EVALUATION REPORT Entegra Roof Tile, LLC Evaluation Report E39310.11.11 .

Transcription

EXTERIOR RESEARCH & DESIGN, LLC.Certificate of Authorization #9503353 CHRISTIAN STREET, UNIT #13OXFORD, CT 06478(203) 262-9245EVALUATION REPORTEntegra Roof Tile, LLCth1289 NE 9 AvenueOkeechobee, FL 34972(602) 515-6933Evaluation Report E39310.11.11-1-R4FL7804-R10Date of Issuance: 11/02/2011Revision 4: 10/17/2017SCOPE:This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use ofconstruction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. Theproducts described herein have been evaluated for compliance with the 6th Edition (2017) Florida Building Code(HVHZ) sections noted herein.DESCRIPTION: Entegra Concrete Roof Tiles (HVHZ jurisdictions)LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency notedherein.CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, thereferenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if theproduct changes or the referenced Quality Assurance documentation changes. Trinity ERD requires a completereview of this Evaluation Report relative to updated Code requirements with each Code Cycle.ADVERTISEMENT: The Evaluation Report number preceded by the words “Trinity ERD Evaluated” may be displayed inadvertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer orits distributors and shall be available for inspection at the job site at the request of the Building Official.This Evaluation Report consists of pages 1 through 8.Prepared by:Robert J.M. Nieminen, P.E.Florida Registration No. 59166, Florida DCA ANE1983The facsimile seal appearing was authorized by Robert Nieminen,P.E. on 10/17/2017. This does not serve as an electronically signeddocument. Signed, sealed hardcopies have been transmitted to theProduct Approval Administrator and to the named clientCERTIFICATION OF INDEPENDENCE:1. Trinity ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing ordistributing products it evaluates.2. Trinity ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products forwhich the evaluation reports are being issued.4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of theproduct.5. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for anyproject on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retainedspecifically for that purpose.

ROOFING SYSTEM EVALUATION:1.SCOPE:Product Category:RoofingSub-Category:Roofing TilesCompliance Statement: Entegra Concrete Roof Tiles, as produced by Entegra Roof Tile, LLC, have demonstratedcompliance with the following sections of the Florida Building Code through testing in accordance with the followingStandards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set 3.6.5.2.3Physical PropertiesWind Driven RainStatic Uplift ResistanceStatic Uplift ResistanceStatic Uplift ResistanceTAS 112TAS 100TAS 101TAS 102TAS ceDateERD (TST6049)ATL (TST3782)ATL (TST3782)ATL (TST3782)ATL (TST3782)ATL (TST 3782)ATL (TST 3782)ATL (TST 3782)ATL (TST 3782)ATL (TST 3782)Miami-Dade (CER1592)Miami-Dade (CER1592)Miami-Dade (CER1592)Miami-Dade (CER1592)Miami-Dade (CER1592)Tile Roof InstitutePRI (QUA9110)TAS 101Physical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesPhysical PropertiesHVHZ ComplianceHVHZ ComplianceHVHZ ComplianceHVHZ ComplianceHVHZ ComplianceTAS 100, TAS 101, 102, 102(A)Quality 6-0112.0616-0112.0716-0112.08Membership ConfirmationService 1602/25/2016CurrentExp. 11/02/2018REFERENCES:Exterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 2 of 8

4.PRODUCT DESCRIPTION:4.1TAS 112, Type 3a (flat-profile)BERMUDA FLAT, PLANTATION FLAT and HORIZON FLATBermuda FlatPlantation FlatHorizon FlatExterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 3 of 8

4.2TAS 112, Type 1a (interlocking, high-profile)BELLA HIGH “S”Bella High “S”4.3TAS 112, Type 1b (interlocking, low-profile)ESTATE “S” and HACIENDAEstate “S”4.3HaciendaTAS 112, Type 2a (non-interlocking, high-profile)GALENA SPANISH “S” and REGALGalena Spanish “S”RegalExterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 4 of 8

