OSU EHS Addressable Fire Alarm System Standard

Transcription

OKLAHOMA STATE UNIVERSITYENVIRONMENTAL HEALTH&SAFETYADDRESSABLE FIRE ALARM SYSTEMSTANDARDRevised 6/15

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDENVIRONMENTAL HEALTH & SAFETYRevised: 6/15Contact(s)Implementation DateCommentsGerald Petre, EHSJune 2016Review and UpdatePage 1

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD1.1GENERAL1.2Scope:1.3ENVIRONMENTAL HEALTH & SAFETYRevised: 6/15A.This Standard outlines the requirements for an addressable fire detection and alarm system.B.This Standard consists of all materials, equipment and services necessary and required tocomplete and test the automatic fire detection and alarm system. Any material notspecifically mentioned in this Standard or not shown on drawings but required for properperformance and operation shall be furnished and installed.C.The contractor shall design, furnish and install (complete and ready for operation) an up-todate automatic fire detection and alarm system including control panel, software, schematics,detectors, manual pull stations, alarm devices, wiring, components, appurtenances andaccessories, and all wiring and connections to devices furnished by others.Codes, Ordinances, and Standards:A.This installation shall be made in accordance with the drawings, this Standard, and thefollowing:1.IFC, International Fire Code, Current edition as recognized by Oklahoma Statestatute.2.NFPA 70, National Electric Code, Current edition as recognized by Oklahoma Statestatute.3.NFPA #72, "National Fire Alarm Code", Current edition as recognized byOklahoma State statute.4.NFPA #101, "Life Safety Code", Current edition as recognized by Oklahoma Statestatute.5.A.D.A. (American Disability Act)6.All applicable State and local codes.B.All equipment and component parts shall be Underwriters Laboratories Listed and/orFactory Mutual Approved for use as a fire protective signaling system.C.Architects’ Fire Alarm Drawings shall be used to indicate the area of protection. AllSymbols dictate the area of protection—not the location of devices. Contractor shall beresponsible for proper location and coverage of all areas.D.Contractors proposal submission and shop plans shall be prepared by a ManufacturerTrained, NICET Certified Level 3 for fire alarm systems or a licensed fire protectionengineer, and be an Oklahoma Licensed Commercial Fire Alarm Technician employed by aLicensed Commercial Fire Alarm CompanyE.The Contractor shall correct, at no added cost, all equipment that is installed outside theabove-mentioned codes. Authority Having Jurisdiction has the authority to accept or rejectany installed equipment outside of these codes.Page 2

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD1.41.6Revised: 3/14Workmanship:A.1.5ENVIRONMENTAL HEALTH & SAFETYAll work shall be performed by Manufacturer trained and certified technicians licensed bythe State of Oklahoma for Fire Alarm Installation. All connections to fire alarm equipmentshall be supervised by a NICET Certified Level 2 for fire alarm systems technician that shallbe onsite while connection work is in progress.Contractor Qualifications:A.The Contractor shall provide on-call 24-hour, 7-days-a-week service. Service personnel shallbe available at any time for emergency service.B.The Contractor shall be a stocking distributor for all equipment included in the system forimmediate replacement of parts from inventory and shall have been actively engaged in thistype of work for a period of not less than ten (10) years and located within ninety (90) milesof the Owner.C.The Contractor shall be licensed by the State of Oklahoma to perform fire alarm work in theState of Oklahoma.Submittals:A.The contractor shall submit three (3) complete sets of documentation to Long RangeFacilities Planning (LRFP) for review. Documentation shall indicate the type, size, rating,style, catalog number, manufacturers' names, photos, and/or catalog data sheets for all itemsto ensure compliance with this standard. Upon delivery to EHS from LRFP, the review andreturn of submitted documentation to LRFP may take up to 30 calendar days.Documentation shall consist of but not limited to the following:1.2.List of Data on the addressable fire alarm control panel.a.CPU (Central Processing Unit)b.Serial/Parallel communication boardsc.Loop interface boardsd.Display interface board (LCD with Operator Keypad)e.Up-to-date Software Versionf.Power SupplyList of data on the Field Initiating and Notification Devices.a.Monitor Modulesb.Control Modulesc.Addressable smoke detectorsd.Addressable heat detectorsPage 3

