Air Circuit Breakers - Terasaki

Transcription

NEWAirCircuitBreakersMORE POWER QUALITY MONITORING:with new AGR-31B “H” relay

[Terasaki is the world leader for circuit breakers in switchgear in the marine market]Terasaki supply circuit breakers which protectpeople and equipment from electrical faults.Safety and protection are the prime purposesof our products.We supply products to switchboard builders,shipbuilders and equipment manufacturers.We are global market leaders for switchgear inthe marine market. Terasaki have worldwideexport experience and the necessaryprofessional skills to support your business.[Telehouse Data Centre, London. 199 TemPower 2 ACBs, 423 TemBreak 2 MCCBs.]

Upgrade for AGR-31B Protection RelayMORE MONITORING FEATURESThe new AGR-31B “H” ensures optimium monitoring and performance.Safe ModeA safe mode can be enabled during switchboard maintenance. Two independent INST thresholds can be saved in on-board memory.The user can toggle INST settings quickly via the LCD menu or over the data communication link. A lower INST threshold will reduce theincident arc energy. Settings can be quickly returned to normal after maintenance to provide optimum performance.Accurate SettingOverload protection settings can be matched exactly to the circuit needs. LTD current threshold settings can be fine-tuned to the nearestAmpere.New AlarmsUnder/over-voltage; under/over-frequency. Take action automatically if these parameters go outside your acceptable limits. Voltfree output contacts included. AVAILABLE AS AN OPTIONAL EXTRA FEATURE OF AGR-31B.-.H.HarmonicsHarmonic current measurement. Identify loads causingharmonic pollution, optimise harmonic filtering and ultimatelysave money with this new feature. Monitors individual harmoniccurrents per phase at each harmonic order. INCLUDED ASSTANDARD WITH AGR-31B.-.H.

Special VersionsTempower 2 ACBs for800V and 1000V ACHigh AC voltages are used to minimise cable costs for installationswhere long cable runs are necessary.Terasaki supply ACBs for large solar farms, mines and railways.The latest addtions to our range are the AR316H-V8, AR325H-V8& AR332-V8 which can all interrupt 30kA at 800VAC.DC ACBsTerasaki now offer a new broad range of dedicated DC aircircuit breakers and moulded case circuit breakers. Therange of Terasaki DC circuit breakers are ideally suitedfor all types of industries, information technology andcommunication sectors where highly reliable sources ofelectric power are required.DC ACBs are suitable for 600V and 800V DC applications.[Standard AR ACBs (S&H types) are only suitable for250V DC applications].4 TemPower 2 Air Circuit Breakers

3C Overheating Protection for Contacts, Connection & ConductorsCondition BasedMaintenanceBENEFITSOVERHEATINGPROTECTION LOW INVESTMENT [system is integrated with circuit breakers]FAST INSTALLATION [breakers are supplied with sensors already fitted]EASY UPGRADE [the 3C system can be retrofitted to existing installations]FREE EXTENDED WARRANTY ON NEW CIRCUIT BREAKERS[when 3C overheating protection is included with the order]Contact temperature monitoring function (optional)This function monitors the temperature of the ACBs main contacts. An alarm indicateswhen the temperature exceeds the withstand temperature of the contacts. Continuousmonitoring of the contact temperature provides valuable input for preventative andpredictive maintenance programmes.3C overheating protection is new and unique!It is only available from Terasaki for TemPower 2 ACBs and TemBreak 2 MCCBs.Terasaki Profile 5

FeaturesTERASAKI PROFILEMr. Taizo TerasakiPresident“We want to meet theneeds of more customersaround the world in ourcircuit breaker andlifecycle servicebusinesses.”Mr. Taizo Terasaki, PresidentMr. Yasuhiko TerasakiMr. Yasutaro TerasakiLate chairman of the companyFounder of the companyNUCLEAR POWER:Ringhals, SwedenDATA CENTRE:TelehouseLondon, UKOIL PRODUCTION:Sakhalin Island,RussiaSOLAR POWER:South ItalyALUMINIUMSMELTER:ALBA, BahrainAUTOMOTIVE:Toyota ManufacturingPlant, Argentina6 TemPower 2 Air Circuit BreakersDESALINATIONPLANT:SpainMARINE: Oil Tanker“Belokamenka”,RussiaMINING:BHP Billiton,Australia

