Product Submittal And Wiring IEEPBR

Transcription

Product Submittal and WiringIEEPBRTable of ContentsSection 1. E3 Point SystemSection 2. IEEPBR StationSection 3. Gas ValveSection 4. HO-CO testing canSection 5. TransformerSection 6. WiringPrepared By:Interstate HVAC Controls30 Vineland St, Brighton, MA 02135Office (617) 782-9000Fax (617) 254-2247www.interstatecontrols.com

1. E3 Point SystemE3Point SPECIFICATIONSToxic and Combustible Gas DetectorStandalone Platform (Single or Dual-Gas Monitoring)General SpecificationsUsesWall or duct-mounted gas detector for monitoring carbon monoxide (CO), nitrogen dioxide (NO2), oxygen (O2),methane (CH4), hydrogen (H2), hydrogen sulphide (H2S), and propane (C3H8), installed as a standalone device withsingle-gas or dual-gas monitoring. (Note: E3Point standalone version replaces Vulcain models VA201T,VA201M and VA301M)Size20.56 x 14.90 x 6.72cm (8.09 x 5.87 x 2.65”) (H x W x D); Remote Sensor: 3.5 x 4.5 x 6.5 cm (1.36 x 1.75 x 2.56”)Power Requirement24 Vac nominal (17-27Vac), 50/60 Hz, 0.35 A; 24Vdc nominal (20-38Vdc); with remote sensor: 7 W max.Optional Main AC Input120Vac nominal, /- 10% (with on-board transformer)Relay Output2 DPDT relays, 5A @ 250Vac; 5A @ 30VdcCommunications4-20mAOperating EnvironmentCommercial, Indoor, Extreme Temperature EnvironmentsOperating TemperatureH2S, NO2, O2, CH4, H2, C3H8: -40 to 50ºC (-40 to 122ºF)CO: -20 to 50ºC (-4 to 122ºF); future available CO version: -40 to 50ºC (-40 to 122ºF)Sensor TypeElectrochemical cell (CO, NO2, H2S, O2); catalytic (CH4, H2, C3H8,)Display8 character, 2 line backlit LCDVisual IndicatorsGreen LED: PowerAmber LED 1: Alarm/FaultAmber LED 2: Alarm/FaultAudible Alarm 85 dBA at 3 m (10 ft)Accuracy /- 3% of full scale @ 25 CDetection Ranges and Alarm LevelsGasResolutionRangeAlarm AAlarm BAlarm CCO (Carbon monoxide)1 ppm0-250 ppm25 ppm100 ppm225 ppmH2S (Hydrogen sulfide)0.1 ppm0-50 ppm10 ppm15 ppm20 ppmNO2 (Nitrogen dioxide)0.1 ppm0-10 ppm0.7 ppm2 ppm9 ppmO2 (Oxygen)0.1% vol.0-25% vol.19.5% vol.22% vol.22.5% vol.H2 (Hydrogen)0.5% LEL0-100% LEL25% LEL50% LEL90% LELCH4 (Methane)0.5% LEL0-100% LEL25% LEL50% LEL90% LELC3H8 (Propane)0.5% LEL0-100% LEL25% LEL50% LEL90% LELEnclosurePolycarbonateCertificationCSA C22.2 No. 61010-1, UL 61010-1; FCC part 15; ICES-003 issue 4; ISO 9001-2008

