Worldwidewww.tyco-fire.comContactsSeries DS-1 Dry-Type Sprinklers5.6K Pendent, Upright, and Horizontal SidewallQuick Response, Standard CoverageGeneralDescriptionTYCO Series DS-1 Dry-Type Sprinklers,5.6K Pendent, Upright, and HorizontalSidewall, Quick Response (3 mm bulb)and Standard Coverage are decorative glass bulb automatic sprinklersde signed for commercial use. Dry-typesprinklers are typically used where: pendent sprinklers are re quiredon dry pipe systems that areexposed to freezing temperaturesfor example, sprinkler drops fromunheated portions of buildings sprinklers and/or a portion of theconnecting piping are exposed tofreezing temperatures; for example,sprinkler drops from wet sys temsinto freezers, sprinkler sprigs fromwet systems into unheated attics, orhorizontal piping extensions througha wall to protect an unheated areassuch as loading docks, overhangs,and building exteriorsauthorities having jurisdiction. Failureto do so may impair the performanceof these de vices.The owner is responsible for maintain ing their fire protection system andde vices in proper operating condi tion. Contact the installing contrac tor or product manufacturer with anyquestions.The Series DS-1 Dry-Type Sprinklersmust only be installed in fittings thatmeet the requirements of the DesignCriteria section.SprinklerIdentificationNumbers (SINs)3/4 in. NPT:TY3935 – PendentTY3735 – Horizontal Sidewall1 in. NPT:TY3235 – PendentTY3135 – UprightTY3335 – Horizontal Sidewall sprinklers are used on systems thatare seasonally drained to avoidfreezing for example, vacation areasTechnicalDataNOTICEThe Series DS-1 Dry-Type Sprinklersdescribed herein must be installedand maintained in compliance with thisdocument, as well as with the applica ble standards of the NATIONAL FIREPROTECTION ASSOCIATION (NFPA),in addition to the standards of anyApprovalsIMPORTANTRefer to Technical Data SheetTFP2300 for warnings pertaining toregulatory and health information.Always refer to Technical DataSheet TFP700 for the “INSTALLERWARNING” that provides cautionswith respect to handling and installation of sprinkler systems and components. Improper handling andinstallation can permanently damagea sprinkler system or its components and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.Page 1 of 10UL and C-UL ListedFM ApprovedNYC Approved under MEA 352-01-ETemperature RatingsPrevious New York City Approval andMEA certification numbers apply toproduct as shown in this data sheet.In accordance with Section BC 3502of the Construction Code, current NYCApprovals for use in the City of NewYork apply to all products that containUL or FM Approvals and Listings;therefore, not all products currentlyApproved for use in the City of NewYork will carry an actual MEA Certification number.See Tables A and B.Sprinkler: Natural Brass, Chrome Plated,or Signal WhiteMaximum Working Pressure175 psi (12,1 bar)Inlet Thread Connections3/4 in. NPT1 in. NPT or ISO 7-R 1Discharge CoefficientSee Tables A and BFinishesEscutcheon: Signal White, Chrome Plated,or Brass PlatedPhysical CharacteristicsInlet CopperPlug CopperYoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless SteelCasing. . . . . . . . . . . . . . Galvanized Carbon SteelInsert BronzeBulb Seat Stainless SteelBulb GlassCompression Screw BronzeDeflector BronzeFrame BronzeGuide Tube Stainless SteelWater Tube Stainless SteelSpring. . . . . . . . . . . . . . . . . . . . . . Stainless SteelPlug Spring* Stainless SteelSealing Assembly. . Beryllium Nickel w/TEFLONEscutcheon. . . . Carbon Steel or Stainless Steel* For 3/4 in. NPT onlyK 5.6 gpm/psi½ (80,6 lpm/bar½)NOVEMBER 2019TFP510

