SEMI-INSTANTANEOUSCOMPACTWATERHEATERContentsAbout the P-K COMPACT.2Anticipator' Temperature Control.Features and Benefits.Sizing Instructions.Fixture Capacity Table.DimensionsSteam to Water.DimensionsBoiler Water to Water.Selection TablesSteam to Water, Single Wall.Steam to Water, Double Wall.Boiler Water to Water, Single Wall.Boiler Water to Water, Double Wall.Piping Arrangements.14,15,Specilications.Inside Back Co' 1994, Patterson-Kelley, Division of Harsco Corporationreprinted 2005

PATTERSON-KELLEY’SFULLY PACKAGED HEATERIn'the late 1950s, Patterson-Kelleydeveloped the first line of completelypackaged commercial-industrial waterheaters. The P-K COMPACT semiinstantaneous water heater was part ofthat new concept when it was introducedback then. Over the years, improvementsto the heater’s design have representeda continuing evolution of the originalconcept. The P-K COMPACT has alwaysbeen completely assembled at our facilityand, since it requires only four pipingconnections, is shipped ready foreasy installation.HISTORY OF PERFORMANCEP-K COMPACT water heaters have performed reliably, providinglong, trouble-free operation in thousands of installations in all typesof commercial, institutional and industrial buildings as well as onNavy ships. Its present design, which focuses on a small heater thatproduces high hot water output at a closely controlled temperature,makes it the ideal water heater for any building owner.HIGH-OUTPUT HEATEROperating on steam, boiler water or high-temperature water,the P-K COMPACT produces up to 250 gpm at 40 F to 140 F.Though the largest unit has a footprint of only 8 sq. ft., the heatercan handle any building’s water heating requirements, either singlyor via multiple-unit installation.PRECISE TEMPERATURE CONTROLThe heater features P-K’s unique Anticipator control, whichcontinuously meters heating medium demand to exact proportionsof hot water requirements and regulates the hot water outlettemperature to a close tolerance of 4 F of set point, even withsudden fluctuating draws.PREVENTS SCALEConstantly pumped circulation prevents scale formation andaccumulation of foreign matter on the heating surfaces in mostwater conditions (water softening may be required with extremelyhard water). The constant circulation also continually monitorswater temperature, stabilizing temperature control at all draw rates.CONSTRUCTED FOR LONG SERVICE LIFEThe P-K COMPACT is built to last. Potable water in the shellcontacts only nonferrous materials, preventing rusty water, Theshell is constructed of solid 90-10 copper nickel, the premiumcorrosion-resistant material for potable water service. Standardheat exchanger construction is copper tubing, which will handlemost water conditions. Copper nickel is available for unusualwater conditions.

THE P-K GUARANTEEPatterson-Kelley guarantees thateach P-K COMPACT water heater willperform at the rated capacity. P-KCOMPACT capacity tables are basedon data developed by Heat Transferand Fluid Flow Service of AtomicEnergy of Canada. Ltd. The waterTEMPERATURE-LIMIT SYSTEMThe P-K COMPACT water heater is protected by a doublesolenoid temperature-limit system with a hot water dump valve.Should any overheating ot water occur, the lemperature-limit systemimmediately kicks in to shut off the heat source and dump overheatedwater into the dram. The valve controlling the heat source shuts offuntil normal hot water temperature is restored; the unit then assumesnormal operating conditions. Optional alarm and/or dry contact relayis available for remote service.NO OVERHEAD CLEARANCEThe P-K COMPACT is the easiest to service of the semiinstantaneous water heaters on the market today. The shellalways remains in place, so no overhead clearance is requiredfor service. The tubesheets have drilled and tapped bolt holes forindependent bolting, enabling the bonnet to be removed withoutbreaking the domestic water gaskets. If a tube were to leak, itcould easily be plugged off as a temporary fix and the unit putback into service within an hour. The steam or water chamberis easily removed without disturbing the piping to the unit, andthere is ready access to the lube bundle.DOUBLE WALL DESIGNThe P-K COMPACT is also available with a vented double-walltube bundle with double tubesheets. This design offers the ultimateprotection against cross-contamination of potable water and meetsboth health department and building codes. The P-K double-wall tubedesign creates maximum contact between inner and outer tubes toproduce effective heat transfer, while providing a vented leak pathas a visual means to indicate tube failure. The double-wall heatexchanger can be installed in any existing P-K COMPACT waterheater originally supplied with single-wail tubing. Contact thefactory or your local P-K representative to obtain furtherinformation, including the new rating.A.S.M.E. CONSTRUCTIONThe P-K COMPACT water heater is constructed in accordance withA.S.M.E. Code, Section VIII, Div. 1, and comes with an insurancecompany certificate of inspection and test.heater's capacities have been verifiedby Chalk River Nuclear Laborarories.Chalk River. Ontario, using an actualproduction unit. This is your assuranceof the water heater's performance.We also guarantee that ail materials,components and workmanship in theconstruction of each heater are of thehighest quality. If any part shouldprove defective within one year afterstart-up, a new part will be suppliedwithout charge, provided the waterheater is started within six monthsfrom the date of shipment.THE EXTENDED,NON-PRORATED GUARANTEESThe following componentscarry an extended, unconditional,non-prorated guarantee, included inthe submittal:Tube Bundle10-year guarantee againstfailure caused by thermal shock,mechanical failure or erosionPressure Vessel20-year guarantee against leakageAnticipator- Temperature Control20-year guarantee againstany failure

