Crane Control Class 7004 - Hubbellcdn

Transcription

Crane Control Class 7004CatalogCRANE CONTROLCLASS 700417CONTENTSDescription . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PagePricing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

Crane Control Class 7004Type M Line-Arc DC ContactorsPRICING INFORMATIONType M DC magnetic, mill type, clapper contactors are designed for the control of DC motors. Front connected High strength glass polyester insulating base for steel base mounting Line-Arcâ method of arc extinction for longer tip lifeBasic ContactorThe basic contactor is furnished without power lugs, electrical or mechanical interlocks.Note: For coil voltages other than 230 V, 120 V, 75 V, 60 V, or 45 V add 440 to the list price per contactor.Maximum VDCNumber of Poles 123455A 66A 8123455A 6 8 Class 7004Type MXDO1 ContactorSingle PoleNormally Open600CRANE CONTROLCLASS 7004Single PoleNormally Closed Open 8 HrAmpere RatingNEMA SizeOpen Type Price aTypeMXCO1 .MXDO1 .MEO1 .MFO1 .MGO1 .MGAO1 .MHO1 .MHAO1 .MKO1 .MXCO3 .MXDO3 .MEO3 .MFO3 .MGO3 .MGAO3 .MHO3 .MKO3 See contactor Application Data for double pole contactors.Not a NEMA size/rating.See Class 9998 for coil data.Operating coil forcing circuit may be required; consult factory.Factory Installed ModificationsFormClass 7004Type MGO1 ContactorDescriptionY781 Price aNEMA Size1 .2 .3 .4 .5 & 5A .6 & 6A .8 .Silver Faced Power Contact Tips5A/6A is not a NEMA size/rating.1. Class2. TypeOrdering Information Required:3. Form4. Coil VoltageAccessory Kits For User InstallationClass 9999 user modification kits include all necessary mounting hardware and installation instructions.Mechanical interlocks, pneumatic timers, and tie bars can be mounted on normally open devices only.Mechanical Interlock TypePrice aNEMA Size1&23&45 & 5A 6 & 6A 8 Price aPower Lug TypePrice aMM1 . 0T1 . .MM2 . 0T2160. 0L1 .MM3 . 0T3 . 0L2 .MM4 . 0T4 . 0L3 .MM5 . 0T5 . 0L3 .Contains four clam shell type lugs. For copper conductors only.5A/6A is not a NEMA size/rating.For use with normally open contactors only.Electrical Interlock (one N.O. and one N.C. contact)TypePrice hNEMA Size1 to 8ahTie Bar TypeMX11Disc Sch BDisc Sch CSCH110 2003 The Electric Controller & Mfg. Co., LLCAll Rights ReservedB,C .Ordering Information Required:1. Class2. TypeDISCOUNT SCHEDULES B,C1/17

Crane Control Class 7004Type M Line-Arc DC ContactorsAPPLICATION DATARatings are based on 40 C (104 F), per NEMA standards.MountingThe Type M contactor with its insulated base can be mounted directly on uninsulated steel panels, angleiron frames, etc. The contactors are completely front-connected.WiringSize 1 through 5A Type M contactors have a wire accessway in the base for convenient out-of-the-wayrouting of cables and control wires. Size 6 through 8 contactors have a flat mounting base. Powerconnections to the NEMA Sizes 3 through 8 contactors can be made from either side.Coil DataDC operating coils are designed in accordance with NEMA standards to withstand 110% of ratedvoltage continuously and to operate the contactor successfully at 80% of rated voltage. Standard coilvoltages are 120 VDC and 240 VDC. For other available coil voltages, refer to the Class 9998 Coil DataCatalog Sheet.AC to DC Control Voltage ConversionTo control the DC contactor coil from a 120 VAC supply, order each single pole contactor with 120 VDCcoil or for double pole contactors, order each contactor with a 60 VDC coil.Connect the rectifier and suppressor (MOV) as shown.120VAC(–)( )105VDCMOVRectifier part no. is 27907-34220 (800 PIV, 30 A)CRANE CONTROLCLASS 7004RECTIFIERMOV part no. is 52906-028-59Double Pole ContactorsDouble-pole, normally-open contactors can be built by ordering two single-pole, normally-opencontactors with half-voltage operating coils and one tie bar kit. The two coils must be connected inseries.User Modification KitsA number of Class 9999 user modification kits are available for use with Type M contactors. Powercontact tip parts kits are listed under Class 9998.Maximum Number of Accessories and Accessory CombinationsFor single-pole, normally-open contactors, two electrical interlock kits and any one of the following: Two mechanical interlock kits One tie bar kit and one mechanical interlock kitFor single-pole, normally-closed contactors, two electrical interlock kits1/17111 2003 The Electric Controller & Mfg. Co., LLCAll Rights Reserved