TFP510Page 2 of 10PLUG BEGUIDETUBEFRAMEYOKESPRINGCASINGINSERTBULBSEAT3 mm BULBVENT HOLEDEFLECTORCOMPRESSIONSCREWFIGURE 1SERIES DS-1, 3/4 IN. NPT, DRY-TYPE SPRINKLERASSEMBLYPLUG BEFRAMEVENT HOLEDEFLECTORINLETBANDCASINGINSERTBULBSEAT3 mm BULBCOMPRESSIONSCREWFIGURE 2SERIES DS-1, 1 IN. NPT AND ISO 7-R 1 DRY-TYPE SPRINKLERASSEMBLYOperationWhen the TYCO Series DS-1 Dry-TypeSprinklers, 5.6K Pendent, Upright, andHorizontal Sidewall, Quick Response(3 mm bulb) and Standard Coverageare in service, water is prevented fromentering the assembly by the Plug withSealing Assembly in the Inlet of theSprinkler. See Figures 1 and 2.The glass bulb contains a fluid thatexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatterthe glass Bulb, and the Bulb Seat isreleased.The compressed Spring is then ableto expand and push the Water Tube aswell as the Guide Tube outward. Thisaction simultaneously pulls inward onthe Yoke, withdrawing the Plug withSealing Assembly from the Inlet andallowing the sprin kler to activate andflow water.DesignCriteriaThe TYCO Series DS-1 Dry-Type Sprinklers, 5.6K Pendent, Upright, and Horizontal Sidewall, Quick Response(3 mm bulb) and Standard Coverage are intended for use in fire sprinkler systems designed in accordancewith the standard installation rulesrecognized by the applicable Listingor Approval agency; for example,UL Listing is based on NFPA 13requirements.Sprinkler FittingsInstall the 3/4 or 1 in. NPT SeriesDS-1 Dry-Type Sprinklers in the 3/4or 1 in. NPT outlet or run of the following fittings: malleable or ductile iron threadedtee fittings that meet the dimensional requirements of ANSI B16.3(Class 150) cast iron threaded tee fittings thatmeet the dimensional requirementsof ANSI B16.4 (Class 125)Do not install the DS-1 Sprinklersinto an elbow fittings. The Inlet of thesprinkler can contact the interior of theelbow, potentially damaging the Inletseal.The unused outlet of the threaded tee isplugged as shown in Figure 13.You can also install the Series DS-1Dry-Type Sprinklers in the 3/4 or 1 in.NPT outlet of a GRINNELL Figure 730Mechanical Tee. However, the use ofthe Figure 730 Tee for this arrangementis limited to wet pipe systems.

TFP510Page 3 of 103/4 in. NPTTY3935 PendentTY3935 Pendentwith Deep Escutcheon(Figure 5)TY3735 Horizontal Sidewallwith Top of Deflector-to-CeilingDistance of 4 to 12 in.(100 to 300 mm)with Standard Escutcheon(Figure 8)with Recessed Escutcheon(Figure 4)with Standard Escutcheon(Figure 3)without Escutcheon(Figure 6)with Deep Escutcheon(Figure 9)without Escutcheon(Figure 10)TemperatureRatingBulbColor Code135 F (57 C)155 F (68 C)175 F (79 C)200 F (93 C)286 F (141 PlatedWhitePolyesterNaturalBrassChromePlated1, 2WhitePolyesterNaturalBrass1, 2ChromePlatedWhitePolyester1*, 2*Notes:1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 in.)2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 in.)* Light and Ordinary Hazard occupancies onlyTABLE A3/4 IN. NPT SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERSLABORATORY LISTINGS AND APPROVALS1 in. NPT (and ISO 7-R 1)TemperatureRatingBulbColor Code135 F (57 C)155 F (68 C)175 F (79 C)200 F (93 C)286 F (141 C)OrangeRedYellowGreenBlueTY3235 PendentTY3235 Pendentwith Recessed Escutcheon(Figure 4)with Standard Escutcheon(Figure 3)with Deep Escutcheon(Figure 5)without Escutcheon(Figure 6)TY3135 Uprightwithout Escutcheon5(Figure 7)TY3335 Horizontal Sidewallwith Top of Deflector-to-CeilingDistance of 4 to 12 in.(100 to 300 mm)with Standard Escutcheon(Figure 8)with Deep Escutcheon(Figure 9)without Escutcheon(Figure 10)FinishNaturalBrassChromePlated1, 2, 3, 4WhitePolyesterNaturalBrass1, 2, 4ChromePlated1, 2, 3, 4WhitePolyester1, 2, 4NaturalBrassChromePlated1*, 2*, 3**, 4WhitePolyester1*, 2*, 41, 2, 4Notes:1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 in.)2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 in.)3. Approved by Factory Mutual Research Corporation (maximum order length of 48 in.)4. Approved by the City of New York under MEA 352-01-E5. The Upright Sprinkler without an Escutcheon (TY3135) is available in 1 in. NPT only* Light and Ordinary Hazard occupancies only** Light Hazard occupancies onlyTABLE B1 IN. NPT (AND ISO 7-R 1) SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERSLABORATORY LISTINGS AND APPROVALS

