Vlt 6000 Hvac - Hos Bv

Transcription

VLT 6000 HVAC VLT 6000 HVACMD.60.A2.02 - VLT is a registered Danfoss trademark1

VLT 6000 HVAC Ordering guideThis section makes it easier for you to specify andorder a VLT 6000 HVAC. Choice of frequency converterThe frequency converter should be chosen on thebasis of the given motor current at maximum loadon the system. The rated output current IVLT,N mustbe equal to or higher than the required motorcurrent.VLT 6000 HVAC is available for two mains voltageranges: 200-240 V and 380-460 V. Mains voltageChoose mains voltage for 50/60 Hz:- 200-240 V three-phase AC voltage- 380-460 V three-phase AC voltageMains voltage 200 - 240 VTypical shaft outputP VLT,NVLT 5Max continuous output current Max continuous output powerIVLT,Nat 240 V 1.136.643.254.064.0* The first figure is for a motor voltage of 200-230 V.The next figure is for a motor voltage of 231-240 V.2MD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVACMains voltage 380 - 415 VTypical shaft outputP VLT.NVLT 00Mains voltage 440 - 460 VTypical shaft outputP VLT.NVLT 23.04.05.57.5111518.522303745557590110132160200Max continuous output .544.061.073.090.0106147177212260315368Max continuous output 100125150200250300MD.60.A2.02 - VLT is a registered Danfoss 052.065.077.0106130160190240302361Max continuous output powerat 400 V 3.852.564.773.0102123147180218255Max continuous output powerat 460 V 1.451.861.384.51041271511912412883

