Wastewater Infrastructure Standard Details - Irish Water

Transcription

Wastewater InfrastructureStandard DetailsConnections and Developer ServicesDesign and Construction Requirements for Self‐Lay DevelopmentsJuly 2020 (Revision 4)IW‐CDS‐5030‐01Document IW‐CDS‐5030‐01

Revision LogDateApril 2016August 2016December 2017July 2020Details of RevisionGeneral revisionsGeneral revisions &drawing addedGeneral revisions &drawing addedGeneral revisions &drawings O’D03TO’CMO’D04TO’CMO’D

BackgroundTechnical Documentation has been developed by Irish Water’s Connections andDeveloper Services which outlines the requirements for wastewater servicesinfrastructure within developments.These Standard Details have been developed to outline to developers Irish Water’srequirements for the provision of wastewater infrastructure that is to be installed indevelopments and that would be connected to Irish Water’s networks and subsequentlyvested in Irish Water.The Standard Details outline design and construction requirements to ensureconsistency in the provision of materials, equipment and workmanship, etc. They alsoprovide the basis for developers’ detailed design proposals for wastewaterinfrastructure, leading to the provision of infrastructure that is suitable for connection toIrish Water’s networks and easy operation and maintenance of the new infrastructure.The Standard Details are based on best practice within the water industry. They takeaccount of the experience of Local Authorities in the provision of these services to newdevelopments. They have been successfully used by Irish Water’s own internalfunctions for a variety of projects and they are in line with water utility industry norms.There are 58 No Standard Details dealing with wastewater infrastructure covering allaspects of such infrastructure.These Standard Details are accompanied by a Design Risk Assessment (DRA)(document number IW-CDS-5030-02), which outlines the residual health and safetyresponsibilities of developers and their designers/contractors in the provision of suchinfrastructure.The use of the Standard Details is mandatory in all new Irish Water ConnectionAgreement Offers issued after 1st June 2016.

INDEX SHEETDetail TitleRev.STD-WW-01Wastewater service connection maintenance responsibility2STD-WW-02Typical layout for sewer within new developments2STD-WW-03Drain & service connection pipework2STD-WW-04Typical sewer / service pipe connection2STD-WW-05Typical service layout indicating separation distances2STD-WW-05AWastewater service connection vertical separation distances0STD-WW-06Restrictions on wastewater infrastructure works adjacent to trees2STD-WW-06ARestrictions on new trees/shrubs planting adjacent to sewers1STD-WW-07Trench backfill & bedding2STD-WW-08Concrete protection slab, bed, haunch & surround to wastewater pipes1STD-WW-09Blockwork manhole ( 450mm dia.)3STD-WW-10Pre-cast concrete manhole with cast in-situ base3STD-WW-10APre-cast concrete manhole with pre-cast base0STD-WW-10BPre-cast concrete pumping station inlet manhole with cast in-situ concrete base0STD-WW-10CPre-cast concrete pumping station inlet manhole with precast concrete base0STD-WW-11In-situ concrete manhole3STD-WW-11ACast in-situ concrete pumping station inlet manhole0STD-WW-12Backdrop and cascade manholes3STD-WW-13Private side inspection chamber3STD-WW-14Thrust blocks for rising mains2STD-WW-15Scour valve chamber (foul rising main 200mm dia.)3STD-WW-16Sluice valve details for rising mains ductile iron (D.I.) pipe ( 200mm dia.) (sheet 1 of 2)4STD-WW-17Sluice valve details for rising mains polyethylene (P.E.) pipe ( 200mm dia.) (sheet 2 of 2)3STD-WW-18Air valve chamber (foul rising main 200mm dia.)3STD-WW-19Duct chamber3STD-WW-20Emergency overflow structure & emergency overflow to storm sewer2STD-WW-21Typical ditch/stream crossing for gravity sewer (sheet 1 of 2)2STD-WW-22Typical ditch/stream crossing for ductile iron rising main (sheet 2 of 2)2STD-WW-22ATypical ditch/stream crossing for polyethylene rising main0STD-WW-23Typical bridge crossing for rising main (sheet 1 of 2)2STD-WW-24Typical bridge crossing for rising main (sheet 2 of 2)2STD-WW-24ATypical culvert and services crossing details for rising main0STD-WW-25Security gate & fencing palisade option (preferred)0STD-WW-25ASecurity gate & fencing wire mesh option3STD-WW-26Indicative pumping station site layout – access via lay-by1STD-WW-26AIndicative pumping station site layout – direct access from public road0STD-WW-27Flow meter chamber (foul rising main 200mm dia.) cast in-situ concrete option3STD-WW-27AFlow meter & valve chamber (foul rising main 200mm dia.) cast In-situ concrete option0STD-WW-27BFlow meter & valve chamber (foul rising main 200mm dia.) pre-cast concrete option0STD-WW-27CFlow meter & valve chamber (foul rising main 200mm dia.) pre-cast concrete option0STD-WW-28Cast in-situ Indicative submersible pumping station3STD-WW-28AIndicative pre-cast concrete submersible pumping station with cast in-situ valve chamber2STD-WW-28BIndicative pre-cast concrete submersible pumping station and pre-cast valve chamber0STD-WW-29Rising main discharge stand-off manhole3STD-WW-30Type 1 pumping station control kiosk3STD-WW-30AType 2 and type 3 pumping station control kiosk0STD-WW-31Pumping station wet kiosk3STD-WW-31APumping station wet kiosk water service connection arrangement0STD-WW-32Hardstanding area pumping station (permeable & impermeable)2STD-WW-33Lamp bollard & lamp standard2STD-WW-34Vent stack2STD-WW-35Rising main rodding chamber in-situ concrete option0STD-WW-35ARising main rodding chamber pre-cast concrete option0STD-WW-36Marker posts/plates0STD-WW-37Section showing wastewater services separation details in high density developments 2.5m wide footpaths with 6.0m wide carriageway0STD-WW-38Layout plan showing below ground services separation details in high density developments 2.5m wide footpaths with 6.0m wide carriageway0STD-WW-39Section showing wastewater services separation details in high density developments 1.8m wide footpaths, 2.5m wide parallel parking bays with 6.0m wide carriageway.0STD-WW-40Layout plan showing below ground services separation details in high density developments 1.8m wide footpaths, 2.5m wide parallel parking bays with 6.0m wide carriageway.0Standard Details Wastewater NetworksDetail No.

