Rooftop Ventilatorwith Packaged Cooling & HeatingModels RV and RVE Institutional Commercial Industrial 800 - 13,500 cfm 3.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged DX (5-45 tons), Chilled Water,Split DX Cooling with or without Remote Condenser Optional Energy Recovery Optional Return AirAugust2018

Models RV and RVEProduct OverviewThe models RV and RVE (with energy recovery) are pre-engineeredrooftop ventilators specifically designed to condition anddeliver mixtures of outdoor and return air to a building.Varying outdoor air conditions and building loads create aserious challenge for any HVAC system. To overcome thesechallenges, the unit includes value added features such asa factory mounted variable frequency drive (VFD) for supplyair volume control, outdoor and return air dampers for mixedair control, and an onboard microprocessor system for precisetemperature and humidity control. Pre-engineered features providesemi-custom flexibility while maintaining the quality, consistency andvalue of a standardized product.Model RV and RVE Features Up to 13,500 cfm and 3 in. wg external static pressure 2-inch double-wall construction with R13 foaminsulation Optional side return intake and side supply dischargefor horizontal duct connections Direct drive backward-curved plenum fan Mounted and wired supply/exhaust fan VFD Fan vibration isolation Permatector coated exterior Filter options MERV 8, MERV 13 or MERV 14 Combination MERV 8 and 13 Microprocessor control Stand-alone BACnet MS/TP or IP LonWorks Modbus RTU Sloped intake hood Aluminum mesh filters Double-sloped, stainless steel, insulated drain panwith cooling option Cooling options– Integral air-cooled packaged DX R410A refrigerant Modulating hot gas reheat Standard low sound condenser fans Variable capacity compressors Optional electronically commutated (EC)motor on lead condenser fan 5 to 45 tons of cooling capacity Service/charging valves Liquid line dryer Sight glass– Split system DX coil with or withoutremote condenser– Chilled water coil Heating options– Indirect gas furnace Stainless steel construction High turndown capacity (up to 16:1) Power venting– Electric heat SCR control Optional single-point power– Hot water coilProduct CertificationsGreenheck takes pride in offering a high quality, reliable product. We invest our resources into designing, testingand manufacturing products to ensure customer satisfaction.ETL Listed for electrical andoverall unit safety. Every unit istested at the factory before it isshipped to the jobsite.2AHRI Certified coils and energy wheels. To guaranteeyour coil is going to perform as required, check for AHRICertification.Energy recovery wheels are certified by the AHRI Air-toAir Energy Recovery Ventilation Equipment CertificationProgram in accordance with AHRI Standard 1060. Actualperformance in packaged equipment may vary. Certifiedratings are available in the Certified Product Directory atwww.ahridirectory.org.

Outdoor Air Design ChallengesThe models RV and RVE have been specifically designed to meet the challenges of introducing highpercentages of outdoor air into a building. Features included in the units minimize energy consumption,control outdoor air volume, and maintain high levels of indoor air quality - ideal for ventilation applicationsin which the supply air volume consists of 20% or more outdoor air.SolutionDesign Challenge: Conditioning High Percentagesof Outdoor Air with Minimal Energy Usage High capacity (6-row) cooling coil: Provides proper dehumidification for a widerange of outdoor air conditions. (optional) Energy recovery wheel to precondition the outdoor air: Mechanicalheating and cooling equipment capacity reduction; reduced mechanical heatingand cooling energy consumption. (optional) Modulating hot gas reheat coil: Reheats dehumidified air to preventovercooling the space. (optional) Variable capacity compressor: Modulates DX cooling system to matchthe required load for precise temperature control and saves operational energy. (optional) High turndown indirect gas-fired furnace: Provides accuratetemperature control during heating operations, seamless modulation to eliminate“dead bands” and decreases furnace cycling. (optional) Modulating head pressure control: Improves reheat performance atpart load conditions.SolutionDesign Challenge: Controlling Outdoor Air Volume Low leakage outdoor air and recirculated air dampers with modulating actuator:Provides energy saving control sequences and simplified air balancing. Factory mounted and wired microprocessor controller: Proven control sequenceswith easy set point adjustment and seamless integration to BMS systems. Energy efficient control sequences (economizer, demand control ventilation,outdoor airflow monitoring): Economizer - maximizes free cooling; demandcontrol ventilation - adjusts outdoor airflow to match building occupancy; airflowmonitoring - stand-alone monitoring system to ensure proper ventilation and meetLEED requirements. Direct drive backward-curved plenum fan with factory mounted VFD: Providesprecise airflow control via modulating fan speed; fast and simple airflowadjustment; eliminates belt losses and maintenance.SolutionDesign Challenge: Critical Sound Applications Low sound condenser fans: Offer a sound power reduction on average of5-8 decibels when compared to standard condenser fans resulting in perceivedsound levels being reduced by up to 50%. (optional) Electronically commutated (EC) motor: Provides increased systemefficiency and provides additional sound power reduction at part load conditions.Model Number CodeThe Model Number Code isdesigned to completely identifythe unit. The correct code lettersmust be specified to designatethe configurations and size.RVE - 40 - 36 P - 30 H - 15RV base modelRVE with Energy RecoveryNominal Airflow25 (2,500 cfm)40 (4,000 cfm)45 (4,500 cfm)WheelDiameter(inches)70 (7,000 cfm)85 (8,500 cfm)120 (12,000 cfm)WheelThickness15 (11/2 in.)30 (3 in.)Wheel MaterialP - PolymerNominalTonnageAirflow RateH - HighL - Low3