ANTICIPATOR5 CONTROL SYSTEMPRODUCES CLOSE TEMPERATURE CONTROLThe P-K COMPACT features theAnticipator- integral control systemwhich meters the heating mediumdemand to exact proportions of hotwater requirements and regulates hotwater outlet temperature to a dosetolerance of 4 f from the setpoint.This schematic shows the generalarrangement of the P-K COMPACT.Steam passes through the tubes ofthe heat exchanger bundle. The wateris rapidly heated as it is directed overthe tubes by segmental baffles insidea cylindrical wrapper. Above thewrapped tube bundle, minimumstorage volume is provided to give thecontrols sufficient time to produce theciose temperature control.4

FEATURES/BENEFITS OF THE P-K COMPACT WATER HEATER High-quality design and construction assure reliable performance and long service life. A complete package with only four piping connections enables quick, easy installation. Compact design saves valuable floor space and fits easily into position. High-capacity output: Up to 250 gpm at 40 F to 140 F allows the heater to meet thehot water requirements of any building. Performs equally welt with steam, boiler water or high-temperature water. Anticipator temperature control regulates hot water outlet temperatures 4SF. Constant circulation by the pump prevents scale formation and improves temperature control. All nonferrous construction on the water side prevents rusty water. Tube bundle drops downward from the heater, so no overhead room is required for service. Double solenoid temperature-limit system prevents overheated water from entering thedistribution system. Design meets seismic-restraint requirements, making it earthquake resistant. Built to A.S.M.E. standards; meets code requirements, Double-wall design available; meets B.O.C.A. and I.A.P.M.O. code requirements. Heat-transfer rates verified by independent testing agency, assuring that the heaterwill perform at rated capacity.(QCOMPACT