Crane Control Class 7004Type M Line-Arc DC ContactorsAPPLICATION DATAElectrical InterlocksControl circuit interlocks are available in units of one normally open and one normally closed contacts.On each single pole normally open and normally closed contactor a maximum of two interlock kits canbe mounted. Interlock kits include the movable and stationary contacts plus all necessary hardware formounting.Electrical interlocks are rated in accordance with NEMA Standard ICS- 2-125 (A600 and N600 TableRatings).Class 9999 Type MX11Electrical Interlock BreakMakeBreak102.22.21.11.10.40.4DC Maximum Make and Break Current Amperes m Make and Break Current Amperes 125V250V600VMake and break ratings apply for double-throw contacts only when both the normally open and normally closed contacts areconnected to the same polarity.Mechanical InterlockCRANE CONTROLCLASS 7004A horizontal mechanical interlock is mounted between two single pole normally open or double pole tiednormally open contactors mounted side by side. This interlock prevents the two contactors fromoperating simultaneously.LugsClass 9999Type MM2MechanicalInterlock KitType M contactors are furnished without power lugs. A kit is available consisting of lugs and hardwarefor mounting on Size 3 and larger contactors. No power lug kits are available for the NEMA Size 1 and2 contactors. These contactors are designed to use lugs supplied by the user.Lug Wire Capacity Lug Type Minimum Wire SizeMaximum Wire SizeML1Number 8Number 00ML2Number 0300 MCMML3250 MCM500 MCMContains four clam shell type lugs. For copper conductors only.Power Contact TipsA Class 9998 power contact tips part kit consists of movable and stationary contact tips with necessarymounting hardware for two single pole contactors. Consult Catalog Section 9998 for additionalinformation.Copper contact tips are standard. Silver-faced contact tips are available and are recommended forapplications where the contactors remain closed for long periods of time. Silver-faced contact tips arestandard on crane manual-magnetic disconnect switches.Tie BarApplications requiring double pole Type M contactors can be met by supplying single pole normally openonly contactors with tie bars. The tie bar is made from an insulating material and connects the armaturesof the contactors together. For double pole contactors, it is recommended that the operating coils beconnected in series. Each coil should be rated for one half of system voltage. See Catalog Section 9999,page 160, for additional information.112 2003 The Electric Controller & Mfg. Co., LLCAll Rights Reserved1/17

Crane Control Class 7004Type M Line-Arc DC ContactorsAPPLICATION DATAClass 9999 AI1 Arc SuppressorThe Class 9999 AI1 arc suppressor is designed to reduce arcing of pilot devices in DC inductive controlcircuits of 250 VDC or less.TypePriceAI1360.The AI1 arc suppressor will limit the inductive voltage surge to a maximum of 600 VDC when applied inaccordance with the application chart. When applying the arc suppressor to a circuit, two factors mustbe considered, the current drawn by the inductive load and the number of times per minute that the loadwill be interrupted. Once these two factors are determined, the application is checked against theapplication chart. The chart shows the maximum interruptions per minute that the arc suppressor canhandle at a given current. As long as an application falls below the curve, the arc suppressor will handlethe load. The arc suppressor is connected in parallel with the inductive load and is in the circuit at alltimes.Application Chart for AI1 Arc Suppressor60504030L 11HCRANE CONTROLCLASS 7004PERMISSIBLE INTERRUPTIONSPER MINUTEClass 9999Type AI1Arc Suppress2010L 20H0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4CURRENT IN AMPERESApproximate Dimensions And WeightsClearance for (2)1/4" mtg. screws4.381113.75951.65 3.0042760.256.31.00251.93492.2557Dual Dimensions: inchesmmNet Weight – 1 lb (0.45 kg)Ordering Information Required:1. Class 99992. Type AI1SCH1/17DISCOUNT SCHEDULE BB113 2003 The Electric Controller & Mfg. Co., LLCAll Rights Reserved

Crane Control Class 7004Type M Line-Arc DC ContactorsAPPROXIMATE DIMENSIONS2 Mtg. holesfor screw "F"C2C1EXNEMA SIZES 1, 2SPNO AND SPNCKFigure 1QYDBHArcing clearancezoneASS2 Mtg. holesfor screw "F"4 "G" tappedholesMain TerminalsAC1C2AZEXKCRANE CONTROLCLASS 7004NEMA SIZES 3, 4, & 5SPNO AND SPNCSIZE 5ASPNO AND SPNCQYDBFigure 2Arcing clearancezoneHSHSC1C2ALEAZX4 Mtg. holesfor screw "F"KYNEMA SIZES 6, 8SPNO AND SPNCAND SIZE 6A SPNOQBFigure 3DArcing clearancezone114 2003 The Electric Controller & Mfg. Co., LLCAll Rights ReservedSSHH4 "G" tappedholesMain Terminal1/17

Crane Control Class 7004Type M Line-Arc DC ContactorsAPPROXIMATE DIMENSIONS AND WEIGHTSContactor Dimensions TypeFig.No.ABC1C2DEFGHKLCenter to CenterSpacing of S.P. TiedWeightor 2.13550.8020.1576.0015355A 250.3753/8-16102.78711.0226.30147.0017855A 250.3753/8-16102.78711.0226.30147.0017866A 47570329.002298MKO134.5011422.90 17.40 15.80 .69941607311.302878MKO334.5011422.90 17.40 15.80 .69941607311.30287NEMASizeTypeFig.No.Accessory Dimensions Arcing ClearancesElectrical Interlock240 VDC600 022912.003054.001025A 5A 66A QSXYZXThe table lists recommended minimum enclosure sizes for single pole-240 VDC contactors withcontactor mounted accessories. For double pole contactors, increase width by 50%.NEMA 38118.0045720.0050824.0061024.0061024.0061055A 66A 8 1/17Electrical interlocks and all live electrical parts must have a .50 clearance to ground and other live13electrical parts.Not a NEMA size/rating.Dual Dimensions: inmmDual Weights: lbkg115 2003 The Electric Controller & Mfg. Co., LLCAll Rights ReservedCRANE CONTROLCLASS 7004NEMASize

CRANE CONTROLCLASS 7004Crane Control Class 7004116 2003 The Electric Controller & Mfg. Co., LLCAll Rights Reserved1/17

Maximum Make and Break Current Amperes 120V 240V 480V 600V Make Break Make Break Make Break Make Break. AC 10 60630315 1.5 12 1.2. N600 Maximum Continuous Amperes Maximum Make and Break Current Amperes 125V 250V 600V Make BreakMake BreakMake Break. DC 10 2.2 2.2 1.1 1.1 0.4 0.4. Lug Wire Capacity. Lug Type Minimum Wire Size Maximum Wire Size