300 BROOKSIDE AVENUEBUILDING 18, SUITE 150AMBLER YARDSAMBLER, PA 19002T: 215.646.2003www.gkoarchitects.comShop Drawing/ Submittal ReviewProject Name:Villa Joseph Marie High SchoolGKO Project #:2339Auditorium AdditionSubmittal For:23 74 35 No Exceptions Taken Furnish As Corrected Revise and Resubmit Rejected/ ResubmitReviewed By:1750-01 Aaon RTUsJason Mulligan, GKODate Submitted: 2/22/18Corrections or comments made during this review does notrelieve the Contractor from compliance with requirements ofthe drawings and specifications. This check is only for reviewof general conformance with the design concept of the projectand general compliance with the information given in thecontract documents. The contractor is responsible for;confirming and correlating all quantities and dimensions;selecting fabrication processes and techniques of construction;coordination of his work with that of all other trades; andperforming his work in a safe and satisfactory manner.Date Returned:3/20/18Comments:GODSHALL KANE O’ROURKE ARCHITECTS, LLCKEVIN R. GODSHALL, AIA · DAMON ROYAL KANE, AIA EMERITAS · P. MICHAEL O’ROURKE, AIA
Submittal Review Cover SheetProject Name: Villa Joseph Marie High School - Auditorium AdditionClient: GKO ArchitectsSubmittal #: 23 74 35 - 1Submittal Name: Rooftop AC UnitsReviewed By: Gene HoffmanDate: 03.12.2018 No Exceptions Taken Revise & Resubmit Rejected/Resubmit Furnish as Corrected Furnish as Corrected and ResubmitEngineer’s Review Comments:Corrections or comments made on the shop drawings during this review do not relieve contractor from compliance withrequirements of the drawings and specifications. This check is only for review of general conformance with the designconcept of the project and general compliance with the information given in the contract documents. The contractor isresponsible for: confirming and correlating all quantities and dimensions; selecting fabrication processes and techniquesof construction; coordinating his work with that of all other trades; and performing his work in a safe and satisfactorymanner.
311 County Line Road, Suite 31, Gilbertsville, PA 19525SUBMITTAL COVER SHEETProject:Villa Joseph Marie High SchoolAuditoriumNBRI Project No:Owner:1750XVilla Joseph Marie High School1180 Holland Road3-12-2018GAHHolland, PA 18966General Contractor: Twining Construction Company1801 2nd St. PikeRichboro, PA 18954Manufacturer:Subcontractor / Supplier:AaonH.C. Nye Company, Inc.2999 Revere StreetHarrisburg, PA 17111Specification Section:237435 Rooftop Air Conditioning UnitsCONTRACTORʹS REVIEWAPPROVED:XAPPROVED AS NOTED:BY:Date:Justin RogersNo.Project ManagerDate:2/19/2018NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Units
H.C. Nye Company, Inc.Environmental Solutions2999 Revere Street; Harrisburg, PA 17111(717) 561-2500; Fax: (717) 561-2577SUBMITTAL DATADATE:February 7, 2018JOB NAME:Villa Joseph Marie HS – Auditorium AdditionCONTRACTOR:NB Rogers, Inc.EQUIPMENT:Packaged Rooftop UnitsMANUFACTURER:Aaon, Inc.SALESMAN:Tim WenrichSUBMITTAL NOTES:(Tag: RTU-1 thru 6)NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Units1