TFP510Page 4 of 10SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FACE OFSPRINKLERFITTINGFACE OFSPRINKLERFITTINGORDER LENGTHS:2-3/4" to 48"(69,9 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTSSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)ORDER LENGTHS:3-3/4" to 48"(95,3 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTS1-3/4" DIA.(44,5 mm)FACE OFSPRINKLERFITTINGORDER LENGTHS:1/2" to 46"(12,7 to 1168,4 mm)IN 1/4" (6,4 mm)INCREMENTS2-1/4" DIA.(57,2 mm)FACE OFCEILINGFACE OFCEILING3-1/2" DIA.(88,9 mm)2-1/2" DIA.(63,5 mm)FACE OFCEILING4-1/4" 1/8"(108,0 3,2 mm)2-3/16" 1/8"(55,6 3,2 mm)3" DIA.(76,2 mm)1-3/8" 1/8"(34,9 3,2 mm)FIGURE 3PENDENT TY3235 AND TY3935WITH STANDARDESCUTCHEON2-7/8" DIA.(73,0 mm)FIGURE 4PENDENT TY3235 AND TY3935WITH RECESSEDESCUTCHEONSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FIGURE 5PENDENT TY3235 AND TY3935WITH DEEPESCUTCHEONTOP OFDEFLECTORFACE OFSPRINKLERFITTINGORDER LENGTHS:5" to 48"(127,0 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTSMINIMUM1-3/4" (44,5 mm)DEFLECTORTO CEILINGFIGURE 6PENDENT TY3235 AND TY3935WITHOUTESCUTCHEONORDER LENGTHS:5" to 48"(127,0 to 1219,2 mm)IN 1/4" (6,4 mm)INCREMENTSFACE OFSPRINKLERFITTINGSPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)FIGURE 7UPRIGHT TY3135WITHOUT ESCUTCHEON1 IN. NPT ONLY