PRODUCTS & SERVICESR&DAir Circuit BreakersWe are meeting the needs of customers with acomplete system of development, design andmanufacture based on the know-how we haveaccumulated with electrics, electronics and controlover the decades since our founding.Moulded CaseCircuit BreakersWe have DEKRA (formerly KEMA)-approved testsystems and two generators in house to carry outthe necessary development tests.Din Modular ProtectionTerasaki realises optimised products through 3DCAD, software development, mould and sheet metaldesign, structural design and resin flow analysis.ContactorsCAPABILITIESAutomatic TransferControllerSafety & ReliabilityHigh MTBF; Low MTTR; temperature monitoring,double control circuitsApprovalsMonitoring &CommunicationISO 9001; ISO 14001; OHSAS 18001; Lloyds; BV;GL; GOST; SABS;DEKRA (KEMA); ASTA; IEC 60947-2; IEC 61439;IEC 60898Asset ManagementRetrofits; Preventative Maintenance;Asset ManagementLifecycle ManagementSpecial Protection SolutionsDC; PV; UPS; 1000V AC; Integrated residualprotection; 100kA and aboveRetrofitTerasaki Profile 7

TemPower 2 Air Circuit Breakers5 Reasons to use TemPower 2 ACBsEfficient air convectionthrough a pressure valve1. Patented High Performance 5000A and 6300A ACBsThe air circuit breaker interrupts the current at two points on the lineside while dissipating heat from contacts or terminals by efficient airconvection through pressure valve.2. Double opening and closing coilsDouble Opening and Closing Coils provides extended control systemredundancy to an ACB. Double coils allow designers to implementback-up tripping and closing systems. It provides the end-user withultimate reliability on critical UPS circuits connected to critical loads.3. Fast interruption by unique “Double Break” system*The unique “DoubleBreak” main contact system ensures extremelyfast interruption of short circuit currents and substantially reducesmain contact wear. The internally symmetrical “DoubleBreak” structuremeans the moving contact is isolated from the supply voltage evenwhen the ACB is reverse connected. TemPower 2 ACBs up to 4000Ause DoubleBreak technology.pressure valveCUSTOMER ENDORSEMENT“The performance of Terasaki’s ACBs wasproven on site when a main busbar failed in oneof the switchrooms. The ACB was reclosed onthe short-circuit fault twice during fault diagnosisand is still in operation following a service byTerasaki.”Andy Oswald, BAA(Airport Operating Company, UK)4. Easy MaintenanceThe unique design of TemPower 2 incorporates its isolating clusters andmain contacts on the ACB body. The main contacts and isolating clustersmay be maintained without having to isolate the switchboard.5. Replacement of the main contacts*The fixed and moving contacts can easily be replaced in the field, thusprolonging the life on the circuit breaker. Changing each pole takesaround 15 minutes.*Not available on AR68 TemPower 2 Air Circuit BreakersHeathrow Airport Terminal 5

How to use the Catalogue for TemPower 2Understanding and employing TemPower 2 special features1Choosing a TemPower 2 ACB2Choosing accessories and protection relay3Installing the TemPower 2 ACB4Technical data5Useful related products and services6TemPower 2 Order FormPage 95-96Contents 9

10 TemPower 2 Air Circuit Breakers

Understanding and employingTemPower 2 special features1SECTIONProtection FeaturesPerformance FeaturesACB Accessory OverviewAppearance12-15161718Understanding and employing TemPower 2 special features 11