H.C. Nye Company, Inc.NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsEnvironmental Solutions2999 Revere Street; Harrisburg, PA 17111(717) 561-2500; Fax: (717) 561-2577Submittal Notes:(6) Aaon Packaged Rooftop Units(Tag: RTU-1 thru 6)To Include the following:- 2” Double Wall Construction w/R13 Spray Foam Insulation- RTU-1, 2, 3 shall have horizontal supply and bottom return without use of a plenum curb- RTU-4, 5, 6 shall have bottom supply and return- Voltage 460v-3ph-60hz- Single Point Power Connection- R410A Refrigerant- Copeland digital scroll compressors, capable of modulating to 10% of rated capacity- Fully modulating economizer with enthalpy control- Factory installed power exhaust fans with VFD's- Modulating Hot Gas Reheat Coil - factory installed- Stainless steel natural gas fired heat exchanger with modulating control valve (except RTU-6)- Factory installed hot water heating coil - RTU-6 only- 2" Pleated pre-filter - 30% Eff with 4" thick - 85% efficient filters- 115v Convenience Outlet (Factory Wired)- Supply Fan w/VFD- Non-fused Disconnect Switch- Phase and brown out protection- Stainless Steel Drain Pan- Factory Installed DDC Controller with required sensors- Terminal block for connection to field supplied smoke detectors- 1-Year Unit Parts Only Warranty (Labor Not Included)- 5-Year Compressor Parts Only Warranty (Labor Not Included)- 25-year non-pro rated warranty on the SS heat exchanger - parts only- Factory authorized start up- 18" high roof curb with duct kits with 1" spring isolation rails, curb installed on flat roof***ITEMS NOT INCLUDED***- Rigging, hauling, installation- Air Flow Stations- Smoke detectors- Labor warranty- Seismic ratings for roof curb* Factory start up requires a minimum of 3 weeks notice prior to schedule.*Pre-start up checklists must be submitted with request to schedule a date.2
Unit Rating9D9B9C9A876D6B6C6A5D5B5C5A4B4C4A3D3B3C2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)3A21NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Tag: RTU #1, 2(Values do not account for changes described in SPA)Job InformationUnit Information**WEIGHT AND PERFORMANCE DO NOT INCLUDE SPAJob Name:Job Number:Site Altitude:RefrigerantVilla Joseph MarieJob #142380 ftR-410AApprox. Op./Ship Weights:Supply CFM/ESP:Pre-Filter FV / Qty:Coil Filter FV / Qty:Exhaust CFM/ESP/TSP:Outside CFM:Ambient Temperature:Return Temperature:3606 / 3606 lbs. ( 5%)5000 / 1 in. wg.240.00 fpm / 6240.00 fpm / 65000 / 0.50 / 0.75 in. wg.170092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB1.00 in. wg.0.15 in wg0.21 in wg0.35 in. wg.Economizer:Heating:Cabinet:Re-Heat Coil:Total:0.09 in wg0.20 in wg0.08 in. wg.0.03 in wg2.11 in wgStatic PressureExternal:Evaporator:Coil Filters Clean:Dirt AllowanceCooling SectionHeating SectionTotal Capacity:Sensible Capacity:Latent Capacity:Mixed Air Temp:Entering Air Temp:Lv Air Temp (Coil):Lv Air Temp (Unit)Digital Comp. Capacity Ratio:Supply Air Fan:SA Fan RPM / Width:Exhaust Air Fan:EA Fan RPM / Width:GrossNet188.93180.89 MBH139.41131.37 MBH49.52 MBH80.78 ºF DB66.44 ºF WB80.78 ºF DB66.44 ºF WB54.40 ºF DB53.44 ºF WB55.87 ºF DB54.04 ºF WB100%1 x 270 @ 2.83 BHP993 / 4.965"1 x RM220A @ 1.38 BHP1197 / 4.920"Evaporator Coil:Evaporator Face Velocity:19.9 ft² / 3 Rows / 14 FPI251.7 fpmPreHeat Type:Std (No Preheat)Heating Type:Heating CFM:Total Capacity:OA Temp:RA Temp:Entering Air Temp:Leaving Air Temp:Input:Heater Qty:Consumption:Total Turndown Ratio:Nat. Gas Heat5000218.7 MBH0.0 ºF DB / -1.0 ºF WB75.0 ºF DB / 62.0 ºF WB49.5 ºF DB / 46.6 ºF WB90.0 ºF DB / 62.9 ºF WB270.0 MBH1270.0 MBH3:1Re-Heat Coil:Capacity:LA DB / WB:RH:84 MBH70.00 ºF / 59.53 ºF54%Minimum Circuit Amp:Maximum Overcurrent:4050Rating InformationListing Model: RN-016-3-H-BAAY-V0-21-000-ACooling Capacity (MBH):Cooling EER:Cooling IEER:Rated in accordance with AHRI 340/360184.011.813.8Application EER @ Op. Conditions:10.7Electrical DataRating:Unit FLA:Compressor 1:Compressor 2:Condenser Fans:Supply Fan:Exhaust RLA12.612.2Cabinet Sound Power Levels*Octave Bands:Discharge LW(dB):6383Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)400076800072Date Printed: 2/7/2018 11:06:56 AM