These Standard Details show the acceptable typical details and outline the minimum standards that are required by Irish Water for theprovision of wastewater pipes and related infrastructure which are to be connected to the Irish Water Network. They shall be used inconjunction with the associated Code of Practice for Wastewater Infrastructure and Design Risk Assessments that have been developedwhich identify the risks that designers shall take into account in the detailed design of the wastewater pipes and related infrastructure tobe connected to the Irish Water Network. The pipes and related infrastructure to be put in place within developments shall comply fullywith these Standard Details. Ultimate responsibility (including, but not limited to, any losses, costs, demands, damages, actions,expenses, negligence and claims) for the detailed design, construction and provision of such pipes and related infrastructure shall restentirely with the Developer, his/her Designer(s), Contractor(s) or other connected party. Irish Water assumes no responsibility for andgives no guarantees, undertakings or warranties in relation to the pipes and related infrastructure to be provided in accordance with theseStandard Details.No part of the Standard Details shall be reproduced or transmitted in any form or stored in any retrieval system of any nature without theprior written permission of Irish Water as copyright holder, except as agreed for use.These Standard Details shall be used in conjunction with current Irish Water Codes of Practice, which will take precedence over theStandard Details.These Standard Details may also be used for the installation of wastewater infrastructure for Asset Delivery Works & Capital ProjectWorks Programmes at the discretion of Irish Water.July 2020

VENT STACKCUSTOMER PROPERTYSEE NOTE 2 ONSTD-WW-03PROPERTY BOUNDARYWITHIN1m OFBOUNDARYFOOTPATHROADSERVICE CONNECTIONINSPECTION CHAMBERDRAINSEWER( IRISH WATER RESPONSIBILITY )PROPERTY OWNER MAINTENANCE RESPONSIBILITYMAINTENANCE RESPONSIBILITY OF THEWASTEWATER SERVICE CONNECTIONS FROMTHE SEWER TO THE BOUNDARY IS SET OUT INTHE PIPE MAINTENANCE RESPONSIBILITYDIAGRAMS INCLUDED ON THE IW WEBSITE @WWW.WATER.IEMAINTENANCERESPONSIBILITY( A ) SEWER( B-C ) SERVICE CONNECTION( INCLUDING SADDLE )IRISH WATERSEE NOTE ABOVEINSPECTION CHAMBERPROPERTY OWNER( C-D ) DRAINPROPERTY OWNERINTERNAL PLUMBINGPROPERTY OWNERREFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLEWASTEWATER SERVICECONNECTION MAINTENANCE RESPONSIBILITY2 07/'20 RH TOC B-C ownership revised1 11/'17 JMC TOC Note reference added0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

