Industrial Power Supplies

Transcription

Industrial Power SuppliesTIS Series, 50–600 WattCBFeatures Switch mode power supplies for(LVD)DIN-rail mountSchemeUL 60950-1 UL 508UL 62368-1 UL 1604 6 power ranges with 2, 3, 6, 12, 20 and24 A output current (24 VDC models) Selectable 115/230 VAC input Very low ripple and noise EMI complies with EN 61000-6-3 andEN 61000-6-4 Operating temp. range –25 C to 70 C For system operation available withbuilt-in functions:RED: Redundancy module for N 1Systems with true current sharingSIG: Signal module with AC-powerfail, power good signal andexternal On/Off controlUDS: DC-UPS module for uninterruptable battery backed-uppower systems Worldwide safety approvals incl.class I, div. 2 location Easy snap-on mount on DIN-railsor chassis mount 3-year product warrantyThe switching power supplies of the TIS series have been particularly designed forapplications in industrial process control systems and with machine tools. Excellentspecifications and high immunity against electrical disturbances guarantee reliablepower for sensitive loads in rugged industrial environments. With the help of optional function modules specific requirements for system applications can be easilyrealized with a standard model. With the UDS module the power supplies can beextended to a perfect DC-UPS with automatic battery- backup. This function is veryoften required in applications where a time delayed shutdown of a system is necessary. To monitor and control the power supply a signal module can be installed.For parallel operation with active power sharing a redundancy option is available.This flexibility makes the TIS series power supplies a cost effective solution for manyindustrial applications.ModelsOrder Code(includes terminal plugs)TIS 50-112TIS 50-124TIS 75-112TIS 75-124TIS 75-148TIS 150-124TIS 150-148TIS 300-124TIS 300-148TIS 300-172TIS 500-124-115TIS 500-124-230TIS 600-124TIS 600-148TIS 600-172http://www.tracopower.comInput Voltagenom.115–240 VACuniversal inputOutput Powermax.50 W115/230 VACselectable75 W115/230 VACselectable150 W115/230 VACselectable300 W115 VAC230 VAC500 W500 W115/230 VACselectable600 WOutput Voltagenom.12 VDC24 VDC12 VDC24 VDC48 VDC24 VDC48 VDC24 VDC48 VDC72 VDC24 VDC24 VDC24 VDC48 VDC72 VDCOutput Currentmax.3.5 A2.0 A6.0 A3.0 A1.5 A6.0 A3.0 A12.0 A6.0 A4.2 A20.0 A20.0 A24.0 A12.0 A8.5 APage 1 of 12

Industrial Power SuppliesTIS Series 50–600 WattInput SpecificationsInput voltage rangeTIS 50:TIS 75, 150, 300, 600:TIS 500-124-230.TIS 500-124-115:93 – 264 VAC93 – 132 VAC / 187 – 264 VAC187 – 264 VAC93 – 132 VACInput frequency 47 – 63 HzInput current at full load (typ.)TIS 50:TIS 75:TIS 150:TIS 300:TIS 500:TIS 600:at 115 VAC0.85 A1.3 A2.7 A4.9 A6.0 A7.0 ARecommended circuit breaker,TIS 50:characteristic CTIS 75:or fuse, slow blow typTIS 150:TIS 300:TIS 500:TIS 600:5.0 A5.0 A10.0 A15.0 A15.0 A20.0 Aat 230 VAC0.50 A0.75 A1.6 A2.9 A4.3 A5.0 AOutput SpecificationsOutput voltage adj. range12 VDC models:24 VDC models:48 VDC models:72 VDC models:12 – 14 VDC24 – 28 VDC48 – 52 VDC60 – 76 VDCRegulation0.2 %1.0 %0.3 %(2.0 % in parallel operation)– Input variation– Load variation (10–90%) TIS 50, TIS 75, TIS 150:TIS 300, TIS 500, TIS 600:Ripple and noise (20MHz bandwidth) 50 mV pk-pkElectronic short circuit protection current limitation at 110 % typ.(constant current, automatic restart)Over voltage protection, trigger point at 140 % typ. Vout nom.Hold-up timeTIS 50 . TIS 300:TIS 500:TIS 600:http://www.tracopower.com115 VAC 230 VACmin. 25 msmin. 30 msmin. 20 msmin. 40 msmin. 15 msmin. 25 msPage 2 of 12

