ProfinetUnrestricted Siemens AG 2020siemens.com/switches

PROFINET on 100% EthernetPROFINET is EthernetFor comparison: PROFIBUS Ethernet is an established standard in the IT world for fast datatransfer (IEEE 802.3) One line of “cable” to whicheveryone is connected PROFINET is always full duplex simultaneous communicationin both directions Performance dependson the number of devicescontroller100 MbpsMaster100 Mbps100 Mbps full duplex PROFINET is always"switched Ethernet"SlavesSwitches connected into a line The topology can be influencedDevicesnetwork loadPROFINET take full advantage of the possibilities offered by EthernetUnrestricted Siemens AG 2018

Profinet Vs. ProfibusProfinet works on the same principle as Profibus.Except : Higher carrier frequency100-600MHz (3-20MHz) 2-4 twisted pair cable Bandwidth 10-1000Mbps (0,184-12Mbps) Different cables can be used in the same application Maximum length 100m and with flexible cables 80mUnrestricted Siemens AG 2018

Cable technology – FastConnect (electric/twisted pair) IndustrialEthernet/PROFINETStrippingIndustrial Ethernet/PROFINET:For quick installation RJ45 liittimet 2 x 2 and 4 x 2Stripping Tools!Install RJ45Link to Video:https://youtu.be/9e4G5DPPXHMLink to Video:https://youtu.be/XQjVYFMR8Mk M12 plugs (using stripping tool)IE FC cables: 4 ja 8- wiresInstall M12Link to Video:https://youtu.be/CSwDQptuIdsUnrestricted Siemens AG 2018Page 4

Installation and groundingUnrestricted Siemens AG 2018

Installation and groundingUnrestricted Siemens AG 2018Page 6

Profinet telegram – no TCP/IP frame – no roamingUnrestricted Siemens AG 2018Page 7

PROFINET device configurations and topology in TIA PortalTIA Portal – PROFINET PROFINET devices (including networkproducts) are configured using the TIAPortal. These settings are transferred to theSIMATIC CPU and from there to thePROFINET devices. The CPU defines IP addresses and PNnames according to the topology madein the TIA Portal. Also for networkdevices. In the topology, all devices mustsupport the Profinet mechanism.Unrestricted Siemens AG 2018Sivu 8PROFINET TIA in PortalAll parameters relevant to PROFINET are defined in the TIA portaland then transferred to the SIMATIC CPU.

Topology definition allows automatic configurationTopology editory (Classic STEP7) Define cablingUnrestricted Siemens AG 2018Topology editory (STEP7 – TIA Portal) Define cabling

Topology detection uses LLDP communicationTopology queryof STEP7LLDP MIBs arereadingTopology editorI am "X208"I am "CPU319-3PN/DP"Unrestricted Siemens AG 2018Page 10

Topology Defined - Automatic Configuration WITH PROFINET YOU ALWAYS HAVE USE MANAGERED SWITCHES! Automatic configuration saves time and minimizes errors With this function, the PROFINET IO controller automatically enters the IP address and devicename of the PROFINET IO devices without a programming device (PG). The requirements for automatic configuration are : The IO controller and IO devices must support the PROFINET function "Device replacementwithout exchangeable medium / PG". In STEP7, you must select the option "Replacing the device without removable media” –”Devicereplacement without exchangeable medium" The devices must be reset to factory settings – factory reset. Profinet GSDxml device description must be found on all devices - includingswitches! The configured topology must correspond to the actual topology!Unrestricted Siemens AG 2018

Profinet network topologiesStar(typically motor centers - Simocode)TreeLinearUnrestricted Siemens AG 2018Sivu 12Ring - MRP

Response time in line topology – 14 stations (1.8 ms)Siemens Profinet IO device with “cut through” switch – Ertec Asicscircuit has been used for interface.Tt Transmission time of minimum frame approximately 7μsRtb Run time of bit on the cable at 100 Mbps and 100 m cable between two nodes - 0,5 μsTPTswitch Throughput time through a switch. For RT Class 1 approximately 10 μs (in GSD file)Basic calculation:Length of minimum frame:Including preamble and SFD:Idle time:Total:64 bytes including process data08 bytes as header12 bytes after each Ethernet frame84 bytesRT Minimum/maximun transmission time without waittimesByte TtNn (asemien määräs[μs] ketjussa)84 6,7Rtb[μs]14TPTswitch[μs]0,5Tt min [ms]Tt max [ms]100,1541,729TPTswitch[μs]Tx [μs]10Unrestricted Siemens AG 2018Page 13153,72This calculation can only be used with Siemensdevices. It has been found that some othermanufacturers has used standard “store and forward”switches in device Profinet interface. These do notguarantee a stable response time.