ROCKER PIPE END TO BE CAPPED TO ENSUREPIPE IS KEPT FREE FROM DEBRIS & VERMINPLAN CO-ORDINATES &I.L. OF PIPE END TBC BYDEVELOPERS DESIGNENGINEER PRIOR TOCOMMENCEMENT OFWORKS1. THE MINIMUM SIZE FOR A GRAVITY FOUL SERVICE CONNECTION SHALL BE 100mm DIAMETER.2. THE MINIMUM SIZE OF GRAVITY FOUL SEWER SHALL BE 225mm DIAMETER IN GENERAL. GRAVITYSEWERS ON BRANCHES SERVING 20 OR LESS PROPERTIES TO BE 150mm DIAMETER SUBJECT TOAGREEMENT WITH IRISH WATER.MANHOLE3. THE MINIMUM SIZE FOR RISING MAINS SHALL NOT BE LESS THAN 80mm & THE DESIRED MINIMUMSIZE OF RISING MAIN SHALL BE 100mm DIAMETER.SITEBOUNDARY4. EACH PROPERTY SHALL HAVE A SEPARATE WASTE WATER SERVICE CONNECTION. A CONNECTIONSHALL NOT BE TAKEN FROM AN EXISTING SERVICE CONNECTION.5. FOR SITES WITH HIGH DENSITY DEVELOPMENTS, EARLY ENGAGEMENT IS REQUIRED IN RELATIONTO AGREEING A CO-ORDINATED UTILITY SERVICES LAYOUT PLAN TO ENSURE THAT THEREQUIRED SEPARATION DISTANCES ARE ACHIEVED BETWEEN THE VARIOUS SERVICES.IRISH .1.WATER MAIN20.16.CABLE TVGAS MAINELECTRICITY41.STORM WATERTHE LOCATION OF THE WATER MAIN OFF OF THE FOOTPATH MAY BE CONSIDEREDBY IRISH WATER SUBJECT TO EARLY ENGAGEMENT BY THE DEVELOPERWITH THE CDS DESIGN TEAM.26.21.FOUL BOUNDARY4.FOOTPATHROADWHERE SUCH AREAS ARE AVAILABLEREFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 07/'20 RH TOC1 11/'17 JMC TOC Updated Note 20 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppTYPICAL LAYOUT FOR SEWERWITHIN NEW DEVELOPMENTSSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.2. AN INSPECTION CHAMBER SHOULD BE LOCATED AT OR WITHIN 1m OF THEPROPERTY BOUNDARY AT THE UPSTREAM END OF EACH SERVICECONNECTION ON THE PRIVATE SIDE OF THE CURTILAGE, IF PRACTICABLE,CONSULT WITH IRISH WATER ON ALTERNATIVE LOCATIONS.3. ANY PIPE AND ASSOCIATED ACCESS UPSTREAM OF THE POINT OFCONNECTION TO A PUBLIC SEWER WITHIN THE CONFINES OF A PRIVATEBOUNDARY IS A PRIVATE DRAIN AND SHOULD BE CONSTRUCTED INACCORDANCE WITH BUILDING REGULATIONS.SLIDINGCOUPLING45 LONG RADIUS BENDROLLED 45 LONG RADIUS BENDWASTEWATER SERVICECONNECTION PIPEGRANULARMATERIAL45 ANGLE JUNCTIONOR OBLIQUE PIPE SADDLE.SEE DRAWING STD-WW-04FOR DETAILSOWFLWASTEWATER SEWERBOUNDARYPROPERTY OWNERMAINTENANCE RESPONSIBILITYPROPERTY3D VIEW SHOWING SERVICE CONNECTION PIPEWORKMAINTENANCE RESPONSIBILITY OF THEWASTEWATER SERVICE CONNECTIONSFROM THE SEWER TO THE BOUNDARY ISSET OUT IN THE PIPE MAINTENANCERESPONSIBILITY DIAGRAMS INCLUDEDON THE IW WEBSITE @ WWW.WATER.IESEWERIRISH WATER RESPONSIBILITYWITHIN 1000mm(SEE NOTE 2)FOOTPATHVARIES1.2m MAX.VARIESMAX.150mmROADSLIDING COUPLING45 LONG RADIUS BENDCONNECTION PIPEROLLED 45 LONG RADIUS BEND45 ANGLE JUNCTIONOR OBLIQUE PIPE SADDLE.SEE DRAWING