PORTABLE POWER CABLES - Nexans

Transcription

PORTABLE POWERCABLESENGINEERED FOR LONGER SERVICE LIFE

PortablePower CablesIndexn DLO Power CablesDLO Flexible Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3n Type W CablesType W 1/C Motor Lead Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5Type W 2/C Magnet Crane Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7Type W 3/C P&R Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9Type W 4/C P&R Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11Nexans AmerCable believes the information presented throughout this catalog to be reliable and current.All information is subject to change without notice. The information listed is approximate, and ispresented only as a guide for product selection. We make no claims or warranties for the suitabilityof any product for any particular application.AmerCable is a registered trademark of AmerCable IncorporatedMade in America 2020, AmerCable Incorporated

Harsh operatingenvironmentsrequire cablesengineered forlonger service lifeNo matter what type of environment you operatein, Nexans AmerCable has a cable productivitysolution for you. Our innovatively engineered andmanufactured Industrial Cable Family is designedfor your toughest conditions. As a leading producerof portable power cables in North America, NexansAmerCable is dedicated to producing:n cables that last longer in difficultoperating environmentsn cables designed to help provide greaterlevels of safety and productivityCABLE INNOVATIONn Designing insulating and jacketing materials thatare more flexible with greater resistance toabrasion and moisturen Cable constructions that last longer – providingreduced down time for increased productivityn New product development that addressesenvironmental, safety and cost reductionissues specific to your application.OPERATING EXCELLENCEn The industry leader in on-timedelivery. For our currentdelivery rate, visitour website atwww.amercable.comn Standard lead-timeof 8 to 10 weeksn Urgent responseshipment capabilityof 2 to 4 weeksn AmerCable is an ISO-9001certified manufacturerHANDS-ON FIELD SUPPORTOur experienced field application engineers areavailable for on-site evaluation and solutions.They also conduct education and trainingsessions that address safety, splicing andcable handling issues.www.AmerCable.nexans.come-mail: industrial.sales@nexans.com1

37-119FLEXIBLE POWER CABLE DLO2000 VOLTS 90 CDIESEL LOCOMOTIVE CABLE LIMITED SMOKE (SIZES 2/0 AND HIGHER) EP/CPE RHH, ted annealedcopperSEPARATORJACKETFlame retardant,oil and sunlightresistantChlorinatedPolyethylene (CPE)Suitable separator tapeprovides easy strippingof insulationINSULATIONEthylene-Propylene rubber(EPR)See belowfor jacketcolor options(Special order)RATINGS & APPROVALSn ICEA S-95-658/ NEMA WC-70: Nonshielded PowerCables Rated 2000 Volts or Less for the Distribution ofElectrical Energyn UL Standard 44: Thermoset Insulated Wires &Cables, Types RHH, RHW-2. UL VW-1n UL Standard 1685: Vertical Tray Fire propagationand Smoke Release Test for Electrical andoptical Fiber Cables. (UL,ST-1)n ASTM B-33: Standard Specification for Tinned Soft orAnnealed Copper Wire for Electrical Purposesn ASTM B-172: Standard Specification forRope-Lay-Stranded Copper Conductors havingBunch-Stranded Members, for ElectricalConductorsn MSHA P-184n RoHS CompliantNexans AmerCable’s 2000V DieselLocomotive Cable (DLO) is a single conductorportable power cable suitable for use inapplications needing great flexibility, excellentwearability and good flex life. Applicationsinclude locomotive and car equipment, motorand generator leads, battery leads, shipyards,telecommunications power, heavy earthmoving equipment, renewable energy andother heavy duty flexing applications.FEATURESn A two layer composite of flame retardant,oil and sunlight resistant ChlorinatedPolyethylene (CPE) outer layer and EthylenePropylene rubber (EPR) inner layer. Thecomposite design provides significantdiameter reductions compared to designsusing full thickness jackets.n Suitable for continuous operatingtemperatures of 90 C, wet or dryn Rated RHH, RHW-2; 2/0 – 1111 kcmillisted and marked “for CT use”n UL listed as Sunlight Resistantn UL listed as Marine Shipboard Cable(4/0 and larger) – Special order onlyn Insulation and jacket meet hazardouswaste regulations, per Code of FederalRegulations 40 Section 261 (40CFR261)for characteristic lead contentn Flame Resistance: FT-4/IEEE1202 for2/0 – 1111 kcmil and UL VW-1n Meets smoke release and otherrequirements of Vertical Cable TrayTest UL 1685 and is marked “ST-1”for 2/0 – 1111 kcmiln Extremely flexible stranding used forincreased flexibility and ease of installation2Manufactured by Nexans AmerCable (870) 862-4919 (800) 643-1516 Fax (870) 862-9613