SIZING INSTRUCTIONS FOR THE P-K COMPACT1. Determine total fixture units for all fixtures by using the Fixture CapacityTable and following the example below,2. Determine the demand gpm from the Hot Water Demand Curves below,3. Select the proper size heater from the Steam to Water or Boiler Waterto Water Selection Tables on pages 10-13. For other capacities, contactyour P-K representalive or the factory.SIZE SELECTIONSelect a heater to heat 75 gpm of water from 40 F to 140 with steamin the line at 25 psig. From page 10 of the Selection Tables, select a sizePK08S to heat 80 gpm from 40“F to 140eF.EXAMPLE: 200 BOOM HOTELNO.FIXTURES20010201851046DemandTYPE OF FIXTUREFIX. UNIT75Private LavatoryPublic LavatoryPrivate ShowerTub and ShowerSlop BasinsBarber BasinsBeauty Parlor Basinsgpm from curve below 75 gpm,DEMANDFIX. UNITS1 01 51 525202.5150103027825815TOTAL FIXTURE UNITS: 516HOT WATER DEMAND CURVESFIXTURE UNITSThese tables arud Lhe P/ehmi.iary Ho! Water [tem-ang Table are reprinted tnpm the A.S.H.R.A.E. banuDoCA 'latest Systems Guide) with permission from A.S.H RAECORRECTION FACTOR FOR WATER TEMPERATURE VARIATIONSThe Fixture Capacity Table is based on consumption of 140 Fhot water using 40 F cold water to obtain 100 F mixed water atthe fixture. Any variation of these standard temperatures will affectthe hot water consumption.Therefore, the required gpm is: 75 x .71 54 gpm from 70 F to 140f'F.Your heater selection would be size PK06S, which has a rating of55 gpm from 70 F to 140 F. In most cases, the heater will operate at140 F and a mixed temperature of 100 F is satisfactory; however,the cold water supply may vary from job to job.To determine the effect on the size of the P-K COMPACT, use thefollowing procedure:1, Determine heater size from instructions above,2. Multiply the gpm rating by the correction factor from thefollowing formula:.i M —40 Correction FactorH-C100Where: M mixed temperature at fixture, C cold water temperatureand H hot water temperature from heater.% HOT FORMULAFor example, if the heater determined above has a rating of 75 gpm from40 F to 140“F and the actual cold water temperature is 70 F:The percentage of hot water for any application can be determined fromthe formula:100 TO i 100 — 40 140-170100.71Correction factorCorrection Factor tor Cold Water TemperaturesTemperature - Cold Water Supply, F40506070Correction Factor*1.00.93.83.71’Based on HOT water Irom the heater and 100 F mixed at fixtureM C x 100-%HotH-CSHOWER APPLICATIONSSpecial consideration should be given to applications involving periodic use of gang showers, such as may occur in field houses, gymnasiums, factories,institutions, YMCAs, etc. Use the following procedure: Multiply the number of shower heads by the hot water consumption rate in gpm. This gives the totalgpm hot water draw rate. The maximum gpm of hot water may be modified in accordance with Correction Factor for Water Temperature Variations.6