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD3.ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14e.Any other initiating devices (ex: Duct Detectors)f.Manual pull stations shall be Fire Lite BG-8 or Notifier BNG-1Rg.Speaker/Strobesh.Remote power supplyVoice Evaca.Audio Voice Message Systemb.Multi-channel Amplifiersc.Speaker/StrobesThe above-mentioned items are the basic for a Fire Alarm System. Any other item that isrequired by code and building configuration shall be added to the above list.This equipment shall be subject to the approval of the OSU Environmental, Health andSafety Dept. and no equipment shall be ordered without this approval.B.Equipment and devices are to be shown on the contract drawings. Provide the followingshop drawings and lists.1.Complete one-line riser diagram showing all equipment and the size, type, andnumber of all conductors.2.Large-scale drawing of the Fire Command Center Room.3.Large-scale drawing of all field panels.4.Provide calculations to support the size of standby batteries submitted.5.A complete floor-by-floor fire alarm plan, showing devices, zone layout and wireinterconnections.6.A complete flow chart or outline of the programming that is going to be used for thefire alarm panel.a.Main subroutine. (General Alarm, System disables)b.Subroutines. (Zones, Buildings, wings, floors and large areas)c.Sub-subroutines. (Auditoriums, large classrooms, and any rooms that havemore than 3 initiating devices)Page 4

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD2.1ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14SYSTEM DESCRIPTION AND FUNCTION:A.The automatic fire detection and alarm system shall consist of a main control panel, remotepower supply panels, remote control panels, detection devices, manual stations, HVAC fanrelay control modules, and magnetically-held fire door relay control modules that are wiredin accordance with the schedule on the drawings and shall function as specified herein. Thesystem shall be capable of being expanded at any time.B.The system shall be capable of operating both addressable and non-addressable thermal andphotoelectric detecting devices, manual stations, sprinkler supervisory switches and waterflow switches.1.C.Supervisory switches shall be set up for supervisory (trouble) causing only.The system shall function as follows when any smoke detector, heat detector, duct detector,manual pull station or water flow switch operates:1.Sound the required audible notification devices as shown on the drawings.a. Activate the EVAC message.2.Illuminate all visual notification devices as shown on the drawings.3.Automatically notify the fire department via the OSU Digitize central reportingstation. Contact Facilities Management , MEP Life Safety group for accountnumber, Digitize phone numbers or any other required information andprogramming.4.Display the device(s) and location of the device(s) in alarm and in trouble on theLCD Display and interactive display system.5.Conventional zones (monitor modules) are to display the area of protection.6.Light an indicating lamp on the device initiating the alarm.7.Shut down the HVAC system and operate dampers as shown on the drawings.8.Close all magnetically-held fire doors as shown on the drawings.9.Operate Smoke Removal systems, if required for that initiating device.10.Activate Emergency Elevator operation, if required for that initiating device.11.Activate natural gas shutoff (only if alarm exists in the area of natural gas).NOTE: There shall be no limit, other than the maximum system capacity, as to thenumber of addressable devices that may be in alarm simultaneously.Page 5

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDENVIRONMENTAL HEALTH & SAFETYRevised: 3/14D.The System shall function as follows when a Building, Zone, Floor, and/or Device aredisabled.E.When the Building is disabled:F.G.H.1.All notification devices in that Building shall not be activated.2.All AHU and fire doors in that Building shall not be activated.3.Transmission of Fire alarm Signal shall not be activated.When the Zone is disabled:1.All notification devices within that zone shall not be activated.2.All AHU and fire doors within that zone shall not be activated.3.Transmission of Fire alarm Signal shall not be activated.4.All other areas outside the disabled zone shall activate the fire alarm system and itsprogrammed functions.When the Floor is disabled:1.All notification devices on that floor shall not be activated.2.All AHU and fire doors on that floor shall not be activated.3.Transmission of Fire alarm Signal shall not be activated.4.All other areas outside the disabled floor shall activate the fire alarm system and itsprogrammed functions.When the Sprinkler System alarm circuit is disabled.1.All notification devices shall not be activated2.All AHU and Fire Doors shall not be activated.3.Transmission of fire alarm signal shall not be activated.4.All other parts of the Fire Alarm system shall activate the fire alarm system and itsprogrammed function.Page 6