37-119 SINGLE CONDUCTOR PORTABLE POWER CABLE DLOPart /03/04/02623133734445356467779291111MinimumWires 925111013321591192423182745Nominal NominalInsulationJacketThickness 0.0650.0900.0650.1300.065* Ampacity – Calculated with at 90 C conductortemperature and 30 C ambient air,per 2008 NEC, Table 310.17Nominal Approx.OutsideWeightDiameter lbs. per *Ampacityin.90 C1,000 .43928999041.685350110051.85041661119 Cable diameters are subject to /-5%manufacturing toleranceSAVETIMEOrder Your DLO Cable withFactory om e-mail: industrial.sales@nexans.com3

37-401PORTABLE POWER CABLE TYPE WSINGLE CONDUCTOR 600-2000 VOLTSMOTOR LEAD CABLE 90 CCONDUCTORAPPLICATIONBunched strands of tinnedannealed copper perASTM B-33SeparatorA suitable separatorprovides for easy stripping of insulationInsulationEthylene-Propylene rubber(EPR) per ICEA S-95-658,and ASTM D-2802ReinforcementPolypropylene reinforcingbraid provides longflex lifeJacketFlame retardant, oiland sunlight resistantChlorinated Polyethylene(CPE). Black standard.See below for othercolor options.RATINGS & APPROVALSn UL listed as Type Wn ASTM B-33: Standard Specification for Tinned Softor Annealed Copper Wire for Electrical Purposesn ASTM D-2802: Standard Specification for OzoneResistant Ethylene-Alkene Polymer Insulation forWire and Cablen ICEA S-95-658/ NEMA WC-70: NonshieldedPower Cables Rated 2000 Volts or Less for theDistribution of Electrical EnergyNexans AmerCable’s 600-2000 Voltsingle-conductor motor-lead cables arerecommended for installations where longflex life, great flexibility and wearability aredesired. Applications include heavy duty ortemporary power supply service, AC orDC, to motor or generators, portable andstationary heavy duty equipment, cranes,conveyors and other mobile equipment.They may be installed in air, in ducts,immersed in water or directly buried in theearth. However, they are not UL Type USE.For cables requiring reduced flamepropagation, refer to the factory.FEATURESn Suitable for continuous operatingtemperatures of 90 Cn Suitable for use in festoons, suspendedloops and power tracksn Suitable for use on Payout andRetractable reels (P&R)n Heavy duty jacket offers excellentprotection against abrasion, impact,heat, oil, flame, ozone, alkali andacids.n Extremely flexible stranding usedfor increased flexibility and easeof installationn Dual Rated 600V and 2kVn Suitable for extra hard usage whichenhances performancen MSHA P-184 for 6 AWG and aboveType W CPE jackets are available in highly visible colorswithout sacrificing performance4Manufactured by Nexans AmerCable (870) 862-4919 (800) 643-1516 Fax (870) 862-9613

37-401 SINGLE CONDUCTOR PORTABLE POWER CABLE TYPE WPart 0MinimumWires 89991221Nominal NominalInsulationJacketThickness 0.0950.0950.095Nominal Approx.OutsideWeightDiameter lbs. per *Ampacityin.90 C1,000 0350405455505570615700* Ampacity is calculated with a 90 C conductor temperature and 30 C ambient air,per 2008 NEC, Table 400.5(B) Cable diameters and weights are subject to /- 5% manufacturing toleranceSAVETIMEOrder Your Type W Cable withFactory om e-mail: industrial.sales@nexans.com5