PRELIMINARY HOT WATER DEMAND ESTIMATEType of BuiltforngFIXTURE CAPACITY TABLEUnitFixture Llrwts Per UniiHospital or Nursing HomoRoom2 50Hotef or MqtelRoom2 50OHioo BuitemgPersona ISElememary SchoolStudentD:20wJr. and Sr. High SchoolsStudeni030'Apanmani3.00Apartment House14DT Temperature from Heater' P US iPiO vcr badHOSPITALRESTAURANT”FACTORYFix. UnitsType of FixtureFix, UnitsType of FixtureFix. UnitsPrivate Lavatories0.75Private Lavatory0.7Private Lavatory0.75Public Lavatories1.0Public Lavatory2.0Public Lavatory1.0Semi-Private Lavatories1.2fPrivate Shower1.5t Private Shower1 5TPublic ShowerType of Fixture3.0f Private Shower1.6TPublic Shower1.7TWard Shower2.5Sink — Kitchen3 0Sink — Slop2 5fSemr-Private Shower1.5Sink — Pantry2.536" Half Bradley1.0Private Bath1.5Sink — Slop2.036" Full Bradley1.5Ward BathSink — Pot (Single)2.554" Half Bradley1.5Sink — Flushing Rim2.02.0Sink — Pot (Double)3.554" Full Bradley2.0Sink — Scrub-Up1.6Sink — Pot (Triple)5.5Sink — Laboratory1.5Sink — Vegetable2,0Sink — General Purpose1.0Sink — Bar2,5Type of FixtureBath — Leg6.0Washer — Silver2,0*Private LavatoryFix. Units0 7Gath — Arm4.0Washer — Glass2.0'Public Lavatory1 0Bath — Sltz3.0Washer — Can3.0TPrivate Shower1,5Bath — Foot3.0Coffee Urn1.2TPublic Shower3.0Bath — Emergency2.0Baine Marie1.0 Tub and ShowerPot & Pan Washer2.0'Sink — SiopHy d rotherapeuti e Showers:CORRECTIONAL OR MENTAL INSTITUTION1.5#1 Shower Head8.0Dish Pre-Rinse2.5Janitor Drop2,02.0#2 Spray1.2P e-Scraper2.036fl Half Bradley1 0Pre-Sera per Conveyor2.5se* Full Bradley1.5Continuous Flow Bath:Continuous Flow Fill2.036 1 Half Bradley1.054’Half Bradley1.5Continuous Flow Operate1.536' Full Bradley1.554" Full Bradley2.0Hubbard4.0Autopsy Table2.0Autopsy Sink and Table2,5DISHWASHERS(use booster to heat from 140*F to I8QCRPublic LavatoryFix, Units0.751.0fPrivate Shower1 52.2TPublic Shower1,518x18 Rack3.7TTub and Shower1.520 x 20 Rack4,0Sink— Kitchen0 75CLUBType of FixtureFix. UnitsPrivate Lavatory0.75Public Lavatory1.016x16 RackT Private Shower1.5t Public Shower1.71.5Sink — Slop2.536" Half Bradley1.036" Full Bradley1.554" Half Bradley1.554" Full BradleyType of FixturePrivate LavatoryType of FixturetTub and ShowerAPARTMENTFix. UnitsSingle Tank. Stationary Rack:Sink — Slop1.52.02.5Sink — Pantry1.5Domestic Clothes Washer1.22.3Domestic Dish Washer1.5Laundry Tray1.5Multiple Tank Conveyor Type:Dishes — inclinedDishes — FlatSingle Tank Conveyor Type2.0HOTEL-MOTELPRIVATE-PUBLIC SCHOOLGYMNASIUMType of FixtureFix. UnitsType of FixtureFix. UnitsType of FixturePrivate Lavatory0.75Private Lavatory0.75Private LavatoryPublic Lavatoiy1.0Public Lavatory1.0Public LavatoryFix. Units0.751.0tPrivate Shower1.5fPrivate Shower1.5TPrivate Shower1.5TPublic Shower3.GtTub and Shower1.5tTub and Shower1.5Basin —- Barber2.0Sink — SlopSank — Si op1.72.5Basin — Foot1.2Sink — Slop2.5Janitor Drop1.536" Half Bradley1.0Basin — Beauty Parlor2.5Domestic Clothes Washer2.036' Full Bradley1.5Domestic Dish Washer2.054" Half Bradley1.52.054" Full BradleyASSOC. BLDG. ,'VMCAOFFICE BLDG.INSTITUTION-HOMEType of FixtureFix. UnitsType of FixtureFix. UnitsPrivate Lavatory0.75Type of FixtureFix, UnitsPrivate Lavatory0.75Public Lavatory1.0Private Lavatory0.7Public Lavatory1.0t Private Shower1 5Public Lavatory1.0tPrivate Shower1.5Sink — Slop2,5TPrivate Shower1.5TTub and Shower1.7Janitor Drop2.5Sink — Slop2.536" Half BradleyJanitor Drop2.036 Full Bradley1 01.5tTub and Shower1.5Sink — Slop2.0Janitor Drop2 0* These ilems require 1WJF hot water. The consumption figures are based on supplying 14G:F water with a booster healer used to oblain 1 SCT’F waler." Add 20% to all figures when nol used in combination with oiner building services from the same heater.f The fixture units listed for shower heads are based on a How rate of 0 gpm These units should be corrected for other flow rales. Multiply Ihe fixture units by Correciion Factor C" Irom theformula' C Gx .33, where “C Correction Factor and G gpm of shower head being used- Example Shower head 4 gpm C 4 x .33 or 1.32. From Fixture Capacily Table. Holel-Motel(showers) which shows 1.5 fixture units, multiply 1-5 * 1.32 2 C fixture units per shower head us mg 4 gpm.

DIMENSIONS:Tank Thermorriete\J5Steam to WaterKoe'.oDrainRelief ValveInsulation — TemperatureLimit System.Circulating Pump1 /2" N.P."Pipetop-'\DrainColdWater Inlet(5”FlangeonFK12)Steam and Boiler WaterTubesideComponentSingle WallDouble WallShell SideSB-171 -706 (Copper-Nickel)TubesSB-75-G12200 (Copper)Tubesheet (inner)SB-171 -464 (Nava) Brass)SA-516-GR 70 (Carbon Steel)Tubesheet (outer)NABonnetSA-278-Class 30 (Cast Iron)Billet'SA-516-GR 70 (Carbon Steel)' Boiler water and high-temperature water only.DIMENSIONS IN INCHESRoughing-ln Dimensions OnlyBPK061-1/2*2*69-1/8 22-1/4 18-1/831-1/820PK0B2*3*69-1/4 22-1/8188-3/413-7/8 31 -3/420PK102-1/2*4**3*72-3/4 22-5/8171214-3/4 33-1/25**85-1/22311-1/441-3/8PK12CDEAModel No.29F8Valve: Dimension varies with valve selected. Allow for maximum 16 ".Pneumatic valve shown. Self-contained available.8G1218H F.P.T * 150 # flangeLM78853/478841-1/22481-1/28923497-3/4 1012JK

