Temperature And Relative Humidity Sensor - Prochista.ir

Transcription

1

Temperature and Relative Humidity Sensor(PBUS Series with Display)Part No.PCT-RM05DTH0119DDocument No.951205119-6/12

This sensor enables your monitoring systemto monitor a location's temperature andrelative humidity.Using PBUS Rack monitor and via SNMPprotocol this sensor can be integrated withmany different tools such as Schneider,Emerson, Prochista DCM, IO, Nlyte, iTracs,HP OpenView, IBM Tivoli, CA, BMC, Modius,MRTG, Cacti, Nagios, Zenoss, ds & more . Plug and play config via one button No External power supply needed. The unit operates with PBUS line(Cat6 Ethernet Cable) Bright 7 Segment two line display Up to 16 sensors can operate on single bus Daisy chain connection support Accurate Swiss made factory trimmed sensor Design for wall mounted and rack mounted installationInstallationTo function properly, the unit must be oriented upward (upward direction marked onenclosure). Install the sensor in a location that represents the air to be monitored. Avoidplacing the sensor anywhere that may affect the sensor reading, such as near windows,room entrances, air ducts, other heat sources, or in direct sunlight.3

SpecificationElectricalInput voltagePBUS (7-15 VDC)Input currentMax 20 mAPower consumptionMax 200 mWNetworkProtocol support (via RM)HTTP, SNMP v1,SNMP v2, SNMP v3,SNMP Trap, DHCP, DNS, ICMPInterfacesRJ45 PBUS(single or double perrequest)Max cable lengthdepending on cable quality up to300mSensorTemperature resolutionMax 0.01 C̊Temperature accuracy0.3 C̊Temperature repeatability0.1 C̊Temperature long term drift 0.04 C̊ /yrHumidity resolutionMax 0.05 %RHHumidity accuracy1.8 %RHHumidity repeatability0.1 %RHHumidity long Term drift 0.5 %RH/yrEnvironmental conditionsOperation Temperature Range-10 C̊ –70 ̊COperation Humidity Range95%RH or less (without dewcondensation)Recommended Storage Temperature-20 C̊ – 85 C̊4

ConfigurationFor configuring the unit simply login into rack monitor’s webpage, by defaultthe unit boots in static IP mode. The unit's default IP is "172.16.0.1", defaultUsername and Password is "prochista”. Then press sensor’s button(sensor’sled turn green),after that in rack monitor’s webpage select “set probe” ondesire ID.Mechanical Dimension (mm) :5

HTTP, SNMP v1,SNMP v2, SNMP v3, SNMP Trap, DHCP, DNS, ICMP Protocol support (via RM) RJ45 PBUS(single or double per request) Interfaces depending on cable quality up to 300m Max cable length Sensor Temperature resolution Max 0.01 ̊C Temperature accuracy 0.3 ̊C Temperature repeatability 0.1 ̊C Temperature long term drift 0.04 ̊C/yr