isolation between the EEx ioutputs and the EEx e bus line, aswell as between the EEx i outputsGPowder-coated die-cast aluminiumhousingGPressure compensation element forprotection against condensationwaterGConnection of the housing potentialvia an M5 x 1 boltGTemperature range: -20. 70 C(-4. 158 F)GIntegrated terminating resistor(switch-in)GCable shielding: capacitive connection to housing potentialGOutput data: 10 V/40 mA (short-circuit proof)Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

ñ Edition:Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.comPROFIBUS-PAMultibarrier, 11270Fieldbus standardIEC 61158-2Operating voltage (Pwr)Current self-consumptionGalvanic isolation16.32 VDCð 40 mAinput circuits (EEx e) to output circuits (EEx i)for 253 Vrms; output circuits (EEx i) to eachDimensions260901602other for 60 VrmsOutput circuitsOutput currentOutput voltageShort-circuit protectionð 40 mAï 10 VDCð 45 mAIndicationShort-circuit message4 x redEx approval acc. to conformity certificateMax.output voltage UoPTB 04 ATEX 2021ð 14.3 VMax. output current Ioð 268 mAMax. output power Poð 958 mWInternal resistance RiInternal inductance/ capacitance Li/Ci53.3 òTypical curveMarking of the devicelinearÉ II 2(1 G/D)G EEx m e [ia] IIC T4FISCO / Entity multibarrierConnectionSegment INSegment OUTDrop lineConnection cross-sectioncable glands1 x M20 x 1.5 (Ø 10.14 mm); black1 x M20 x 1.5 (Ø 10.14 mm); black4 x M20 x 1.5 (Ø 5.9 mm); blueTrunk-lineSS EEx eOutputS1S2 S S SEEx inegligibleEarthing bolt2.5 mm2M5 x 1Protection degreeAmbient temperatureRelative humidityHousing materialHousing colourDimensionsConnection modeIP66-20. 70 Cð 95 %, non condensingpowder-coated die-cast aluminiumblack/yellow260 x 160 x 90 mmwall mountingS3S4 SCurrent ans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com26283032 V13 /0407

ñ Edition:Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.comPROFIBUS-PAFieldbus display, 3-channelFD-48-T317/EXThe three-channel digital indicator FD-48T317/EX displays the process informationof the fieldbus nodes belonging toPROFIBUS-PA-Network.Apart from a measuring value indicator, thedisplay contains a 41-segment bargraph fortrend monitoring, which can be scaled separately from the display value.The device scans the programmed fieldbusaddresses and displays their values. Parameterisation is keyword protected and implemented with the front keypad.Adjustments can be made for each channelseparately. The process value of the actuator i.e. sensor is displayed as a 5 digitnumber and the process value status vialimiting value tags.The indicator FD-48-T317/EX performs as a"listener", i.e. initialisation by the master isnot required (integration via software redundant) and it doesn't appear in the networkas a node with an own address.14 /0407GEntity and FISCO compliance acc.to IEC TS 60079-27GDigital fieldbus display for mappingof process valuesGPowder-coated die-cast aluminiumhousingGConnection of the housing potentialvia external earthingThe device is supplied with energy by thefieldbus ( 10 mA) and can be applied in Exareas up to temperatures of the class T6.Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

ñ Edition:Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.comPROFIBUS-PAFieldbus display, 01315Fieldbus standardIEC 61158-2Operating voltage (Pwr)Current self-consumption9.30 VDCð 10 mAIndicationDisplayLCD, five-digit 7-segment displayEx approval acc. to conformity certificateMax. input voltage UiTÜV 07 ATEX 553588ð 30 VMax. input current Iið 660 mAMax. input power Pið 1600 mWInternal inductance/ capacitance Li/CinegligibleMarking of the deviceÉ II 2(1) G EEx ia IIC T6 resp. T5É II 2 D IP65 T70 CFISCO / Entity FielddeviceConnectionConnection cross-section2.5 mm2Protection degreeAmbient temperatureHousing materialHousing colourDimensionsConnection modeIP66-10. 60 Cpowder-coated die-cast aluminiumblack140 x 140 x 71 mmwall mountingDimensions125 140210314071cable glandsHans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com15 /0407