Standard andOptional Features12Plenum Supply/Exhaust Fan Direct drive backward-curvedplenum fan Neoprene isolation Factory provided variablefrequency drive6Total Energy Wheel (RVE) Sensible and latent energy recoveryLightweight, segmented wheel for easy cleaningL10 rated bearing life in excess of 400,000 hoursPermanently bonded, silica gel desiccant for latenttransfer — long term durability Stainless steel housingConstruction 2-inch double-wall construction R13 foam insulation thermally broken Easy lift-off removable hinged accessdoors with stainless steel hinges andquarter turn latches.723454Filters Outdoor air and exhaust filters (pre-wheel)- 2-inch MERV 8 Supply filters (pre-coil)- 2-inch MERV 8 or MERV 13- 4-inch MERV 14- Combination of 2-inch MERV 8 and 138111Control Center 24 VAC control voltageControl transformerNon-fused disconnect switchUL Listed, Recognized, or Classifiedelectrical components Factory prewired for single pointpower connection Phase and brownout protection (PDX) Optional exhaust fan only powerWeatherhood 2-inch aluminum mesh filters(mist eliminating) Downturn intake Wind-driven rain prevention947Cooling Options Packaged direct expansion (PDX)– Optional modulating head pressure control(EC motor on lead condenser fan)– Optional hot gas reheat Chilled water coil Split DX coil with or without remote condenser All coils with copper tubes and permanentlyexpanded aluminum fins Mounted on a stainless steel drain pan

Standard andOptional Features8SCompressors Standard FeatureQuiet operating hermetic, scroll-type5 to 45 tons of mechanical cooling1 circuit up to 10 tons2 circuits 10 tons and over4 circuits (unit size RV-70 and RVE 120 only)Optional variable capacity compressor forlead circuit 106313Optional FeatureOptional Accessories57OBuilding Pressure SensorCO2 SensorCondenser Hail GuardsDirty Filter SensorDuct Pressure SensorEconomizer ControlEnergy Wheel Bypass DamperMicroprocessor Remote InterfaceOutdoor/Exhaust Airflow MonitorRoof CurbsRoom DehumidistatRoom Humidity SensorRoom Temperature SensorRoom ThermostatRotation SensorService ReceptacleSmoke DetectorsWheel Frost Controls3109Heating Options Indirect gas-fired furnace- Optional high turndown furnace(up to 16:1) - patent pending- Optional stainless steel heatexchanger with optional5 or 10 year extended warranty Electric heater- SCR control Hot water coil11Outdoor Air and Recirculated Air Dampers Insulated, low leakage Modulating actuatorReheat Modulating hot gas reheat 6 in. separation between DX and reheatcoil components to prevent evaporationof condensate5

