Fire Resistance Test Standards For Elements And Assemblies

Transcription

Fire-Resistance TestStandards forElements andAssembliesRich WalkeUL Codes and Regulatory ServicesUL and the UL logo are Trademarks of UL 2019October 3, 2019

Fire-Resistance-Rated Construction2

Fire-Resistance-Rated dConstruction3

Code Requirements IBC Section 703.2 – Fire-resistance ratingsshall be determined in accordance withANSI/UL 263 or ASTM E119 LSC 8.2.3.1 – The fire resistance ofstructural elements and buildingassemblies shall be determined inaccordance with test procedures set forthin ANSI/UL 263 or ASTM E1194

Fire Resistance Expressed as an Hourly Time Period Ratings range from 1/2 to 4 hours Containment of Fire to Room or Floor ofOrigin, and Structural Fire Resistance5

Fire-Resistance-Rated ConstructionEstablishingFire-ResistanceRatings6

Standards ANSI/UL 263 ASTM E119 NFPA 251 (Withdrawn)7

Building Components Columns Beams Floor/Ceilings or Roof/Ceilings Walls8

Time - Temperature CurveTemp(ºF)Time (Hr)9

Columns Sample size – Minimum 9 ft Tested unloaded10

11

12

Conditions of Acceptance – Columns 1000ºF / 1200ºF13

14

15

Beams Sample size – Minimum 12 ft Load applied – Per design16

17

18

19

20

21

22

Conditions of Acceptance – Beams Support load 1100ºF / 1300ºF23

Floor/Ceiling or Roof/Ceilings Sample size – 180 sq ft / 12 ft Load applied – Per design12 ft180 sq ft24

25

26

27

28

29

30

31

32

33

34

Conditions of AcceptanceFloor/Ceilings or Roof/Ceilings Support load Flame passage 250ºF / 325ºF Support temperatures35

36

Walls Sample size - 100 sq ft / 9 ft Load applied - Per design9 ft100 sq ft37

38

39

40

41

42

43

Conditions of Acceptance – Walls Flame passage 250ºF / 325ºF Support load Hose stream44

Where Can I Find TheMost Current Listing?UL Product iQ onwww.ul.com45

Breaches in Fire-Resistance-RatedConstruction Penetrations Joint Systems Opening Protectives Ducts and Air Transfer Openings46

Breaches in Fire-Resistance-RatedConstruction Cont.Do breaches really impact the performanceof a fire-resistance-rated assembly?Absolutely!!!47

Breaches in Fire-Resistance-RatedConstruction Cont. Unsealed or improperly sealed breaches cost lives andproperty! MGM Grand, Las Vegas, NV – Fire confined to 1st floor.Eighty-four fatalities, most on upper floors. Hilton Hotel, Las Vegas, NV – Fire spread from 8th to 23rdfloor in 25 minutes at exterior of building. Eight fatalities. First Interstate Bank, Los Angeles, CA – Fire spread from12th to 16th floor through improperly protected penetrationsand through unprotected perimeter joint. One fatality. One Meridian Plaza, Philadelphia, PA – Fire spread from22nd to 30th floor through improperly protected penetrationsand through perimeter joint. Three fatalities.48

IBC Requirements IBC – Breaches shall be protected Section 714 – Penetrations Section 715 – Fire-Resistant Joint Systems Section 716 – Opening Protectives Section 717 – Ducts and Air Transfer Openings49

LSC Requirements LSC – Breaches shall be protected Penetrations Joint Systems Opening Protectives Ducts and Air Transfer Openings50

Code Requirements Each type of breach has a unique fire teststandard associated with it whichcompliments ANSI/UL 263 and ASTME119 Where breach occurs in, through orbetween assemblies intended to restrict themovement of smoke, the code also setslimits on the leakage through the breach51

Where Can I Find TheMost Current Listing?UL Product iQ onwww.ul.com52

Fire Resistive ConstructionUL’sProduct iQOnline Directory53

Product iQ – UL’s New Online Directory Replaces the old Online CertificationsDirectory which was developed in 1999 Helps you achieve code compliance Is continuously updated Requires registration to create user account Basic Service – no charge for use54

Product iQ – UL’s New Online Directory Paid Subscription Service provides morefeatures Save Searches Tags and Groups Confirmation Letters Same listing information as the old platform No impact on testing results orcertifications https://iq.ulprospector.com/en/55

UL Product iQ – www.ul.comScroll to the bottom of the page56

UL Product iQ57

UL Product iQ Cont.58

UL Product iQ Cont.59

UL Product iQ Cont.60

UL Product iQ Cont.61

UL Product iQ Cont.62

UL Product iQ Cont.Smart Search63

UL Product iQ Cont.iQ Plus Search64

UL Product iQ Cont.iQ Plus Search65

Questions / Comments66

Thank You for Attending!!!Rich WalkeCodes and Regulatory Services DepartmentUnderwriters Laboratories750 Anthony TrailNorthbrook, IL 60062Richard.N.Walke@UL.com(847) 664-3084www.ul.com67

Breaches in Fire-Resistance-Rated Construction Cont. Unsealed or improperly sealed breaches cost lives and property! MGM Grand, Las Vegas, NV –Fire confined to 1st floor. Eighty-four fatalities, most on upper floors. Hilton Hotel, Las Vegas, NV –Fire spread from 8th to 23rd floor