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD3.1PRODUCTS3.2General:3.3ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14A.All materials, equipment, accessories, devices and other facilities and appurtenances coveredby these standards or noted on the contract drawings and on the contractor’s approvedworking drawings and installations shall be up to date, new, best suited for its intended useand shall conform to applicable and recognized standards for their use. All equipment shallbe the standard cataloged products of a single manufacturer for the system being installedwith the exception of the manual stations (Notifier Model BNG-1R or Fire Lite BG-8), andthe Emergency Notification Interior System Interface (ISI) (RTU-ISI) .NOSUBSTITUTES.B.Since this system is to be part of an overall existing campus fire alarm system, NO FIREALARM CONTROL PANEL OTHER THAN A, SIMPLEX GRINNELL 4100ES, orNOTIFIER NFS2-3030 shall be accepted for the equipment specified in this section.Control Equipment:A.Fire Alarm Control Panel (FACP):1.The FACP shall provide power, annunciation, supervision and control for thedetection and alarm system. The FACP shall be modular in construction andcontain all necessary integrated modules to operate in accordance with this sectionand the applicable drawings.2.The system shall provide fail-safe operation, i.e. incoming alarms shall automaticallyoverride all other modes of operation, and the panel shall automatically return tonormal operating mode from any operator-initiated mode.3.Dynamic supervision of system electronics, wiring, and detection devices shall beprovided by the control system. Failure of system hardware or wiring shall beindicated by type and location on the alphanumeric annunciator. Ground faultdetection shall be provided for all initiating and audible circuits. Lamp test capabilityshall be provided for all visual panel indicators.4.A service mode shall permit the arming and disarming of individual detection devicesand a group of detection devices (Zones). Status of these devices shall be displayedupon command from the control panel. If any change in status degrades systemoperation as configured, a trouble condition shall be reported and remain untilsystem operation again meets configured status.5.Panel shall be capable and programmed for one button operation for the followingbypasses: speaker /strobe, AHU, Elevator and Sprinkler.6.Owner shall be capable of entering the FACP programming software to makechanges when needed.7.No audible signal shall be heard from the fire alarm control panel upon receiving atrouble signal.Page 7

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD8.B.ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14Fire Alarm Control Panel shall be installed in a room or location that has beenapproved by the University Fire Marshal.Power Supply Panels:Fire Alarm Control Panel Power1.The primary power supply shall operate from 120 volts AC. Power shall originatefrom either an emergency panel located at the main distribution panel or emergencygenerator panel.a. 120 Volt AC power shall be dedicated to the Fire alarm system panels only.Powers supply panel location will be annotated inside control panel.b. Breaker shall be marked in red, labeled as Fire Alarm and locked to the onposition.2.The secondary power supply shall consist of batteries and charger, enablingautomatic switching to battery power in the event of loss of power from the primarysupply and switching back to the primary power supply when it is restored. Anautomatic tapering charge battery charger capable of fully recharging the batteries intwelve (12) hours shall be supplied to maintain the batteries. Supervision of batteryconnections, battery fuse or breaker, and battery condition shall be provided andshall produce a trouble signal when any condition occurs that would preventoperation of the secondary power supply.Remote Power Supply (Notification and Auxiliary)1.There shall be at least four 24-volt outputs per Remote Power Supply. Each outputshall be used for Audio, Visual, and Auxiliary (AHU or Fire Doors).2.Shall be activated by the Fire Alarm Control Panel.3.Shall operate from 120 volts AC. (Receive AC power from the same power supply/panel as the FACP AC power).4.There shall be a second source of power that consists of batteries and chargerenabling automatic switching to battery power in the event of loss of power from theprimary supply and switching back to the primary power supply when it is restored.An automatic tapering charge, battery charger capable of fully recharging thebatteries in twelve (12) hours shall be supplied to maintain the batteries.5.There shall be supervision of the following:a.Main power source.b.Battery and Charger.c.All output circuits.d.Ground Faults.Page 8