STD-WW-04FOR DETAILSDRAIN TO BE INSTALLEDTO RELEVANT BUILDINGREGULATION REQUIREMENTSFOR DETAIL OF INSPECTIONCHAMBER SEE DRAWINGSTD-WW-13GRANULARMATERIAL AS PER BACKFILLINGDRAWING STD-WW-07SECTION SHOWING DRAIN AND SERVICECONNECTION PIPEWORKPIPE SIZE (mm)GRADIENT1001:40 - 1:80REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 07/'20 RH TOCDRAIN AND SERVICE CONNECTION PIPEWORK1 11/'17 JMC TOC Updated Notes0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.2.AS FAR AS PRACTICABLE, JUNCTIONS AND SERVICE CONNECTIONS SHALL BE BUILT IN FOR ALL PLANNEDUSERS WHEN THE SEWER IS BEING CONSTRUCTED. WHERE IT IS NECESSARY TO MAKE APOST-CONSTRUCTION CONNECTION THE DEVELOPER SHALL BRING THE SERVICE CONNECTION TO THEINSPECTION CHAMBER, INSTALL THE INSPECTION CHAMBER AND SEAL THE UPSTREAM END UNTIL THECONNECTION IS REQUIRED.3.THE VERTICAL ANGLE BETWEEN THE SERVICE CONNECTING PIPE AND THE HORIZONTAL SHALL BE WITHINTHE ACCEPTABLE RANGE OF 30 to 90 .4.WHERE THE SERVICE PIPE CONNECTION WITHIN THE FOOTPRINT OF THE SELF LAY AGREEMENT IS BEINGMADE TO A SEWER WITH A NOMINAL INTERNAL DIAMETER OF 300mm DIAMETER OR LESS, CONNECTIONSSHALL BE MADE USING 45 ANGLE JUNCTIONS.5.WHERE THE CONNECTION IS BEING MADE TO A SEWER WITH A NOMINALINTERNAL DIAMETER GREATER THAN 300mm, THE FOLLOWING SHALL APPLY :A.WHERE THE DIAMETER OF THE CONNECTING PIPE IS GREATER THAN HALF THE DIAMETER OF THE SEWER,AN ACCESS MANHOLE SHALL BE CONSTRUCTED TO FORM THE CONNECTION POINT; OR,B.WHERE THE DIAMETER OF THE CONNECTION PIPE IS LESS THAN OR EQUAL TO HALF THE DIAMETER OF THESEWER, THEN THE CONNECTION SHALL BE MADE USING A PREFORMED Y-BRANCH FITTING WITH A 45 DEG.SLOW BEND TO FORM THE CONNECTION TO THE WORKS.6.CONNECTION USING SADDLES MAY ONLY BE USED IN EXCEPTIONAL CIRCUMSTANCES AND ONLY TO WHERETHE CONNECTION IS TO AN EXISTING SEWER. CONNECTIONS MADE WITH SADDLE FITTINGS SHALL BE MADEBY CUTTING AND SAFELY REMOVING A CORE FROM THE PIPE AND JOINTING THE SADDLE FITTING TO THEPIPE IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS TO ENSURE A WATERTIGHT JOINT. THECONNECTING PIPE SHALL NOT PROTRUDE INTO THE SEWERS7.THE USE OF 90 "Y"-BRANCH OR SADDLE CONNECTIONS TO THE SEWER MAY BE ALLOWED, PROVIDED THESADDLE OR BRANCH INCORPORATES A SWEPT TEE CONNECTION TOWARDS THE DIRECTION OF FLOW OFTHE SEWER.45 90 6060 1.CONNECTION PIPESEE NOTE 7ACCEPTABLERANGE30 30 0 CLCLFLOW 6060 90 SEWER45 SEE NOTE 7CONNECTION PIPEACCEPTABLERANGE30 30 0 CLCLFLOWSEWERREFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 07/'20 RH TOC1 11/'17 JMC TOC0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppTYPICAL SEWER / SERVICE PIPECONNECTIONSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