Unit RatingReturn LW(dB):8584817271706559*Sound power levels are given for informational purposes only. The sound levels are not guaranteed.NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsDate Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Date Printed: 2/7/2018 11:06:56 AM
NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsJOB INFORMATION:27.0" STAR Plenum2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)WHEEL SPECIFICATION:Job Name:Job Tag:Rep Firm:Date:Villa Joseph MarieRTU #1, 2Max RPM:Diameter x Qty:Width%:Tip Speed:Inertia:02/07/2018OPERATING CONDITIONS:Air Flow:Static Pressure:Plenum DP:Inlet Grill DP:TSP:Site Altitude:TSP @ Sea Level:1,80027.4 in. x 1817,123 FPM16 WR²MOTOR SELECTION:5,000 CFM2.11 in. Wg.0.00 in. Wg.0.00 in. Wg.2.11 in. Wg.0.00 Ft2.11 in. Wg.Rated HP / Bypass:Frame Size:Nominal RPM:VAC/PH/HZ:EfficiencyEnclosure Type:Max Inertial Load:FAN PERFORMANCE:5 / No215T1170460V/3Ø/60HzPremium / 0.895ODP117 WR²FAN SOUND POWER (Inlet/Outlet):RPM:BHP:Efficiency:In/Out Velocity:Plenum Out Velocity:9932.8358.7%1305/1366 FPM83 FPMMax Duct SP with Blocked Airway:Octave Band:(Re 10 -12 watts)12345677978767476767581818584828380SOUND POWER A-Weighted: 83 / 88 dB874762.3 in. Wg. @ 993 rpmSupply Fan Model: 270 @ 993 RPM and 81% WidthDesign Conditions: 5000 CFM @ 2.11" SPRPMBHPSYSTEMEfficiencySP SurgeCFM Min7RPM: 9932640%5EFFICIENCY: 58.67SP1BHP4320%2BHP: 2.83100%123456708CFM x 1000Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Date Printed: 2/7/2018 11:06:56 AM
NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsJOB INFORMATION:Job Name:Job Tag:Rep Firm:Date:2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)WHEEL SPECIFICATION:Villa Joseph MarieRTU #1, 2Max RPM:Diameter x Qty:CFM:Tip Speed:Inertia:02/07/2018OPERATING CONDITIONS:2,20022.0 in. x 150006,894 FPM5 WR²MOTOR SELECTION:Air Flow:Static Pressure:Relief Dampers DP:5,000 CFM0.50 in. Wg.0.25 in. Wg.TSP:Site Altitude:TSP @ Sea Level:0.75 in. Wg.0.00 Ft0.75 in. Wg.Rated HP / Bypass:Frame Size:Nominal RPM:VAC/PH/HZ:EfficiencyEnclosure Type:Max Inertial Load:FAN PERFORMANCE:RPM:BHP:Efficiency:In/Out Velocity:Plenum Out Velocity:22.0" STAR Plenum2 / No145T1760460V/3Ø/60HzPremium / 0.865ODP27 WR²FAN SOUND POWER (Inlet/Outlet):11971.3843.0%1529/1684 FPM83 FPMOctave Band:(Re 10 -12 watts)12345678585858074726785858580747267SOUND POWER A-Weighted: 85 / 85 dBExhaust Fan Model: RM220A @ 1197 RPM and 100% WidthDesign Conditions: 5000 CFM @ 0.75" SP86161RPMBHPSYSTEMEfficiencySP SurgeCFM Min560%24RPM: 1197EFFICIENCY: 43.0340%3SPBHP1220%BHP: 1.381012340%50CFM x 1000Date Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Date Printed: 2/7/2018 11:06:56 AM
Unit 5 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)3A21NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsTag: RTU #1, 2Job Name:Job illa Joseph MarieJob #14238Unit Submittal For:Unit Submittal Date:Base OptionDescriptionGenerationRN SeriesMajor RevisionMajor Revision AUnit SizeSixteenSeriesC SeriesMinor RevisionMinor Revision 0Voltage460V/3Ø/60HzCompressor StyleR-410A Variable Capacity Scroll CompressorCondenser StyleMicrochannel Air-Cooled CondenserIndoor Coil ConfigurationStandard EvaporatorCooling Heat Exchanger ConstructionStandardCooling Staging1 Variable Capacity Comp 1 On/Off CompHeat TypeNatural GasHeat ConstructionStainless Steel Heat ExchangerHeat