VLT 6000 HVAC EnclosureVLT 6000 HVAC is available with the followingenclosures:-IP 00:IP 00:Bookstyle IP 20:Bookstyle IP 20:IP 20:IP 20:IP 54:IP 54:30 to 4555 to 2001.1 to 3.01.1 to 7.51.1 to 451.1 to 2001.1 to 451.1 to 0-460200-240380-460200-240380-460VVVVVVVVIP 00: This enclosure is only available for the largerpower sizes of the VLT 6000 HVAC series. It isrecommended for installation in standard cabinets. RFI filterAs standard, the VLT 6000 HVAC has an integralRFI filter up to and including 7.5 kW (3 kW 200 V).IP 20 Bookstyle: This enclosure is designed forcabinet installation. It takes up a minimum of spaceand can be fitted side-by-side without installation ofextra cooling equipment.IP 20: This enclosure is used as standard enclosurefor VLT 6000 HVAC. It is ideal for cabinet installationin areas where a high degree of protection isrequired. This enclose also permits side-by-sideinstallation.IP 54: This enclosure can be fitted direct to the wall.Cabinets are not required. IP 54 units can also beinstalled side-by-side.Select a RFI filter for dampening of interference inaccordance with EN 55011-1A and EN 55011-1B.These RFI filters comply with EMC standards EN55011-1A, provided max. 150 m screened/armoured cable is used, and with EN 55011-1B,provided 50 m screened/armoured cable is used(Bookstyle max. 20 m screened/armoured). Harmonic filterThe harmonic currents do not directly affect theelectricity consumption, but they do increase theheat losses in the installation (transformers, cables).That is why in systems with a rather highpercentage of rectifier load it is important to keepthe harmonic currents at a low level in order toavoid transformer overloads and high cabletemperatures. Control unit (LCP)The VLT 6000 HVAC is available with or withoutcontrol unit (LCP); however, IP 54 units alwayscome with the control unit.This control unit makes up a complete interface forcontrol and programming of the VLT 6000 HVAC.The control panel is detachable and may - as analternative - be mounted up to 3 metres away fromthe VLT frequency converter, i.e. in a cabinet, bymeans of a fitting kit delivered with the unit.Data information is given in a 4-line alpha-numericaldisplay, which under normal operation is able tocontinuously show four operating data items andthree operating modes. During programming, all theinformation required for quickly and efficiently settingup VLT frequency converter parameters will beshown.4As standard, the VLT 6000 HVAC has coils in theintermediate circuit in order to ensure lowharmonic currents. This typically reduces theinput current IRMS by 40 %.As a supplement to the display, there are threeindicator lamps for voltage (ON), warning(WARNING) and alarm (ALARM).All VLT frequency converter parameter Setups canbe changed directly via the control panel.The following options are available:- Control panel LCP (only for IP 20 units).- LCP remote-mounting kit for remote control ofIP 00 and IP 20 units.- LCP remote-mounting kit for remote control ofIP 54.- 3 metre cable for LCP.MD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC Fieldbus protocolsDanfoss VLT frequency converters are able to fulfilmany different functions in an automated buildingmanagement system. The VLT frequency convertercan be integrated directly in an overall monitoringsystem.This means that detailed process data can betransmitted via serial communication. The protocolslisted below are based on a RS 485 bus systemwith a maximum transmission speed of 9600 bauds.As standard, the following protocols are supported:- Danfoss FC protocol- Johnson's Control Metasys N2- Landis & Staefa FLNA frequency converter can be set and applied in allbuilding management control systems.Status messages, warnings and alarms providevaluable assistance in visualising and assessingprocesses. Fieldbus optionsThe increasing need for information in buildingmanagement systems makes it necessary to collector visualise many different types of process data.Important process data can help the systemtechnician in the day-by-day monitoring of thesystem, which means that a negative development- e.g. an increase in energy consumption - can berectified in time.The substantial amount of data in large buildingsmay generate a need for a higher transmissionspeed than 9600 baud. Danfoss VLT 6000 HVAC isavailable with LonWorks or Profibus , both of whichhave higher performance than standard integratedserial communication.MD.60.A2.02 - VLT is a registered Danfoss trademark ProfibusProfibus is a fieldbus system with FMS and DP,which can be used for linking automation units,such as sensors and actuators, to the controls bymeans of a two-conductor cable.Profibus FMS is used if major communication tasksare to be solved at cell and system level by meansof large volumes of data.Profibus DP is an extremely fast communicationprotocol, made specially for communicationbetween the automation system and various units. LON - Local Operating NetworkLonWorks is an intelligent fieldbus system whichimproves the possibility of decentralising control, ascommunication is enabled between individual unitsin the same system (Peer-to-Peer).This means that there is no need for a big mainstation for handling all the signals of the system(Master-Slave). Signals are sent direct to the unitthat needs them via a common network medium.This makes communication much more flexible andthe central building state control and monitoringsystem can be changed into a dedicated buildingstate monitoring system whose task is to ensurethat everything is running as planned. If the potentialof LonWorks is fully utilised, sensors will also beconnected to the bus, which means that a sensorsignal can quickly be moved to another controller. Ifroom dividers are mobile, this is a particularly usefulfeature.Two feedback signals can be linked to the VLT 6000HVAC by means of LonWorks, thereby enabling theinternal PID regulator to regulate directly on the busfeedback.5

VLT 6000 HVAC Unpacking and ordering a VLT frequencyconverterAre you are in doubt as to which VLT frequencyconverter you have received and which options itcontains? Use the following table to find out. Thetable can also be used for ordering a VLT 6000HVAC. Type code ordering number stringOn the basis of your order, the VLT frequencyconverter is given an ordering number that can beseen from the nameplate on the unit. The numbermay look as follows:Units in the range of 1.1-45 kW come withenclosure IP 20, IP 54.Mains voltage, rated:Motor power400 V 1)460 V 1)55 kW75 kW90 kW110 kW132 kW160 kW200 kW250 kWVLT 6075VLT 6100VLT 6125VLT 6150VLT 6175VLT 6225VLT 275Units in the range of 55-250 kW come withenclosure IP 00, IP 20 or IP 54.1) The max. output depends on the mains voltageconnected to the unit.4 -B20-R3-DL-F10-A10VLT-6008-H-TVLT-6008-H-T4This means that the frequency converter ordered isa VLT 6008 for three-phase mains voltage of 380T4B20460 V (T4T4) in Bookstyle enclosure IP 20 (B20B20). Thehardware variant is with integral RFI filter, classes AR3& B (R3R3). The frequency converter features a controlDLF10unit (DLDL) with a PROFIBUS option card (F10F10).H ) indicates the application rangeCharacter no. 8 (Hof the unit: H HVAC.Bookstyle IP 20Mains voltage, rated:Motor power 200-240 V380-460 V1.1 kWVLT 6002VLT 60021.5 kW2.2 kW3.0 kW4.0 kW5.5 kW7.5 kWVLT 6003VLT 6004VLT r powerMains voltage, rated:200-240 V380-460 V1.1 kW1.5 kW2.2 kW3.0 kW4.0 kW5.5 kW7.5 kW11 kW15 kW18.5 kW22 kW30 kW37 kW45 2VLT 6002VLT 6003VLT 6004VLT 6005VLT 6006VLT 6008VLT 6011VLT 6016VLT 6022VLT 6027VLT 6032VLT 6042VLT 6052VLT 6062Hardware variantsAll units in the programme are available in thefollowing hardware variants:ST: Standard unit w/ or w/o control unit.RFI-filterBookstyle units always come with an integral RFIfilter that complies with EN 55011-1B with 20 mscreened /armoured motor cable and EN 55011-1Awith 150 m screened/armoured motor cable.Units for a mains voltage of 240 V and a motorpower of up to and including 4.0 kW (VLT 6006) andunits for a mains voltage of 380-460 V and a motorpower of up to 7.5 kW (VLT 6011) are alwayssupplied with an integral class 1A & 1B filter.Units for higher motor power than these (4.0 and7.5 kW, respectively) can be ordered either with orwithout an RFI filter.Control unit (keypad and display)All types of units in the programme, except for IP 54units, can be ordered either with or without thecontrol unit. IP 54 units always come with a controlunit.MD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC Ordering form VLT 6000 HVACH TVLT 6 ST R D Power sizes Application rangeHHVACMains 090/110110/132132/160160/200200/2503 x 200 - 240 V3 x 380 - 460 VT2T4EnclosureBookstyle IP 20B 206002-6005 200-240 V6002-6011 380-460 VkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWkWC 00IP 006042-6062 200-240 V6075-6275 380-460 VC 20IP 206002-6062 200-240 V6002-6275 380-460 VC 54IP 54 5260626075610061256150617562256275e.g. 6008 6002 1.1 kW6003 1.5 kW6004 2.2 kW6005 3.0 kW6006 4.0 kW6008 5.5 kW6011 7.5 kW6016 11 kW6022 15 kW6027 18.5 kW6032 22 kW6042 30 kW6052 37 kW6062 45 kW6002-6062 200-240 V6002-6275 380-460 VHardware variantSTstandard onlyRFI filterAvailable w/o filter in the ranges R06006-6062 200-240 V6016-6275 380-460 VWith integral 1A 1B filterNo. units ofthis typeRequireddelivery dateR3Control unit (LCP)W/o LCP (not an option with IP 54) D0W/ LCPFieldbus option cardNo optionOrdered by:DLProfibusLonWorks Free Topology ProcessLonWorks 78 KBPSLonWorks 1.25 MBPSF 00F 10F 40F 41F 42Application option cardW/ relay cardA 31(not with fieldbus option)Date:Take a copy of the ordering forms. Fill them in andsend or fax your order to the nearest office of theDanfoss sales organisation.MD.60.A2.02 - VLT is a registered Danfoss trademark7

VLT 6000 HVAC PC software and serial communicationDanfoss offers various options for serial communication. Using serial communication makes itpossible to monitor, programme and control one orseveral VLT 6000 HVAC from a centrally placedcomputer. For example, Danfoss offers an optioncard for Profibus. In addition, all VLT 6000 HVAChave an RS 485 port as standard, which enablesthem to communicate e.g. with a PC. Aprogramme entitled VLT Software Dialog is availablefor this purpose.VLT Software Dialog comes in three modules and as a minimum - contains the programmes includedin the Basic module.The Logging module covers:LOGGINGis used for collecting and displaying historical orreal-time operating data.- graphical representation of selectedparameters from several frequencyconverters,- collection of log data to file,- option of DDE link e.g. to a spreadsheet.MODEM SETUPis used for setting up the frequency convertermodem.- sets the frequency converter modem via thecommunication port of the PC.The Basic module covers:TEST RUNis used for controlling and commissioning ofa frequency converter, including:- setting of reference value,- simultaneous display of selectedparameters in graphs,- option of DDE link, e.g. to a spreadsheet.PARAMETER SETUPis used for setting up and transferring parameter sets, including:- setting of frequency converterparameters,- parameter sets can be obtained from andcopied to a frequency converter,- documentation/print-out of the Setupincluding diagrams.The template module covers:TEMPLATE SETUPis used for setting up template files forPARAMETER SETUP:- the template file functions as a mask that limitsthe number of accessible parameters when aparameter file is to be made or edited inPARAMETER SETUP,- the template file may contain preset values forthe parameters of the frequency converter.NB!The logging and template module calls for aBasic module to be installed on the samePC.The guided tour covers:HISTORYprovides information about the differentstages of development of the VLT Softwaredialogue.GUIDED TOURoffers a demonstration of the VLT SoftwareDialog programme.BUS ADDRESS SETUPis only used for addressing the VLT FCM.8MD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC Accessories for VLT 6000 HVACIP 20 bottom coverTerminal coverIP 4x top coverControl unitApplication optionLCP Ordering numbers, misc.TypeDescriptionOrder no.Option, VLT type 6002-6005 200-240 V175Z0928Option, VLT type 6002-6011 380-460 V175Z0928NEMA 12 bonding plateOption, VLT type 6002-6005 200-240 V175H4195NEMA 12 bonding plate 2)Option, VLT type 6002-6011 380-460 V175H4195IP 20 terminal coverOption, VLT type 6006-6016 200-240 V175Z4622IP 20 terminal coverOption, VLT type 6022-6027 200-240 V175Z4623IP 20 terminal coverOption, VLT type 6016-6032 380-460 V175Z4622IP 20 terminal coverOption, VLT type 6042-6062 380-460 V175Z4623IP 20 bottom coverOption, VLT type 6042-6062 200-240 V176F1800IP 20 bottom coverOption, VLT type 6060-6100 380-460 V176F1800IP 20 bottom coverOption, VLT type 6125-6250 380-460 V176F1801Control panel LCPSeparate LCP175Z7804IP 4x top cover1)IP 4x top cover 1)2)LCP remote-mounting kit IP 00 & 20 3) Remote-mounting kit for LCP, for IP 00 and IP 20 units 175Z0850incl. 3 m cableLCP remote-mounting kit IP 54 4)Remote-mounting kit for LCP, for IP 54 unitsincl. 3 m cableLCP blind coverfor all IP00/IP20 drives175Z7806Cable for LCPSeparate cable175Z0929VLT Software, DialogVLTSoftware,Basic moduleDanish manual175Z0900VLT Software, DialogVLTSoftware,Basic moduleEnglish manual175Z0903175Z0904 175Z7802VLT Software, DialogVLTSoftware,Basic moduleGerman manualVLT Software, DialogVLTSoftware,Basic moduleItalian manual175Z0905VLT Software, DialogVLTSoftware,Basic moduleSpanish manual175Z0906VLT Software, DialogVLTSoftware,Basic moduleFrench manual175Z0907 VLT Software, DialogVLTSoftware,Logging module175Z0909VLT Software, DialogVLTSoftware,Template module175Z0908VLT Software, DialogVLTSoftware,Guided tour175Z0952Relay cardApplication card with four relay outputs175Z7803Profibus option175Z7800LonWorks option, Free topology176F1515LonWorks option, 78 KBPS176F1516LonWorks option, 1.25 MBPS176F15171) IP 4x/NEMA 1 top cover is for IP 20 units only and only3 m cable3 m cableVLT 6000 HVAC is available with an integral fieldbus option orhorizontal surfaces comply with IP 4x. The kit also containsapplication option. Ordering numbers for the individual VLTa bonding plate (UL).types with integrated options can be seen from the relevant2) NEMA 12 bonding plate (UL) is only for IP 54 units.manuals or instructions. In addition, the ordering number3) The remote-mounting kit is only for IP 00 and IP 20 units.system can be used for ordering a VLT frequency converterOPTIONSEnclosure of the remotemounting kit is IP 65.with an option.4) The remote-mounting kit is only for IP 54 units. Enclosureof the remote-mounting kit is IP 65.MD.60.A2.02 - VLT is a registered Danfoss trademark9

