PIR switch sensorCatalogue Number(s): 0 488 04CONTENTSPage1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12. Technical characteristics . . . . . . . . . . . . . . . .13. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46. Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58. Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69. Performance . . . . . . . . . . . . . . . . . . . . . . . . . . 710. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 811. Standards and approvals . . . . . . . . . . . . . . . 812. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 81. USE2. TECHNICAL CHARACTERISTICS (continued)This device allows a light source to be controlled automatically throughthe detection of movement in the surveillance zone.It is equipped with a "presence" output for ventilation or lightingcontrol. This output is separate from the level of light.Motion sensor with 360 detection angle.Detection type: infrared (PIR)Mounting type: ceilingCover removedLight level cellLEARN button2. TECHNICAL CHARACTERISTICS2230 V 2000 W1000 VA8.5 A110 V 1000 W3410x(2x36 W)500 VASensor/PIRsensor67500 VA4.3 A5x(2x36 W)GreendetectionindicatorProtective cover54.3 AIR transmission LED(for configurationtool)LEARN LEDGreenprogrammingindicatorVoltage: 100 - 240 V Frequency: 50/60 HzNo-load power consumption: 0.8 WOutput via normally open contact connected to the phaseWiring: 2 x 2.5 mm2Drilling diameter: 85 mm without flush-mounting box85 mm with flush-mounting boxWeight: 114 gImpact resistance: IK04Penetration by solid and liquid matter: IP20Usage temperature: - 5 C to 45 CStorage temperature: - 20 C to 70 C1IR receiver LED(for configurationtool or remotecontrol)1000 VA2.1 A250 VA89 500 VA4.3 A500 VA2.1 A I max. 2A250 VA1 - Halogen bulb 2 - ELV halogen bulb with separate electronic ballast3 - ELV halogen bulb with separate ferromagnetic ballast4 - Fluorescent tube with separate ferromagnetic ballast5 - ELV fluorescent tube with separate electronic ballast6 - Compact fluorescent bulb with built-in electronic ballast7 - Compact fluorescent bulb with separate ferromagnetic ballast8 - Compact fluorescent bulb with separate electronic ballast9 - LED bulb230 V 2000 W110 V 1000 WU 30 V 10 - Contactor8.5 AI max. 2A2 A max.11 - MotorTechnical data sheet: S000074404EN-1Updated:Created: 18/01/20131/8

PIR switch sensorCatalogue Number(s): 0 488 043. DIMENSIONS4. CONNECTIONWithout protective cover66Number of terminals: 6Type of terminals: automaticTerminal capacity: 2 x 2.5 mm2Stripping length: 8 mm724.1 Wiring with auxiliary control: 62230 VAC1102AØ:1058.5 AWith protective cover71L1PB73100 m max.U 30V 1052AØ:8.5 AL1Ext. supply DCWiringTechnical data sheet: S000074404EN-1CONTENTSUpdated:Created: 18/01/20132/8

PIR switch sensorCatalogue Number(s): 0 488 044. CONNECTION (continued)4.2 Wiring for a single load connected in parallel2AS1S2SN8.5 ALPB100 m4.3 Wiring for several loads connected in parallelS1S28.5 A8.5 AL12ASN8.5 AL2LNPB100 mTechnical data sheet: S000074404EN-1CONTENTSUpdated:Created: 18/01/20133/8

PIR switch sensorCatalogue Number(s): 0 488 045. INSTALLATION5. INSTALLATION (continued)505.1 Sensor positioningØ 851Ø 850.3 to20 mm15.2 Recommended light exposure222.5 m4m36. REMOVALTechnical data sheet: S000074404EN-1CONTENTSUpdated:Created: 18/01/20134/8