Protection Features1AGR-11BAGR-21BAGR-31BProtection FunctionsDial AdjustmentProtection FunctionsLCD AmmeterProtection FunctionsBack-Lit Energy AnalyserL – Long TimeS – Short TimeI – InstantaneousL – Long TimeS – Short TimeI – InstantaneousPre-Trip (load shedding)Fault Indication ContactsL – Long TimeS – Short TimeI – InstantaneousPre-Trip (load shedding)Fault Indication ContactsOptional Protection FunctionsOptional Protection FunctionsOptional Protection FunctionsUnrestricted Ground FaultNeutral ProtectionManual Reset(Optional - AGR-11BL-ASAGR-11BL-GS)Ground Fault (Unrestricted or Restricted)Neutral ProtectionCommunicationPhase Rotation ProtectionGenerator Protection CurvesIDMT Protection CurvesField TestNEWNon-Automatic (switch-disconnector) versions without protection are available in every frame size.12 TemPower 2 Air Circuit BreakersGround Fault (Unrestricted or Restricted)Neutral ProtectionReverse PowerZone Interlocking3C Overheating ProtectionCommunicationPhase Rotation ProtectionGenerator Protection CurvesIDMT Protection CurvesField TestUnder/over FrequencyUnder/over Voltage AlarmHarmonic MonitoringEvent historyDual settings capability

Protection FeaturesOverload ProtectionReverse power trip function (S-characteristic)Adjustable from 40-100% of rated current. Thermal memory isavailable on the AGR21B.31B.This feature provides additional protection when parallelinggenerators. The AGR22B/31B protection relay for generatorprotection with the reverse power trip function , negates the needfor installation and wiring in an external reverse power relay. Thisfeature is available using an AGR protection relay with a generator“S” type characteristic only. (ANSI-32R)Two channel pre-trip alarm function (optional)This function can be used to monitor critical circuits. Forexample, the function can be set so that when a pre-trip alarm isactivated, non-essential loads can be switched off. This featureis only available on AGR22B/31B protection relay models with agenerator “S” characteristic.Negative Sequence Current Protection FunctionIn 3-phase, 4 wire systems that contain harmonic distortion,large currents may flow through the neutral conductor. TheN-phase protection function prevents the neutral conductorfrom sustaining damage or burn-out due to these large currents.(ANSI-46).Ground fault trip functionThis function eliminates external relays to provide a ground faultprotection to TN-C or TN-S power distribution systems on theload side. Ground fault protection on the line side (restrictedearth fault) is also available as an option.Earth leakage trip functionUsed in conjunction with Zero phase Current Transformer (ZCT),this function provides protection against leakage to earth of verysmall levels of current. Trip or alarm indication, and contactoutput is available to enhance the level of system protection.Phase rotation protection functionThis function detects the negative-phase current occurring due toreverse phase or phase loss and prevents burnout of a motor ordamage to equipment.Advanced LCD display, Protection RelayThe AGR-31B protection relay comes standard with the backlitLCD display. It can monitor and indicate phase currents, voltages,power, energy, power factor, frequency and more. For featuresrefer to page 40. The backlit LCD is optional for AGR-21B andAGR-22B.Remote Communications Protocols (optional)Data communications via Modbus, an open network, aresupported.Energy MeasurementI, V, kW, MWh, kVar, cosø, frequency, harmonicsIntelligent Fault AnalysisStatus, fault type, fault size, tripping time, fault historyMaintenance InformationTrip circuit supervision, contact temperature monitoring.For details please refer to page 14.For other protocols please contact Terasaki.3C Overheating Protection (optional)This function monitors the temperature of the ACBs maincontacts. An alarm indicates when the temperature exceedsthe withstand temperature of the contacts. Continuousmonitoring of the contact temperature provides valuable inputfor preventative and predictive maintenance programmes. Thisoption can be used with communication.New Features (more details on page 3)Two independent INST thresholds for quick toggling of safe mode.Fine adjustment of overload current LTD threshold to the nearestAmpere.Harmonic current measurement.Under/over voltage protection (ANSI 27A/810) (optional).Under/over frequency protection (ANSI 81U/59A)(optional).Understanding and employing TemPower 2 special features 131

