FIRE ALARM SYSTEM - Fireguard-uk

Transcription

FIRE ALARMSYSTEMFIREGUARD GLOBAL LTD.Tel: 00-44-8450751042 Fax: 00-44-8459751043Email: Info@Fireguard-Uk.com www.fireguard-Uk.comUnit 11 Chancel Industrial Estate Newhall StreetWillenhall WV13 1NX United KingdomFS546607Fire Alarm System 1

FIREGUARD ANALOGIC FIRE ALARM CONTROL PANELEN54 ApprovedCustom Colors2 FIREGUARD GLOBAL -Uk.com

FG901CP AP1 loop expandable to 9 addressablefire alarm control panelEN 900 series Model FG901CP AP, is the fire alarm controlpanel of the future generation with touch-screen technologyand certified to EN 54-2 and 4. The GUI interface is userfriendly, you can program the panel without a manual.With itsminimal set-up it is able to manage open or closed loops of240 compatible devices. Basic configuration can be expandedadding two loops each time to control up to 2160 devices, bothoptical and thermical, from a single control panel. In complexapplications, it can be installed in a ring network (up tp 128contol panels). In this distributed architecture, areas and zonescan be monitored by detectors and they can be combinedby means of logical expressions in order to trigger events forthe panel to which they belong or for other panels of the ringnetwork. With the installation of dedicated cards, it is alsopossible to connect the control panel to external peripheral,such as keyboards and LED panels.user (installer, safety responsible and final user). The touchinterface, simple and ergonomic, permits to any user tointeract intuitively without training time and costs. Theconfiguration procedure is immediate, autoprogramming andauto-addressing mechanisms allow to recognize, consult andprogram the devices on the field in a fast, systematic andcorrect way.The control panel can be programmed locally or from remote,by means of the dedicated online platform OneCloud, datacan be exported and imported with any USB key. Monitoringis made possible thanks to WINWATCH32 supervision system.Detectors and devices diagnostics are carried on directly fromthe control panel, and a single operator is able to performautonomously all the test procedures, and to check in plantoperativity of all its components. Regular maintenanceinterventions can be optimally planned and executed.Diagnostic data and historical data stored by the control panelcan be easily exported and analyzed.Certified to UNI EN 54-2 e 54-4 for fire detection, this controlpanel provides three different access levels according to theControl panel can be customized for any installation condition:colour, display background, programmable LED colour,logo displayed in welcome screen and the language can beselected as preferred.HARDWARE featuresSOFTWARE features Addressable fire alarm panel with 32-bit microprocessorLCD touchscreen display (480x272 TFT 4.3”)Back light on/off and three settable colors 1 addressable loop, expandable up to 9 loops (with 4FG901LC AP) configurable as open or closedDigital protocolFrontal LEDs with three settable color: white, blue and greeneach loop supports 240 addressable devicesShort-cut circuit protection14 front LED for eventsSilenceable and excludable signaling buzzer1 monitored output for siren or dialer (24Vdc 1A)General Output dry contact 1A 30Vdc 120 Vac1 general open collector output1 RS 485 line for perifericals (maximum current value) 1 RS 232 and 1 micro USB for programming and remotemanagementEthernet card 10 Mbit/s (Optional PTLAN)56 LED zone (option card FG90156LRD AP )Ring Network Card between central (optional FG901NC AP tab) Maximum 16 remote control panels can be connected to theRS485 BUS max 800m distance (FG901RP AP)With four additional FG901LC AP needed supplementarypower supply (FGPower)Two 12 V Battery: capacity 17Ah each Automatic test of efficiency batteries and batterydisconnection in case of deep dischargeAuxiliary power output 24 Vdc 500mA with shortcutprotectionDimensions: 410 x 410 x 120 mmWeight: 6,1Kg (without batteries)Power supply: 230VacCurrent absorption: 300mAMaximum current external loads: 500mAOperating Temperature: 0C / 50C Maximum current on loop: 500mA 240 addressable devices for one loophybrid systems wired/radio192 programmable zones192 logic functionsmore than 1000 events reported into archiveInternal clockAuto programming analog devices on loopAuto addressing analog devices on loop*Mapping analog devices on the loopRing connection with other stations using a fault tolerantnetworkMultilingual managementCustomizable with personal logoManagement of detectors and analog modules of differenttypes:- Managed Thermal and optical detectors in the sema loop- Input modules- Output Modules- Buttons addressed- Analogue Addressable Sirens multiprotocolColorful LED selectableProgrammable locally or remotely by dedicated softwareMulti - Protocol FIREGUARD and Fireguard MODBUS TCPIP/MODBUS RTU protocol over IP(TCP option card FG901MD AP)Certified Product Standards EN54-2 and EN54-4CE Marking (EMC low-voltage directive)“FG901CP AP, is the fire alarm control panel of the future, completely made in UK.”First alarm control panel with touch-screen technology and certified EN 54-2 and 4.Fire Alarm System 3