PIR switch sensorCatalogue Number(s): 0 488 047. OPERATION7. OPERATION (continued)Manual ON/Automatic OFF modePressing the auxiliary control allows the load to be switched on or offmanually. If the control is not pressed, the sensor will cut off the loadat the end of the time delay or when the light level threshold has beenreached.6.1 Several sensors connected to a single loadS1 OFFL OFFAuto ON/OFF mode:The load will be switched on and off automatically.S1 ON7.1 More than one sensor and more than one loadThe products can be synchronised in two steps:L ON- one long press ( 1s) - all the sensors (S) change to ON- one short press - all the sensors (S) invert their state from OFF to ONand ON to OFFS1 OFFL2 OFFS2 OFFLn OFFL2 ONS2 ONLn ONSn ONLn OFFL1 ONL2 OFFLn OFFL1 ONL2 OFFLn OFFS1 ONPB 1sS1 ONL2 ONS2 ONLn ONSn ON 1sSn OFFPB 1s 1sS2 OFFS2 OFFL2 OFFS2 OFFS1 ONL ONLn ONSn ONL1 OFFS1 OFFL2 OFFS2 OFFPB 1sSn OFFL OFFS1 OFFPB 1sS2 OFFL ONL ONS2 OFFS2 ONSn ONPBS2 OFFS1 ONS2 OFFSn OFFS1 OFF 1s 1sL OFFSn OFFS1 OFFS2 ON 1sSn OFFL ONS2 ONS1 OFFPBSn ONSn OFFL2 ONLn OFFSn OFFS1 ONS1 OFFL1 OFFPBS2 OFFS1 ONL1 OFFLn OFFTechnical data sheet: S000074404EN-1CONTENTSL1 ONL ONSn ONS2 ONS1 ONS1 ONL2 OFF 1sSn OFFL1 ONL1 ONPB 1sS2 OFFSn OFFOption: It is possible to control the sensor by infrared remote controlusing Cat. Nos. 0 882 00/01/20/31/32/33.L1 OFFS1 ONPBS2 OFFSn OFFS1 ONPB 1sL ONSn OFFS2 ONSn ONSn OFFL1 ONS1 ONL2 ONS2 ONLn ONSn ONUpdated:Created: 18/01/20135/8

PIR switch sensorCatalogue Number(s): 0 488 048. SETTINGS8. SETTINGS (continued)8.1 Detection parametersSensor parameterDefaultvalue8.2 Light nsor parameterDefaultvalueModifiableparameters500 lux20, 100, 300, 500,1000 lux0 882 30 0 882 35SensitivityModesAuto on/Auto offWalk-throughmodeDetectionsystemManual on/Auto off15 min0 - 59 min 59 s Light level thresholdPIRLow, medium,(very high) high, very ifiable MaintainPIRNon-modifiable RestartPIRPIR, Deactivate Activate/Deactivate Alarm0 882 30 0 882 35 AdvancedmodeTime delay3, 5, 10, 15, 20 minInactive Time delay: Length of time the load is on after detection.Calibration 0 - 1275 lux 0 - 99995 lux onAutoAuto - 1275 lux Light level threshold: Value at which the load comes on if thenatural light level is less than the setting. Eye function: Value 0 (eye on configuration tool 0 882 30) isused to save the ambient light level in the room as the light levelthreshold.Advanced mode: Calibration: The ambient light level measured with a luxmetermust then be transmitted to the sensor.Sensitivity: Detection range setting. Regulation: Automatic switch-off of the load 10 minutes after thelight level threshold is exceeded with an additional safety threshold(to avoid lights switching off at the wrong moment).Modes:Auto on/Auto off mode:Automatic switch-on:- On detection of presence if there is insufficient natural light.Automatic switch-off:- If no presence is detected and at the end of the set time delay.- Or if there is sufficient natural light (regulation activated)Another detection causes automatic switch-on if there is insufficientlight.ConfigurationtoolsLight contribution: Quantity of additional lux provided by the loadbeing switched on.When the light contribution parameter is set to "Auto" (value 0) on theconfiguration tool Cat. No. 0 882 30, the sensor automatically calculatesthe light contribution.8.3 Modifying the parameters using the configuration toolsWalk-through mode:- If no presence is detected in the 20 seconds following an initialdetection, the product will cut off the load after 3 minutes.- If another presence is detected in the 3 minutes following initialdetection, the device will cut off the load at the end of the set timedelay.Manual on/Auto off mode:Manual switch-on, automatic switch-off:- When no presence is detected and at the end of the set time delay.After switch-off, any new detection within a 30 second period triggersan automatic switch-on. The Restart function must be activated.After 30 seconds the device is switched on via a manual switch.Detection system:Initial detection: The load is switched on as soon as the first detectionoccurs if the natural light level is below the light level threshold.Maintain: The load remains active if another presence is detected.Restart: In manual mode. After switch-off, any new detection within a30 second period triggers an automatic switch-on.After 30 seconds the device must be switched on manually.Possible in Manual on/Auto off mode only.Alarm: An audible signal is emitted before switch-off (1 minute before,then 30 seconds, then 10 seconds).Technical data sheet: S000074404EN-1CONTENTS 0 882 35: Simplified configuration tool 0 882 30: Advanced configuration toolWhen the sensor receives an IR command via a configuration tool,it emits a beep confirming that the modification has been taken intoaccount.For more information about setting parameters, refer to the data sheetfor the configuration tool Cat. No. 0 882 30.- Restore to factory settings:1st press: Short press on LEARN: the LED flashes slowly.2nd press: P ress and hold down LEARN for 10 seconds until theLED flashes quickly.Updated:Created: 18/01/20136/8