Response time in line topology – 20 stations (2,6 ms)Siemens Profinet IO device with “cut through” switch – Ertec Asicscircuit has been used for interface.Tt Transmission time of minimum frame approximately7 μsRtb Run time of bit on the cable at 100 Mbps and 100 m cable between two nodes - 0,5 μsTPTswitch Throughput time through a switch. For RT Class 1 approximately 10 μs (in GSD file)Basic calculation:Length of minimum frame:Including preamble and SFD:Idle time:Total:64 bytes including process data08 bytes as header12 bytes after each Ethernet frame84 bytesRT Minimum/maximun transmission time without waittimesByte TtNn (asemien määräs[μs] ketjussa)84 6,7Rtb[μs]20TPTswitch[μs]0,5Tt min [ms]Tt max [ms]100,2172,527TPTswitch[μs]Tx [μs]10Unrestricted Siemens AG 2018Page 14216,72This calculation can only be used with Siemensdevices. It has been found that some othermanufacturers has used standard “store and forward”switches in device Profinet interface. These do notguarantee a stable response time.

RT: Media Redundancy Protocol (MRP)1/2MRP is a ring redundancy method used in Profinetapplications. The redundancy manager sends testmessages from each of its ring ports as long as themessages arrive at the other ring port. This way themanager knows that the ring is intact. At the sametime, it prevents messages from circulating indefinitelyin the ring, closing one of the ring ports.Unrestricted Siemens AG 2018

RT: Media Redundancy Protocol (MRP)2/2When test messages no longer arrive at another ringport, such as a damaged cable, the manager opensthe closed ring port. In this case, post-breaksubscribers are available.Network recovery (reconfiguration) takes up to 200 ms(50 subscribers).Unrestricted Siemens AG 2018

IRT: MRPD seamless ring. Max. 32 devicesThe MRPD mechanism is based on IRT and MRP. Areconfiguration time of 0ms is possible by sending cyclic IRTpackets duplicated in both directions on the ring. The recipientreceives the same IRT frame twice if there are no errors on thenetwork.The devices receive this information on both ring ports, so there isno ring remodeling time. As with MRP, redundancy managementprevents loops.Unrestricted Siemens AG 2018

Redundancy exampleUnrestricted Siemens AG 2018Page 18

Segmented production network – PN/PN CouplerLine ControlWinCCProduction OT networkProduction cellUnrestricted Siemens AG 2018Sivu 19Production cellProduction cellProduction cell

Web extension - Network topology - graphical viewUnrestricted Siemens AG 2018

Online view on the TIA Portal.Unrestricted Siemens AG 2018

Service bridge (Scalance XC200 series)Unrestricted Siemens AG 2018Page 22

Sinetplan – Offline simulation for load in Profinet networkReport function withdetailed results Validation of the PROFINETplanning guideline Online scan function Import of the configuration with AutomationMLImport of STEP7 & TIA Portal projectsPort-by-port simulationUnrestricted Siemens AG 2018Page 23

SinetplanUnrestricted Siemens AG 2018Page 24

Proneta (PROFINET network analyzer - free!)Requirements Easy to set up devices and network without PLC “tools” Detects devices and topology automatically Address settings IO testingUsed to cabinet manufacture Commissioning www.siemens.com/pronetaUnrestricted Siemens AG 2018Page 25Date

SINEC PNI Basic – for freeSINEC PNI is a program that can be set for a network-specificparameter to SCALANCE and RUGGEDCOM devicesThe configuration can be performedsimultaneously for multiple devices. Unrestricted Siemens AG 2018Page 26Network Scanning of all PROFINET andRUGGEDCOM devicesInitialization by setting the followingparameters for the devices : address, subnet and gateway Initial password change (Scalance jaRuggedcom) name (PROFINET) I&M information to identify the device(PROFINET) SysName, sysContact and sysLocationActivate DHCP-clientResets to factory settingsResets to the default PROFINET settingspingFlashes LEDsOpen Web Based Management

