OneWireless XYR 6000 TransmitterProfessional Installation Guide34-XY-25-47Revision 1January 2011

Notices and TrademarksCopyright 2011 by Honeywell International Inc.Revision 1 January 2011While this information is presented in good faith and believed to be accurate, Honeywell disclaims the impliedwarranties of merchantability and fitness for a particular purpose and makes no express warranties except as maybe stated in its written agreement with and for its customers.In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information andspecifications in this document are subject to change without notice.Honeywell, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell International Inc.Other brand or product names are trademarks of their respective owners.Honeywell Process Solutions1860 West Rose Garden LanePhoenix, Arizona 85027iiOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

About This DocumentThis document outlines professional installation requirements for the Honeywell XYR 6000 Transmitterfor the Honeywell OneWireless Network. Professional installation is required to comply with certificationagency and legal requirements. This document must be adhered to for all installations of the HoneywellOneWireless XYR 6000 Transmitters.Honeywell does not recommend using devices for critical control where there is a single point of failure or wheresingle points of failure result in unsafe conditions. OneWireless is targeted at open loop control, supervisorycontrol, and controls that do not have environmental or safety consequences. As with any process control solution,the end-user must weigh the risks and benefits to determine if the products used are the right match for theapplication based on security, safety, and performance. Additionally, it is up to the end-user to ensure that thecontrol strategy sheds to a safe operating condition if any crucial segment of the control solution fails.Revision InformationDocument NameDocument IDRevisionNumberPublication Date34-XY-25-47Revision 1January 2011OneWireless XYR 6000 Transmitter ProfessionalInstallation GuildeNewReferencesThe following list identifies all documents that may be sources of reference for material discussed in this publication.Document TitleXYR 6000 Transmitters Quick Start GuideGetting Started with Honeywell OneWireless SolutionsRevision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guildeiii

Support and contact infoUnited States and CanadaContact:Honeywell Process Solution Global Technical Support - Phone: 001-800-423-9883 Customer Service (HFS) - Phone: 001-800-343-0228 Outside United States - Phone: 001-215-641-3610Calls are answered by dispatcher between 6:00 am and 4:00 pm Mountain StandardTime. Emergency calls outside normal working hours are received by an answeringservice and returned within one hour.Email support: ask-ssc@honeywell.comMail:Honeywell Process Solutions1860 West Rose Garden Lane,Phoenix, AZ, 85027EuropeContact:Phone:Facsimile:Mail:Honeywell TAC-EMEA 32-2-728-2732 32-2-728-2696TAC-BE02Hermes PlazaHermeslaan, 1HB-1831 Diegem, BelgiumContact:Phone:Honeywell Global TAC – Pacific1300-300-4822 (toll free within Australia) 61-8-9362-9559 (outside Australia) 61-8-9362-9564Honeywell Limited Australia5 Kitchener WayBurswood 6100, Western well Global TAC – India 91-20- 6603-9400 91-20- 6603-9800Honeywell Automation India Ltd.56 and 57, Hadapsar Industrial EstateHadapsar, Pune –411 013, one:Facsimile:Mail:Email:ivHoneywell Global TAC – Korea 82-2-799-6317 82-11-9227-6324 82-2-792-9015Honeywell Co., Ltd17F, Kikje Center B/D,191, Hangangro-2GaYongsan-gu, Seoul, 140-702, KoreaGlobal-TAC-Korea@honeywell.comOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

People’s Republic of ChinaContact:Honeywell Global TAC – ChinaPhone: 86- 21-5257-4568Mail:Honeywell (China) Co., Ltd33/F, Tower A, City Center, 100 Zunyi Rd.Shanghai 200051, People’s Republic of Contact:Phone:Facsimile:Mail:Email:Honeywell Global TAC – South East Asia 65-6580-3500 65-6580-3501 65-6445-3033Honeywell Private LimitedHoneywell Building17, Changi Business Park Central 1Singapore csimile:Mail:Email:Honeywell Global TAC – Taiwan 886- 7- 536-2567 886-7-536-2039Honeywell Taiwan Ltd.17F-1, No. 260, Jhongshan 2nd Road.Cianjhen DistrictKaohsiung, Taiwan, ne:Facsimile:Mail:Email:Honeywell Global TAC – Japan 81-3-6730-7160 81-3-6730-7228Honeywell Japan Inc.New Pier Takeshiba, South Tower Building,20th Floor, 1-16-1 Kaigan, Minato-ku,Tokyo 105-0022, JapanGlobal-TAC-JapanJA25@honeywell.comWorld Wide WebHoneywell Solution Support l your nearest Honeywell office.Training ClassesHoneywell Automation College:http://www.automationcollege.comRevision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guildev