Industrial Power SuppliesTIS Series 50–600 WattGeneral SpecificationsTemperature ranges– Operating (ambient temp.) –25 C to 70 C– Derating above 50 C (122 F) 2 %/K– Storage (non operating) –25 C to 85 CHumidity (non condensing) 95 % rel. H max.Pollution degree 2Temperature coefficient 0.02 %/KAltitude during operation 2’000 m max.Switching frequency 80 kHz typ. (pulse width modulation)EfficiencyTIS 50 . TIS 300: 85 % typ.TIS 500: 90 % typ.TIS 600: 90 % typ.Isolation according to IEC/EN 60950, UL 60950, UL 508Reliability, calculated MTBF(MIL-HDBK-217F, at 25 C, ground benign)TIS 50/75: 450’000 h / 420’000 hTIS 150/300: 420’000 h / 360’000 hTIS 500/600: 340’000 h / 300’000 hSafety standards IEC/EN 60950-1 (SELV, except 72 VDC models)UL/cUL 60950-1, UL 508, UL/cUL 1604Safety approvals– CB report for IEC 60950, IEC 62368-1– UL approvals UL/cUL 60950, File e181381UL 62368-1UL/cUL 508, File e210002UL/cUL 1604, File e213613 not for TIS 50 & 500(Class I, Div. 2, Groups A, B, C and D hazardous locations)www.ul.com - certifications– CSA certificate UL 60950-1, CSA 60950-1– Certification documents www.tracopower.com/overview/tisElectromagnetic compatibility (EMC), Emissions– Conducted RI suppression on input– Radiated RI suppressionEN 61000-6-3 / EN 61000-6-4EN 55011 class B, EN 55022 class B,FCC part 15, level BEN 55011 class A, EN 55022 class A,FCC part 15, level AElectromagnetic compatibility (EMC), Immunity– Electrostatic discharge (ESD)– Radiated RF field immunity– Electrical fast transient / burst immunity– Surge immunity– Immunity to conducted RF disturbances– Power frequency field immunityEN 61000-6-2IEC/EN 61000-4-2IEC/EN 61000-4-3IEC/EN 61000-4-4IEC/EN 61000-4-5IEC/EN 61000-4-6IEC/EN 61000-4-84 kV/8 kV10 V/m2 kV2 kV/4 kV10 V30 A/mSafety class degree of electrical protection 1 (IEC 536)Case protection IP 20 (IEC 529)Environment– Vibration IEC 60068-2-6; 1 gn, 200 sweeps, each axis– Shock IEC 60068-2-27; 15 gn, 11 ms, each axisEnclosure material aluminium (chassis) / zinc plated steel (cover)Mounting (snap-on with self locking spring) for 35 mm DIN-rails as per EN 50022Connection detachable screw terminal block(plugs included)(TIS 600: fixed screw terminal block)Instruction manual can be downloaded under:www.tracopower.com/overview/tisAll specifications valid at nominal input voltage, full load and 25 C after warm-up time unless otherwise stated.http://www.tracopower.comPage 3 of 12