5.LIMITATIONS:6.5.1This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, theDesigner of Record for any project on which this Evaluation Report, or previous versions thereof, is/was usedfor permitting or design guidance unless retained specifically for that purpose.5.2This Evaluation Report is for use in FBC HVHZ jurisdictions or others adopting FBC HVHZ requirements.5.3Fire classification is not part of this evaluation; refer to FBC 1516 or listing by an approved testing agency forfire rating of this product.5.4Reference is made to FBC 1512.4.2.4 regarding field testing of completed tile roof installations.5.5Applicant shall retain the services of an FBC listed, accredited laboratory to perform quarterly tests inaccordance with TAS 112, Appendix ‘A’.5.6Minimum underlayment shall comply with the RAS 118, RAS 119 or RAS 120, as applicable. Underlaymentproducts shall hold current Florida Statewide Product Approval or Local Approval for use in tile roofassemblies in FBC HVHZ jurisdictions.5.7Minimum roof deck requirements shall be in accordance with applicable FBC HVHZ requirements.5.8All products in the roof assembly shall have quality assurance audit in accordance with the F.A.C. Rule61G20-3.INSTALLATION:6.1Entegra Concrete Roof Tiles may be mechanically fastened, mortar-set or adhesive-set. Installation shallcomply with manufacturer’s current published instructions, but not less than the requirements of RAS 118,RAS 119 or RAS 120, as applicable.6.2Attachment Calculations: Entegra Concrete Roof Tile shall be evaluated as a ‘Moment-Based System’ inaccordance with Roofing Application Standard RAS 127-11 using the data outlined herein.TABLE 1: AERODYNAMIC MULTIPLIERS – (FT )3TileBatten ermuda FlatPlantation FlatHorizon FlatBella High “S”Estate “S”HaciendaGalena Spanish “S”RegalDirect-Deck 1TABLE 2: RESTORING MOMENT DUE TO GRAVITY – MG (FT-LBF)Roof Slope ( )2:12 3:123:12 4:124:12 DirectBattensDirectBattensDirectBermuda 83Plantation .897.55Bella High 06.13Estate .395.416.22Galena Spanish 61Tile5:12 6:12Exterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof Tiles6:12 7:12 7:12Evaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 5 of 8

TABLE 3A: ATTACHMENT RESISTANCE EXPRESSED AS A MOMENT – MF (FT-LBF)MECHANICALLY ATTACHED SYSTEMSFastenerTileBermuda Flat,Plantation Flat orHorizonTypeShankClip(min. 19/32”plywood)Battens4.9One (1)10dSmooth or ScrewN/A7.39.8NailTwo (2)10dSmooth or ScrewN/A14.018.87.4NailOne (1)10dSmooth or ScrewEave19.019.022.1NailOne (1)10dSmooth or ScrewField24.324.324.2NailTwo (2)10dSmooth or ScrewEave31.931.932.2NailTwo (2)10dSmooth or ScrewField35.535.534.8NailTwo (2)10dRingN/A30.938.117.2N/A50.3165.5148.31NailTwo (2)ScrewScrew111110dRingOne (1)#8N/AN/A30.830.818.2Two (2)#8N/AN/A51.751.724.4Installation with a 4-inch tile headlap and fasteners located min. 2½-inch from head of tile.NailOne (1) 210dSmooth or ScrewN/A8.8 211.8 24.1 2NailTwo (2)10dSmooth or ScrewN/A16.421.97.1One (1)2NailOne (1)2NailNailNailBella High “S”, GalenaSpanish “S” or RegalSizeDirect-Deck(min. 15/32”plywood)Nail1Estate “S” or Hacienda#Direct-Deck10dSmooth or ScrewEave19.02219.0222.1 224.3224.2 210dSmooth or ScrewField24.3Two (2)10dSmooth or ScrewEave31.931.932.2Two (2)10dSmooth or ScrewField35.535.534.8NailTwo (2)10dRingN/A27.837.428.8Nail1Two (2) 110d1Ring1N/A43.0167.5150.91ScrewOne (1) 2#8N/AN/A25.8 225.8 222.9 2ScrewTwo (2)#8N/AN/A47.147.149.11Installation with a 4-inch tile headlap and fasteners located min. 2½-inch from head of tile.2For one (1) fastener installations, utilize hole that is approximately 4¾-inch from the interlocking edge.NailOne (1)10dSmooth or ScrewN/A5.16.82.8NailTwo (2)10dSmooth or ScrewN/A6.99.27.3NailOne (1)10dSmooth or ScrewField23.123.119.0NailOne (1)10dSmooth or ScrewEave29.329.324.0NailTwo (2)10dSmooth or ScrewField27.627.638.6NailTwo (2)10dSmooth or ScrewEave38.138.141.8NailTwo (2)10dRingN/A28.641.219.4Nail1Two (2) 110d1Ring1N/A33.1148.1150.91ScrewOne (1)#8N/AN/A20.720.718.1ScrewTwo (2)#8N/AN/A43.243.229.81Installation with a 4-inch tile headlap and fasteners located min. 2½-inch from head of tile.Exterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 6 of 8