PROFIBUS-PATemperature TransmitterGeneral InformationThe KMU-40Ex/3G and KMU-40Ex/1GDtransmitters are intended for connection tothe PROFIBUS-PA. The unique conversionfunction enables automatic switch-overbetween both protocols. The bus connection is free of polarity consid-erations.Applications: Linear temperature measurements withresistance thermometers orthermocouples Differential, average value or redundanttemperature measurements with resistance thermometers or thermocouples Linear resistance, compensator andbipolar mV measurementsThe 24 bit A/D converter guarantees ahigh resolution.Both transmitters can be mounted in atype B terminal housing (DIN standard).Whereas the KMU-40Ex/3G is used inthe explosion hazardous area in zone 2,the KMU-40Ex/1GD can also be usedin zones 0, 1 and 2 in intrinsically safecircuits.General technical dataAccuracy (general values)Input type– AllAbsolute accuracy 0.05 % of measured valueTemperature coefficient 0.002 % of measured value/ CAccuracy (fundamental values)Input type– Pt100/Pt1000– Ni100– Cu10– Linear resistor– Voltage– Thermocouple type: E, J, K, L, N, T, U– Thermocouple type: B, R, S, W3, W5Fundamental accuracy 0.1 C 0.15 C 1.3 C 0.05 Ω 10 µV 0.5 C 1 CTemperature coefficient 0.002 C/ C 0.002 C/ C 0.02 C/ C 0.002 Ω/ C 0.2 µV/ C 0.010 C/ C 0.025 C/ CElectrical input data (resistance thermometer and linear resistance)TypeMinimum value– Pt25.Pt1000-200 C– Ni25.Ni1000-60 C– Cu10.Cu1000-50 C– Linear resistor0Ω– Potentiometer0ΩConductor resistance per conductor50 ΩSensor currentnom. 0.2 mAElectrical input data (thermocouple and mV input)TypeMinimum value– B 400 C– E-100 C– J-100 C– K-180 C– L-200 C– N-180 C– R-50 C– S-50 C– T-200 C– U-200 C– W30 C– W50 C– Ext. cold junction compensation-40 C– mV input-800 mVCold junction compensation (CJC) 0.5 CSensor fault recognitionyesShort-circuit recognition 3 mV16 /0407Maximum value 850 C 250 C 200 C10 kΩ100 kΩStandard/remarksIEC 60751/JIS C 1604DIN 43760a 0.00427––Maximum value 1820 C 1000 C 1200 C 1372 C 900 C 1300 C 1760 C 1760 C 400 C 600 C 2300 C 2300 C 135 C 800 mVStandardIEC 584IEC 584IEC 584IEC 584DIN 43710IEC 584IEC 584IEC 584IEC 584DIN 43710ASTM E988-90ASTM E988-90IEC 60751–Hans Turck GmbH & Co.KG D–45466 Mülheim/Ruhr Tel. 0208/4952-0 Fax 0208/4952-264 E-Mail: more@turck.com Internet: www.turck.com

PROFIBUS-PATemperature TransmitterKMU-40Ex/3G Configuration via PROFIBUS-PA withSiemens Simatic PDM , ABB Melody/Harmony, Honeywell Ax and MetsoDNA software Suitable for use in zone 2 Type B terminal housingM4 x 3020,22General information:see page 16Wiring diagrams:see page 19ø 44ø 6,3TypeIdent-No.KMU-40Ex/3G7506619Operating voltage (Pwr)Current consumptionInsulation voltage – test/operationSignal to noise ratioResponse time (programmable)Refresh timeExecution time (PID controller)Execution time (analogue input)Signal resolution (input)Calibration temperature9.32 VDC 11 mA1500 VAC/50 VAC 60 dB1.60 s 400 ms 200 ms 50 ms24 Bit20.28 CEx approval according toEC type examination– U0– I0– P0– C0/L0Marking of deviceFM, UL and CSA approvalKEMA 05 ATEX 1031 X5.71 V8.4 mA12 mW40 µF/200 mHÉ II 3 G EEX nA [L] IIC T4.T6Class I, Div. 2, Gr. A, B, C, D; Class I, Zone 2, NIFW/FNICOOutputPROFIBUS-PA protocol standardPROFIBUS-PA function blocksPROFIBUS-PA address (ex-works)EN 50170, Vol. 22 analogue126HousingHousing materialHousing and terminal degree of protectionDimensions/weightVibration resistanceRelative humidityAmbient temperatureCycoloyIP68 or IP00 (IEC 60529/EN 60529)Ø 44 20.2 mm/55 gto IEC 60068-2-6, Test FC 95 % (non-condensating)-40. 85 C (-40. 185 F)Hans Turck GmbH & Co.KG D–4546

6 /0407 Hans Turck GmbH & Co.KG † D-45466 Mülheim/Ruhr † Tel. 0208/4952- † Fax 0208/4952-264 † E-Mail: more@turck.com † Internet: www.turck.com PROFIBUS-PA Basics PROFIBUS-PA - bus physics With the publication of the international standard IEC 61158-2 in October 1994, a suitable transmission technology was