Industrial Power SuppliesTIS Series 50–600 WattPower Supplies with Redundancy FunctionWith this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N 1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure.This option is available for TIS 150 W, TIS 300 W and TIS 600 W models.Please note: This option cannot be combined with other options.ModelsInput VoltageOutput PowerOutput VoltageOutput Currentmax.nom.max.24 VDC6.0 A48 VDC3.0 A24 VDC12 A48 VDC6.0 A24 VDC24 A48 VDC12 A(includes terminal plugs)TIS 150-124 RED115/230 VACselectableTIS 300-124 RED115/230 VACTIS 300-148 REDselectableTIS 600-124 RED115/230 VACTIS 600-148 REDselectable115/230VACTIS 150-148 REDLNCon1Pin3Con1Pin2150 W300 W600 WCon2 - Pin3/4ACBusIndicatorDCCon2 - Pin1/2 Vout24/48VDCOrder Code-VoutCon1Pin1I-SenseV-SenseCon3 - Pin4Con3 - Pin3Con3 - Pin2Con3 - Pin1RegulatorCurrentSharelineUnit OKCommonUnit OKUnitOKSpecificationsRating per relay contact 60 VDC /0.36 A max.Instruction manual for RED option can be downloaded acopower.comPage 4 of 12

Industrial Power SuppliesTIS Series 50–600 WattPower Supplies with Powerfail FunctionsThese models provide 3 functions required in many process control system applications: AC-Powerfail signal (relay contact) Power Good signal (relay contact) Remote On/OffModelsOutput Powermax.(includes terminal plugs)TIS 150-124 SIG115/230 VACTIS 150-148 SIGselectableTIS 300-124 SIG115/230 VACselectableTIS 600-124 SIG115/230 VACTIS 600-148 SIGselectable115/230VACTIS 300-148 SIGLNCon1Pin3Con1Pin2150 W300 W600 WOutput Voltagenom.max.24 VDC6.0 A48 VDC3.0 A24 VDC12 A48 VDC6.0 A24 VDC24 A48 VDC12 ACon2 - Pin3/4AC VoutOutputOKDCCon2 - Pin1/2Con1Pin1Con3 - Pin2RemoteON/OFF-Vout Con3 - Pin1-Con3 - Pin7Con3 - Pin6MainsFailDetectionOutput Current24/48VDCInput VoltageRemoteON/OFFOrder CodeCommonAC-PowerfailMains OK(Relay A)Con3 - Pin5Con3 - Pin4Con3 - Pin3Power GoodDetection(Relay B)Power GoodCommonPower GoodPower GoodSpecificationsPower Good signal trigger pointmodels with 24 Vout: 22.8 VDC 0.5 V relay B closed (pin 4 – pin 3)models with 48 Vout: 45.6 VDC 1.0 V relay B closed (pin 4 – pin 3)AC-Powerfail signal Vin 93 resp. 187 VAC relay A closed(pin 7 – pin 6)Raiting per relay contact 60 VDC /0.36 A max.Remote On/Off– Onshort circuit con 3 pin 1 and pin 2– Off open circuit con 3 pin 1 and pin 2Instruction manual for SIG option can be downloaded acopower.comPage 5 of 12

Industrial Power SuppliesTIS Series 50–600 WattDC-UPS-SystemIn addition to the standard power supply function, these modelsinclude a professional battery management system to charge andmonitor an external battery. In the event of a power failure thebattery is switched automatically and without any interruption tothe DC output. Once mains power is available again, the batteryis switched off. The backup time is limited only by battery capacityand load. Charge current and voltage can be adjusted to values asrequired by battery type. Power fail and low battery alarm signalsare available via two independent relay contacts. During normaloperation the battery status is monitored by periodically loadingthe battery for a short time. If a cell resistance is high, there is arelay alarm is available. The battery is fully protected under anyoperational conditions. The power supply is short circuit protectedeven in battery backup operation but, for safety reasons, the battery should be fitted with a fast blow fuse. Battery mode can beactivated by interconnecting pin 7 and 8.ModelsOrder Code 1)TIS 300-124 UDSInput Voltage115/230 VACOutput PowerOutput VoltageOutput Current 2)max.nom.max.300 W24 VDC12 A600 W24 VDC24 AselectableTIS 600-124 UDS115/230 VACselectable1) Includes terminal plugs, does not include batteries2) reduce max. output current by battery charging currentExternal BatteriesFor external batteries we recommend:Two Panasonic LC-R123R4PG in series for 3.4 Ah: www.tracopower.com/products/tsp-panas 034.pdfTwo Panasonic LC-R127R2PG1 in series for 7.2 Ah: www.tracopower.com/products/tsp-panas 072.pdfMounting Devices for BatteriesOrder Code:TIS 24-32AF Frame & wiring for two Panasonic LC-R123R4PG batteriesTIS 24-70AF Frame & wiring for two Panasonic LC-R127R2PG1 batterieshttp://www.tracopower.comPage 6 of 12