Relief VolvoDIMENSIONS:Boiler Water to WaterC fi'j'fir ceLXBoilervVot.p'Ojt'etPRESSURE VESSEL DESIGN DATASteam and Boiler Water *oU Design PressureBundleRemovalArea155 psigDesign Temperature220T TubesideCOHydrostatic Test Pressure1 Design Pressure330 psig150 psigDesign Temperature315*FHydrostatic Test PressureJ300 psigDIMENSIONS IN INCHESRoughing-ln Dimensions /413-7/8 31-3/420788584PK102-1/2*3*72-3/414-3/4 33-1/224 81-1/289PK124**34 97-3/4101Model No,PK065” 85-1/21841-3/8Valve: Dimension varies with valve selected. Allow for maximum 161'.Pneumatic valve shown. Self-contained available. FPT.” 150 # flangePalterson-Kelley reserves the nghl to discontinue models or options al any time, or change speciticalions. equipment or designs without notice and wdhoul incurring obligation.

SELECTION TABLES: Steam to Water, Single WallHow to use the Selection Tables: To obtain the Model Number, intersect the gpm with steam line pressure.Example Required recovery' 38 gpm at 40QF to 140 F at 15 psig line pressure. Select Model Number PK08SAfrc*tu 1LUGPM1LINE PRESSURE PSIGn c . .2510Steam1525405075tooBUNDLE PRESSURE K06SPK06SPK06SPK06SPK06S 8SPKOBS1004000PK1 5075100LINE PRESSURE PSIG4u r to 14U rGPMSteam1525BUNDLE PRESSURE 2SPK12SPKlOSPKlOSPKlOS—NOTE For temperature ranges other than those shown here, please contact the P-K represenlative in your area10

SELECTION TABLES; Steam to Water, Double WallSizing selection for the doubSe-wall design is similar to single wall as described on page 10.Aft c fr\ nrvc4Ur [0 I4U rGPMLINE PRESSURE PSIG2510Steam1525405075100BUNDLE PRESSURE 2DPK1GDPK10DPKlODPKlODPKlOD2510405075100LINE PRESSURE PSIGi jiiyc4U r 10 14U rGPMSteam1525BUNDLE PRESSURE DPKlODPKlODNOTE: For temperature ranges other than those shown here, please contact the P-K representative in your area.

m INLET WATER20 8OILER WATER DIFFERENTIALBoiler Water Temperature180 to 160TempRangeHeaterSize200 to 180190 to 170210 to 190230 to 210220 to raWtrWtr0WtrWtraWtrWtraWtrWtraWtrWtraPDsFlow FlowPDsFlow FlowPDsFlow FlewPDsFlow FlowPDsFlow FlowPD 9pm gpmPSEsgpm gpmpsisgpm gpmpsisgpm gpmpsisgpm gpmpsi3psisEClcnFlow Flowgpm40PK06S12485.9413516 371491 92501973,32491963.32491963.22491953 293.3283327332PK12S1255003.72125313 34.7663126410496.1425972 1963 32391963.2239195322140PK10S331676.94412021 PK06SN/A3165 73,2416986 ,84392331 72553293.22553273 211452.74362487 44644412.927i4913.52m INLET WATER4(FF BOILER WATER DIFFERENTIALBoiler Water Temperature210 to 170200 to 160TempRangeHeaterSize230 to 190220 to aWtrWtrPaFiow FlowPDsFlow FlowPDSFlow FlowPDsFlow FlowPDgpmgpmpsisgpm gpmpsisgpm gpmpsisgpm 140PK10S38952.44631566 14671656,8468167092PK12S1002487,541002487 541353341.721984903 6240PK06S260,884102 4a5165.68722426toPK08S5161,68103157815465,1619567 56160PK10S17525.7829876 852521 0240PK06SN/AN/A271.283123 18toPKoasN/AN/A6192,2810357 56602075 346fPF INLET WATER40 F BOILER WATER DIFFERENTIALBoiler Water Temperature200 to 160TempRangeHeaterSize220 to 180210 to 170DomBlrPDomBlrPDomBlrWtrWtraWtrWtraWtrWtrPaFlow FlowPDsFlow FlowPDsFlow FiowPDsgpm gpmpsisgpm gpmpsisgpm 6996 K12SN/AN/A451347,56MHTFi-or temperatureother than thoseplease contact trepresentative itSELECTION TABLESBoiler Water to WaterSingle Wall