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDENVIRONMENTAL HEALTH & SAFETYRevised: 3/14Note: The supervisory signal shall be sent to the Fire Alarm Control Panel. Thereshall be proper Annunciation of the Remote Power Supply panels.C.6.Remote Power Supply panels shall be installed no more than six feet above the floor,measured from the top of the Remote Power Supply panel and easily accessible.Location shall be approved by OSU Environmental, Health and Safety Dept.7.Locate Remote Power Supply in the building area in which it is being used.Indicators:1.The FACP shall provide an alphanumeric display, which shall provide a userdefinable message associated with each heat, smoke, control module, monitormodule, remote power supply or zone.2.Normal condition shall be indicated by a green light, trouble conditions by an amberlight, and fire conditions by a red light. Trouble indicating lights shall automaticallyreset when trouble conditions are cleared. Fire indicating lights must remain lit atthe control panel until manually reset.3.Remote Annunciators shall display the alarm and trouble message on LCDalphanumeric display. The annunciator shall also be capable of silencing the alarmsignal. The annunciator shall be placed in a cabinet with a window door and locked.a. Remote annunciator shall have the capability of selective zone paging.4.D.Remote Annunciator(s) shall be located at a main entrance on the first floor of abuilding/wing, other annunciators may be required dependent on buildingconfiguration. OSU Environmental Health and Safety Dept. shall give the approvalof the location.Signal Initiation Circuits:1.Individual input and output device addressability shall be performed on the samepair of wires. Wiring shall be Class B. No special wiring sequence shall be requiredon addressable device circuits. An unlimited number of wiring branches shall bepermitted with no loss of supervision. All wiring branch origination points shall beindicated on the As-Built drawings. Addressable detection devices shall beindividually identified by the system using user-defined messages. The system shallbe capable of reading the sensitivity of remote addressable ionization andphotoelectric detection devices.2.All smoke detectors shall provide alarm verification via the control panel.3.All control function of the smoke detectors shall be provided via the control panel,and software control.4.All smoke detector sensitivities shall be controlled by the FACP. System shall becapable of showing all smoke detector values.5.There shall be 20% of device space available for each Signal Initiation Circuit forfuture expansion.Page 9

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD6.E.ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14Each floor shall have its own signal initiation circuit installed.Notification Circuits:1.2.Audible Notification Circuits:a.At least Two, Class "B" supervised, general alarm, audible notification outputcircuits shall be provided. It shall be possible to disarm these output circuitsfrom the control panel without the disconnection of wiring. Disarming theseoutput circuits shall cause a trouble signal to be generated and shall alsoindicate by user-defined message on the alphanumeric display the cause ofthe trouble signal.b.The disarming of the Audible Notification devices shall be set for buildingdisarm, floor disarm, and zone disarm.c.These output circuits can be used to activate the remote power supplypanels.Voice Evacuation (required)a.Emergency voice/alarm communications service shall be provided by asystem with automatic or manual voice capability that is installed to providevoice instructions to the building occupants.b.In response to an initiating signal indicating a fire emergency, the system shallautomatically transmit a message (that has been recorded by the user) eitherimmediately or after a delay acceptable to the authority having jurisdiction,consisting of the following:1.A tone of a “whooping” sound of 3 seconds to 10 seconds durationfollowed by a message. An example of a message may be this:“MAY I HAVE YOUR ATTENTION PLEASE. MAY IHAVE YOUR ATTENTION PLEASE. THERE HAS BEENA FIRE EMERGENCY REPORTED IN THE BUILDING,PLEASE GO TO THE NEAREST EXIT AND LEAVE THEBUILDING. DO NOT USE THE ELEVATORS.” Thenrepeat the tone and message until silenced by the user.c.Failure of the message described by (b), where used, shall sound theevacuation signal (whooping sound) automatically. Provisions for manualinitiation of voice instructions or evacuation signal generation shall beprovided.d.Live voice instructions shall override all previously initiated signals on thatchannel and shall have priority over any subsequent automatically initiatedsignals on that channel.e.System shall be capable of multi-channel operation.Page 10