Industrial Power SuppliesTIS Series 50–600 WattDC-UPS-SystemCon3 - Pin2Battery V Battery ChargerCon3 - Pin1ICon1Pin3LNCon1Pin2ACCon2 - Pin3/4OutputOKDCCon2 - Pin1/2Con1Pin1 Vout24VDC115/230VACBattery --VoutVBat 18VBat ON/OFFMains FailBattery SwitchLogicCon4Pin8BatteryON/OFFCon4 - Pin3Con4 - Pin2Con4 - -Power OKAC-Powerfail(Relay A)Con4 - Pin6Con4 - Pin5Con4 - Pin4BatteryTestBattery Low / failureCommonBattery OKLow Battery(Relay B)SpecificationsCharging current (factory set)TIS 300-124 UDS: 1.2 ATIS 600-124 UDS: 2.4 AAdjustment range of charging currentTIS 300-124 UDS: 0.15 – 1.5 ATIS 600-124 UDS: 0.25 – 2.5 AHolding current for charged battery at voltage 27.3 VDC 50 mAOverload or short circuit during battery operation system switches offAC-Powerfail signal Vin 93 or 187 VAC relay A closed(pin 2 – pin 3)Low battery signal– Battery voltage below 22 V relay B closed (pin 5 – pin 6)– Raiting per relay contact 60 VDC /0.36 A max.During battery charge operation output current reduction by 1.4 x battery charge currentSupporting documents : er.comPage 7 of 12

Industrial Power SuppliesTIS Series 50–600 WattCase DimensionsModelTIS 50-112InputL NOutput –12 VDC115/230 VAC1,2/0,7 A 3,5 A575 (2.95)(0.2) –39.5adj(1.56)34 (1.34)114.6 (4.51)IndustrialPower SupplyOutputL N115/230 VAC 12 VDC6 A1,7/0,9 AIndustrialPower SupplyDC-ON86.5 (3.4)(1.24)26InputDC-ON74.0 (2.91)100.0 (3.94)adj31.5TIS 75 models(1.02)TIS 50 modelsModelTIS 75-11256.7590 (3.54)(2.23)(0.2)37.556.7(2.23)1010(0.39)Weight: 0.41 kg (0.9 lb)(0.39)45 (1.77)(1.48)Weight: 0.48 kg (1.06 lb)IndustrialPower SupplyModelTIS 150-124Input115/230 50/60Hz3,7/1,7 AN L(1.56) –24 VDC / 6 ADC-ON86.5 (3.4)114.6 (4.51)Output39.534 (1.34)TIS 150 models5157 (6.18)56.7 (2.23)(0.2)38.580 (3.15)10(0.39)(1.52)Connectors ( Included in shipment)Weight: 0.80 kg (1.76 lb)TIS PLUG-1Connector Set for TIS 50/ 75/ 150TIS PLUG-1-REDConnector Set for TIS 150-1xx REDDimensions in [mm], () InchTolerances: 0.5 ( 0.02)http://www.tracopower.comPage 8 of 12