37-430MAGNET CRANE CABLE TYPE WTWO CONDUCTOR 600-2000 VOLTSMAGNET CRANE CABLE 90 CCONDUCTORSSeparatorAPPLICATIONBunched strands oftinned annealed copperper ASTM B-33. Strandingother than those listed inthe table are availableupon special order.A suitable separatorprovides for easystripping of insulationNexans AmerCable’s 600-2000 Volt twoconductor cables are recommended forinstallations where long flex life, greatflexibility and wearability are desired.Applications include heavy duty ortemporary power supply service, AC orDC, to motor or generators, portable andstationary heavy duty equipment, cranes,conveyors and other mobile equipment.They are especially recommended to supply power for magnet crane applications.They may be installed in air, in ducts,immersed in water or directly buried in theearth. However, they are not UL Type USE.For cables requiring reduced flamepropagation, refer to the factory.InsulationEthylene-Propylenerubber (EPR) per ICEAS-95-658 and ASTMD-2802. Insulationmaterial color codedthrough AWG size #2.Larger sizes are codedwith fabric tape wraps.One black, one white.FillersFibrous filler providesgreat impact resistanceand flexibility. Rubber fillersare available upon specialorder.JacketFlame retardant, oil andsunlight resistant ChlorinatedPolyethylene (CPE).Black standard. See belowfor other color options.FEATURESRATINGS & APPROVALSn UL listed as Type Wn UL listed as Type TCn ASTM B-33: Standard Specification for Tinned Softor Annealed Copper Wire for Electrical Purposesn ASTM D-2802: Standard Specification for OzoneResistant Ethylene-Alkene Polymer Insulation forWire and Cablen ICEA S-95-658/ NEMA WC-70: NonshieldedPower Cables Rated 2000 Volts or Less for theDistribution of Electrical Energyn MSHA P-184n Flame Resistance: FT-4n Suitable for continuous operatingtemperatures of 90 Cn Suitable for use in festoons, suspendedloops and power tracksn Suitable for use on Payout andRetractable reels (P&R)n Heavy duty jacket offers excellentprotection against abrasion, impact,heat, oil, flame, ozone, alkaliand acids.n Extremely flexible stranding used forincreased flexibility and easeof installationn Dual Rated 600V and 2kVn Suitable for extra hard usage whichenhances performanceType W CPE jackets are available in highly visible colorswithout sacrificing performance6Manufactured by Nexans AmerCable (870) 862-4919 (800) 643-1516 Fax (870) 862-9613

37-430 TWO CONDUCTOR MAGNET CRANE TYPE W ROUNDPart il86421/02/04/0250350500MinimumWires perConductor1331331332592663425326278881221Nominal NominalInsulation JacketThickness ghtlbs. per *Ampacity90 C1,000 440238544955191613* Ampacity is calculated with a 90 C conductor temperature and 30 C ambient air,per 2008 NEC, Table 400.5(B) Cable diameters and weights are subject to /- 5% manufacturing tolerance A full line of UL listed Type G cables with grounding conductorsis available. Consult factory.SAVETIMEOrder Your Type W Cable withFactory InstalledConnectorsSAVEMONEYPhoto provided by NASCOOPwww.AmerCable.nexans.com e-mail: industrial.sales@nexans.com7

37-431PORTABLE POWER CABLE TYPE WTHREE CONDUCTOR 600-2000 VOLTSQUALIFIED FOR P&R REELING SERVICE 90 CAPPLICATIONCONDUCTORSBunched strands of tinnedannealed copper perASTM B33. Strandingother than those listed inthe table are availableupon special order.SEPARATORA suitable separatorprovides for easy strippingof insulationINSULATIONEthylene-Propylene rubber(EPR) per ICEA S-95-658,also meeting ASTM D2802. Insulation materialcolor coded through AWGsize #2. Larger sizes arecoded with fabric tapewraps. One black, onewhite, one green.FILLERSFibrous filler providesgreat impact resistanceand flexibility. Rubberfillers are availableupon special order.REINFORCEMENTPolypropylene reinforcingbraid provides longflex lifeJACKETFlame retardant, oiland sunlight resistantChlorinated Polyethylene(CPE). Reinforced, twolayer jacket constructionis used on AWG size 1/0and larger cables. Blackstandard. Consult factoryfor colored jackets.FEATURESRATINGS & APPROVALSn UL listed as Type Wn UL listed as Type TC-ERn ASTM B-33: Standard Specification for Tinned Softor Annealed Copper Wire for Electrical Purposesn ASTM D-2802: Standard Specification for OzoneResistant Ethylene-Alkene Polymer Insulation forWire and Cablen ICEA S-95-658/ NEMA WC-70: Nonshielded PowerCables Rated 2000 Volts or Less for the Distribution ofElectrical Energyn MSHA P-184n Flame Resistance: FT-48Nexans AmerCable’s 600-2000 Volt threeconductor cables are recommended forinstallations whe

n ICEA S-95-658/ NEMA WC-70: Nonshielded Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy n UL Standard 44: Thermoset Insulated Wires & Cables, Types RHH, RHW-2. UL VW-1 n UL Standard 1685: Vertical Tray Fire propagation and Smoke Release Test for Electrical and optical Fiber Cables. (UL,ST-1) n ASTM B-33: Standard Specification for Tinned Soft or