1. SEPARATION DISTANCES BETWEEN SEWERS ASSOCIATED WITH THE WORKS FROM OTHER UTILITY PIPES AND ACCESSORIES SHALL BE IN ACCORDANCE WITH SECTION 3.5.9 TO 3.5.21OF THE CODE OF PRACTICE. SEPARATION DISTANCES FOR ALL NEW INSTALLATIONS FROM EXISTING IRISH WATER PIPES SHALL BE AS OUTLINED IN SECTION 3.20 OF THE CODE OF PRACTICE.2. SPECIFIC SEPARATION CLEARANCE DISTANCES IN EXCESS OF THESE MINIMA SHALL BE PROVIDED FORSERVICES SUCH AS GAS, ELECTRICITY, FIBRE-OPTIC OR OIL FILLED CABLES AS THE CASE MAY BE.THE PARTICULAR UTILITY PROVIDERS SHALL BE CONSULTED TO DETERMINE THESE MINIMUM SEPARATIONDISTANCES AND EVIDENCE OF THIS CONSULTATION, WITH THE SPECIFIED SEPARATION DISTANCES,SHALL BE PROVIDED TO IRISH WATER AT DESIGN STAGE.3. NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN THE FOLLOWING DISTANCES FROM AN EXISTING WATER MAIN OR WASTEWATER RISING MAINWHERE THE DEPTH OF THE EXISTING INFRASTRUCTURE DOES NOT EXCEED 1.5m:HORIZONTAL1m AT EITHER SIDE OF AN EXISTING PIPE LESS THAN 200mm IN DIAMETER.2m AT EITHER SIDE OF AN EXISTING PIPE OF 200mm TO 350mm IN DIAMETER.5m AT EITHER SIDE OF AN EXISTING PIPE OF 350mm OR GREATER IN DIAMETER.WHERE DUCTS OR PIPES ARE TO BE LAID CLOSE TO AN EXISTING WATERMAIN OR SEWER IN THE OWNERSHIP OF IRISH WATER. NOTIFICATION IN WRITING SHALL BE PROVIDED A MINIMUMOF 10 DAYS AHEAD OF ADVANCEMENT OF THE WORK. THIS ALSO APPLIES WHERE THE DEPTH OF THE IRISH WATER WATERMAIN OR SEWER EXCEEDS 1.5m. IN ALL OF THESE INSTANCES,SPECIFIC WRITTEN APPROVAL WILL BE REQUIRED FROM IRISH WATER BEFORE PROCEEDING WITH THE WORKNOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN 1.5m DISTANCE OF A WASTEWATER SEWER.REQUIREMENTS SHALL ALSO APPLY TO TRIAL HOLES OR SLIT TRENCHES TO LOCATE THE MAIN OR GAIN GROUND INFO DATA.LARGER DIAMETERS 350mm DISTRIBUTION AND TRUNK MAINS, IRISH WATER MUST BE NOTIFIED AT LEAST 1 MONTH IN ADVANCE.DEVELOPERS SHALL ALSO COMPLY WITH ANY NOTIFICATION REQUIREMENTS OF OTHER UTILITY PROVIDERS (ESB, GAS MAIN, TELECOMMUNICATION ETC.).4. DETAILED PROPOSALS, INCLUDING WORK METHOD STATEMENTS, INSURANCE CONFIRMATION AND DETAILS OF WORK COMPLETED OF A SIMILAR NATURE MUSTBE SUBMITTED TO IRISH WATER FOR ITS CONSIDERATION BEFORE AGREEMENT WILL ISSUE. ALL SUCH WORKS IN THE VICINITY OF ARTERIAL WATER MAINS AND SEWERS(MAINS GREATER THAN 400mm) SHALL BE SUBJECT TO WRITTEN AGREEMENT WITH IRISH WATER BEFORE CONSTRUCTION COMMENCES ON SITE. THIS AGREEMENTSHALL ALSO INCLUDE ANY NECESSARY PROTECTION FOR WATER MAINS.5. ANY DAMAGE SHALL BE NOTIFIED IMMEDIATELY TO IRISH WATER. THE PERSON WHO CAUSES THE DAMAGE TO A SEWER MAIN OR FITTING WILL BE DEEMED TO HAVECOMMITTED AN OFFENCE UNDER SECTION 45 OF THE WATER SERVICES ACT 2007.6. UNDER NO CIRCUMSTANCES WILL IRISH WATER ACCEPT SEWER MAIN INSTALLATIONS UNDER STRUCTURES, EXISTING OR PROPOSED, OR IN CLOSE PROXIMITY TOANY EXISTING STRUCTURES OR FEATURES THAT WILL INHIBIT ACCESS FOR POST INSTALLATION MAINTENANCE AND ACCESS.7. THE MINIMUM CLEAR HORIZONTAL DISTANCES SHOWN BELOW WILL BE INCREASED IF THE DEPTH OF THE SEWER EXCEEDS 3M OR IF THE DIAMETER IS GREATER THAN 375mm.THE MINIMUM CLEAR DISTANCES FOR PIPE DIAMETERS OF 450mm AND GREATER OR FOR DEPTHS EXCEEDING 4.0m SHALL BE BASED ON SPECIFIC CONSULTATION WITH IRISH WATER.THESE SEPARATION DISTANCES SHALL ALSO APPLY TO SEPARATION FROM EXISTING STRUCTURES, INCLUDING ATTENUATION TANKS AND SWALES.8. THE EXTERNAL FACES OF MANHOLES SHALL BE AT LEAST 0.5m FROM THE EXTERNAL FACE OF THE KERB LINE.9. THE EXTERNAL WALL OF THE SEWER IS TO BE AT LEAST 1.0m FROM THE EXTERNAL FACE OF THE KERB LINE.10. WHERE DESIGN DEVIATES FROM TYPICAL DETAILS, THE LAYOUT SHALL BE SUBMITTED TO IRISH WATER FOR REVIEW ANDAGREEMENT, WHICH IS TO BE OBTAINED IN WRITING BEFORE WORK COMMENCES.3000mm MINIMUMBUILDINGGRASS VERGEFOOTPATHCABLE TVKERBTELECOMMUNICATIONSELECTRICITYMIN. 500mmFOUNDATIONGAS MAINELECTRICAL CORRIDOR( DEPTH AND LAYOUTREQUIREMENTS TO BECONFIRMED WITH SERVICEPROVIDER )MINIMUM 1200mmBOUNDARY WALLWATER MAINALTERNATIVE LOCATION OF THEWATERMAIN ON THE TRAFFICKEDAREA WIL BE CONSIDERED BYIRISH WATERMIN.300mmFOUL SEWERSTORM WATER3000mm MINIMUMMIN. 1000mmMIN. 900mmREFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 07/'20 RH TOC1 11/'17 JMC TOC Updated notes0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppTYPICAL SERVICE LAYOUT INDICATINGSEPARATION DISTANCESSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE0 07/'20 RH TOC Initial IssueNo. Date Drn ChkDescriptionAppWASTEWATER SERVICE CONNECTIONVERTICAL SEPARATION DISTANCESSCALENOT TO SCALEDRAWING No.DATEFEB. 2020REV