Protection FeaturesCommunications facility added to TemPower 21Data MeasurementPhase currentTemPower 2 is equipped with an optional communicationinterface unit that allows data exchange with a host PC viaa Modbus open network. Data communication includesmeasurements, fault log, maintenance information. ON/OFFstatus, settings and control (ON/OFF/RESET) signals.Fault logPhase current I1, I2, I3, IN, Ig and max currentImax are measured and transmitted.Harmonic currents.Line-to-line voltageV12, V23, and V31 are measured.Demand active powerActive power demand (over time) and historicalmax. power are recorded.Accumulated powerAccumulated power is measured.Power factorCircuit power factor is measured.FrequencyFrequency is measured.Note: Above is for type AGR-31 Protection relay.Type AGR-21 and AGR-22 measure only phase current.CauseWhichever trip functions, LTD, STD, INSTor GF is activated is then transmittedFault currentThe fault current at which the breakertripped open is transmitted.Network Interface I/O specificationsTrip pick-up timeThe trip pick-up time is transmitted.ItemModbusTransmission standardRS-485Transmission methodTwo-wire half-duplexTopologyMulti-drop busTransmission rate19.2 kbps maxTransmission distance1.2 km max (at 19.2 kbps)Data formatModbus-RTU or ASCIIMax number of nodes1 - 31Maintenance InformationTripping circuitmonitoringThe tripping coil is always monitored fordisconnection. If the breaker is not openwithin approx. 300 ms of a trip signaldelivered from the OCR, an alarm signalis generated.Communication networkOn-screen PC monitorPower MonitoringHost PCNext pageTR 3 ø750 kVA6600/460VFault cause protection relay statusLong time-delayShort time-delayInstantaneousGround faultFault currentAACB Tripping timesec.ACB No.1I1V12Power factorPowerElectric energyHost networkPrintON729 A455 V95 %546 kW1041 kWhCommercial gateway or PLCRS485ON320A418 KWhPower supply No. 1ON206A364 KWhPower supply No. 2ONOFFON180A235 KWh0A13 KWh23A11 KWhPower supply No. 3PumpConveyerModbusUp to 31 units can beconnected per system14 TemPower 2 Air Circuit Breakers

Protection FeaturesOptimum protective co-ordinationWhy use a separate panel mounted protection relay when youcan have all the benefits of I.D.M.T. protection integral to theACB?1TemPower 2 is available with a choice of flexible protectioncurves to assist in selectivity applications.S.I. Standard InverseV.I. Very InverseE.I. Extremely InverseAll these curves are user definable and comply with IEC 60255-3.Standard transformer and generator protection characteristics arealso available.AGR-L Industrial & transformer protectionAGR-S Generator protectionAGR-R Characteristics to IEC 60255-3Inverse Definite Minimum Time (I.D.M.T.)Zone interlockingIn conventional discrimination systems, short time delays are usedto allow a short-circuit current to be tripped by the circuit breakernearest the fault. The disadvantage of this type of system is duringa fault considerable thermal and mechanical stresses are placedon the entire system. With the TemPower 2 Z Interlock system thebreaker nearest the fault will trip first, irrespective of the short timedelay setting or ground fault trip time delay setting.Example of operation:ACB AACB BACB CUnderstanding and employing TemPower 2 special features 15

Performance FeaturesDouble opening and closing coils1Double Opening and Closing coils provides extendedcontrol system redundancy to an ACB. Double coils allowdesigners to implement back-up tripping and closingsystems. It provides the end user with ultimate reliabilityon critical UPS circuits connected to critical loads.Earthing DeviceThe unique design of TemPower 2 ACBs allows for theearthing of either the busbar (line) or the circuit (load) of alow voltage system; thus allowing system flexibility.Some other manufactures only offer one option either,busbar or circuit earthing.For full details refer to page 36.Protection Relay performanceExternalRelayEnsure that the ACB you specify suffers no loss ofperformance when tripped by an external protection relay.100kAThe TemPower 2 ACB suffers no loss in performancewhen tripped through an external protection relay.Some competitor’s ACBs have reduced breakingperformance when an external protection relay is used.16 TemPower 2 Air Circuit Breakers“TemPower 2 ACB”with internal or externalprotection relay.