PIR switch sensorCatalogue Number(s): 0 488 049. PERFORMANCE9. PERFORMANCE (continued)9.1 Walk-through9.2 PresenceHeightHeight1.2 mm:421012m:4Height (m)Ø (m)6.58.512.5128.5SensitivityVery high(100%)Ø (m)811.51416.512.5Technical data sheet: S000074404EN-1CONTENTSHeight (m)SensitivityMedium (50%)Ø (m)66.57.510.55.52.53456SensitivityLow (25%)Ø (m)2.53.5442.5SensitivityHigh (75%)Height (m)Height (m)SensitivityLow (25%)Ø (m)45.56.564SensitivityHigh 53456Ø (m)4587.55SensitivityMedium (50%)Ø (m)4456.53.5SensitivityVery high(100%)Ø (m)579108Created: 18/01/20137/8

PIR switch sensorCatalogue Number(s): 0 488 0410. CARE11. STANDARDSKeep the lens clean.Clean the surface with a cloth.Do not use acetone, tar-removing cleaning agents or trichloroethylene.Resistant to the following products: - Hexane (EN 60669-1)- Methylated spirit- Soapy water- Diluted ammonia- Bleach diluted to 10%- Window-cleaning productsDirective: CEInstallation standards: NFC 15-100Product standards: IEC 60669-2-1Environmental standards:- European Directive 2002/96/EC:WEEE (Waste Electrical and Electronic Equipment)- European Directive 2002/95/EC:RoHS (Restriction of Hazardous Substances)Note:- Decrees and/or regulations: Public buildingsWorkplace buildingsHigh-rise buildingsAlways test before using other special cleaning products.12. TROUBLESHOOTINGPROBLEMLighting stays on when there is no-one presentCAUSESSources of interference, such as draughts,vibration or radiators, may cause nuisancetrippingSOLUTIONS1- R educe the sensitivity level2- I f the interference continues: using theconfiguration tool, go into the Detectionsystem parameters, select Maintain and thenchoose PIR and US3- I f the interference still continues, movethe sensor away from the source(s) ofinterferenceLighting does not switch off during the daywhen there is an adequate level of natural lightRegulation function not activeActivate the regulation functionLight level threshold set too highReduce the light level thresholdLight contribution too highCheck that the sensor is positioned correctly inrelation to the windowDecrease the power of the luminairesLighting switches off when there are peoplepresent and the natural light level is notadequate (darkness)Time delay too shortIncrease the time delayDetection sensitivity too low10 to 1 minutes is recommended for workareasLight level threshold too lowIncrease the sensitivityMove the sensor closer to the work areaIncrease the thresholdTechnical data sheet: S000074404EN-1CONTENTSUpdated:Created: 18/01/20138/8

PIR switch sensor Catalogue Number(s): 0 488 04 1. USE This device allows a light source to be controlled automatically through the detection of movement in the surveillance zone. It is equipped with a "presence" output for ventilation or lighting control. This output is separate from the level of light. Motion sensor with 360 detection angle.