EXISTING PLANTING:REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 11/'17 JMC TOC1 08/'16 JMC TOC Added new section & notes0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppRESTRICTIONS ON WASTEWATERINFRASTRUCTURE WORKSADJACENT TO TREESSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

NOTE: OTHER SPECIES NOTNAMED TO BE PLANTED TO THESAME SPACINGS DEPENDING ONROOT FORMATION.REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLEAppNOT TO SCALEDRAWING No.RESTRICTIONS ON NEW TREES / SHRUBSPLANTING ADJACENT TO SEWERS1 07/'20 RH TOC Text Revised0 11/'17 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSCALEDATEJUL. 2017REV

1.2.A)ROAD/FOOT PATH SURFACEB)SEE NOTE 2BACKFILL REFER TONOTE 3 FOR DETAILSC)D)E)MARKER TAPE REFERTO NOTE 9 FOR DETAILSF)300mm3.PIPE BEDDING REFER TONOTE 5 FOR DETAILS4.5.'C'6.PIPE DIAMETER - 'A'MINIMUM TRENCH WIDTH - 'B'CROSS SECTION IN ROADSGRASSED AREAS7.8.SELECTED BACKFILLREFER TO NOTE 4FOR DETAILS9.MARKER TAPE REFERTO NOTE 9 FOR DETAILS10.11.VARIESSEE NOTE 7SEE NOTE 2DEPTH OFREINSTATED TOPSOILTO MATCH EXISTING12.ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.THE MINIMUM DEPTH OF COVER FROM THE FINISHED SURFACE TO THE CROWN OFGRAVITY PIPES WITHOUT PROTECTION SHOULD BE AS FOLLOWS:GARDENS AND PATHWAYS WITHOUT ANYPOSSIBILITY OF VEHICULAR ACCESS - DEPTH NOT LESSTHAN 0.5 M. (THIS WOULD NORMALLY RELATE TO DRAINSIN PRIVATE PROPERTY, SHALLOW PIPES OF THIS NATUREARE UNDESIRABLE AND SHOULD BE INSTALLED INACCORDANCE WITH THE CURRENT BUILDING REGULATIONS).DRIVEWAYS, FOOTWAYS, PARKING AREAS AND YARDS WITHHEIGHT RESTRICTIONS TO PREVENT ENTRY BY VEHICLESWITH A GROSS VEHICLE WEIGHT IN EXCESS OF 7.5TONNES - DEPTH NOT LESS THAN 0.75 M.DRIVEWAYS, FOOTWAYS, PARKING AREAS AND NARROWSTREETS WITHOUT FOOTWAYS (E.G. MEWS DEVELOPMENTS)WITH LIMITED ACCESS FOR VEHICLES WITH A GROSS VEHICLEWEIGHT IN EXCESS OF 7.5 TONNES - DEPTH NOT LESS THAN 0.9 M.DEPTHS OF SEWERS IN GATED ESTATES SHALL BE SIMILAR TOTHAT OUTLINED ABOVE.AGRICULTURAL LAND AND PUBLIC OPEN SPACE - DEPTH NOTLESS THAN 0.9 M.OTHER ROADWAYS, HIGHWAYS AND PARKING AREAS WITH UNRESTRICTEDACCESS TO VEHICLES WITH A GROSS VEHICLE WEIGHT INEXCESS OF 7.5 TONNES - DEPTH NOT LESS THAN 1.2m.CLAUSE 804 / 808 MATERIAL IN ACCORDANCE WITH THE TRANSPORTINFRASTRUCTURE IRELAND SPECIFICATION FOR ROAD WORKS IS TO BE USED ASBACKFILL MATERIAL WHERE THE SEWER MAIN IS LOCATED IN ROADS,FOOTPATHS ORWHEN THE NEAREST PART OF THE TRENCH IS WITHIN 1m OF THE PAVED EDGE OFTHE ROADWAY. CLAUSE 804 / 808 IS TO BE COMPACTED AS PER CLAUSE 802 OF THETRANSPORT INFRASTRUCTURE IRELAND SPECIFICATION FOR ROAD WORKS. CLAUSE808 IS TO BE USED WITHIN 500mm OF CEMENT BOUND MATERIALS, CONCRETEPAVEMENTS, CONCRETE STRUCTURES OR CONCRETE PRODUCTS. OTHERWISECLAUSE 804 MAY BE USED. ALTERNATIVE BACKFILL MATERIAL TO THAT DESCRIBEDABOVE (CLAUSE 804 OR CLAUSE 808) OF THE PIPE TRENCH WILL ONLY BE ALLOWEDBY IRISH WATER WHERE THE ROADS AUTHORITY IN WHOSE FUNCTIONAL AREA THEDEVELOPMENT IS LOCATED, PROVIDES WRITTEN APPROVAL TO THE DEVELOPER TOTHE USE SUCH ALTERNATIVE MATERIAL EVIDENCE OF THIS WRITTEN APPROVAL TOBE PROVIDED TO IRISH WATER IN ADVANCE OF THE COMMENCEMENT OF WORKS.SELECTED EXCAVATED MATERIAL COMPLYING WITH THE REQUIREMENTS OF"ACCEPTABLE MATERIAL" AS OUTLINED ON