1. E3 Point SystemORDERING INFORMATIONSingle-Gas Configuration: Base Unit, Surface-Mount* Base unit and sensor cartridge sold together ** Base unit only; sensor cartridge sold separatelyPart NumberDescriptionE3SASCO*E3Point, CO sensor cartridge, Surface-mount, 24Vac/dc, -20 to 50ºC (-4 to 122ºF)E3SA**E3Point, Surface-mount, 4-20mA, 24Vac/dc, -40 to 50ºC (-40 to 122ºF)E3SAHSCO*E3Point, CO sensor cartridge, Surface-mount, 120Vac, -20 to 50ºC (-4 to 122ºF)E3SAH**E3Point, Surface-mount, 4-20mA, 120Vac, -40 to 50ºC (-40 to 122ºF)Dual-Gas Configuration: Base Unit w/Remote Sensor Capability, Surface-MountPart NumberDescriptionE3SARSCO*E3Point, CO sensor cartridge, Surface-mount, 24Vac/dc, Dual-mode, -20 to 50ºC (-4 to 122ºF)E3SAR**E3Point, Surface-mount, 4-20mA, 24Vac/dc, Dual-mode, -40 to 50ºC (-40 to 122ºF)E3SARHSCO*E3Point, CO sensor cartridge, Surface-mount, 120Vac, Dual-mode, -20 to 50ºC (-4 to 122ºF)E3SARH**E3Point, Surface-mount, 4-20mA, 120Vac, Dual-mode, -40 to 50ºC (-40 to 122ºF)Remote Sensors (always sold with sensor cartridge included)Part NumberDescriptionE3SRMCOE3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), Carbon MonoxideE3SRMNO2E3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), Nitrogen DioxideE3SRMH2SE3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), Hydrogen SulfideE3SRMH2E3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), HydrogenE3SRMO2E3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), OxygenE3SRMME3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), MethaneE3SRMPE3Point, Remote Sensor, -20 to 50ºC (-4 to 122ºF), PropaneStand-Alone Platform, Duct-MountPart NumberDescriptionE3DASCO*E3Point, CO, Duct-mount, 24Vac/dc, -20 to 50ºC (-4 to 122ºF)E3DA**E3Point, Duct-mount, 4-20mA, 24Vac/dc, -40 to 50ºC (-40 to 122ºF)Sensor CartridgesPart NumberDescriptionE3SCOCO Cartridge -20 to 50ºC (-4 to 122ºF), Carbon MonoxideE3NO2NO2 Cartridge -40 to 50ºC (-40 to 122ºF), Nitrogen DioxideE3H2SH2S Cartridge -40 to 50ºC (-40 to 122ºF), Hydrogen SulfideE3H2H2 Cartridge -40 to 50ºC (-40 to 122ºF), HydrogenE302O2 Cartridge -40 to 50ºC (-40 to 122ºF), OxygenE3MCH4 Cartridge -40 to 50ºC (-40 to 122ºF), MethaneE3PC3H8 Cartridge -40 to 50ºC (-40 to 122ºF), PropaneSensor cartridges need tobe replaced every 2.5 yearsEXAMPLES OF HOW TO ORDERTo order a stand-alone version, surface-mount, analog, CO detector, -20 to 50ºC (-4 to 122ºF): Order E3SASCOTo order a stand-alone version, surface-mount, analog, dual-gas CO NO2, -20 to 50ºC (-4 to 122ºF): Order E3SARSCO E3SRMNO2To order a stand-alone version, duct-mount, analog, propane detector, -40 to 50ºC (-40 to 122ºF): Order E3DA E3PTo order a stand-alone version, surface-mount, analog, dual-gas CO C3H8, 120Vac, -20 to 50ºC (-4 to 122ºF): Order E3SARHSCO E3SRMPSS01018STAND v4 6/11 2011 Honeywell Analytics

2. IEEPBR StationPushbutton & Enclosed Relay Package ForGas Detection Systems (Manual Reset)Part Number: IEEPBRKit Includes:(1) UL Listed Push Button(1) UL Listed Switching Relay(1) UL Listed 4" x 6" Enclosure(Some Assembly Required)RESETPushButton131431SwitchingRelay5424" x 6" Enclosure(Shown Actual Size)30 Vineland StreetBrighton, MA 02135T: 617-782-9000F: atecontrols.comIndicates Field Wiring