4QCF JKILET WATER2ITBOILER WATER DIFFERENTIALBoiler Water Temperature180 to 160TempRangeHeaterSize40PK06DtoPKOBD190 to raWtrWtraWtrWtraWtrWtraWtrWtrPDsFlow FlowPOsFlow FlowPDspsi gpm gpmpsisgpm gpmpsisFlow FlowPDsFlow FlowPDSFlow FlowPDsQpmgpmpsisgpm gpmpsisgpm PK06DtoPK08D140PK10DPK12D40PKOGDtoPK08D160PK10D*TF INLET 22267433.0171056.24392401.9to2N/AN/A2644N/A1393220 to 180210 to lrsFlow FlowP0sFlow FlowPDsFlow FlowPDsgpm gpmpsisgpm gpmpsisgpm gpmpsisgpm gpmpsi OD606F INLET WATER30847123205308317520530815511082829196 154302 682 1506 76 194414816864392350N/A61 432623.3466 0 9 2136 1.42 84 174 2 2 2308 3.22 150 308 3.2 2186,8 6 9 24 5 1 62446263 4493.84414108 8.0108 8.0210 0.8 2 119 308 3 2 210 3.7 6 4 13 3 8 6284.86 12 38 7 0 6722.8 4 33 102 6.2 451160 0 9 4155 6.74N/A152.1 8 6 22 6 7 8376.8 8 17 62 6.8 66 36 130 4.7 4836.73116SELECTION TABLESBoiler Water to WaterDouble WallBoiler Water TemperatureRangeHeaterSize210 to 170220 to 180DomBlrPDomBlrPDomBlrWtrWtraWtrWtraWtrWtrPaFlow FlowPDsFlow FlowPDsFlow FlowPDsgpmgpmpsiagpm gpmpsisgpm gpmpsis60PK06D12196.8 " F BOILER WATER DIFFERENTIAL200 to 160Temp29 223.123.023.32.6 23 022.923 224752.2 22923225.766.2 42.0 223.1aPDN/APK10D1232052 16 662 30 1233.12 50 2053.03.32 75 3081.42 12 623.02 24 1232 40 2052,92 60 3083,247,55311.0 2 17 1052.92 33 2052 50 3083.26,36 3 2243,79666,1 4 23 1662.6 2 43 3082.9PFlow FlowPK06DPKG8D56230 to 190SirPK12Dto12063Dom40PK06D22.6 63.664.362 6 2 1630123 3 12 302 5050 205 3 075 308 3.32 756 31 5.6 4 9982.0 2 241940 205 2.92 402 6060 308 3.245252.7410 62 6 3 4 12148 1.5242 332 5050 308 3.22N/A524296 712 86 4 3 4 1522 158 6 6 4 3915aBoi 1 er Wa t er Temperatu re6.8 6 10 21 1 122 46 3.4 4 30 62 6 42 50 103 6 350103 6,32 130 270 2 587180 1.2411 3.1 6 5 13 3.411 29 3.9 6 14 36 7.023602.2 4 38 98 5.5460155 6.760155 6.7N/A2 7 16310 1.5 8 6 20 5.310 31 5.2 8 18 54 6 0245,26 36 112 3.57540134Flow Flowgpm gpmP40‘F BOILER WATER DIFFERENTIAL200 to 160Temp230 to 210220 to 200Blr18 22308 3.37575 308 3 32421 4 2 6164.3312 62 6 4 436 2.44720 102 6.3 4 25 127 1 2 2198 1.42 60 308 32 239N/AN/A191.8 6 4 25 4.0 636 37 6.8 & 12 75 57 613806.76 25 T 54 67 4120210 to 190200 to 180Dom1,2 211 5.8 63154618284 51838450104475156aa9246252361451172.04.82.2626?2 4646.7664422.8 21996.8 6427565.244450104 6.24111 230 1.8 26 4 11 6,5 68 13 34 5.9 66 29 75 3.3 46 60 157 6.6 4N/A42,1 81312 38 6.8 86.72784626NOTEFor temperature rangesother than those shown here,please contact the P-Krepresentative in your area.