Designation270 MBHHeat StagingModulating Gas Heat - Temperature ControlHeat Pump Auxiliary HeatingNo Heat PumpFeature OptionDescription1. Unit OrientationStandard Access - Hinged Access Doors with Lockable Handles2. Supply & Return LocationsHorizontal Configuration - End Supply--End Return3A. Supply Fan Configuration1 Fan Factory Installed VFD3B. Supply Fan Size27" Direct Drive Backward Curved Plenum - 100% Width Aluminum3C. Supply Fan Motor TypeHigh Efficiency Motor (1,200 nominal rpm)3D. Supply Fan Motor Size5 hp4A. Outside Air SectionEconomizer Power Exhaust4B. Energy Recovery TypeNo Energy Recovery4C. Energy Recovery SizeNo Energy Recovery5A. Return Fan ConfigurationStandard5B. Return Fan SizeStandard5C. Return Fan Motor TypeStandard5D. Return Fan Motor SizeStandard6A. Exhaust Fan Configuration1 Fan Factory Installed VFD6B. Exhaust Fan Size22" Backward Curved Plenum Fan - 100% Width Aluminum6C. Exhaust Fan Motor TypeHigh Efficiency Motor (1,800 nominal rpm)6D. Exhaust Fan Motor Size2 hp7. Outside Air ControlReturn and Exhaust Air8. 0XFebruary 07, 2018CO2 Override Fully Mod. Act. - Enthalpy LimitStandard Barometric Relief EA Dampers9A. Unit Filter Type2" Pleated MERV 8 4" Pleated MERV 139B. Unit Filter Size & LocationHigh Efficiency Filters in Standard Position9C. Final Filter TypeNo Final Filters9D. Filter OptionsNoneDate Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Date Printed: 2/7/2018 11:06:56 AM
Unit 5 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)3A21NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsTag: RTU #1, 2Job Name:Job 2221201918B18C18A17BUnit Submittal For:Unit Submittal Date:February 07, 2018Description10A. Refrigeration Control ANone10B. BlankStandard11A. Refrigeration Options AModulating Hot Gas Reheat11B. BlankStandard12. Refrigeration Accessories17A16D16B16C16A151413B13CVilla Joseph MarieJob #14238Feature XNone13A. Unit Disconnect TypeSingle Point Power - Non-fused Disconnect Power Switch13B. Disconnect 1 Size100 Amps13C. BlankStandard14. Safety OptionsRemote Safety Shutdown Terminals15. Electrical AccessoriesPhase & Brown Out Protection16A. Control SequenceSingle Zone VAV Unit Controller - VAV Cool CAV Heat16B. Control SupplierWattMaster VCC-X16C. Control Supplier OptionsNone16D. BMS Connection & Diagnostics BACnet MSTP17A. Preheat ConfigurationStandard - None17B. Preheat SizingStandard - None18A. Option Box LocationNone18B. Option Box SizeNone18C. Option Box AccessoriesNone19. Outside Air AccessoriesOutside Air Hood20. Cabinet OptionsBase Insulation21. BlankStandard22. Maintenance AccessoriesFactory Wired 115V Convenience Outlet23. Code OptionsStandard - ETL U.S.A. Listing24. Shipping SplitsAir-Cooled Condenser25. AccessoriesStandard26. BlankWater-Cooled Condenser27. AccessoriesStandard28. Energy Recovery AccessoriesNone29. VFD OptionsStandard30. Miscellaneous OptionsStandard31. BlankStandard32. BlankStandard33. BlankStandard34. BlankStandard35. WarrantyStandard Warranty36. Cabinet MaterialGalvanized Cabinet - Double Wall R-13 Foam Insulation37. Specials & PaintSPA Premium AAON Gray Paint Exterior PaintVFD Condenser Fan Head Pressure ControlNoneDate Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Date Printed: 2/7/2018 11:06:57 AM