CLAUSE 601 OF THE TII SPECIFICATIONFOR ROADWORKS, TABLE 6/1,CLASS 8,CLASS 2. MAY BE USED IN GREEN-FIELD AREASABOVE GRANULAR PIPE SURROUND MATERIAL SUBJECT TO REVIEW BY IRISH WATER.PIPE BEDDING SHALL COMPLY WITH WIS 4-08-02 AND IGN 4-08-01.THE PIPE BEDDING GRANULAR MATERIAL SHALL BE 14mm TO 5mm ( d D 2 14) GRADEDAGGREGATE OR 10mm ( d D 4 10) SINGLE SIZED AGGREGATE TO IS EN 13242. CONCRETEBED, HAUNCH, & SURROUND, WHERE REQUIRED, SHALLBE TO STD-WW-08.IN SOFT GROUND CONDITIONS (CBR 5) THE MATERIAL SHOULD BEEXCAVATED AND DISPOSED OF IN ACCORDANCE WITH THE WASTEMANAGEMENT ACT AND CLAUSE 804 / 808 MATERIAL IN ACCORDANCE WITHTHE TRANSPORT INFRASTRUCTURE IRELAND SPECIFICATION FOR ROADWORKS SHALL REPLACE THE EXCAVATED MATERIAL, WRAPPED INGEO-TEXTILE WRAPPING. ALTERNATIVELY, SPECIAL PIPE SUPPORTARRANGEMENTS, INCLUDING PILING ETC. MAY BE REQUIRED WHERETHE DEPTH OF SOFT MATERIAL IS EXCESSIVE. SUCH ARRANGEMENTSSHALL BE SUBJECT TO ASSESSMENT BY IRISH WATER BEFOREADVANCING WITH THE WORK.IN GREEN FIELD AREAS, TYPE B BACKFILL (SELECTED EXCAVATED MATERIALCOMPLYING WITH THE REQUIREMENTS OF "ACCEPTABLE MATERIAL" ASOUTLINED ON CLAUSE 601 OF THE TII SPECIFICATION FOR ROADWORKS, TABLE6/1,CLASS 8,CLASS 2. ) WILL BE ALLOWED ABOVE THE SIDE HAUNCH GRANULARMATERIAL IN THE CASE OF RIGID PIPES. A GRANULAR SURROUND OF A MINIMUM,DEPTH OF 150mm ABOVE THE CROWN OF THE PIPE IS REQUIRED FOR FLEXIBLE PIPESAND TYPE B MATERIAL MAY BE USED AS BACKFILL ABOVE THIS. ALL RISING MAINS INGREENFIELD AREAS SHALL HAVE A MINIMUM COVER OF 300mm OFGRANULAR MATERIAL ABOVE THE EXTERNAL CROWN OF THE PIPE.PIPES SHALL NOT BE SUPPORTED ON STONES, ROCKS OR ANYHARD OBJECTS AT ANY POINT ALONG THE TRENCH. ROCK SHALL BEEXCAVATED TO A DEPTH OF 150mm BELOW THE ACTUAL DEPTH OFTHE TRENCH WITH THE VOID FILLED WITH CLAUSE 804 / 808 MATERIAL INACCORDANCE WITH THE TRANSPORT INFRASTRUCTURE IRELANDSPECIFICATION FOR ROAD WORKS. THE GRANULAR MATERIAL SHALL BE LAIDABOVE THIS VOID BACKFILL MATERIAL.NON DEGRADABLE MARKER TAPE SHOULD BE INSTALLED AT THE TOP OFPIPE BEDDING LAYER FOR SEWERS AND RISING MAINS. IT SHOULD RUNCONTINUOUSLY AROUND MANHOLES. IN THE CASE OF NON METAL PIPE MATERIAL,THE MARKER TAPE SHOULD INCORPORATE A TRACE WIRE WHICH IS LINKED TOFITTINGS AND TERMINATED AT THE WASTE WATER PUMPING STATION (IF PROVIDED)AND THE DISCHARGE MANHOLE.TRENCH WIDTHS FOR PIPE SIZES 80mm MAY BE 500mm, SUBJECT TOCONSIDERATION BEING GIVEN TO THE TRENCH DEPTH, HEALTH &SAFETY & CONSTRUCTION ACCESS REQUIREMENTS.NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITYREQUIREMENTS.EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF"GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OFTRANSPORT, TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELANDREQUIREMENTSPIPE DIAMETER'A' (mm)PIPE BEDDING REFER TONOTE 5 FOR DETAILS'C'80 RISING MAINTRENCH WIDTH'B' (mm)SEE NOTE 10.100500150 - 200600 200 - 350750 350 - 450900PIPE DIAMETER'A' (mm)DEPTH OF BEDDING'C' (mm)PIPE DIAMETER - 'A'MINIMUM TRENCH WIDTH - 'B'CROSS SECTION IN GRASSED AREAS100150 - 450100200REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE2 07/'20 RH TOC0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppNOT TO SCALEDRAWING No.TRENCH BACKFILL AND BEDDING1 11/'17 JMC TOC Updated & Added NotesSCALEDATESEPT. 2015REV