FIRE ALARM SystemUSBFG CLOUDSERVERNETWORKLOOP (128)BEAM DETEXTINGUISHERPANELUP TO 9 LOOPFG901SI APFG901CP APPT LANFG901MMIOS AP (FG901SD1 APFG901SHD APFG901SD1 APCLIENTFG901RP APFG901MMI APFG901MI3 APFIREALARMDISPLAYTCPIP NETWORK(CAT5 cable)RS485 LINE(Shielded, antiflame cable with 2 connectorsfor power supply and 2 connectors RS484 for signal)POWER SUPPLY AND SIGNAL(Shielded, antiflame cable with 2 connectorsfor signal and power supply)4 FIREGUARD GLOBAL LTD.WIRELESS(Radio connection with870 MHZ Frequence)00-44-845075104200-44-8459751043INOUT FOR FF INTERFACESIGNAL(Shielded, antiflame cable with 2 connectorsfor power supply and 2 connectors RS484 for signal)NETWORK LOOP(Cat 5 cable)Info@Fireguard-Uk.com

WIRELESSDETECTORSFDWVMI 100 [32]FDSLPG100 [32]HAVC/FANSWF 1000 [32](240)FG901MMO APGAS DETECTOR 4-20mAFG901SFI APFG901MCP APFDWCP100 [32]FDW2W (7)WIRED CONNECTIONFG901SD1 APFG901SB APFG901MMI APFG901MI03 APFG901SHD1 APFG901SBFR APFIREALARMFAN FEED BCKLED DISPLAYMAGNETIC DOORBEAM DETUSB(Upload download programmazione)CLOSE LOOP WITH POWER SUPPLY(Shielded, antiflame cable with 2 connectorsfor signal and power supply)(x) Maximum Number of connected device.The devices can be added tougher ex: (x) (x)[x] Maximum Number of connected device.The device cannot be added tougher ex: (x) or (x)Fire Alarm System 5

FIRE ALARM SystemSuperior technology and ease of use make this system truly UNIQUE!1. End UserFor the first time in the fireindustry, even the end-user caninteract with a control panel!End-user can access to their ownpersonal screen at any time, withouta password, allowing them to see theevents divided by: All , Alarms, Faults, Dates,Loop or by area. Or simply call assistance with a touch!2. Log InOnce logged on the system, the end-user,maintenance technician or programmerwill gain immediate access to his ownuser menu. Only the 4-6 keys speciallydesigned for each user will appear on thetouch screen! Everything is quick and easy:mistakes are virtually impossible! Finally afire control panel that’s easy-to-understand!3. Operator MenuFireguard FG901CP AP is amaintenance technician’s dream.Traditional fire control panel force you touse conventional mini displays, often poorlyback-lit, with endless menus, perhaps not even inyour language, or require you to connect to a pc,6 FIREGUARD GLOBAL -Uk.com

4. Diagnostic MapFireguard FG901CP AP displays the status of the system in a single glance,thanks to its diagnostic map which provides full information: immediatelyvisualizing detectors, input\ouput modules and all wireless devices marketwith a “W”. The level of dust and consequent inefficiency of a detector isindicated with different colours.5. Detailed InformationBy touching the icon of the device, detailed information will appearabout the exact percentage of dust, making it easier to plan periodicmaintenance. Since dusty detectors are no longer able to detect anysmoke, you always need a complete maintenance tool for the entiresystem at your fingertips.6. Configuration MenuFireguard FG901CP AP is alsothe dream of every installer: it isautoadressable, with no need fortime-wasting dip-switches orconventional programming devices.7. AutoprogrammingThe control panel reads the entire field andautomatically programs all the devices. Next,the diagnostic map displays everythingthat’s been programmed by the controlpanel. It’s so simple!Fire Alarm System 7