VCCX 25 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)3A21NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsTag: RTU #1, 2Job Name:Job Number:Villa Joseph MarieJob #14238VCCX For:VCCX February 07, 2018Hardware Included For VCCX ControllerPart luded PartsVCCX CONTROLLEROSA Temp/Hum SensorSpace Digital Temp/Hum SensorSupply Temp Sensor - Field InstalledDuct Mount C02Building Pressure SensorSupply Fan Control Signal 0-10VDCEconomizerBuilding Pressure Control SignalProof of Air FlowSafety Shut DownSupply FanExhaust FanDIGITAL REFRIGERATION MODULEComp Discharge Temp AComp Discharge Temp BSuction Pressure Sensor BSuction Pressure Sensor ADischarge Pressure Sensor ADischarge Pressure Sensor BModulated Condenser Signal BModulated Condenser Signal AComp Status Input AComp Status Input BEmergency ShutdownCondenser Enable ABComp Enable AComp Enable BCondenser Enable BMODULATING HOT GAS REHEAT MODULEReheat HGR ValveMODULATING GAS MODULEModGas Gas Valve SignalModGas High Speed EnableModGas Low Speed EnableDate Created/Modified: 2/7/2018 11:06:46 AM Using Ver 5.0.266.1 (OSN# 0123456)Assigned ChannelEBUS2 communicating sensorEBUS3 communicating sensorVCCX control point AI 3EBUS4 communicating sensorVCCX control point AI 5VCCX control point AO 1VCCX control point AO 2VCCX control point AO 4VCCX control point BI 1VCCX control point BI 8Configured Relay pointConfigured Relay PointRSMD point TEMP1RSMD point TEMP2RSMD point AI3RSMD point AI1RSMD point HP-1RSMD point HP-2RSMD point AO2RSMD point AO1RSMD point BIN1RSMD point BIN2RSMD point BIN4RSMD Fixed Relay pointRSMD Fixed Relay pointRSMD Fixed Relay pointRSMD Fixed Relay pointBACnet DGAS-XAI:43Date Printed: 2/7/2018 11:06:57 AM
NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top UnitsSPECIAL RN SERIESC- CABINET HORIZONTAL AIR COOLEDECONOMIZER WITH POWER EXHAUST ANDBOTTOM RETURNTOP VIEWCLEARANCESLOCATIONOUTSIDE AIR(BACK)SUPPLY AIR(FRONT)LEFT SIDERIGHT SIDETOP20*6660UNOBSTRUCTED*CLEARANCE IS MEASURED FROMTHE END OF THE OUTSIDE AIRRAIN HOODDETAIL ADETAIL BRIGHT SIDE VIEWFRONT VIEWBACK VIEW
NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Units919 LBS.946 LBS.C OF G862 LBS.838 LBS.AREV138.162MATERIAL:N/ATOLERANCES DWG BY:kce-acTOTAL WEIGHT 3565 LBS.FRAC.: /- 1/32 48 INCHES /- 1/16 48 INCHESCKD BY:2425 S. YUKONBYECN NUMBERDATEAAON INC.TULSA, OKLAHOMAcatalog corner weight villa joseph marie 16t rncDEC. /- 0.03 48 INCHES /- 0.06 48 INCHESANG.APPD BY: /- 1 UNLESSOTHERWISESPECIFIEDSQUARE FT. :N/ADATE01/16/18DRAWING NUMBERDT002868-001SHEET 1 / 1REVA
RN SERIESC- CABINET KNOCKDOWN CURB HORIZONTALAIR COOLEDNB ROGERS, INCSUBMITTAL 1708-003 16 - 30 TONSPEC SECTION 237435Packaged Roof-top UnitsTOP VIEWRIGHT SIDE VIEW
NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Units
Unit Rating9D9B9C9A876D6B6C6A5D5B5C5A4B4C4A3D3B3C2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.266 (SN: 5728272-)3A21NB ROGERS, INCSUBMITTAL 1708-003SPEC SECTION 237435Packaged Roof-top Tag: RTU #3(Values do not account for changes described in SPA)Job InformationUnit Information**WEIGHT AND PERFORMANCE DO NOT INCLUDE SPAJob Name:Job Number:Site Altitude:RefrigerantVilla Joseph MarieJob #142380 ftR-410AApprox. Op./Ship Weights:Supply CFM/ESP:Pre-Filter FV / Qty:Coil Filter FV / Qty:Exhaust CFM/ESP/TSP:Outside CFM:Ambient Temperature:Return Temperature:3608 / 3608 lbs. ( 5%)4000 / 1 in. wg.192.00 fpm / 6192.00 fpm / 64000 / 0.50 / 0.70 in. wg.110092 ºF DB / 74 ºF WB75 ºF DB / 62 ºF WB1.00 in. wg.0.24 in wg0.15 in wg0.35 in. wg.Economizer:Heating:Cabinet:Re-Heat Coil:Total:0.07 in wg0.14 in wg0.05
Aaon H.C. Nye Company, Inc. 2999 Revere Street Harrisburg, PA 17111 237435 Rooftop Air Conditioning Units APPROVED: X APPROVED AS NOTED: BY: Date: Justin Rogers No. Project Manager Date: 2/19/2018 311 County Line Road, Suite 31, Gilbertsville, PA 19525 Project: Specification