A.A.LESS THAN DESIREDMINIMUM COVERMARKER TAPEREINFORCED CONCRETEPROTECTION SLABPIPE BEDDING1.FOR ANY SLABBING WORKS TO BE CARRIED OUT WITHIN THE VICINITYOF THE PIPELINE, A METHOD STATEMENT IS TO BE SUBMITTED FORREVIEW BY IRISH WATER.2.MARKER TAPE TO BE PLACED ABOVE THE SLAB AND ALONG THEDIRECTION OF THE PIPELINE3.CONCRETE TO BE GRADE C30/354.MINIMUM COVER TO STEEL REINFORCEMENT 40mm5.SLABS TO BE DESIGNED FOR USE UNDER A HB25 LOAD INACCORDANCE WITH BS5400-2. DESIGN TO BE SUBMITTED TO IRISHWATER FOR ASSESSMENT PRIOR TO INSTALLATION.6.THE SOIL ON WHICH THE SLAB RESTS MUST HAVE A CBR OF 4% ORGREATER.WHERE THE CBR IS LESS THAN 4% THE MATERIAL SHALL BEREMOVED AND REPLACED WITH IMPORTED GRANULAR MATERIAL ASAPPROVED BY IRISH WATER.7.IF DIRECTION OF PIPELINE AND DIRECTION OF TRAFFIC FLOW AREPARALLEL, THE DIRECTION OF LAY OF THE SLAB IS TO BE AGAINSTTHE DIRECTION OF TRAFFIC FLOW.2 No. 1 TONNE LIFTING ANCHORS175mm REINFORCEDCONCRETE.DIRECTION OF TRAFFIC FLOWDIRECTION OF LAYMINIMUM TRENCH WIDTHTYPE "A" OR TYPE "B" CONCRETECRADLE TO BE PROVIDED WHEREADDITIONAL SUPPORT IS REQUIREDTO THE PIPE IN POOR GROUNDCONDITIONS9.ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTEDOTHERWISE.12 xEXTERNALDIAMETERPIPE11. CONCRETE SURROUNDS SHALL HAVE A MINIMUM THICKNESS OF150mm WITH AN ABSOLUTE MINIMUM DEPTH OF COVER ABOVE THEEXTERNAL CROWN OF THE PIPE OF 750mm.12. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206 AND TO BEGRADE C16/20 TO IS EN20612013. THE HAUNCHES AND SURROUNDS TO BE FORMED USING FORMWORK TO PROVIDE A ROUGH CAST FINISH.14. EXPANSION JOINTS IN THE CONCRETE SHALL BE PROVIDED AT ALLPIPE JOINTS TO ALLOW FOR PIPE FLEXIBILITY, COMPRESSIBLE FILLERBOARD TO BE IN ACCORDANCE WITH BS EN 622-1 AND BS EN 622-4,AND TO BE 18mm THICK.120EXTERNALDIAMETER OF PIPE15. POLYETHYLENE AND uPVC PIPES SHALL BE WRAPPED IN PLASTICSHEETING HAVING A COMPOSITION IN ACCORDANCE WITH BS 6076BEFORE BEING CAST INTO CONCRETE.12016. BITUMINOUS MATERIAL SHALL NOT BE PUT IN CONTACT WITH PE ORPVC PIPES.EXTERNALDIAMETER OF PIPE120120EXTERNALDIAMETER OF PIPE120120120EXTERNALDIAMETER OF PIPEIF PIPELINE PROTECTION SLAB IS TO BE USED SOLELY FOR IMPACTPROTECTION & OVERALL DEPTH OF COVER IS GREATER THAN 1.2m,THE DISTANCE BETWEEN UNDERSIDE OF SLAB & TOP OF PIPE MAY BEINCREASED AFTER CONSULTATION WITH IRISH WATER.10. CONCRETE BED AND HAUNCHES MAY BE REQUIRED TO PROVIDEADDITIONAL SUPPORT IN POOR GROUND CONDITIONS. PROPOSALSTO BE PROVIDED TO IRISH WATER WITH GEOTECHNICAL REPORTSUPPORTING THEIR USE.TYPE "C" OR TYPE "D" CONCRETE SURROUND TO BE PROVIDED WHERE DEPTHOF COVER IS LESS THAN 900mm IN FIELDS OR 1200mm IN ROADS AS ANALTERNATIVE TO PROVISION OF SUPPORT SLAB, SUBJECT TO IRISH WATERAGREEING TO THE OMISSION OF THE SLAB IN LIEU OF THE SURROUND.1208.CONCRETE PIPE SURROUNDFlow150FlowEXTERNALDIAMETER OF PIPE150EXPANSION JOINT WITHCOMPRESSIBLE FILLER BOARDCOMPRESSIBLE FILLERTO BE PROVIDED IN CONCRETE BED,HAUNCH AND SURROUNDSREFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENTSTANDARD DETAILS - WASTEWATERTITLE1 07/'20 RH TOC0 09/'15 JMC TOC Initial IssueNo. Date Drn ChkDescriptionSLAppCONCRETE PROTECTION SLAB, BED,HAUNCH, AND SURROUND,TO WASTEWATER PIPESSCALENOT TO SCALEDRAWING No.DATESEPT. 2015REV

1.2.3.4.MANHOLE COVER AND FRAME SHALL COMPLYTO IS EN 124 AND BS 7903 (ALL CLASS D400COVERS SHALL HAVE MIN. FRAME DEPTH 100OR 150mm) MIN. OPE. 600 x 600mm or 600mm Ø.5.COVER TO BE SET IN CEMENTITIOUSEPOXY RESIN/POLYESTER MORTAR30N/mm21 Min. TO 3 Max. COURSES OFCLASS B SOLID ENGINEERINGBRICKS SET IN M30 MORTAR TOISEN 998 (PROPRIETARY PRECASTRISER PIECES BEDDED ON M30MORTAR MAY BE USED TO ACHIEVECORRECT TOP OF COVE

STD-WW-13 Private side inspection chamber 3 STD-WW-14 Thrust blocks for rising mains 2 STD-WW-15 Scour valve chamber (foul rising main 200mm dia.) 3 STD-WW-16 Sluice valve details for rising mains ductile iron (D.I.) pipe ( 200mm dia.) (sheet 1 of 2) 4 . PIPE IS KEPT FREE FROM DEBRIS & VERMIN SITE BOUNDARY DEVELOPER RESPONSIBILITY IRISH .