3. Gas Valve4Aluminum Body Solenoid Valves1/8" to 3" NPTFeatures% Lightweight, low-cost valves for air serviceSERIES80408215 # ) Ideal for low pressure applications Provides high flow, Cv up to 138 (Kv 118) Air and vacuum serviceConstructionValve Parts in Contact with FluidsAluminumBodySeals, Diaphragms, DiscNBRDisc-HolderPA (10.1 and 11.6 watt Normally Open only)Core GuideCACore Tube305 Stainless SteelRider RingsPTFECore and Plugnut430F Stainless SteelSprings*302 Stainless SteelShading CoilCopperNC* For 8040H006, 8040H007, 8040H008, spring material is 17-7 PHElectricalNOWatt Rating and PowerConsumptionStandardCoil andClass ofDCInsulation WattsFF11.6B14.9FF-Spare Coil Part No.ACGeneral Purpose ExplosionproofVAVAWatts Holding InrushACDCACDC6.1164023821023821410.12570238610 238710 238614 2387146269115.427160992579925728.250385 206409206409-Standard Voltages: 24, 120, 240, 480 volts AC, 60 Hz (or 110, 220 volts AC, 50 Hz),6, 12, 24, 120, 240 volts DC. Must be specified when ordering.Other voltages available when required.Solenoid EnclosuresStandard: RedHat II - Watertight, Types 1, 2, 3, 3S, 4, and 4X; RedHat - Type I.Optional: RedHat II - Explosionproof and Watertight, Types 3, 3S, 4, 4X, 6,6P, 7, and 9; RedHat - Explosionproof and Raintight, Types 3, 7, and 9.(Except EF8215A40 and EF8215A90, which are suitable for Types 3 and 7(C and D) only and have a T2B temperature rating code.)To order, add prefix “EF” to catalog number.See Optional Features Section for other available options.Nominal Ambient Temp. RangesACSeries80408215DCRedHat II/RedHat-40 F to 125 F(-40 C to 52 C)RedHat IIRedHat--32 F to 125 F(0 C to 52 C)32 F to 104 F(0 C to 40 C)32 F to 77 F(0 C to 25 C)(104 F/40 C occasionally)Refer to Engineering Section for details.8040Approvals:CSA certified to:8040 Series:1) Standard C22.2 No. 139 "Electrically OperatedValves," File 10381.2) Automatic Gas Valves Z21.21 (6.5), File 112872.3) Automatic Gas Safety Shutoff Valves C/I (3.9),File 112872.8215 Series Normally Closed:1) Standard C22.2 No. 139 "Electrically OperatedValves," File 10381.2) Automatic Gas Valves Z21.21 (6.5), File 112872.8215 Series Normally Open:1) Standard C22.2 No. 139 "Electrically OperatedValves," File 10381.UL listed, as indicated. FM approved (Normally Closedonly, except Catalog Numbers 8215A090 and 8215A040).RedHat II meets applicable CE directives.Refer to Engineering Section for details.72-WAY2/2Direct Acting or Piloted

3. Gas Valve2/22-WAYSERIES480408215Specifications (English units)Operating PressureDifferential sCapacityBtu/hr Min.Max. ACMax. DCMax.FluidTemp. FAir-FuelGasAir-FuelGasACDCCatalog NumberAluminum BodyWatt Rating/Class of CoilInsulation Const.Ref.ACDCUL ListingACDCNORMALLY CLOSED (Closed when de-energized)1/85/161.053,700015-125-8040H00611 6.1/F-1/45/161.159,000015-125-8040H00711 6.1/F-3/85/161.264,400015-125-8040H00811 6.1/F-3/83/43.4183,000050251251048215G0102 10.1/F11.6/F3/83/43.5-51251251251048215G001 1 6.1/F11.6/F1/23/45.4291,00002-125-8040G02213A 10.1/F-1/23/44.4238,500050251251048215G0202 10.1/F11.6/F1/23/44.8-51251251251048215G002 1 6.1/F11.6/F3/43/49.5512,00002-125-8040G02313B 10.1/F-3/43/45.1247,500050251251048215G0304 10.1/F11.6/F3/43/45.1-51251251251048215G003 6.1/F11.6/F11 5/8211,119,00002525125778215B050 616 15.4/F14.9/B1 1/41 5/8321,730,00002525125778215B060 616 15.4/F14.9/B1 1/21 5/8351,900,00002525125778215B070 616 15.4/F14.9/B22 3/32603,251,00002515125778215B080 717 15.4/F14.9/B2 1/231175,821,00005-125-8215A0908 28.2/F-331387,430,00005-125-8215A0408 28.2/F-9 10.1/F11.6/F11.6/F3NORMALLY OPEN (Open when 1/23/43/44206,25001251251251048215G0239 10.1/F3/44.6247,50001251251251048215G03310 10.1/F11.6/F11 5/8221,191,75002515125778215C0531218 15.4/F14.9/B1 1/41 5/8331,793,25002515125778215C0631218 15.4/F14.9/B1 1/21 5/8371,988,25002515125778215C0731319 15.4/F14.9/B22 3/32583,100,00002515125778215C0831420 15.4/F14.9/B2 1/231176,290,00005-125- 28.2/F-8215B093 Do not use for Fuel Gas. On 50 hertz service, the watt rating for the 6.1/F solenoid is 8.1 watts. FM Approved Process Control Valves. See Engineering Section (Approvals) for details.Type I enclosure only. Safety Shutoff Valve; General Purpose Valve. Refer to Engineering Section (Approvals) for details. 1" W.C. Drop @ 2" W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity Gas.815