PIPING ARRANGEMENTSSteam System:Single Unit Installation-tx Slop Valve'VV* Check ValveSlrainerRelief ValveH&-Control VatveVOnfice UnionSleam T rapThermalControl GageCirculatorPressure GageBalancing Cock(p)-tftH(c)Pipe Unionor FlangesCompound'Pressure Gagev-5?ThermometerPetcockFlow IrUiCstorSteam System:Accumulator Type TankApplication:High RecoveryWater Heater

PIPING ARRANGEMENTSBoiler Water System:Single Unit InstallationTwo-Way Control Valve-IX}-Slop Valvg-Slraine--u4Check Valvefleliel Valve-c%-Control ValveVOrifice Union (?)(c)1-EhThermometerSteam TrapThermalControl GageCirculatorPressure GageSalarcmg CockPipe Unionor FlangesPetecckCompoundPressure GagePFlow Indicator

SPECIFICATIONS FORP-K COMPACT Semi-Instantaneous Water HeaterSTEAM TO WATERBOILER WATER TO WATERFurnish and install as shown on the plansP-K COMPACT water heater(s), Model Number ,manufactured by Patterson-Kelley Co.Each water heater shall be a factory-assembled package, rated to healgpm of water from. F to F, and control thedomestic fixture outlet temperature to within 4 F of the selectedtemperature when supplied with (select one):Steam to Water:psig saturated steam before the control valve.Boiler Water to Water:gpm of boiler water entering at F and leaving at F.Due to overhead clearance restrictions, each heater shall be capableof being disassembled in place, for maintenance and inspectionpurposes, without having to remove the shell from the domestic waterpiping. The heater's support shall provide ample clearance for tubebundle removal. A full diameter threaded tube sheet shall be providedto allow for inspection and maintenance while the shell remains underpressure.Each packaged water heater shall consist of the following components,completely factory-assembled, ready for connection to services:t. P-K COMPACT water heater with vertical support.2. Bronze A S M E. rated pressure and temperature relief valve setat 150 psig and 2lOaF3. Bronze circulator pump pre-wired with pilot fighted ON/OFF switchoperating at 115 volts/60 hertz/single phase. The purpose of the pumpis to prevent scale.4 Double solenoid temperature limit system.5 Insulation is in accordance with the current A S.H R A E standards. It isa flexible foam insulation laminated to a durable, reinforced PVC jacket.6. Integral Anticipator temperature control systemSteam to Water7. Temperature control valve — steam pilot operated or pneumaticwith air kit (select one)8. Float and thermostatic trap9. Domestic water thermometer (3-1/2“ diameter dial minimum) directmounted with separable thermowell.10. Steam pressure gauge (3-1/2" diameter dial minimum) with shut off cockBoiler Water to Water7 Boiler water control valve - 2 way (or 3-way bypass) pneumatic withtemperature controller and air kit NOTE: 3-way valve not suitable forservice over 250CF. Diverting valves will not be accepted8. Domestic water thermometer (3-1/2" diameter dial minimum) direct mountwith separable thermowell9. Boiler water thermometer (3-1/2" diameter dial minimum) direct mountwith separable thermowell.MATERIALS OF CONSTRUCTIONSHELL —90/10 Copper-Nickel, A,S M.Ecertified for 155 psigworking pressureTUBES — Copper or 90/10 Copper-Nickel (select one)Single Wall or Double Wall (select one}TUBE SHEET — Solid Copper AlloyBAFFLES-TeflonSHELL CONNECTIONS - Solid Copper AlloyFINAL ASSE

1994, Patterson-Kelley, Division of Harsco Corporation reprinted 2005 SEMI-INSTANTANEOUS COMPACT . WATER . HEATER . Contents About the P-K COMPACT.2 . Anticipator .