ACB Accessory Overview1Position SwitchesInterpole BarriersShunt Trip CoilOpen / Close CounterIP55 Transparent CoverAuxiliary SwitchesCapacitor Shunt Trip 48V DCLifting PlatesIP3X Chassis Protection CoverIP31 Door FlangeDouble Opening/Closing CoilsFixing Bolts (For Draw Out ACBs)Trip Indicator SwitchSpring Status SwitchAuto SpringDischarge DeviceStorage Draw Out HandleMotor OperatorLifter LoaderProtection RelayCheckerOVERHEATINGPROTECTIONTropicalisation, Anti-Corrosion,Cold Climate treatmentsTest JumperStep DownTransformer440V to 220VMechanical Interlock,Key Interlock,Castell InterlockShutterTruckUnderstanding and employing TemPower 2 special features 17

TemPower 2 Air Circuit BreakersAPPEARANCE118 TemPower 2 Air Circuit Breakers

Choosing a TemPower 2 ACB2SECTIONRatingsSpecifications20-2122-23Choosing a TemPower 2 ACB 19

RatingsSeriesAMPERE RATING(A)TYPERATED CURRENT (max) [AR208SI n ](A)AR212SAR212HAR216SAR216HAR316HAR220SAR220HJIS , IEC, EN, ASNEMA, ANSIMarineNEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLESRATED PRIMARY CURRENT OF OVER–CURRENTRELEASE [ I CT ](A)InInInRATED CURRENT OF OVER–CURRENT RELEASE(A)[I n2AC RATED INSULATION VOLTAGERATED OPERATIONAL VOLTAGEInInInInInInInInIn[U i[U eJIS[I INKLR, AB,REVERSE CONNECTEDU](kV)CURRENT[ ITOTAL BREAKING TIME (s)CLOSING OPERATION TIMEOUTLINE DIMENSION (mm)FIXED TYPEbabbabaTYPEaAGR protection relays cannot be used for DC. Please contact TERASAKINote:20 TemPower 2 Air Circuit BreakersInInInInInInInInInInInIn1000 I n 2000InInInIn1000 I n 2000

AR440SAR650SAR440H1000 I n 2000 400 I n 800 1250 I n 2500 1250 I n 2500 1600 I n 3200 1600 I n 3200 2000 I n 4000 2000 I n 4000 2000 I n 40001000 I n 2000AR663SInAR663H2500 I n 50003150 I n oosing a TemPower 2 ACB 21

SpecificationsTemPower 2 series ACBs have an extensive range of accessories available, enabling the ACBs to be “custom built” to suitevery application.222 TemPower 2 Air Circuit Breakers

Specifications1TypesTypesMountingof ofMountingDraw-out typeFixed typeThis type of ACB consists of a breaker body and a draw-outcradle. The breaker body can be moved within or removed fromthe draw-out cradle that is fixed in the switchboard.This type of ACB has no draw-out cradle and is designed to bedirectly mounted in the switchboard.There are four breaker body positions: CONNECTED, TEST,ISOLATED and WITHDRAWN. The switchboard panel door canbe kept closed in the CONNECTED, TEST and ISOLATED positions(“shut-in three positions).Main Circuit terminalsCONNECTED positionTerminal arrangementsThree (3) types of main circuit terminal arrangements are available:vertical terminals, horizontal terminals and front connections.Different types of terminal arrangements can be specified for theline and load sides.Note: The max. rated current [In] may be reduced depending on the main circuitterminal arrangement. For more information see page 84.Both the main and control circuits are connected for normal service.TEST positionThe main circuit is isolated and the control circuits are connected.This position permits operation tests without the need for opening theswitchboard panel door.ISOLATED positionBoth the main and control circuits are isolated. The switchboard paneldoor does not need to be opened.WITHDRAWN positionControl circuit terminalsControl circuit terminals are front located to allow easy wiring/access.The breaker body is fully withdraw

generators. The AGR22B/31B protection relay for generator protection with the reverse power trip function , negates the need for installation and wiring in an external reverse power relay. This feature is available using an AGR protection relay with a generator “S” type characteristic