3. Gas Valve480408215Specifications (Metric units)Operating PressureDifferential (bar)PipeSize(ins.)OrificeSize(mm)Kv FlowFactor(m3/h)GasCapacityBtu/hr Min.Max. ACMax. DCMax.FluidTemp. CAir-FuelGasAir-FuelGasACDCCatalog NumberAluminum BodyWatt Rating/Class of CoilInsulation Const.Ref.ACDCUL ListingACDCNORMALLY CLOSED (Closed when de-energized)1/87.9.8653,70001.0-52-8040H00611 6.1/F-1/47.9.9459,00001.0-52-8040H00711 6.1/F-3/87.91.0364,40001.0-52-8040H00811 6.1/F-3/8192.91183,00003.41.752408215G0102 10.1/F11.6/F3/8193.00-0.38.68.652408215G001 1 6.1/F11.6/F1/2194.63291,00000.1-52-8040G02213A 10.1/F-1/2193.77238,50003.41.752408215G0202 10.1/F11.6/F1/2194.11-0.38.68.652408215G002 1 6.1/F11.6/F3/4198.14449,00000.1-52-8040G02313B 10.1/F-3/4194.37247,50003.41.752408215G0304 10.1/F11.6/F3/4194.37-0.38.68.652408215G003 3 6.1/F11.6/F14118.001,119,00001.71.752258215B050 616 15.4/F14.9/B1 1/44127.431,730,00001.71.752258215B060 616 15.4/F14.9/B1 1/24130.001,900,00001.71.752258215B070 616 15.4/F14.9/B25351.433,251,00001.71.052258215B080 717 15.4/F14.9/B2 1/276100.285,821,00000.3-52-8215A0908 28.2/F-376118.287,430,00000.3-52-8215A0408 28.2/F-NORMALLY OPEN (Open when de-energized)3/8192.74172,50008.68.652408215G0139 10.1/F11.6/F1/2193.43206,25008.68.652408215G0239 10.1/F11.6/F3/4193.94247,50008.68.652408215G033 18 15.4/F14.9/B1 1/44128.281,793,25001.71.052258215C0631218 15.4/F14.9/B1 1/24131.711,988,25001.71.052258215C0731319 20 15.4/F14.9/B2 1/276100.286,290,00000.3-52- 28.2/F-8215B0931015 Do not use for Fuel Gas. On 50 hertz service, the watt rating for the 6.1/F solenoid is 8.1 watts. FM Approved Process Control Valves. See Engineering Section (Approvals) for details.Type 1 enclosure only. Safety Shutoff Valve; General Purpose Valve. Refer to Engineering Section (Approvals) for details. 1" W.C. Drop @ 2" W.C. Inlet Pressure, 1,000 Btu/cu.ft. or more, 0.64 Specific Gravity Gas.92-WAY2/2SERIES

3. Gas Valve2/22-WAYSERIES480408215Dimensions: inches (mm)Const. Ref. 1-4, 9, 10, 13A, 13BConst.Ref.12346 7 8 91011121313A13B14 15 160IMPORTANT: Valves may be mounted in any positionexcept all DC constructions and those marked , whichmust be mounted with the solenoid vertical and upright.Constructions marked must be mounted with thesolenoid vertical and upright or horizontal only.1/2 NPTPNPTBOTH ENDSLWFLOW1.66 [42]2 MOUNTING HOLESØ .28 [Ø 7.1]Const. Ref. 6, 7, 8, 16, 177/8 DIA HOLEFOR 1/2 CONDUITCONN.PHKNPTBOTH ENDSLWFLOWConst. Ref. 11W1/2 NPTP2 CORED HOLES.350 [8.9] DEEP FOR.164-32 TH’DFORMING SCREWKHNPTBOTH ENDS.60 [15].800 [20.3].406 [10.3]R .088 [R 2.2]4 PLACES.90 [23].250 [6.4].115 [2.9] 2 PLACES.750 [19.1]BOTTOM VIEW OF BODY.97 [25]LFLOWConst. Ref. 12-15, 18-20LØ .88 [Ø 22]HOLE FOR1/2 CONDUITCONN.PHNPTBOTH ns.mmins.mmins.mmins.mmins.mmins.mmins.mmW