Symbol DefinitionsThe following table lists those symbols used in this document to denote certain conditions.SymbolDefinitionATTENTION: Identifies information that requires special consideration.TIP: Identifies advice or hints for the user, often in terms of performing a task.CAUTIONIndicates a situation which, if not avoided, may result in equipment or work (data) onthe system being damaged or lost, or may result in the inability to properly operatethe process.CAUTION: Indicates a potentially hazardous situation which, if not avoided, mayresult in minor or moderate injury. It may also be used to alert against unsafepractices.CAUTION symbol on the equipment refers the user to the product manual foradditional information. The symbol appears next to required information in themanual.WARNING: Indicates a potentially hazardous situation, which, if not avoided, couldresult in serious injury or death.WARNING symbol on the equipment refers the user to the product manual foradditional information. The symbol appears next to required information in themanual.WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUSLIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.ESD HAZARD: Danger of an electro-static discharge to which equipment may besensitive. Observe precautions for handling electrostatic sensitive devices.Protective Earth (PE) terminal: Provided for connection of the protective earth(green or green/yellow) supply system conductor.Functional earth terminal: Used for non-safety purposes such as noise immunityimprovement. NOTE: This connection shall be bonded to Protective Earth at thesource of supply in accordance with national local electrical code requirements.Earth Ground: Functional earth connection. NOTE: This connection shall bebonded to Protective Earth at the source of supply in accordance with national andlocal electrical code requirements.Chassis Ground: Identifies a connection to the chassis or frame of the equipmentshall be bonded to Protective Earth at the source of supply in accordance withnational and local electrical code requirements.continuedviOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

SymbolDescription The Factory Mutual Approval mark means the equipment hasbeen rigorously tested and certified to be reliable.The Canadian Standards mark means the equipment has beentested and meets applicable standards for safety and/orperformance.The Ex mark means the equipment complies with the requirementsof the European standards that are harmonized with the 94/9/ECDirective (ATEX Directive, named after the French "ATmosphereEXplosible").For radio equipment used in the European Union in accordancewith the R&TTE Directive the CE Mark and the notified body (NB)identification number is used when the NB is involved in theconformity assessment procedure. The alert sign must be usedwhen a restriction on use (output power limit by a country at certainfrequencies) applies to the equipment and must follow the CEmarking.The C-Tick mark is a certification trade mark registered to ACMA(Australian Communications and Media Authority) in Australia underthe Trade Marks Act 1995 and to RSM in New Zealand undersection 47 of the NZ Trade Marks Act. The mark is only to be usedin accordance with conditions laid down by ACMA and RSM. Thismark is equal to the CE Mark used in the European Union.N314 directly under the logo is Honeywell’s unique supplieridentification number.Revision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guildevii

viiiOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

ContentsSupport and contact info.iv1.DESIGNATION, SCOPE AND PREFACE . 11.1Designation.11.2Scope.21.3Preface .21.4Site survey .21.5Abbreviations & Definitions .32.FEDERAL COMMUNICATION COMMISSION (FCC) . 52.1FCC Compliance Statement .52.2Industry Canada (IC) .52.2.12.2.22.3IC Compliance Statements .5RF Safety Statement .5FCC and Industry Canada (IC) Identification Numbers .62.3.12.3.22.4FHSS Radios.6DSSS and ISA100 Radios .6Japan MIC Identification and Certification Numbers.72.4.12.5DSSS and ISA100 Radios .7Intended Country Usage.72.5.12.5.22.5.32.5.43.NORTH AMERICA .7ASIA PACIFIC .7EUROPEAN UNION.7MIDDLE EAST.8XYR 6000 TRANSMITTER GENERAL DESCRIPTION. 93.1Intended Used.93.2XYR 6000 Transmitter Diagrams.94.PRODUCT SPECIFICATION . 104.1Frequency Hopping Spread Spectrum (FHSS) Radio, 2.4 GHz .104.2Direct Sequence Spread Spectrum (DSSS) and ISA100 Radio, 2.4 GHz .114.3Direct Sequence Spread Spectrum (DSSS) Radio for Kuwait Oil Company Applications,2.4 GHz .114.4XYR 6000 Transmitter User Environment.124.5XYR 6000 Instrument Power Specifications.124.6Weight .124.7Dimensions .13Revision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guildeix