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARD3.4.Revised: 3/14f.All other requirements by code shall comply with NFPA 72.g.Speakers shall be set up for building, wing, floor, and zone notification. Shallbe capable of selecting, activating or deactivating the speakers by building,wing, floor, or zone individually. .Visual Notification Circuits:a.At least one, supervised general alarm visual output circuit shall be provided.It shall be possible to disarm this output circuit from the control panelwithout the disconnection of wiring. Disarming this output circuit shallcause a trouble signal to be generated and shall also indicate the cause of thetrouble signal by a user-defined message on the alphanumeric display.b.The disarming of the Visual Notification devices shall be capable ofbuilding, floor, or zones disarm.c.Do not overload the fire alarm control panel power supply. There shall be aseparate power supply or output circuit from the remote power supply forthe visual notification devices. This supply of power shall have supervisioncapabilities and shall be monitored by the fire alarm control panel.Central Station Notification:a.5.ENVIRONMENTAL HEALTH & SAFETYAutomatically notify the fire department via the OSU Digitize centralreporting station. Contact OSU Environmental Health and Safety Dept. formore information.Emergency Notification Interior System Interface (ISI):a.The ISI controller shall be an American Signal Corporation (ASC) Model #RTU-ISI, and shall be obtained through SimplexGrinnell of Tulsa,Oklahoma. NO SUBSTITUTION SHALL BE ALLOWED.b.The ISI controller must be capable of interfacing with the SimplexGrinnell4100ES or Notifier NFS2-3030, Fire Alarm Panel allowingactivation/control all speaker circuits. This will be achieved through relaycontact closure and a 1 volt Peak to Peak Line Level Audio Input. This relaycontact must have a minimum rating of 5 amperes at 240 volts AC.Controller must operate with an input power of either 120 or 240 volts AC,field selectable. Additional capability must be available in the controller togenerate signals with special timing requirements. A CANCEL signal mustbe available to immediately halt an active signal.c.The controller will be contained in a weatherproof enclosure suitable foroutdoor environments. All metallic surfaces will be painted or otherwiseprotected to retard corrosion.d.The controller should use state-of-the-art electronics in its design. Allcontroller information shall be contained in EEPROM memory, and shallbe field changeable for programming changes. A modular design shall beemployed to aid in servicing requirements.e.The controller will use an FSK-FM (Frequency Shift Keyed FrequencyPage 11

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDENVIRONMENTAL HEALTH & SAFETYRevised: 3/14Modulated) method for data communication. This FSK-FM data stream willhave additional security features available to prevent false ISI activationfrom “hackers”. The data packet format must be compatible with thesystem currently in operation at Oklahoma State University. The use ofTwo-Tone or DTMF communications for control are not acceptable.F.f.Radio communications must be compatible with a radio frequency of theexisting radio signaling protocol currently in use at Oklahoma StateUniversity. The ISI controller shall have circuitry, which will wait forchannel availability before communications are initiated.g.The ISI controller will provide status monitoring to the central activationsites. The controller will provide status change indications for controllerdoor open (tampering), AC power fail, and low battery voltage. These statuschanges will be reported immediately when the condition occurs.h.Each controller will have a backup battery to operate the electronics andradio transceiver in case of AC mains failure. A built-in charger system willkeep the battery at full charge during normal operationi.The controller will have capability for local activation. A total of 6 functionsmust be available for use, along with a cancel function. Each functionbutton must be programmable via software to activate any standard signalor custom signal. Local operation of ISI will be reported to the centralactivation sites.j.Each controller will be identified to the master system by use of a 3character address. Each ISI address will be assigned by the Manufacturer inaccordance to the existing schematic developed for Oklahoma StateUniversity in conjunction with SimplexGrinnell Management according toits quadrant numbering plan.Auxiliary Output Circuits and Devices:1.2.General:a.Individual input and output device addressability shall be performed on thesame pair of wires. Addressable relay control devices shall be individuallyand collectively (group) controlled within the programming. It shall bepossible to disarm these addressable relay control devices from the controlpanel without the disconnection of wiring. Disarming any of theseaddressable relay control devices shall cause a trouble signal to be generatedand shall also indicate by user-defined message on the alphanumeric displaythe group disarmed. It shall be possible to activate these addressable relaycontrol devices individually from the control panel.b.If auxiliary devices require 24 volt DC power, this power will be supplied bythe FACP or the use of a 24-volt output from the remote power supply.Air Handling Unit Shutdown:a.HVAC fan shutdown shall be achieved by the use of addressable relaycontrol modules.Page 12