4. HO-COCoCheck HSI products are Environmentally Friendly. Our CoCheck , Carbon Monoxide Detector Tester doesnot have HFC or CFC. Our products do not damage the Ozone layer and do not contribute to GlobalWarming.CoCheck , Carbon Monoxide Detector Tester complies with both the Kyoto and Montreal Protocolsand the California state requirements.CoCheck is 100% All Natural and Non-Flammable This product contains material found in the air webreathe. Designed and packaged in a size that prevents any accidents. There is not enough CO in theproduct to produce any ill effects. It is safe, effective and it works! The perfect solution.The Original Carbon Monoxide Detector Tester Since 1997CoCheck has been updated and reformulated to an easy to use aerosol product. CoCheck has beenused by professionals world-wide since 1997. This is the original and still the best option for test yourcarbon monoxide detector.CoCheck Carbon Monoxide Detector Tester.876 oz Size, 5-10 tests per canPart Number: HO-CO2Standard Pack: 6 cases/Master Pack 22x13x10 (558.8x330.2x254mm)Weight: 14 lbs.MSDS Sheet

4. HO-COCO Detector Test Gas Accessory For use with UL Certified FTAM Gas Detectors and/or Sensors 3WH9. For compatibility between CODetector Test Kit and the Detector refer to E328172 Listing Card for Details.The facts of Carbon Monoxide TestingHow a Carbon Monoxide Detector works; Carbon Monoxide is found in small concentrations in the air webreath. The detector is constantly testing the surrounding air for the presence of CO, when concentrationsbegin to rise and reach a set/predefined level, the alarm will sound, warning of a dangerous condition inthe area. CO becomes dangerous in higher concentrations. After exhaustive testing, HSI determined thatthe key to functional CO testing is the length of exposure time and the level of concentration. CoCheck , when used with Versa-Tools Enclosed Delivery Tools, provides an isolation of the COchemical (concentration level) without using dangerous amounts. The convenient fiberglass extensionpole allows you to place the enclosed head around the detector, brace with the pole and walk away. Nostanding there and holding the tools for extended periods of time!

5. TransformerFunctional Devices, Inc. r Q r G r XXX GVODUJPOBMEFWJDFT DPN r TBMFT!GVODUJPOBMEFWJDFT DPNTR50VA005TransformerTransformer 50 VA, 120 to 24 Vac, Circuit Breaker, Foot and Single Threaded Hub Mount1.26"BlkYel/WhtPRIMARY WIRES120V 60HzSECONDARY WIRES24Vac 50VAWhtYel2.00"Class 2Secondary Yel/Wht wire in phase with Primary Blk wire.1.950"Mounting Hole .350" x .175"2.525"3.000"3.475"9.00".50"SpecificationsVA Rating:Frequency:Mounting:Over Current Protection:Dimensions:Wire Length:Operating 0/60 HzFoot & Single Threaded HubCircuit Breaker3.000 x 2.525 x 3.475 (w/ .500 NPT Hub)9 Typical w/ .5 Strip-30 to 140 F100,000 Hours @ 77 FSplit-Bobbin2.60 lbs.Class 2 UL5085-3 Listed, C-UL, CE, RoHS

6. WiringDrawing courtesy of Interstate Hvac ControlsSuggested wiring diagrams for commercial kitchensOption 1-Manual rest gas valve with fan proving systemOption 2-Dual CO detectors with manual reset with NON manual reset gas valve, as long as manual resetdoes not reset when the CO clears the detectors. For instance if the CO detector senses CO it shuts off the electricalpower to the rest of the system, tripping the manual reset. If the CO clears and the control panel is reactivated thepower remains OFF until someone manually resets the system.Control Panel &CO DetectorCO DetectorNOCNCRelay switches when unit is powered.Relay returns to de-energized on: powerloss, sensor alarm/failure, or circuit failureManual ResetTransformerL1120/60AC24/60L2Gas valveInterstate HVAC Controls - Supplying Controls and Solutions since 1945www.InterstateControls.comT) 617-782-9000 F) 617-254-2247

E3Point SPECIFICATIONS Toxic and Combustible Gas Detector Standalone Platform (Single or Dual-Gas Monitoring) General Specifications Uses W all or duct-mounted gas detector for monitoring carbon monoxide (CO), nitrogen dioxide (NO 2), oxygen (O 2), methane (CH 4), hydrogen (H 2), hydrogen sulphide (H 2S), an