ContentsSymbol Definitions5.CABLES. 145.1XYR 6000 Transmitter with RP-TNC Connectors Antenna or Lightning Arrestor Cables .145.2XYR 6000 Transmitter with N Connectors Antenna or Lightning Arrestor Cables .145.3Transmitter connection status.155.4Antenna Lightning ArrestorsIn PV display.156.APPROVED ANTENNA TYPES/GAINS. 166.17.Antenna Details .16EQUIVALENT ISOTROPICALLY RADIATED POWER (EIRP). 187.18.EIRP LIMITS .19SETTING TX POWER. 258.19.TX Power Setting.25AGENCY LABEL INFORMATION . 269.1External FCC/IC Labels.269.1.19.1.250016195-001 – Transmitters with FHSS Radios . 2650016195-002 – Transmitters with DSSS and ISA100 Radios . 269.2Internal FCC/IC Labels.279.3Internal Japan Ministry of Internal Affairs and Communications Label.2710.RF SAFETY, MAXIMUM PERMISSIBLE EXPOSURE (MPE) STATEMENT . 2810.111.MPE Statement.28AGENCY COMPLIANCE . 2911.1Radio and EMC Certifications roduct Safety Agency Certifications .3011.2.111.2.211.2.311.2.411.2.512.12.1xFederal Communication Commission (FCC). 29Industry Canada (IC). 29European Telecommunications Standards Institute (ETSI). 29Australian communications and media authority (ACMA) . 29Thailand National Telecommunications Commission (TNTC) . 29Japan Ministry of Internal Affairs and Communications (MIC) . 29Kuwait Ministry of Communications (KMOC) . 29Canadian Standards Association (CSA) . 30Factory Mutual (FM). 30European ATEX Certification (ATEX). 31European Union Certification (CE-mark). 31Japan Technology Institution of Industrial Safety (TIIS) Certification . 31REFERENCE DOCUMENTS . 32OneWireless refenece documentation .32OneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

ContentsTablesTablesTable 1-1 – XYR 6000 Transmitter Types .1Table 1-2 –Table of Abbreviations and Definitions.3Table 4-1 Specifications of FHSS Radio Module in XYR 6000 Transmitter.10Table 4-2 Specifications of DSSS and ISA100 Radio Module in XYR 6000 Transmitter .11Table 4-3 Specifications of DSSS Radio Module in XYR 6000 Transmitter for KOC Applications.12Table 4-4 User Environment Specifications for XYR 6000 Transmitter .12Table 5-1 Transmitter toAntenna or Lightning Arrestor Cable Specifications for XYR 6000 with RP-TNCconnectors .14Table 5-2 Transmitter to Antenna or Lightning Arrestor Cable Specifications for XYR 6000 with Nconnectors .14Table 6-1 Approved Antenna Types/Gains .16Table 7-1 Maximum EIRP Limits for FHSS Radios .19Table 7-2 Maximum EIRP Limits for DSSS and ISA100 Radios.20Table 7-3 FHSS Transmit Power Settings for the antennas and cable lengths specified above for FCC,IC, ETSI, ACMA and TNTC approvals .22Table 7-4 DSSS and ISA100 Transmit Power Settings for the antennas and cable lengths specifiedabove for FCC, IC, ETSI, ACMA, MIC, KMOC and TNTC approvals .23Table 12-1 – Reference documents .32Revision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guildexi

ContentsFiguresFiguresFigure 3-1 XYR 6000 Transmitters showing Right-angle -2 dBi Integral Antenna (left), Straight Integral -2dBi Antenna (center) and Remote Antenna connector (right) options .9Figure 4-1 Dimensions of a typical XYR 6000 Transmitter with the Right-angle -2 dBi Integral AntennaOption .13Figure 6-1 Comparison of instruments with -2 dBi Integral Antenna (left) and 4 dBi Integral Antenna.17Figure 6-2 Remote Antennas.17xiiOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