TABLE 4: ATTACHMENT RESISTANCE EXPRESSED AS A MOMENT – MF (FT-LBF)MORTAR AND ADHESIVE-SET SYSTEMSNote from Entegra Roof Tile, LLC.: The performance data listed in Table 4 are based on the respective adhesive manufacturers’ testreports and Miami-Dade NOAs. Entegra Roof Tile, LLC. relies upon the adhesive manufacturers to provide these values for our inclusionin this FBC HVHZ Evaluation Report. Please consult the individual adhesive manufacturer for information on product approvals,limitations, revisions or other information for determining wind load and overturning moment performance.TileBermudaFlat,PlantationFlat orHorizonEstate “S” orHaciendaBella High“S”, GalenaSpanish “S”or Regal“TILE BOND ” by Dow Chemical“Touch N’ Seal Storm Bond” by DAP Foam“Polyset RTA-1” by ICP Adhesives & SealantsNOA 16-0222.01NOA 16-0421.03NOA 16-0315.03“Polyset AH-160” by ICP Adhesives &SealantsNOA 17-0322.03“TILE BOND ” by Dow Chemical“Touch N’ Seal Storm Bond” by DAP Foam“Polyset RTA-1” by ICP Adhesives & SealantsNOA 16-0222.01NOA 16-0421.03NOA 16-0315.03“Polyset AH-160” by ICP Adhesives &SealantsNOA 17-0322.03Mortar“TILE BOND ” by Dow Chemical“Touch N’ Seal Storm Bond” by DAP Foam“Polyset RTA-1” by ICP Adhesives & SealantsVariousNOA 16-0222.01NOA 16-0421.03NOA 16-0315.03“Polyset AH-160” by ICP Adhesives &SealantsNOA 17-0322.03Mortar7.Tile AdhesiveProduct ApprovalProductVariousPlacementMf (ft-lbf)Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Independent (medium paddy, 30 g)Independent (large paddy, 45 g)Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Independent (medium paddy, 30 g)Independent (large paddy, 54 g)Per RAS 120Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Interdependent (2-paddy)Independent (medium paddy, 30 g)Independent (large paddy, 63 g)Per RAS G:7.1Each unit shall bear the imprint and/or identifiable marking of the manufacturer’s name or logo, as detailedbelow. Tile lots shall be labeled in accordance with the requirements of the Accredited Quality AssuranceAgency noted herein.and/orLabeling: Bermuda Flat, Plantation Flat, Estate “S”, Bella High “S”, Galena Spanish “S”Exterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 7 of 8

and/orLabeling: Horizon Flat, Hacienda, Regal8.BUILDING PERMIT REQUIREMENTS:As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation ofthis product.9.MANUFACTURING PLANTS:PlantOkeechobee, FLFt. Myers, FLDeerfield Beach, FL10.ProfilesBermuda Flat, Plantation Flat, Estate “S”, Bella High “S”, Galena Spanish “S”Horizon Flat, HaciendaHorizon Flat, Hacienda, RegalQUALITY ASSURANCE ENTITY:PRI Construction Materials Technologies, LLC. – QUA9110; (813) 621-5777- END OF EVALUATION REPORT –Exterior Research and Design, LLC.Certificate of Authorization #95036TH EDITION (2017) FBC HVHZ EVALUATIONEntegra Roof TilesEvaluation Report E39310.11.11-1-R4FL7804-R10Revision 4: 10/17/2017Page 8 of 8

Entegra Roof Tiles Revision 4: 10/17/2017 Page 5 of 8 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained .