Multilin 850 Advanced Feeder Protection And Management Relay Brochure

Transcription

GEGrid Solutions10YEARWORLDWIDEMultilin 850Feeder and Bay Controller Solutions forIndustrial and Utility ApplicationsThe Multilin 850 relay is a member of the Multilin 8 Series protective relay platform and has beendesigned for the management, protection and control of feeder applications. The Multilin 850 is usedto provide primary (main) or backup protection for underground and overhead single or dual feedersfor utility and industrial power networks.With 11 Switchgear control elements, fully configurable Single Line Diagram on a large color graphicaldisplay, 36 alarm integrated annunciator panel and 20 push buttons makes the 850 the ideal choice forbay control and protection as a “One Box Solution”.Designed with advanced communications options and detailed asset monitoring capabilities, theMultilin 850 provides advanced functionality, including high-performance protection, extensiveprogrammable logic and flexible configuration capabilities. With support for industry leadingcommunications protocols and technologies, the 850 provides easy integration into new or existingSCADA or DCS for enhanced situational awareness.Key Benefits One Box Solution with advanced logic and configuration flexibility, providing primary or backupprotection for up to 2 feeders or feeders with 2 sets of voltage inputs User configurable Single Line Diagram on color display for local control, system status, and meteringWARRANTYInnovative Technology& Design Advanced feeder One Box Solutionfor protection, control monitoring anddiagnostics of single/dual feeder applications Patented environmental monitoring anddiagnostics Advanced, flexible and embeddedcommunications: IEC 61850 Ed2,IEC 62439/PRP, Modbus RTU & TCP/IP,DNP3.0, IEC 60870-5-104, IEC 60870-5-103 Single setup and configuration softwareacross the 8 Series platform Field swappable power supply Enhanced relay draw-out construction Elimination of electrolytic capacitors Integrated arc flash detection using light sensors supervised by overcurrent to reduce incidentenergy and equipment damageExceptional Quality& Reliability Advanced cyber security features including AAA, Radius, RBAC, and Syslog enabling NERC CIPrequirements IPC A-610-E Class 3 manufacturingstandards Draw-out design simplifies testing, commissioning and maintenance, increasing process uptime Highest reliability standards for electronicstesting Advanced breaker diagnostics with comprehensive fault and disturbance recording Patented environmental monitoring, providing visibility to changes in environmental conditions thatcan affect relay life 100% Environmental Stress Screening andfull functional testingApplications Rated for IP54 (front) applications Single/dual feeder applications for utility, oil & gas, mining & metals, process industry,commercial, and waste water segments Harsh Environment Coating Fast protection pass enabling load shedding schemes Bay controller for wide range of switchgear applicationsUncompromising Service& Support High speed fault detection for arc flash mitigation Covered under GE’s 10 year warranty plan Reliable automatic bus transfer & autoreclose schemes Designed, tested and assembled by GEimagination at work

850 Feeder Protection SystemMultilin 850 OverviewSwitchgear Control and Configurable SLDThe Multilin 850 is an advanced feeder protection device designed forhigh performance, protection, control and monitoring of incoming andoutgoing feeders.The Multilin 850 provides a configurable dynamic SLD up to six (6)pages for comprehensive switchgear control of up to 2 breakers and 9disconnect switches; including interlocks. Up to 15 digital and meteringstatus elements can be configured per SLD page. These can be configuredto show breakers, switches, metering, and status items.With up to 57 digital inputs and 22 digital outputs in a compact box,the 850 provides a versatile and cost effective control, protection,measurement & monitoring solution. Flexelements and Flexlogic enableusers to customize schemes to meet a variety of applications.Individual SLD pages can be selected for the default home screen pages.Automatic cycling through these pages can also be achieved throughdefault screen settings.From dual main to main-standby configurations, the Multilin 850D deliversa more economical and reliable solution, enabling customers to reducehardware requirements and simplify device integration, including safe andsecure Wi-Fi communications for system configuration and diagnostics.The provision of such powerful control and display capability within the relay(“One Box” concept) eliminates the need for external controls, switches andannunciation on the panel reducing equipment and engineering cost.Bay Controller/One Box SolutionAnnunciator Panel and Virtual Push ButtonsThe 850 offers comprehensive switchgear control aided by a configurableSingle Line Diagram & breaker control. A total of 10 switchgear elementscan be displayed and 8 elements controlled. The integrated solution forprotection, control, monitoring and diagnostics eliminates the need forother external devices thus offering an integrated solution for switchgearsystems. The device supports 6 user programmable pages. The Multilin 850is an integrated solution that performs protection, control & monitoringof assets, and ease of retrieval of fault & event records. Coordinatingremotely with SCADA over multiple communication protocols gives theMultilin 850 an added advantage for fast and efficient management offault isolation and service restoration.The Multilin 850 offers a configurable annunciator panel that canbe constructed to show up to 36 alarms in either self-reset mode orlatched mode per ISA 18.1 standard similar to a physical annunciatorpanel; eliminating the need for a physical one. This removes the need foradditional programmable LEDs. The alarms can be displayed on the frontpanel in a configurable grid layout of 2x2 or 3x3.The Multilin 850 extends the local control functionalities with 20virtual pushbuttons that can be assigned for various functions. Eachprogrammable pushbutton has its own programmable LED which can beused to acknowledge the action taken by the tab pushbutton.With a fast protection pass, running every 2 msec, the 850 relay providesfast response to current, voltage, power, and frequency protectionelements; helping reduce stress on assets. The Multilin 850 supports thelatest communication protocols, including DNP, ModBus, IEC 60870-5103, IEC 62439/PRP and IEC 61850; facilitating easy integration into newor existing SCADA/DCS networks.The Multilin 850 is a cost-effective retrofit solutions where individualcomponents of protection, metering, control switches, annunciator &panel mimic can be replaced by only one relay.Functional Block DiagramBUSAux VTDESCRIPTIONYN2527P27Q27T27X3232NYN Neutral AdmittanceSynchrocheckPhase UndervoltageUV Reactive PowerTimed Undervoltage ProtectionAuxiliary UndervoltageDirectional PowerWattmetric Ground Fault (Wattmetriczero sequence directional)37*4950BF50G50SGUndercurrentThermal OverloadBreaker FailureGround Instantaneous OvercurrentSensitive Ground InstantaneousOvercurrent50N50P50PD50 2Neutral Instantaneous OvercurrentPhase Instantaneous OvercurrentPole Discordance*Negative Sequence InstantaneousOvercurrent51G51SG51N51P51 25559N59P59XGround Time OvercurrentSensitive Ground Time OvercurrentNeutral Time OvercurrentPhase Time OvercurrentNegative Sequence Time OvercurrentPower FactorNeutral OvervoltagePhase OvervoltageAuxiliary Overvoltage227X21YN27Q27P27TV 259P59N59 2VTFF81U81O59X2581RV 03 CTs3 CTsAFP50BFCLP51G3751P50G/50G51G50P5567P51 2 50 267 23249CT32N51N50N67NSOTFRGF67GLI GHTANSI DEVICEBroken ConductorCT SupervisionHarmonic DetectionLoad EncroachmentDemandPulsed Outputs50SG51G 67SG51SG 50G/UF RestorationUV RestorationFast UnderfrequencyBREAKER5279TRIPMCBMETERINGTRANSIENT RECORDEREVENT RECORDERFAULT E DISCORDANCEPOLE DISCORDANCE3 VTs3 VTs850-D Dual Feeder Protection System.LOADLOAD894211A1.cdrANSI DEVICEDESCRIPTIONANSI DEVICEDESCRIPTION59 267G67SG67N67P67 27981O81UNegative Sequence OvervoltageGround Directional ElementSensitive Ground Directional ElementNeutral Directional ElementPhase Directional ElementNegative Sequence Directional ElementAutomatic 12MCBSOTF*VTFFFrequency Rate of ChangeRestricted Ground Fault (RGF)Arc Flash ProtectionCold Load PickupBroken ConductorManual Close BlockingSwitch Onto FaultVoltage Transformer Fuse FailureGEGridSolutions.com* Only for 850DBREAKER

850 Feeder Protection SystemDistribution FeederSimplified Management - Platform Based SolutionWith support for up to 8 CT inputs & 2 sets of 4 traditional VT inputs, the850 can be used for 2 feeders or feeders with 2 sets of voltage inputs,simplifying system architectures and operational costs. Reduced training needs Standardized part number across systems Harmonized look and feel, operational experienceThe 850 offers redundancy with the same number of devices, enabling:Protection & ControlAs part of the 8 Series family, the Multilin 850 provides superior protectionand control. The 850 offers comprehensive protection and controlsolutions for incoming, outgoing bus-tie/bus-coupler feeders. It containsa full range of selectively enabled, self-contained protection and controlelements.Single feeder, dual voltageThe voltage and frequency protection functions detect abnormal systemconditions, potentially hazardous to the system. Some of these conditionsmay consist of over and undervoltage, over and underfrequency, andphase reversal.Fast UnderfrequencyThe 850 has an 8 stage Fast Underfrequency element that measuresfrequency by detecting the consecutive voltage zero crossings andmeasuring the time between them. The measured frequency has a rangebetween 20 to 70 Hz. This is useful for performing fast load-sheddingwhen frequency variations from unbalance conditions arise due to: Inadequate load forecast or deficient generation capacity programming. Busbars, generator group or interconnection feeders trip. System splits into islands.Dual feederFlexCurves For applications that require greater flexibility, FlexCurves can be used todefine custom curve shapes. These curves can be used to coordinate withother feeders to achieve fault selectivity.RTD ProtectionThe Multilin 850 supports up to 13 programmable RTD inputs that can beconfigured for an Alarm or Trip.The RTDs can be assigned to a group for monitoring ambient temperaturesor any other desired temperature. The RTD voting option gives additionalreliability to ignore and alarm for any RTD failures.Integrated Arc Flash ProtectionRedundant feederArchitecture Simplification - Reduced Number of Devices Less capital cost Less O&M costMean Time to Repair - Less than 15 minutes Field swappable PSU Draw out construction Ready to consume service reportsExtended Asset and Relay LifeThe Multilin 8 Series supports an integrated arc flash module providingconstant monitoring for an arc flash condition within the switchgear,motor control centers, or panelboards. With a 2ms protection pass,the 8 Series is able to detect light and overcurrent using 4 arc sensorsconnected to the relay. In situations where an arc flash/fault does occur,the relay is able to quickly identify the fault and issue a trip command tothe associated breaker thereby reducing the total incident energy andminimizing resulting equipment damage.Self-monitoring and diagnostics of the sensors ensures the health of thesensors as well as the full length fiber cables. LEDs on the front paneldisplay of the 850 can be configured to indicate the health of the sensorsand its connections to the relay. Built-in Environmental monitoring Advanced breaker monitoring TGFD and Cable incipient fault detection/locationGEGridSolutions.com3

850 Feeder Protection SystemBreaker Health MonitoringWANT TO LEARN MORE?EXPLORE IN 3DThe breaker is monitored by the relay not only for detection of breakerfailure, but also for the overall “breaker health” which includes: Breaker close and breaker open times Trip circuit monitoring Spring charging time Per-phase arcing current Trip countersAll algorithms provide the user with the flexibility to set up initial breakertrip counter conditions and define the criteria for breaker wear throughouta number of set points.MV SwitchgearMultilin 8 SeriesFast, reliable arc flash protection with integrated light based arc flashsensors. This delivers detection in as fast as 2 msec, reducing the costsassociated with equipment damage and unplanned downtime.Inputs and OutputsThe 850 provides a max of 57 Digital inputs and 22 Digital outputs with anoption for 7 Analog Outputs (dc mA), 4 Analog Inputs (dc mA), and 1 RTDinput. The configurable analog inputs can be used to measure quantitiesfed to the relay from standard transducers. Each input can be individuallyset to measure 4-20 mA, 0-20 mA or 0-1 mA transducer signals.Breaker Health Reporting assists Condition-Based Maintenance andsavings in Operational CostsAdvanced AutomationThe Multilin 850 incorporates advanced automation capabilities whichexceed those found in most feeder protection relays. This reduces theneed for additional programmable controllers or discrete control relaysincluding programmable logic, communication, and SCADA devices.Advanced automation also enables seamless integration of the 850 intoother protection or process systems (SCADA or DCS).Monitoring & DiagnosticsFlexElements Environmental MonitoringFlexElement is a universal comparator, that can be used to monitorany (analog) actual value measured or calculated by the relay, or a netdifference of any two analog (actual) values of the same type.The 850 has an Environmental Awareness Module (EAM) to recordenvironmental data over the life of the product. The patented modulemeasures temperature, humidity, surge pulses and accumulates theevents every hour in pre-determined threshold buckets over a period of15 years. This data can be retrieved using the EnerVista Setup Software.This report helps identify the operating condition of the installed fleet sothat remedial action can be taken.The element can be programmed to respond either to a signal level or to arate-of-change (delta) over a pre-defined period of time.This can be used to generate special protection or monitoring functionswhich allow the user to flag a user-defined abnormality to give bettervisibility to a certain condition.The Multilin 850 includes high accuracy metering and recording for all ACsignals. Voltage, current, and power metering are built into the relay as astandard feature. Current and voltage parameters are available as totalRMS magnitude, and as fundamental frequency magnitude and angle.FlexLogic FlexLogic is the powerful programming logic engine that provides the abilityto create customized protection and control schemes, minimizing theneed for and associated costs of auxiliary components and wiring. UsingFlexLogic, the 850 can be programmed to provide the required tripping logicalong with custom scheme logic for feeder control interlocking schemeswith adjacent protection (for example, preventing sympathetic tripping ofhealthy feeders), and dynamic setting group changes.4GEGridSolutions.com

850 Feeder Protection SystemEnterpriseWANOperator AOperator BEngineeringReason S20Ethernet SwitchDual RedundantLANs (PRP)PLC / GatewayControlNetworkReason S20Ethernet SwitchReason S20Ethernet SwitchSiteNetworkLV NetworkLV MotorControllers850869845MM200MM300 IEC 61850 (8 Clients, 4 Logical Devices, Tx & Rx expansion, AnalogGOOSE), IEC 62439 / PRP DNP 3.0 serial, DNP 3.0 TCP/IP, IEC 60870-5-103, IEC 60870-5-104 Modbus RTU, Modbus TCP/IPThe 850 has two interfaces, a USB front port and Wi-Fi for ease of accessto the relay.Wi-Fi Connectivity: Simplify set-up and configurationEnvironmental health report is available via Multilin PC Software Simplify diagnostic retrievalMetering Allows personnel to be a safer distance from the front of the switchgearThe Multilin 850 offers high accuracy power quality monitoring for faultand system disturbance analysis. It delivers unmatched power systemanalytics through the following advanced features and monitoring andrecording tools: Harmonics measurement up to 25th harmonic for both currents andvoltages including THD. The length of the transient recorder record ranges from 31 to 1549 cycles(typically half a second to half a minute). WPA-2 securityCyber SecurityThe 8 Series delivers a host of cyber security features that help operatorsto comply with NERC CIP guidelines and regulations. AAA Server Support (Radius/LDAP) Role Based Access Control (RBAC) Event Recorder (Syslog for SEM) 32 digital points and 16 analog values. Comprehensive data logger provides the recording of 16 analog values.Security Server Detailed Fault Report. The 850 stores fault reports for the last 16events. 1024 Event Recorder.Access Request:CommunicationsThe Multilin 8 Series provides advanced communications technologies forremote data and engineering access, making it easy and flexible to useand integrate into new and existing infrastructures. Direct support for fiberoptic Ethernet provides high-bandwidth communications, allowing for lowlatency controls and high-speed file transfers of relay fault and event recordinformation. The 850 also supports two independent IP addresses, providinghigh flexibility for the most challenging of communication networks.Providing several Ethernet and serial port options and supporting a widerange of industry standard protocols, the 8 Series enables easy, directintegration into DCS and SCADA systems. The 8 Series supports thefollowing protocols:Role, User,PasswordAuthentication Request:Role, User, PasswordEncrypted (SSH)Authentication Request:Role, User, PasswordEncrypted (SSH)Cyber Security with Radius AuthenticationGEGridSolutions.com5

850 Feeder Protection SystemFront View - Advanced Membrane Front PanelWANT TO LEARN MORE?EXPLORE IN 3DMenu path display indicatinglocation within menu structureGraphic ControlPanel (GCP)Context-sensitive menu forfast navigationSoft menu navigation keysLED status indicatorsNavigation keysFront USB port10 User-ProgrammablePush ButtonsCaptive screw prevents inadvertentor unauthorized draw-outRear ViewStandard serial and RJ45Ethernet moduleGrounding screwPower supplyRTDsAdvanced communications module (Fiber Opticor Copper ports)Digital I/O, DCmA,Arc Flash sensorsCT, VT inputsOptional IP20 cover availableDimensions & utions.com7.5

850 Feeder Protection System850D Wiring DiagramJ6NJ5ICJ4NJ3IBJ2NIAJ1J12 VBCONNECTIONJ11 VBJ10 VAJ9 VAGROUNDGROUNDL IN EN EUTRALPWR SUPPLYSLOT KSLOT ADI GI TAL INPU TS*K8I sg K7*H2H3H4H5H6H7H8H9H10H11H1DIGITAL INPUT 1DIGITAL INPUT 2DIGITAL INPUT 3DIGITAL INPUT 4DIGITAL INPUT 5DIGITAL INPUT 6DIGITAL INPUT 7DIGITAL INPUT 8DIGITAL INPUT 9CH1H12 24 VCOMMONCH2CH3N* AVAILABLE WITH SENSITIVEGROUND ONLYGNDSTUDSLOT H: I/O F (OPTIONAL)N K8I G K7NPHASE CTsK6I C K5N K4IB K3N K2I A K1SEE GROUNDINPUT WIRING ININSTRUCTION MANUALVB K12VB K11VA K10VA TRIPVF352aF4F5CLOSEF13DIGITAL INPUT 1F14DIGITAL INPUT 2F15DIGITAL INPUT 3F16DIGITAL INPUT 4F17DIGITAL INPUT 5F18DIGITAL INPUT 6F19DIGITAL INPUT 7F20COMMONF21 24 VC1DIGITAL INPUT 1C2DIGITAL INPUT 2OUTPUT RELAYSSEE VT WIRING ININSTRUCTION MANUALVDIGITAL INPUT 3C4DIGITAL INPUT 4C5DIGITAL INPUT 5F9C6COMMONC7DIGITAL INPUT 6C8DIGITAL INPUT 7C9DIGITAL INPUT 8C10DIGITAL INPUT 10C12COMMONC13PERSONALCOMPUTERETHERNET[BACK PANEL ETHERNET PORT RJ45 OR ST]USB[FRONT PANEL LOCALPROGRAMMING PORT]DIGITAL INPUT 9C11DIGITAL INPUT 12C15DIGITAL INPUT 13HOTB4B6B7RETURNB8SHIELDB9C16DIGITAL INPUT 15COMMONRTDRTDHOT B10COMP B11HOT B12RTD 5COMP B13RTD 5/6RETURN B14HOT B15RTD 6C18B5HOTCOMPRTD 4* SUPPORTS 10 OHM COPPER RTD AS WELLB1B2B3COMPRTD 3/4OUTPUT CONTACTSSHOWN WITH NOCONTROL POWERF24COMPRTD 3SLOTS B AND C:6 RTDs (I/O R OR I/O S*)OR 15 DIGITAL INPUTS (I/O C)F23RETURNRTD 2THRESHOLDSETTINGGROUP 2C17Rear PanelF22HOTRTD 1/2THRESHOLDSETTINGDIGITAL INPUT 14 GROUP 3APPLICABLE FORCOMMUNICATIONOPTION ‘SE’ ONLYF11F12DIGITAL INPUT P 152bF8AUXILIARY 3RTD 1C3F6SEE TRIP ANDCLOSE COILMONITORINGIN INSTRUCTIONMANUALF7A2AUXILIARY 4SLOT F: I/O A (OPTIONAL)DIGITAL INPUTSLOADAUXVTJ16 VXJ15 VX52VC K14VC K13VOLTAGE INPUTS850-D Distribution FeederProtection SystemVOLTAGE INPUTSJ14 VCJ13 VCWYE VTA3SLOT JSEE GROUNDINPUT WIRING ININSTRUCTION MANUAL52ARC FLASHA1 A2CURRENT INPUTSIGGROUNDBUSPHASE A PHASE B PHASE CNJ7DIGITAL INPUT 10J8PHASE A PHASE B PHASE CPHASE CTsCURRENT INPUTS*J7 I sgFIBER INPUT 1CH4NGROUND*J8FIBER INPUT 2FIBER INPUT 4* AVAILABLE WITH SENSITIVEGROUND ONLYFIBER INPUT 3DIRECTION OF POWER FLOW FOR POSITIVE WATTSPOSITIVE DIRECTION OF LAGGING VARSCONTROLPOWERDIRECTION OF POWER FLOW FOR POSITIVE WATTSPOSITIVE DIRECTION OF LAGGING VARSBUSCOMP B16SHIELD B17RESERVED B18OPEN DELTA VT CONNECTIONSLOT ECOMMUNICATIONS(OPTIONAL)ETHERNETFIBER/COPPERSLOT G: I/O L (OPTIONAL)ST/RJ45ST/RJ45SLOT DG4G6 G7RTDANALOG INPUTG8G91234 RESERVED G57RESERVED6SHIELD G35RETURN G24HOT G13RESERVED2RESERVED1COMPANALOG OUTPUTD1 D2 D3 D 4 D 5 D6 D7 D8 D9 D 10ACCESS POINTDCmA I/OCANRESRVDRS485COMIRIG-BRESERVEDUSBTYPE BCOMMUNICATIONSRETURNFront RNETHERNETJ9 J10 J11 J12 J13 J14G10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24AMBIENTTEMPERATURECANRMIO**SLOT D OPTIONAL RMIOD8 is Ground ( )COMCABLE SHIELD TO BE GROUNDEDAT PLC/COMPUTER END ONLYD8 D9 D 10ANY MEASUREDOR METEREDANALOG PARAMETEROUTPUTSA ANY MEASURED ORMETERED ANALOG PARAMETERINPUTSGEGridSolutions.comB-RMIOCOMCABLE SHIELD TO BE GROUNDEDAT PLC/COMPUTER END ONLY7

850 Feeder Protection System850E Wiring DiagramDIRECTION OF POWER FLOW FOR POSITIVE WATTSPOSITIVE DIRECTION OF LAGGING VARSPHASE CTsLOAD52WYE VTCONNECTIONSEE VT WIRING ININSTRUCTION MANUALCONTROLPOWERSEE GROUNDINPUT WIRING ININSTRUCTION MANUALK7 K8J9 J10 J11 J12 J13 J14J15 J16I C N I G N I sg NVA VA VB VB VC VCVX VXVOLTAGE INPUTSAUXVTNPHASE A PHASE B PHASE CGROUNDCURRENT INPUTS* AVAILABLE WITH SENSITIVEGROUND ONLYF13A1 A2PWR SUPPLYGNDSTUDSLOTS J & KF1DIGITAL INPUT 1DIGITAL INPUT 4F17DIGITAL INPUT 5F18DIGITAL INPUT 6F19DIGITAL INPUT 7F20COMMONF21 24 VG/H13DIGITAL INPUT 1G/H14DIGITAL INPUT 2G/H15DIGITAL INPUT 3G/H16DIGITAL INPUT 4G/H17DIGITAL INPUT 5G/H18DIGITAL INPUT 6G/H19DIGITAL INPUT 7G/H20COMMONG/H21VF5CLOSEF12F22F23DIGITAL INPUT 3H4DIGITAL INPUT 4H5DIGITAL INPUT 5H6DIGITAL INPUT 6H7DIGITAL INPUT 7H8DIGITAL INPUT 8H9DIGITAL INPUT 9H10DIGITAL INPUT 10H11COMMONH12G/H1FIBER INPUT 4ARC FLASHFIBER INPUT OTC7COMPC8RETURNC9SHIELDC10 HOTC11 COMPC12 HOTC13 COMPC14 RETURNC15 HOTPERSONALCOMPUTERC16 COMPETHERNET[BACK PANEL ETHERNET PORT RJ45 OR ST]USB[FRONT PANEL LOCALPROGRAMMING PORT]G/H11SLOT H: I/O F (OPTIONAL)G/H22A2G/H24HOTRTD 1/2RTD 7RTD 7/8B2B3HOTB4COMPRTD 3/4RTD 9RTD 9/10B6B7B8SHIELDB9COMP B11HOT B12RTD 5SLOT B OR C: I/O R OR I/O S* (OPTIONAL)RTD 11/12* SUPPORTS 10 OHM COPPER RTD AS WELLRTDRTDHOT B10RTD 4RTD 10B5HOTCOMPRETURNRTD 3RTD 8B1COMPRETURNRTD 2RTD 11G/H23AUXILIARY 16RTD 1C1G/H8AUXILIARY 11G/H12* SLOT H I/O A IS AVAILABLE WHEN SLOT G IS WITH I/O LFIBER INPUT 3G/H6AUXILIARY 12SLOT G OR H: I/O A* (OPTIONAL)FIBER INPUT 2G/H4G/H5AUXILIARY 10 24 VCH2G/H2G/H3CH1CH3OUTPUT CONTACTSSHOWN WITH NOCONTROL POWERF24A2OUTPUT RELAYSH3MANUALF9F11CRITICALFAILURERELAYDI GI TAL INPU TSDIGITAL INPUT 2SEE TRIP ANDCLOSE COILMONITORINGCLOSECIRCUIT IN INSTRUCTIONF10A2AUXILIARY 4SLOT F: I/O ARY 3AUXILIARY 9DIGITAL INPUT 1F6VA2 24 VH1F3TRIPCOILF4OUTPUT RELAYSDIGITAL INPUT 3F16DIGITAL INPUTSDIGITAL INPUT 2F15F2TRIPDI GI TAL INPU TSF14C3A3GROUNDJ5 J6 J7 J8IBL IN E*J3 J4IA NN EUTRAL*J1 J2SLOT ABUSCOMP B13RTD 5/6RETURN B14HOT B15RTD 6COMP B16SHIELD B17RTD 12RESERVED B18C17 SHIELDC18 RESERVEDRear PanelAPPLICABLE FORCOMMUNICATIONOPTION ‘SE’ ONLYSLOT ECOMMUNICATIONS(OPTIONAL)ETHERNETOPEN DELTA VT CONNECTION850-E Industrial Feeder Protection SystemFIBER/COPPERSLOT G: I/O L (OPTIONAL)ST/RJ45ST/RJ45SLOT D**G46 G5G67 G7RTDANALOG INPUTG8G91234 J9 J10 J11 J12 J13 J14RESERVED G35SHIELD G24RESERVED G13RETURN2HOT1COMPANALOG OUTPUTD1 D2 D3 D 4 D 5 D6 D7 D8 D9 D 10ACCESS POINTDCmA I/OCANRESERVEDRESRVDRS485RESERVEDIRIG-BCOMTYPE BCOMMUNICATIONSRESERVEDUSBRETURNFront RNETHERNETG10 G11 G12 G13 G14 G15 G16 G17 G18 G19 G20 G21 G22 G23 G24AMBIENTTEMPERATURECANRMIO**SLOT D OPTIONAL RMIOD8 is Ground ( )COMCABLE SHIELD TO BE GROUNDEDAT PLC/COMPUTER END ONLYD8 D9 D 10ANY MEASUREDOR METEREDANALOG PARAMETEROUTPUTS8ANY MEASURED ORMETERED ANALOG PARAMETERINPUTSGEGridSolutions.comA B-RMIOCOMCABLE SHIELD TO BE GROUNDEDAT PLC/COMPUTER END ONLY

850 Feeder Protection SystemOrdering850 *Base unitApplicationPhase Currents - Bank 1/2Phase Currents - Bank 3Ground CurrentsPower SupplySLOT B - LV I/OSLOT C - LV I/OSLOT F - HV I/OSLOT G - HV I/OSLOT H - HV I/OFaceplateCurrent Protection** NN ** * * * A * * * * * * * * * * * * N Description850Feeder Protection Relay (Standard: English Language; High Voltage PS, Graphical Control MMGASMDAVoltage Monitoring nsS E1 E1 P3 A3 EAdvanced CommunicationConnectorWireless CommunicationSecurityNSCNWBAIndustrialDistribution Feeder1A three phase current inputs (J1) with 4 voltage inputs (J2)5A three phase current inputs (J1) with 4 voltage inputs (J2)No phase current inputs1A ground input (NA for N1)5A ground input (NA for N1)1A ground 1A sensitive ground input (NA if 2nd set of CT selected)5A ground 5A sensitive ground input (NA if 2nd set of CT selected)1A ground 1A polarizing current input (NA if 2nd set of CT selected)5A ground 5A polarizing current input (NA if 2nd set of CT selected)110 - 250 V dc/110 - 230 Vac24 - 48 VDCNone6 X RTDs (Pt100, Ni100, Ni120)6 X RTDs (Pt100, Ni100, Ni120, Cu10)None6 X RTDs (Pt100, Ni100, Ni120)6 X RTDs (Pt100, Ni100, Ni120, Cu10)15 Digital Inputs (for 24 V DC, Int/Ext supply)2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply)4 SSR (HSHB) 1 Critical Failsafe Relay 7 Digital Inputs (Low/High voltage, Int/Ext supply)None2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply)10 Digital Inputs 9 Digital Outputs8 Double Pole Output10 Digital Inputs 5 Digital Outputs (No Internal wetting, TCS) 1 Critical Failsafe Relay7 DcmA O/P 4 DcmA I/P 1 RTD4 SSR (HSHB) 1 Critical Failsafe Relay 7 Digital Inputs (Low/High voltage, Int/Ext supply)None2 Form A (Vmon), 3 Form C, 7 Digital Inputs (Low / High voltage, Int/Ext supply)10 Digital Inputs 9 Digital Outputs8 Double Pole Output10 Digital Inputs 4 Arc flash inputs10 Digital Inputs 5 Digital Outputs (No Internal wetting, TCS) 1 Critical Failsafe Relay4 SSR (HSHB) 1 Critical Failsafe Relay 7 Digital Inputs (Low/High voltage, Int/Ext supply)Basic : Membrane key padStandard : Rugged key padAdvanced : Membrane Front Panel with 10 PBsBasic 50P, 50N, 50G, 51P, 51N, 51GStandard Basic 50SG, 50 2, 51SG, 51 2, RGFStandard 37 (3), 50P (4/CT bank), 50N (4/CTbank), 50G (4/CT bank), 51P(4), 51N(4), 51G(2/CTbank), 50SG(4/CT bank), 50 2(4/CT bank), 51SG(2/CT bank), 51 2 (2/CT bank), RGF(3), SOTF (3/Bkr),67P (4), 67N (4), 67G (1/CTbanks), 67SG (1/CTbanks), 67 2 (1/CT bank), 49 (2), Load Encroachment(1/CT bank), Broken Conductor (3)Advanced Standard 67P, 67N, 67G, 67SG, 67 2, 49, Load Encroachment, Broken ConductorStandard 27P (4/VT banks), 27X (2/VT banks), 59P(4), 59N(4), 59X (2/VT banks), 81O (6/VT banks),81U (6/VT banks)Advanced Standard 25 (1/CT bank), 27T(4), 27Q (3/Bkr), 32(4), 32N(4), 55(4), 59 2(2/VT banks),81R (6/VT banks), Fast U/F (8), Neutral Admittance (3)Standard Basic Flexlogic, CLP, 50BF (2/CT bank), CT Spvn (3)Standard Setpoint Group Control, Virtual Inputs, Trip Bus (6), Breaker Control (1/Bkr), VTFF (1/ VTbank), FlexLogic, CLP (1/Bkr), 50BF (2/CT bank), Pole Discordance (3), Autorelcose (1/Bkr), CT Spvn (3)Advanced Standard Autorelcose, Bus Transfer (Requires voltage option P)Advanced HMI Advanced Tab PBs, Annunciator Panel, Configurable SLDs with Bay ControlAdvanced HMI Standard Tab PBs, Annunciator Panel, Configurable SLDs with Bay ControlBasic Breakers Coil Monitoring (1/Bkr), Breaker Arcing (1/Bkr), Harmonic Detection (6), THD,Current Demand (1/CT bank), Digital Counters (16), Data LoggerStandard Basic Advanced Breaker Health (1/Bkr)Advanced Standard Harmonic Detection (6) TEFD (1/Bkr)Standard Front USB, 1 x Rear RS485 : Modbus RTU, DNP3.0, IEC60870-5-103 1 x Ethernet(Modbus TCP, DNP)Advanced Front USB, 1 x Rear RS485 2 x Ethernet Fiber, MODBUS RTU / TCP, DNP3.0, IEC60870-5-103/104, 1588, SNTP, OPC UAAdvanced PRPAdvanced Extended IEC 61850Advanced PRP Extended IEC 61850NoneST, Multi-mode 1310nmRJ45, Copper 10/100MNoneWiFi 802.11BasicAdvanced - CyberSentry Level 1Note: Harsh Environment Coating is provided as standard on all 8 series units.* HV I/O, Option A - Max 2 across slots F through HArc Flash Detection (Option F): Includes 4 x Arc Flash sensors, each 18 feet (5.5 meters) longGEGridSolutions.comCONFIGURE ONLINE9

GEGridSolutions.comIEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registeredtrademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark ofSchneider Automation. NERC is a registered trademark of North American Electric Reliability Council. NISTis a registered trademark of the National Institute of Standards and Technology.GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General ElectricCompany.GE reserves the right to make

The Multilin 850 relay is a member of the Multilin 8 Series protective relay platform and has been designed for the management, protection and control of feeder applications. The Multilin 850 is used to provide primary (main) or backup protection for underground and overhead single or dual feeders for utility and industrial power networks.