SINEC PNIProduct editionsNo licenceOnly one License per copySINEC PNI Basic (02/2020)SINEC PNI Advanced (11/2020)SINEC PNI Professional (03/2021) Step 1Features Step 2 PriceScan networkSet IP, subnet, gatewaySet DHCP ClientSet PROFINET / System nameSet I&M DataReset to factoryChange Default PasswordFlash LEDPingFirmware UpdateDiagnostic Downloads (logs with config)Configuration copy (up/down)Set SNMP (V1, V2C, V3)Free of chargeUnrestricted Siemens AG 2018Page 27 Set Time Set DNS Proxy Set Syslog-Client Set NTP-Client Set RADIUS-Client Configure DHCP Server Set SSID Set WLAN Mode Set Country Set Channel Set frequency Set SSID Security Set static VLANs Set VLAN IP addressesxxx Generate SSL and SSH Keys Set Hardening profile Set NAT/ NAPT Set Firewall / ACLs Set SINEMA RC Client Password protectionxxx

SINEMA Server V14Home screenTopologyEvent listReportsCustomer-specific viewServer overviewUnrestricted Siemens AG 2018Page 28

The automation network is connected to the OT network, notdirectly to the IT network. ADVANTAGE: A more secure datatransfer to the entire production line is achieved. The production cells areconnected to each otherwith PN / PN CouplersManagement /EngineeringIT / toimistoSINEC �per toimittajaOTVPNetäohjelmointiyhteysratkaisu soluihinBackboneLinjaohjausCPUTuotantolinja osa 1Solu 1Tuotantolinja osa 2Solu 2Solu 3Solu 4Solu 5 Each cell is connected tothe OT network with itsown Firewall / VPNmodule VPN modules can beused to build a horizontalremote connection withinthe production line - network monitoring andmaintenance of the entireproduction line and, ifnecessary, a-cyclic datatransfer between cells The devices on the OTnetwork are managedand controlled centrallyby Sinec NMS. Production networkprotected from IT networkvulnerabilities - troublefree productionUnrestricted Siemens AG 2018Sivu 29 The line control CPU isconnected to an OTnetwork or a separatenetwork

Segmented production network (IEC62443)Scalance S/SC VPNWinCCITnetworkDMZ - areaSinema RC serveriCloud PGSinec NMSProduction OT networkProduction cellUnrestricted Siemens AG 2018Sivu 30Production cellProduction cellProduction cell

SINEC software family (NMS, PNI & INS)Network levels (OT) – Factory automationManagement /EngineeringSINEC NMSSINEC INSSINEC PNITIA PortalUnrestricted Siemens AG 2018Page 31

Sinec NMShttps://siemens.com/sinec-NMSUnrestricted Siemens AG 2018Page 32

SCALANCE X managered switchesLayer 2 applications (Profinet)FunctionSCALANCE XR-500SCALANCE XM-400Layer 2/3managedSCALANCE XR-300SCALANCE XC-200Layer 2managedSCALANCE XF-200SCALANCE XR-300WGSCALANCEXB-200SCALANCEX005Layer 2unmanagedSCALANCE XP-200SCALANCEXR-100WGSCALANCEXC-100Managed Layer 2 Industrial Ethernet Switches SCALANCE XCompact SCALANCESwitch modules XB-000SCALANCE X-100media converterUnrestricted Siemens AG 2018Page 33Price

Thank you for your interest!Tero PyykköPD PA CITarvonsalmenkatu 1902600 EspooPuh: 358(0)10 nswerssiemens.com/profinet-driverUnrestricted Siemens AG 2018

RT: Media Redundancy Protocol (MRP) 1/2. MRP is a ring redundancy method used in Profinet applications. The redundancy manager sends test messages from each of its ring ports as long as the messages arrive at the other ring port. This way the manager knows that the ring is intact. At the same time, it prevents messages from circulating indefinitely