VLT 6000 HVAC LC filters for VLT 6000 HVACWhen a motor is controlled by a frequencyconverter, resonance noise will be heard from themotor. This noise, which is caused by the design ofthe motor, occurs each time one of the inverterswitches in the frequency converter is activated.Consequently, the resonance noise frequencycorresponds to the switching frequency of thefrequency converter.For the VLT 6000 HVAC, Danfoss offers a LC filter todampen the acoustic motor noise.This filter reduces the voltage rise time, the peakvoltage UPEAK and the ripple current I to the motor,thereby making current and voltage almostsinusoidal. The acoustic motor noise is thereforereduced to a minimum.Because of the ripple current in the coils, there willbe some noise from the coils. This problem can besolved entirely by integrating the filter in a cabinet orsimilar. Examples of the use of LC filtersSubmersible pumpsFor small motors with up to and including 5.5 kWrated motor power, use a LC filter, unless the motoris equipped with phase separation paper. Thisapplies e.g. to all wet running motors. If thesemotors are used without LC filter in connection witha frequency converter, the motor windings will shortcircuit. If in doubt, ask the motor manufacturerwhether the motor in question is equipped withphase separation paper.Well pumpsIf immersion pumps are used, e.g. submergedpumps or well pumps, the supplier should becontacted for clarification of requirements. It isrecommended to use a LC filter if a VLT frequencyconverter is used for immersion operations.Long motor cablesIf screened/armoured motor cables longer than 150m or unscreened/unarmoured motor cables longerthan 300 m are used, a LC filter should be applied.The LC filter reduces the capacitive earth leakagecurrents and the voltage peak loads.NB!:If a VLT frequency converter controls severalmotors in parallel, the motor cables must beadded up to give the total cable length.10MD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC Ordering numbers, LC filter modulesMains supply 3 x 200 - 240 VLC filterfor VLT type6002-6003 Bookstyle6004-6005 Booksyle6002-60056006-600860116016602260276032LC filterenclosureIP 20 BookstyleIP 20 BookstyleIP 20IP 00IP 00IP 00IP 00IP 00IP 00Rated currentat 200 V7.8 A15.2 A15.2 A25.0 A32 A46 A61 A73 A88 AMax. outputfrequency120 Hz120 Hz120 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 HzRated currentat 400/460 V7.2 A / 6.3 A16 A / 16 A16 A / 16 A24 A/ 21.7 A32 A / 27.9 A37.5 A / 32 A44 A / 41.4 A61 A / 54 A73 A / 65 A90 A / 78 A106 A / 106 A147 A / 130 A177 A / 160 A212 A / 190 A260 A / 240 A315 A / 302 A395 A / 361 AMax. outputfrequency120 Hz120 Hz120 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 Hz60 HZ60 HZ60 HzPowerloss85 W90 W110 W170 W250 W320 WOrder 2175Z4603175Z4604175Z4605Mains supply 3 x 380 - 460 VLC filterfor VLT type6002-6005 Bookstyle6006-6011 610061256150617562256275LC filterenclosureIP 20 BookstyleIP 20 BookstyleIP 20IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 20IP 20IP 20IP 20IP 20IP 20IP 20MD.60.A2.02 - VLT is a registered Danfoss r 75Z4703175Z4704175Z4705175Z4706175Z470711

VLT 6000 HVAC LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 VThe drawing on the left gives the measurements ofIP 20 LC filters for the above-mentioned powerrange.Min. space above and under enclosure: 100 mm.IP 20 LC filters have been designed for side-by-sideinstallation without any space between enclosures.Max. motor cable length:- 150 m screened/armoured cable- 300 m unscreened/unarmoured cableIf EMC standards are to be complied with:- EN 55011-1B:Max. 50 screened/armoured cableBookstyle: Max. 20 m screened/armoured cable- EN 55011-1A: Max. 150 m screened/armoured cableWeight: Installation of LC filter IP 20 Bookstyle175Z0825175Z0826175Z08327.5 kg9.5 kg9.5 kg Installation of LC filter IP 20VLTVLT12LC filterLC filterMD.60.A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC LC filters VLT 6008-6032, 200 - 240 V / 6016-6062 380 - 460 VMax. motor cable length:The table and the drawing give the measurements- 150 m screened/armoured cableof IP 00 LC filters for Compact units.- 300 m unscreened/unarmoured cableIP 00 LC filters must be integrated and protectedIf EMC standards are to be complied with:against dust, water and corrosive gases.- EN 55011-1B:Max. 50 screened/armoured cableBookstyle: Max. 20 m screened/armoured cable- EN 55011-1A: Max. 150 m screened/armoured cableLC filter IP 00LC typeA [mm]B [mm]C [mm]D [mm]175Z460022013592190E [mm]68F [mm]170G [mm]8Weight 01263101165ADCGBEFMD.60.A2.02 - VLT is a registered Danfoss trademark13