FIREGUARD Peripherals and accessoriesFG901LC APFG90156 LED APFG901NC APExpansion card with 2 loopsfor FG901CP APPanel led for alarms of zonescard for ring networks betweenFG901CP APWith FG901LC AP you can extend themanagement capabilities of FG901CP AP.One card has 2 supplementary loops,both have same features of master panel.The mounting is internal into fire alarmpanel and doesn’t modify the design.Panel led FG90156 LED AP is applicablebelow display of FG901CP AP, withoutto modify form and design. Thanks topanel you can have a light signal of alarmof zones and will be possible individuatemore fast the number of attivate zone.With FG901NC AP you can connect in aring network up to 128 FG901CP AP, sois possible to create a system that sharesall informations of each single panel.Technical FeaturesTechnical FeaturesTechnical Features 2 loops up to 4 FG901LC AP for one CAN BUS Connection speed communication up to 50 Kbps High fault tolerant, able in the presence ofnetwork failure, to maintain the necessaryinformation pass between the nodes Compatible with central Olympia - FG901CP AP Prepared for mounting inside the centralFG901CP AP Certified device according to EN54-2 Loop configurable as open or closed loop Maximum number of devices per loop:240 Internal mounting of the center byconnector of the master board 2 programmable relay output ofmonitored alarm Multi - Protocol FIREGUARD Fireguardnumber of visualizable zones 56Operating Temperature: -5 C/ 40 CDimensions: 219x58mmRed LED ColorPowered by FG901CP APFG901C AP Range up to 1.2 km with a special cableConsumption 250mA max – 50mA nominal12 Vdc power supply from the central Olympia24 Vdc power supply from the centralFG901CP APFG901PSU APFDCANMONOFDCANMULTIAuxillary power supply for fullconfiguration of FG901CP APMono mode optical fibre converterwith ST connector for Olynet card*on requestMulti mode optical fibre converterwith ST connector for Olynet card*on request Power supply: 12Vcc Power supply: 12VccMust be use depending of the number ofexpansion card used.Technical Features 100-240VAC Input - 1.2A50/60 Hzoutput - 27V, 2.3AOperating Temperature: -5 C/ 40 CDimensions: 180x61x349mm8 FIREGUARD GLOBAL -Uk.com

FG901RP APPTLANFG901MD APRemote Touch screen panel withiron case for FG901CP AP andFG901CP-MINI APEthernet interface for FG901CPAPProtocol converter for MODBUSprotocolSame as to the FG901CP AP theFG901RP AP is easy and intuitive touse. All functions can be reached with atouch according to the different levels ofaccess. It offers the possibility of eventsand historical display.This card is a serial TTL interface poweredby FG901CP AP and mounted internallyTechnical Features Technical FeaturesTechnical Features graphical touch screen display (480x272TFT 4.3 “) 14 front LED 2 line RS 485 for the connection Operating Temperature::- 5 C/ 40 C Power supply: 27.6vdc consumption: 90mA Talk Speed: 38400 bps Maximum number of FG901RP AP thatcan be connected to a control center: 14 Dimensions: 210x120x30 mm Weight: 1kg Level of protection: IP30 Powered by centralFrom 300 to 900 kbpsControl signals: RTS, CTS, DTR, DCDEthernet 10 Base - TPJ45 connectorOperating Temperature: -10C to 50 C Dimensions: 45x90x28 m Unit microprocessor controlled 133 MHz32Mbytes Flash expandable to 64Mbytes32Mbytes Ram expandable to 64MbytesEmbedded Operating SystemNetwork interface card Ethernet 10 100Base T Integrated1 RS232 serial line protocol for interfacingwith central IEC 79/5 - 79/6Internal battery backupPower supply: 12VdcPower consumption: 480 mAOperating Temperature: 0 -50 Relative Humidity: 0% -95%Weight: 3,5KgDimensions: 208x152x65mmFUNCTIONALProtocol converter on MODBUS RTU overTCP/IP or Modbus TCP/IP by RS232 serialCEI 79/5 - 79/6Prepared for future expansion andcustomization according to specificprojects.FDSMART400 3g dialer EN5421 certified *Q3 2017Technical Features 4G dialer with Touch screen integratedMultilanguage interfaceAvallabile protocols Contact ID, SIA(1/3 livelli) e Fast format (scancom)SMS message system interface4 Input and 4 relè outputsCertified EN54 21, EN50136-2, EN50131-1& EN50136-1 (grado 2 e 3)Power and consumption 9-28Vdc 151mAWorking temperature -10C 55 CSize 110x150 mmFireguard “safeguarding fromhazardous fires, bydesigning, developingthe latest technologyproducts with highquality and reliability.”Fire Alarm System 9