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDb.3.4.5.6.7.ENVIRONMENTAL HEALTH & SAFETYRevised: 3/14The addressable relay control module shall be designated for HVAC controlonly. No other equipment shall be controlled by this device.Smoke/Fire Door Release and Access Control Doors:a.Magnetically-held fire door release shall be achieved by the use ofaddressable relay control modules.c.Access Control doors shall unlock by an addressable relay control modules.d.The addressable relay control module shall be designated for fire doorcontrol only. No other equipment shall be controlled by this device.Smoke Removal System Control:a.Smoke Removal System actuation (if required) shall be achieved by the use ofaddressable relay control modules. The initiating devices controlling thisaddressable relay control module shall be as indicated on the drawings.b.The addressable relay control module shall be designated for smoke removalcontrol only. No other equipment shall be controlled by this device.c.The capability of remote operation of the smoke removal system shall beinstalled next to the FACP.Fire and Smoke Damper Control:a.Fire and Smoke Damper control shall be achieved by the use of addressablerelay control modules. The initiating devices controlling this addressablerelay control module shall be as indicated on the drawings.b.The addressable relay control module shall be designated for Fire and SmokeDamper control only. No other equipment shall be controlled by this device.Emergency Elevator Control:a.Emergency Elevator Control shall be achieved by the use of addressable relaycontrol modules. The initiating devices controlling this addressable relaycontrol module shall be as indicated on the drawings.b.The addressable relay control module shall be designated for elevator controlonly. No other equipment shall be controlled by this device.Natural Gas Shut Off:a.The natural gas shut off (if required) shall shut the gas off in an area wherenatural gas is used. Example- Kitchen: It shall be achieved by the use ofaddressable relay control modules.b.The addressable relay control module shall be designated for Natural gas shutoff control only. No other equipment shall be controlled by this device.Page 13

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDG.Revised: 3/14Cabinet(s):1.3.4ENVIRONMENTAL HEALTH & SAFETYThe FACP cabinet shall be of the surface, semi-flush or flush mount type and shallcompactly house all solid state cards, indicating lamps, switches, power supplypanels, batteries, etc. for the system. The power supply and batteries will bemounted in the FACP cabinet. All lamps and controls shall be behind a hingedlocked door ("dead front") with glass or plastic vision panel(s) and lock.Devices:A.AC Power:1.FACPDedicated branch circuit shall be used for the FACP power supply and no othernon-fire alarm systems or components. There shall be a surge protector installed inthe FACP. Location of power supply breaker will be annotated inside FACP.2.Remote Power SupplyDedicated branch circuit shall be used for the remote power supply and no othernon-fire alarm systems or components. There shall be a surge protector installed forthe remote power supply. Location of power supply breaker will be annotated insideRemote Power Supply.B.Batteries:1.C.Approved gel cell-type batteries shall be provided as an emergency power source topower the system (FACP and Remote Power Supply panels) in the event of powerfailure. Batteries shall be of sufficient capacity to power the system under troubleand standby conditions for twenty-four (24) hours and to operate all notificationappliances for at least five (15) minutes to the end of this period. Batteries shall be(7) Amp Hours capacity as a minimum.Locks and Keys:1.2.All locks shall be keyed to one of the following 17021, 17003 or “B” key.a.All locks that do not operate with one of the listed keys shall be replacedwith a lock that does work.b.All fire alarm devices associated with the fire alarm panel, shall be keyed thesame as the fire alarm panel. With the exception of EHS specified pull boxes.Close security of all keys to the alarm system is a requirement of this standard. TheEquipment Supplier shall have the responsibility of retaining all except two (2) keysthat are to be checked out to the Contractor for construction and tests. (Additionalkeys may be obtained by the contractor from the OSU Key Department if needed.)The Equipment Supplier shall transfer all keys to the OSU Key Department whenthe equipment is delivered to the contractor. The contractor shall return all keys tothe OSU Key Department at the completion of the job.Page 14

OKLAHOMA STATE UNIVERSITYADDRESSABLE FIRE ALARM SYSTEM STANDARDD.To maintain uniformity on the campus, THERE SHALL BE NO SUBSTITUTESfor NOTIFIER MODEL BNG-1R or FIRE LITE BG-8. The lock shall be keyed tothe, 17021 or 17003 key lock for test purposes. Manual fire alarm stations shall beprovided with addressable monitor modules.Notification Appliances:1.2.Speaker/Strobes combination, speaker only, and strobe only.a.Audio/visual notification appliances shall be speaker -strobe designed forf

H. When the Sprinkler System alarm circuit is disabled. 1. All notification devices shall not be activated 2. All AHU and Fire Doors shall not be activated. 3. Transmission of fire alarm signal shall not be activated. 4. All other parts of the Fire Alarm system shall activate the fire alarm system and its programmed function.