Industrial Power SuppliesTIS Series 50–600 WattCase Dimensions91.5 (3.6)Model(1.56)DC-ONIndustrialPower SupplyTIS300-172(1.36)114.6 (4.51) – –72 VDC / 4 A39.5Output34.534 (1.34)TIS 300 modelsInput115/230 50/60Hz5,4/3,3 AN L207 (8.15)51083 (3.27)(0.39)130 (5.12)38.5(1.52)83 (3.27)(0.2)Connectors ( Included in shipment)Weight: 1.4 kg (3.09 lb)TIS PLUG-3Connector Set for TIS 300TIS PLUG-3-REDConnector Set for TIS 300-1xx REDTIS PLUG-3-UDSConnector Set for TIS 300-1xx UDSTIS PLUG-5Connector Set for TIS 500IndustrialPower SupplyTIS 500-124-23047(1.85)DC-ONModelInput94 (3.7)130 (5.12)41.5 (1.63)TIS 500 modelsOutput230 VAC 50/60Hz5,3 AN L24 VDC / 20 A – –5220 (8.66)83 (3.27)(0.2)(5.12)Weight: 1.9 kg (4.19 lb)http://www.tracopower.com(0.39)1301046 (1.81)Dimensions in [mm], () InchTolerances: 0.5 ( 0.02)Page 9 of 12

Industrial Power SuppliesTIS Series 50–600 WattOutline Dimensions mm (inches)TIS 600 modelsInputIndustrialPower Supply115/230 VAC 50/60Hz10,5/6,4 AOutput– – 24 VDC / 20 A120.2 (4.73)177.2 (6.98)N LModelTIS 600-12482.6 (3.25)243 (9.57)32179 (7.05)6.8(0.27)82.8 (3.26)(1.26)Weight: 2.0 kg (4.41 lb)Connectors ( Included in shipment)TIS PLUG-6-REDConnector Set for TIS 600-1xx REDTIS PLUG-6-UDSConnector Set for TIS 600-1xx UDSDimensions in [mm], () InchTolerances: 0.5 ( 0.02)http://www.tracopower.comPage 10 of 12

Industrial Power SuppliesTIS Series 50–600 WattOptional Mounting SystemsWall mounting kitAB7.54.6ModelsOrder code(0.30)EDC(0.18)ABCDETIS 75MK-7537 (1.46)14.5 (0.57)–134.5 (5.30)150.5 (5.93)TIS 150MK-150132 (5.20)13.5 (0.53)105 (4.13)134.5 (5.30)150.5 (5.93)TIS 300MK-300132 (5.20)13.5 (0.53)105 (4.13)134.5 (5.30)150.5 (5.93)TIS 500MK-500132 (5.20)13.5 (0.53)105 (4.13)134.5 (5.30)150.5 (5.93)TIS 600MK-600190 (7.48)37.5 (1.48)115 (4.53)197.0 (7.76)207.0 (8.15)Rugged DIN-Rail mounting kitAB25countersink M4ModelsOrder codeABCTIS 150RMK-150150 (5.91)115 (4.53)35 (1.38)TIS 300RMK-300200 (7.87)165 (6.50)35 (1.38)TIS 500RMK-300200 (7.87)165 (6.50)35 (1.38)TIS 600standard180 (7.09)165 (6.50)15 (0.59)(0.98)50.1 (1.97)4.2 (0.17)CDimensions in [mm], () InchTolerances: 0.5 ( 0.02)http://www.tracopower.comPage 11 of 12

Industrial Power SuppliesTIS Series 50–600 WattOutline Dimensions mm (inches)TIS 24-32AF (Frame & wiring, excluding batteries)204 (8.03)14184 (7.24)(0.55)Detail A7712Detail B9(0.28)69 (2.72)(0.47)5.8B(0.35)B135 (5.14)A100 (3.94)A(0.23)(0.28)TIS 24-70AF (Frame & wiring, excluding batteries)272 (10.71)ABB69 (2.72)100 (3.94)A152 (5.98)252 (9.92)Dimensions in [mm], () InchTolerances: 0.5 ( 0.02)Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.comwww.tracopower.comRev. November 11, 2021Page 12 of 12

Industrial Power Supplies TIS Series 50-600 Watt Input Specifications Input voltage range TIS 50: 93 - 264 VAC TIS 75, 150, 300, 600: 93 - 132 VAC / 187 - 264 VAC TIS 500-124-230. 187 - 264 VAC TIS 500-124-115: 93 - 132 VAC Input frequency 47 - 63 Hz Input current at full load (typ.) at 115 VAC at 230 VAC