INSTALLATION INSTRUCTIONS

Transcription

INSTALLATION INSTRUCTIONS“EHK” Electric Heater Kitsfor use in Air HandlersATTENTION INSTALLING PERSONNELPrior to installation, thoroughy familiarize yourself with thisinstallation Manual. Observe all safety warnings. Duringinstallation or repair, caution is to be observed. It is yourresponsibility to install the product safely and to educatethe customer on its safe use.

CAUTIONSENSURE THAT ALL POWER IS DISCONNECTEDPRIOR TO ATTEMPTING INSTALLATION OFTHIS HEATER KIT. THERE MAY BE MORE THANONE DISCONNECT SERVICING THE UNIT.A MEANS OF STRAIN RELIEF AND CONDUCTOR PROTECTION MUST BE PROVIDED AT THESUPPLY WIRE ENTRANCE INTO CABINET.USE COPPER CONDUCTORS ONLY.INSTALLATION MUST FOLLOW NATIONALELECTRIC CODE AND OTHER APPLICABLECODES.IF THIS APPLIANCE IS INSTALLED IN AN ENCLOSED AREASUCH AS A GARAGE OR UTILITY ROOM WITH ANYCARBON MONOXIDE PRODUCING APPLIANCE, ENSURETHE AREA IS PROPERLY VENTILATED.

1.Remove the upper access panel from the air handler.2. Remove the cover plate from the air handler.1

3. Slide the heater kit into the slot and secure elementplate with previously removed screws.4. Align the attachment clip and the hole and fasten theloose wires by using wore tie.attachmentclip2

5. Install the circuit breaker into the mounting rail, breakout appropriate area of the plastic circuit breaker cover onthe access panel of the air handler.Connected to CN6Check screwsCheck screwsWARNINGFIRE, ELECTRICAL SHOCK, HAZARDAfter connect all wires ,check all screws of breaker and make sure all screws areproperly tight .Failure to do so will result in breaker malfunction,fire,death, personal injure or property damage."EHK" Electric Heater KitsNO.Kit#DescriptionRef. Air Handler use1EHK05A(UL)5kW Heat Strip18,24,30,36,42,48,602EHK08A(UL)7.5kW Heat Strip18,24,30,36,42,48,603EHK10A(UL)10kW Heat Strip18,24,30,36,42,48,604EHK15B(UL)15kW Heat Strip, Double Breaker's panel36,42,48,605EHK20B(UL)20kW Heat Strip, Double Breaker's panel36,42,48,60NOTE:indoor control board receives W1/W2 signal, electric heater will be energized and Whenindoor blower will be turned on.W1/W2 signal is off, indoor blower will be turned off after 90 seconds delay. WhenBlowermotor runs when “G”is energized, and a 90s off delay when “G”is de-energized. 3

"EHK" MCA/MOP DATAHeat KitModelAir Handler (kW)Electric MIN. Circuit L)EHK10A(UL)3030B364242C4860* Heat kit suitable for AHU 4-way position installation[4Fan speed(AC/HP)MAX.Fuse or Breaker(HACR) Ampacity ---- --- --- --- ---means available,--means not available].Medium High ------

MDV08I-076KW202000100150

1.Remove the upper access panel from the air handler. 2. Remove the cover plate from the air handler. 1 . 3. Slide the heater kit into the slot and secure element plate with previously removed screws. 4. Align the attachment clip and the hole and fasten the loose wires by using wore tie. 2