TFP510Page 5 of 10ORDER LENGTHS:2-3/4" to 48" (69,9 to 1219,2 mm)IN 1/4" (6,4 mm) INCREMENTSFACE OFSPRINKLERFITTINGThe configuration shown in Figure 12is only applicable for wet pipe systemswhere the sprinkler fitting and waterfilled pipe above the sprinkler fitting arenot subject to freezing and where thelength of the Dry-Type Sprinkler has theminimum exposure length depicted inFigure 11. See the Exposure Lengthsection.2-3/8" 1/8"(60,3 3,2 mm)FACE OFMOUNTINGSURFACE3" DIA.(76,2 mm)3.5 SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)1-3/4" DIA.(44,5 mm)CENTERLINEOF WATERWAY 1 in. x 1 in. NPT Female Adapter(P/N 80145)5/16"(7,9 mm) 1 in. x 1 in. x 1 in. NPT SprinklerHead Adapter Tee (P/N 80249)FIGURE 8TY3335 AND TY3735 HORIZONAL SIDEWALLWITH STANDARD ESCUTCHEONORDER LENGTHS:1/2" to 45-3/4" (12,7 to 1162,1 mm)IN 1/4" (6,4 mm) INCREMENTS2-1/2" DIA.FACE OF(63,5 mm)SPRINKLERFITTINGFACE OFMOUNTINGSURFACEFor wet pipe system installations of thethe 3/4 in. NPT Series DS-1 Sprinklersconnected to CPVC piping, use in the3/4 in. x 3/4 in. NPT Female Adapter(P/N 80142).4-1/4" 1/8"(108,0 3,2 mm)3-1/2" DIA.(88,9 mm)3.5 SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)CENTERLINEOF WATERWAY5/16"(7,9 mm)FACE OFSPRINKLERFITTINGMINIMUM2-1/4" (57,2 mm)DEFLECTOR TOMOUNTINGSURFACE3.5 SPRINKLER FITTING(REFER TO DESIGNCRITERIA SECTION)CENTERLINEOF WATERWAYFIGURE 10TY3335 AND TY3735 HORIZONAL SIDEWALLWITHOUT ESCUTCHEONFor dry pipe system installations, useonly the side outlet of maximum 2 1/2 in.reducing tee when locating the SeriesDS-1 Sprinklers directly below thebranch line. Otherwise, use the configuration shown in Figure 13 to assurecomplete water drainage from abovethe Series DS-1 Dry-Type Sprinklersand the branch line. Failure to do somay result in pipe freezing and waterdamage.NOTICEDo not install the Series DS-1 Dry-TypeSprinkler into any other type fitting.Failure to use the appropriate fittingmay result in one of the following:FIGURE 9TY3335 AND TY3735 HORIZONAL SIDEWALLWITH DEEP ESCUTCHEONORDER LENGTHS:5-1/2" to 48" (139,7 to 1219,2 mm)IN 1/4" (6,4 mm) INCREMENTSFor wet pipe system installations of the1 in. NPT Series DS-1 Dry-Type Sprinklers connected to CPVC piping, useonly the following TYCO CPVC fittings:5/16"(7,9 mm) failure of the sprinkler to operateproperly due to formation of iceover the inlet Plug or binding of theInlet Plug insufficient engagement of theInlet pipe threads with consequentleakageDrainageIn accordance with the minimumrequirements of the NATIONAL FIREPROTECTION ASSOCIATION for drypipe sprinkler systems, branch, cross,and feed-main piping connected to DrySprinklers and subject to freezing temperatures must be pitched for properdrainage.Exposure LengthWhen using Dry Sprinklers in wet pipesprinkler systems to protect areassubject to freezing temperatures, use

TFP510Page 6 of 10TO WETSYSTEMFACE OFSPRINKLERFITTINGHEATEDAREADSB-2INTENDEDFOR FREEZERSTRUCTURESEXPOSURELENGTH(SEE DESIGNCRITERIASECTION)HEATEDAREADSB-2INTENDEDFOR FREEZERSTRUCTURESSTRAP TIES(ENDS ONOPPOSINGSIDES OFBOOT)DSB-2 BOOTADHESIVE1-3/4" DIA.(44,5 mm)CLEARANCEHOLEADHESIVESPRINKLERFITTING(SEE DESIGNCRITERIASECTION)DS-1SHOWN WITHSTANDARDESCUTCHEONFIGURE 14MODEL DSB-2 SPRINKLERBOOT WITH PENDENT SERIESDS-1 DRY SPRINKLERAREASUBJECTTOFREEZINGDSB-2INTENDEDFOR FREEZERSTRUCTURESFIGURE 13SPRINKLER FITTINGUNHEATED 1-3/4" DIA.(44,5 FITTING(SEE DESIGNCRITERIASECTION)TO DRYSYSTEMFIGURE 12SPRINKLER FITTINGHEATED AREAFIGURE RENCHFLATSTRAP TIES(ENDS ONOPPOSINGSIDES OFBOOT)DS-1SHOWN WITHSTANDARDESCUTCHEONFIGURE 15MODEL DSB-2 SPRINKLERBOOT WITH SIDEWALL SERIESDS-1 DRY SPRINKLERPUSH WRENCHIN TO ENSUREENGAGEMENTWITH SPRINKLERWRENCHING AREAFIGURE 16W-TYPE 7SPRINKLERWRENCH

TFP510Page 7 of 10T

286 F (141 C) Blue Notes: 1. Listed by Underwriters Laboratories, Inc. (maximum order length of 48 in.) 2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 in.) * Light and Ordinary Hazard occupancies only TABLE A 3/4 IN. NPT SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS TABLE B 1 IN. NPT (AND ISO 7-R 1 .