1. Designation, Scope and Preface1.1. Designation1.Designation, Scope and Preface1.1 DesignationThis document is valid for the following XYR 6000 Transmitter types:Table 1-1 – XYR 6000 Transmitter TypesModelNumberTypeSTTWModel NumberDescriptionTemperatureTransmitterModel Key NumberDescriptionSTTW8XXTemperature Transmitter withintegral probeSTTW400Temperature TransmitterSTTW401Temperature/Two DiscreteInput TransmitterSTXWDiscrete InputTransmitterSTXW500Discrete Input TransmitterSTIWHLAI TransmitterSTIW600HLAIUniversal InputTransmitterSTUW700Multi AI DI TransmitterSTUWSTUW701Multi AI DI DO TransmitterSTAW94LAbsolute PressureTransmitterSTDW924/930/974Differential PressureTransmitterSTAWAbsolute PressureTransmitterSTDWDifferential PressureTransmitterSTGWCETWGauge PressureTransmitterSmartCET ge Pressure TransmitterSmartCET Transmitter(Corrosion)Model Selection Guide Table IV selections XF, EF or JF mean that the XYR 6000 has a FHSS radio.Model Selection Guide Table IV selections XD, ED or JD mean that the XYR 6000 has a DSSS radio.Model Selection Guide Table IV selection XS means that the transmitter has an ISA100.11 compliantradio.For the complete model number information, please see the appropriate XYR 6000 Transmitter ModelSelection Guides.The WCX Series XYR 6000 Valve Position Sensor is not covered by this document and has its ownProfessional Installation Guide.Revision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guilde1

1. Designation, Scope and Preface1.2. Scope1.2 ScopeThis document outlines professional installation requirements for the Honeywell XYR 6000 Transmitterfor the Honeywell OneWireless Network. Professional installation is required to comply with certificationagency and legal requirements. This document must be adhered to for all installations of the HoneywellOneWireless XYR 6000 Transmitters.1.3 PrefaceThis manual covers professional installation of the Honeywell OneWireless XYR 6000 Transmitters. Seethe Getting Started with Honeywell OneWireless, Honeywell OneWireless Planning Guide and HoneywellOneWireless XYR 6000 User’s Guides for general information on overall system implementation,configuration, and management of these devices.The XYR 6000 is classified by the FCC as a device that must be professionally installed. To be incompliance with FCC requirements, the radio must be installed with one of the approved antennas listed inthis document.1.4 Site surveyIt is assumed for the purposes of this document that a site survey has been performed and that the antennatypes, cable lengths and lightning surge arrestors were appropriately selected per the results of that survey.Any changes to these items as a result of the actual installation of the XYR 6000 transmitters into the sitemay require that the TX power setting of the radio board needs to be adjusted from the factory setting inorder to maintain agency approvals. See Section 7 and Section 8 for more information.2OneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

1. Designation, Scope and Preface1.5. Abbreviations & Definitions1.5 Abbreviations & DefinitionsThe term Honeywell XYR 6000 Transmitter will be used to describe the composite unit which includesthe Honeywell FHSS or DSSS RF Module and all subassemblies housed within the XYR 6000 Transmitterenclosure.Table 1-2 –Table of Abbreviations and DefinitionsACMAAustralian Communications and Media AuthorityADAuthentication DeviceATEXPotentially Explosive Atmospheres DirectiveAWGAmerican Wire GaugeColocatedTwo or more radios transmitting simultaneously and with less than20cm of separation distance.CSACanadian Standards AssociationDCSDistributed Control SystemDSSSDirect Sequence Spread SpectrumEMCElectromagnetic CompatibilityETSIEuropean Telecommunications Standards InstituteEUEuropean UnionFCCFederal Communications CommitteeFHSSFrequency-Hopping Spread SpectrumFMFactory MutualFSKFrequency Shift KeyingGFSKGaussian Frequency Shift KeyingGTSHoneywell Global Technical ServicesICIndustry CanadaIEEEInstitute of Electrical and Electronics EngineersIRInfraredIrDAInfrared Data AssociationISA100International Society of Automation open-standard wirelessnetworking technologyKMOCKuwait Ministry of CommunicationsMICJapan Ministry of Internal Affairs and CommunicationsMPEMaximum Permissible ExposureMSGHoneywell Model Selection GuideRevision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guilde3