FIREGUARD Fire Alarm SystemsFG901CP MINI AP (Not networkable)FG901CP MININET AP (Networkable)1 loop addressable fire alarm control panelHARDWARE FeaturesSOFTWARE Features Addressable 32-bit microprocessor panel with graphicaltouchscreen display (480 x 272 TFT 4.3 “) 1 addressable loop with digital protocol configurable as openor closed 240 addressable devices on loop Up to 16 remote control panels can be connected to theRS485 BUS max 800m distance (cod. Art. FG901RP AP) Short circuit protection 14 Front LEDs 2 monitored output for siren or optical-acoustic signaling(24Vdc 1A) General clean contact output 1A 30Vdc 120 Vac 1 general fault output 1 RS 485 for peripherals 1 RS 232/micro USB for programming and remotemanagement. Ethernet card 10-100 Mbit/s (optional cod. Art. PTLAN) 16 LED zones Ring network adapter between panels (optional cod. Art.FG901NC AP) Battery capacity: 2 x 7.2 Ah Efficiency test batteries and battery disconnection in case ofdeep discharge Operatin temperature from 0 to 50 degrees Auxiliary power output 24 Vdc 500mA with short protection Dimensions: 330 x 310 x 80 mm Power supply: 230Vac Up to 240 addressable devices for the loophybrid yarns/radioDivision up to 192 areas96 logic functionsStore more than 1000 eventsAuto programming analog devices on loopAuto addressing analog devices on loopMapping analog devices on loopRing connecting with other central using a fault tolerantnetworkMultilingual managementFully customizable with personal logo, ColorTouch screen and side multi-color LEDManagement of detectors and analog modules of different type- thermal and optical detectors mixed- Input Modules- Output Modules- buttons addressed- Analog Addressable sirens multiprotocolSelectable colored LEDTCPIP Protocol MODBUS/MODBUS RTU overTCP IP (optional cod. Art. FG901MD AP)Certified Product Standards EN54-2 and EN54-4Available expansion and accessories for FG901CP-MINI AP FG901NC APFG901RP APPTLANFG901MDFDSMART40010 FIREGUARD GLOBAL -Uk.com

Programming Software on CloudFG901CP-MINISL APAddressable fire panel 1 loopTouch screen super light versionFG901CP-MINISL AP is a microprocessor basedfire detection panel that allows the detection offires through wired or wireless devices and can beprogrammed and integrated through a fully touchscreen interface.The Mini Light panel, is able to manage an open orclosed loop of 126 compatible devicesCertified to EN 54-2 and 54-4The control panel can be programmed both locallyand remotely, using the dedicated FG Cloud onlineplatformSuitable for small and medium installationsFG CLOUDThe new area of commissioning!With FGCloud, the commissioning now is moreinnovative. The panels has different modes ofprogramming capability, such as USB import , anddirect programming from the touch screen; FG Cloudinnovated cloud based programming, allowing theengineer to program the panel over the cloud savingtime and visits to site.Additional unique industry benefits of FG Cloud are: Same identical and user friendly GUI Interface of all the FIREGUARD panel range(It’s not necessary to learn two different programming tool anymore) Full back up of all your customers vital programming Live remote support on the actual programming which would be installed on site(done with customer authentication sharing permission)Everything free of charge!“FG Cloud innovated cloud based programming, allowing the engineer toprogram the panel over the cloud saving time and visits to site.”Fire Alarm System 11