VLT 6000 HVAC LC filter 6075-6275 380 - 460 VThe table and the drawing give the measurementsof IP 20 LC filters. IP 20 LC filters must be integratedand protected against dust, water and aggressivegases.Max. motor cable length:- 150 m screened/armoured cable- 300 m unscreened/unarmoured cableIf EMC standards are to be complied with:- EN 55011-1B: Max. 50 m screened/armoured cableBookstyle: Max. 20 m screened/armoured cable- EN 55011-1A: Max. 150 m screened/armoured cableLC-filter IP 20LC typeA [mm]B [mm]C [mm]D [mm]E [mm]F [mm]G [mm]Weight A2.02 - VLT is a registered Danfoss trademark

VLT 6000 HVAC General technical dataMains supply (L1, L2, L3):Supply voltage 200-240 V units . 3 x 200/208/220/230/240 V 10%Supply voltage 380-460 V units . 3 x 380/400/415/440/460 V 10%Supply frequency . 50/60 Hz /- 1%Max. imbalance of supply voltage:VLT 6002 - 6011 / 380 - 460 V and VLT 6002 - 6005 / 200 - 240 V . 2.0% of rated supply voltageVLT 6016 - 6062 / 380 - 460 V and VLT 6006 - 6032 / 200 - 240 V . 1.5% of rated supply voltageVLT 6075 - 6275 / 380 - 460 V and VLT 6042 - 6062 / 200 - 240 V . 3.0% of rated supply voltagePower factor / cos. ϕ . 0.90/1.0 at rated loadNo. of switches on supply input L1, L2, L3 . approx. 1 time/min.Max. short-circuit current . 100.000 AVLT output data (U, V, W):Output voltage . 0-100% of supply voltageOutput frequency . 0 - 120 Hz, 0 - 1000 HzRated motor voltage, 200-240 V units . 200/208/220/230/240 VRated motor voltage, 380-460 V units . 380/400/415/440/460/500 VRated motor frequency . 50/60 HzSwitching on output . UnlimitedRamp times . 1- 3600 sec.Torque characteristics:Starting torque . 110% for 1 min.Starting torque (parameter 110 High break-away torque) . Max. torque: 160% for 0.5 sec.Acceleration torque . 100%Overload torque . 110%Control card, digital inputs:Number of programmable digital inputs . 8Terminal nos. . 16, 17, 18, 19, 27, 29, 32, 33Voltage level . 0-24 V DC (PNP positive logics)Voltage level, logical 0 . 5 V DCVoltage level, logical 1 . 10 V DCMaximum voltage on input . 28 V DCInput resistance, Ri . approx. 2 kΩScanning time per input . 3 msec.Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition,the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V DCsupply and opening switch 4.Control card, analogue inputs:No. of programmable analogue voltage inputs/thermistor inputs . 2Terminal nos. . 53, 54Voltage level . 0 - 10 V DC (scalable)Input resistance, Ri . approx. 10 kΩNo. of programmable analogue current inputs . 1Terminal no. ground . 55Current range . 0/4 - 20 mA (scalable)Input resistance, Ri . approx. 200 ΩResolution . 10 bit signAccuracy on input . Max. error 1% of full scaleScanning time per input . 3 msec.Reliable galvanic isolation: All analogue inputs are galvanically isolated from the supply voltage (PELV) and otherhigh-voltage terminals.MD.60.A2.02 - VLT is a registered Danfoss trade mark15

VLT 6000 HVAC General technical dataControl card, pulse input:No. of programmable pulse inputs .

VLT 6000 HVAC 2 MD.60.A2.02 - VLT is a registered Danfoss trademark Ordering guide This section makes it easier for you to specify and order a VLT 6000 HVAC. Choice of frequency converter The frequency converter should be chosen on the basis of the given motor current at maximum load on the system. The rated output current I VLT,N must