1. Designation, Scope and Preface1.5. Abbreviations & Definitions4NANorth America – United States of America and CanadaNEMANational Electrical Manufacturers AssociationOQPSKOffset Quadrature Phase-Shift KeyingTELECJapan Telecom Engineering CenterTIISJapan Technology Institution of Industrial SafetyTNTCThailand National Telecommunications CommissionTXTransmitWi-FiWireless Local Area Network based on IEEE 802.11 SpecificationsWNSIAWireless Network for Secure Industrial ApplicationOneWireless XYR 6000 Transmitter Professional Installation GuildeRevision 1January 2011

2. Federal Communication Commission (FCC)2.1. FCC Compliance Statement2.Federal Communication Commission (FCC)2.1 FCC Compliance Statement This device complies with Part 15 of FCC Rules and Regulations. Operation is subject to thefollowing two conditions: (1) This device may not cause harmful interference and (2) this device mustaccept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device,pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protectionagainst harmful interference in a residential installation. This equipment generates, uses, and canradiate radiofrequency energy and, if not installed and used in accordance with these instructions, maycause harmful interference to radio communications. Operation of this equipment in a residential areais likely to cause harmful interference in which case the user will be required to correct theinterference at his own expense. Intentional or unintentional changes or modifications must not be made to the XYR 6000 unless underthe express consent of the party responsible for compliance. Any such modifications could void theuser’s authority to operate the equipment and will void the manufacturer’s warranty.2.2 Industry Canada (IC)2.2.1 IC Compliance Statements To reduce potential radio interference to other users, the antenna type and its gain should be so chosenthat the equivalent isotropic radiated power (EIRP) is not more than that permitted for successfulcommunication. Operation is subject to the following two conditions: (1) this device may not cause interference, and(2) this device must accept any interference, including interference that may cause undesired operationof the device. This Class A digital apparatus complies with Canadian ICES-003. French: Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.2.2.2 RF Safety Statement To comply with FCC’s and Industry Canada’s RF exposure requirements, the following antennainstallation and device operating configurations must be satisfied. Remote Point-to-Multi-Point antenna(s) for this unit must be fixed and mounted on outdoor permanentstructures with a separation distance between the antenna(s) of greater than 20cm and a separationdistance of at least 20cm from all persons. Furthermore, when using integral antenna(s) the XYR 6000 unit must not be co-located with any otherantenna or transmitter device and have a separation distance of at least 20cm from all persons.Revision 1January 2011OneWireless XYR 6000 Transmitter Professional Installation Guilde5

2. Federal Communication Commission (FCC)2.3. FCC and Industry Canada (IC) Identification Numbers2.3 FCC and Industry Canada (IC) Identification NumbersThis information is shown on the label attached to each RF Module.2.3.1 FHSS Radios Honeywell XYR 6000 Transmitter FHSS Radio Module Identification Honeywell Identification for Class 1 Div 2 RF Modules: 50016517-001 Honeywell Identification for Intrinsically Safe RF Modules: 50025132-001Honeywell XYR 6000 Transmitter FHSS Radio Limited Modular Approval Federal Communication Commission Identification for Class 1 Div 2 RF Modules:S5750016517 Federal Communication Commission Identification for Intrinsically Safe RF Modules:S5750016517Honeywell XYR 6000 Transmitter FHSS Radio Limited Modular Approval Industry Canada Identification for Class 1 Div 2 RF Modules: 573I-50016517 Industry Canada Identificatio

Mail: Honeywell Limited Australia 5 Kitchener Way Burswood 6100, Western Australia Email: GTAC@honeywell.com India Contact: Honeywell Global TAC - India Phone: 91-20- 6603-9400 Facsimile: 91-20- 6603-9800 Mail: Honeywell Automation India Ltd. 56 and 57, Hadapsar Industrial Estate Hadapsar, Pune -411 013, India