FIREGUARD Optical and thermal detectorsFG901SHD APFG901HD1 APFG901SD1 APOptical and thermal detector withshort circuit isolatorThermal and thermovelocimetricdetector with short circuit isolatorOptical detector with short circuitisolatorIt ensures an analysis of air condition andtemperature of the protected area, andimmunity to false alarms. The 360 visibleLED with three different colours signals acondition of alarm (red), fault (yellow) andlocalization (green). Each detector is providedwith an integrated isolator circuit, thatautomatically takes action in case of need.It ensures the analysis of the air temperatureof the protected area and immunity to falsealarms. The 360 visible LED with threedifferent colours signals a condition of alarm(red), fault (yellow) and localization (green).It ensures an analysis of air condition ofthe protected area, and immunity to falsealarms. The 360 visible LED with threedifferent colours signals a condition of alarm(red), fault (yellow) and localization (green).Each detector is provided with an integratedisolator circuit, that automatically takesaction in case of need. The address can beprogrammed by mean of the programmer orwith the addressing function of FIREGUARDsmoke detection panels.Each detector is provided with anintegrated isolator circuit, that automaticallytakes action in case of need. The addresscan be programmed by mean of theprogrammer or with the addressing functionof FIREGUARD smoke detection panels. It isprovided with tools for base numbering andlocking pin against unwanted removal.The address can be programmed by meansof the programmer or with the addressingfunction of FIREGUARD smoke detectionpanels.It is provided with tools for base numberingand locking pin against unwanted removal.It is provided with tools for base numberingand locking pin against removal.FeaturesFeaturesFeatures Low profile thermal andthermovelocimetric smoke detector to becombined with FG901DB AP Thermovelocimetric function at 58 C Thermal function at 78 C Built with multicolored plastic material,modern design. It can be programmed to operate at 58 Cor 78 C Built with ABS plastic material withstabilized UV, Modern and compact design, lowaesthetical impact Integrated self adapting function, to suitenvironmental changes Remote LED control option Power supply: 18-35V Average current consumption: 90 μA IP40 degree of protection Maximum current consumption remoteLED: 15mA Operating temperature: –30 C 70 C Max humidity: 95% non-condense Height: 48mm with base Diameter: 92mm Weight with base: 120g Low profile thermal andthermovelocimetric smoke detector to becombined with FG901DB AP Thermovelocimetric function at 58 C Thermal function at 78 C Built with multicolored plastic material,modern design. It can be programmed to operate at 58 Cor 78 C Built with ABS plastic material withstabilized UV, Modern and compact design, lowaesthetical impact Remote LED control option Power supply: 18-35V Average current consumption: 90 μA IP40 degree of protection Maximum current consumption remoteLED: 15mA Operating temperature: –30 C 70 C Max humidity: 95% non-condense Height: 48mm with base Diameter: 92mm Weight with base: 120g Low profile optical smoke detector to becombined with FG901DB AP Built with ABS plastic material withstabilized UV, Modern and compact design, lowaesthetical impact Integrated self adapting function, to suitenvironmental changes Remote LED control option Power supply: 18-35V Average power consumption: 90 μA IP40 degree of protection Maximum current consumption remoteLED: 15mA Operating temperature: –30 C 70 C Max humidity: 95% non-condense Height: 48mm with base Diameter: 92mm Weight with base: 120gSPC -102APF-1545Fire SafetyCertificationSPC -102SPC -102APF-1544Fire SafetyCertificationAPF-1546Fire SafetyCertification“The new series of analogue sensors ofthe FG901 DETECTOR range constantlymonitor the fire alarm condition.”12 FIREGUARD GLOBAL -Uk.com

FG901MCP APAddressable call pointActivation is signaled with a red led and glass break effect, the call pointcan be reset with the provided key.Each call point is provided with integrated short circuit isolator thatautomatically takes action in case of need.The address can be programmed by means of the programmer orwith the addressing function of FIREGUARD smoke detection panels.It is provided with tools for base numbering and locking pin againstunwanted removal.Features Provided with integrated isolator circuitRed color ledFlush-mounted installation tool includedPower supply: 18-35VAverage current consumption: 120 μALED current consumption: 6mA (24V- line)Operating temperature: –20 C 65 CMax. humidity: 95%Dimension: 87x87x54 mmMax. Cable cross section 2.5 mmSPC -102APF-1543Fire SafetyCertification“The FG901MCP AP is equipped with an integrated short-circuit isolator.This means that in the event of a failure on a loop or on a single device,communication with the devices themselves is not interrupted.”FG-901PR APWIRELESS HAND PROGRAMMERThe FG901PR AP Unit allows to Program and display on the touchscreen, the various stored parameters In Analog Devices Fire Readand set an analog address of a device, Read analog values andvalues of “ dirty” Read the firmware version of a device UnderDevelopment: In next phase user would be able to interface tothe programmer a Wired loop to analyze Earth Foul / Loop Cut /Voltage Level / Signal QualityAutodressing Future Development:Wireless Programming FG901PR AP will be the first Wireless Handprogrammer in the world.Features Touch screen Wireless handheld programmer Pre stored parameters“The FG901PR AP first wirelesshand programmer in the world.”Fire Alarm System 13

FIREGUARD Addressable sounderFG901SI APFG901SFI APFG901SFI23 APAddressable sounder EN54 3with short circuit isolatorAddressable sounder EN54 3with flashing light and shortcircuit isolatorAddressable sounder withflashing light EN54 3 and 23 andshort circuit isolatorSound emission can be manually adjustedon the sounder itself.Sound emission can be manually adjustedon the sounder itself.Each sounder is provided with integratedisolator circuit, that automatically takesaction in case of need. Addresses can beprogrammed by means of the programmeror with the addressing function ofFIREGUARD smoke detection panels.At the moment of activation, groups ofsounders can be synchronized.Each sounder is provided with integratedisolator circuit, that automatically takesaction in case of need. Addresses can beprogrammed by means of the programmeror with the addressing function ofFIREGUARD smoke detection panels.At the moment of activation, groups ofsounders can be synchronized.Each sounder is provided with integratedisolator circuit, that automatically takesaction in case of need. Addresses can beprogrammed by means of the programmeror with the addressing function ofFIREGUARD smoke detection panels.FeaturesFeaturesFeatures Sound emission can be manually adjustedon the sounder itself.At the moment of activation, groups ofsounders can be synchronized. Red plastic enclosureProvided with integrated isolator circuitPower supply: 19-30Vdc (per EN 54-3)Average power consumption: 120 μACurrent consumption with operatingsounder: 5-7mA (24V- line)Sounder output: 80 - 100dBInitiation tripping time: 2 secIP degree: IP65Max. Cable cross section 2.5 mm2Operating temperature: –10 C / 55 CMax. humidity.: 85% non condensingDimensions: diameter 100mm height92mmWeight: 190g Red plastic enclosureProvided with integrated isolator circuitPower supply: 19-30Vdc (for EN 54-3)Average power consumption: 120 μACurrent consumption with operatingsounder: 5-7mA (24V- line)Sounder output: 80 - 100dBInitiation tripping time: 2 secIP degree: IP65Max. Cable cross section 2.5 mm2Operating temperature: –10 C / 55 CMax. humidity.: 85% non condensingDimensions: diameter 100mm height92mmWeight: 190g Red plastic enclosureProvided with integrated isolator circuitPower supply: 19-30Vdc (for EN 54-3)Average power consumption: 120 μACurrent consumption with operatingsounder: 30mA (24V- line)Sounder output: 80 - 100dBInitiation tripping time: 2 secIP degree: IP65Max. Cable cross section 2.5 mm2Operating temperature: –10 C / 55 CMax. humidity.: 85% non condensingDimensions: diameter 95mm height125mmWeight: 305gSPC -102SPC -102SPC -102APF-1549APF-1550APF-1551Fire SafetyCertificationFire SafetyCertificationFire SafetyCertification“The sirens of the FG901 SOUND series are equipped with an integrated short-circuitisolator conforming to the EN54-17 standard that means Guaranteed communication.”14 FIREGUARD GLOBAL -Uk.com

FIREGUARD Sounder baseFG901SB APAVBASE Loop Power Sounder BaseFG901SB AP Base Sounder operate over a wide input voltage rangeof 16 to 40V DC. The conventional range of detector base sounders areavailable in a standard 32 tone version in white with locally controllableoutput levels to enable the sound intensity to be adjusted to suit theapplication. This arrangement provides an extremely low-profile unitwhich is unobtrusive and protrudes only 28mm from the wall. Thedistinctive low-profile shape is acoustically very efficient, producingan omnidirectional high sound output at low current levels. Ruggedconstruction with solid state electronics also provides high reliabilityand stable performance.Features Ultra low current4 volume levelsOptical coverage level32 primary tones32 alternative tonesUp to 92 dba191328FG901SBFR APAVBASE Loop Power Sounder Base and VAD BeaconFG901SBFR AP Base Sounder operate over a wide input voltage rangeof 16 to 40V DC. The conventional range of detector base sounders areavailable in a standard 32 tone version in white with locally controllableoutput levels to enable the sound intensity to be adjusted to suit theapplication and provide a synchronous LED flash rate 0.5Hz. Thisarrangement provides an extremely lowprofile unit which is unobtrusiveand protrudes only 28mm from the wall. The distinctive low-profileshape is acoustically very efficient, producing an omnidirectional highsound output at low current levels.Rugged construction with solid state electronics alsoprovides high reliability and stable performance.Features Ultra low current4 volume levelsOptical coverage level32 primary tones32 alternative tonesUp to 92 dbASynchronized flash191328“The distinctive low-profile shape is acoustically very efficient, producing anomnidirectional high sound output at low current levels. Rugged construction withsolid state electronics also provides high reliability and stable performance.”Fire Alarm System 15

FIREGUARD Addressable modules and multi-modules with integrated isolatorFG901MMI APInput addressable module with short circuit isolator inMicro formatFG901MMO APOutput addressable module with short circuit isolator inMicro formatFG901MMIOS APInput and output addressable modules with shortcircuit isolator in Micro formatUsing these devices it is possible to interface the loopwith different systems, or to activate, by means of outputmodules, any type of output (sounders, light signals, fire doorselectromagnets, etc.). Reduced dimension permits deviceinstallation in any environment type.Devices are provided with integrated short circuit isolator, andaddresses can be programmed by means of the programmer orwith the addressing function of FIREGUARD smoke detectionpanels.Using these devices it is possible to interface the loop with differentsystems, or to activate, by means of output modules, any type ofoutput (sounders, light signals, fire doors electromagnets, etc.).FG901MI3 AP3 input addressable module with short circuit isolatorFG901MIO3 AP3 input and 1 monitored output addressable modulewith short circuit isolatorFG901MI AP1 input, 1 C form output and 1 monitored outputaddressable with short circuitFG901MIO2 AP1 input, 2 C form output addressable module with shortcircuit isolatorReduced dimension permits device installation in any environmenttype. Devices are provided with integrated short circuit isolator, andaddresses can be programmed by means of the programmer or withthe addressing function of FIREGUARD smoke detection panels.FeaturesFeatures Monitored input able to detect different thresholdsAverage current consumption: 120 μALED current consumption: 6mA (24V- line)Provided with integrated isolator circuitRelay output: 30Vdc 2 Operating temperature: –30 C 70 CMax. humidity.: 95% non condensingMax. Cable cross section 2.5 mmPower supply: 18-35VDimensions:58x28x15 mmWeight: 13gMonitored input able to detect different thresholdsAverage current consumption: 120 μALED current consumption: 6mA (24V- line)Provided with integrated short circuit isolatorRelay output: 30Vdc 1AOperating temperature: –30 C 70 CMax. humidity.: 95% non condensingMax. Cable cross section 2.5 mmPower supply: 18-35VDimensions: 106x54x27 mmWeight: 70gSPC -102SPC -102APF-1547APF-1548Fire SafetyCertificationFire SafetyCertification16 FIREGUARD GLOBAL LTD.00-44-845075104200-44-8459751043Info@

Fire Alarm System 3 FG901CP_AP 1 loop expandable to 9 addressable fire alarm control panel EN 900 series Model FG901CP_AP, is the fire alarm control panel of the future generation with touch-screen technology and certified to EN 54-2 and 4. The GUI interface is user friendly, you can program the panel without a manual.With its