Controls &Dimensional DataMicroprocessorThe models RV and RVE include a microprocessor controller that is factoryprogrammed, wired and tested prior to shipment. The controller can operatestand-alone or integrate with a Building Management System (BMS) usingBACnet MS/TP or IP, LonWorks or Modbus RTU protocols. This controlleris responsible for operating the unit in a safe and energy efficient manner whilecontrolling temperature and humidity.Control Features: LCD displayBuilt-in keypad for easy set point adjustmentIntegral 7-day time clockNight setback optionAuto changeover based on outdoor air conditionsHeating and cooling temperature lockoutsBuilding freeze protectionOptional remote interface for service convenienceRoom temperature and humidity controlOptional Control Sequences:Energy Wheel Frost ControlPrevents frost buildup on the energy wheel in climatesthat have cold outdoor winter temperatures (typicallyless than -10ºF) and/or moist indoor conditions suchas a locker room. Available options are: Timed exhaust - Cycles supply blower to melt frostwith only warm return air. Electric preheat - Preheats outdoor air to avoidfrosting. Modulate wheel - Reduces the wheel speed toincrease the time exposed in the warm, return air.Energy Wheel Economizer ControlWhen the outdoor air conditions are favorable, thecontroller will allow for economizer operation. The unitwill increase outdoor airflow to achieve free coolingby adjusting the energy wheel operation to: Stop wheel - Energy wheel rotation will stopand outdoor air can be brought into the buildingunconditioned. Modulate wheel - Energy wheel speed willmodulate to maintain a leaving wheel temperatureof 55ºF (adjustable).Fan Control Constant volume - Provides a constant volumeof supply air to meet the space ventilationrequirements. Variable volume - Varies the supply air to thespace via a factory mounted and wired variablefrequency drive. The required amount of supply aircan be determined by a variety of external factorssuch as duct pressure. Demand control - The supply air volume (100%outdoor air application) is modulated based onbuilding occupancy as determined by a factoryprovided CO2 sensor.Weights and DimensionsUnitSizeNominalHeight ng 0-45906815622/27 2020-45906822422/27 308300OutdoorSupplyIntake deBottom,End**orSide*End orSide*EndBottomorSideBottomSideAll dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat,largest indirect-gas fired furnace, all dampers and largest energy wheel. Actual weights will vary based on the unit configuration.* Only available with powered exhaust** Only available without barometric relief Only available with barometric relief Above 12,000 cfm‡ Length with side return6

Dimensional DataPLANPLANModel RVPLANReturnIntakeReturnAirAirIntakeDX Coil(Optional)(Optional)HGRH CoilIG HeaterSupply FiltersReturn Air Intake(Optional)Outdoor erControlCenterSupply Air DischargeControl CenterOutdoor AirIntake therhoodOutdoor AirWeatherhoodCoilDXDXCoilHGRHCoilHGRHCoilHeaterIG IGHeaterSupplyFiltersSupplyFiltersAAOutdoor AirDamperOutdoorOutdoorAirAirDamperDamperL sCompressorsCompressorsHHModel RVEPLANSupply FiltersReturn Air InletOutdoor Air Outdoor AirWeatherhoodWeatherhoodOutdoor AirIntakeOutdoor AirWeatherhoodOutdoor NELEVATION Outdoor Air Outdoor AirELEVATIONWBBAExhaustFanOutdoor Air FiltersOutdoor Air FiltersEnergy WheelEnergy WheelExhaust FiltersExhaust FiltersOutdoor Air FiltersEnergy WheelExhaust FiltersINTAKEDX CoilDX CoilHGRH Coil HGRH CoilSupplyAir DischargeSupply Air DischargeCoilReturn HGRHAir InletReturn Air InletIGIGSupply Air DischargeIGControl CenterHeaterHeaterControl CenterControlCenterHeaterSupply FiltersSupply FiltersPLAN DX CoilOutdoor ondensingCoilCoilOutdoor AirDamperAL g CondensingCoilCoilExhaust AirExhaust Air Exhaust Air Recirc DamperRecirc DamperRecirc Damper(Optional)(Optional)(Optional)7

Energy Recovery ProductsModel MiniVentA low-profile preconditioner designedfor compact indoor installationsrequiring 150 to 850 cfm and may befloor mounted or ceiling hung.Model MiniCoreThis preconditioner utilizes an energyrecovery core for indoor installationsranging from 300 to 1,000 cfm.Designed to be mounted vertically orhorizontally with optional intake anddischarge connections configurableon site.Model ERVThis reliable preconditioner provides total energyrecovery primarily designed for indoor applicationsrequiring 500 to 12,000 cfm.Model ERVeThis preconditioner provides total energy recovery foroutdoor applications requiring 1,000 to 6,000 cfm.Model ERCHThis dedicated outdoor air unit combines the benefitsof total energy recovery with supplemental heatingand cooling in applications designed to supply 100%outdoor air. Airflow capacities range from 1,000 to10,000 cfm.Our CommitmentAs a result of our commitment to continuous improvement, Greenheck reserves the right to change specificationswithout notice.Specific Greenheck product warranties are located on greenheck.com within the product areatabs and in the Library under Warranties.Greenheck P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.comCopyright 2018 Greenheck Fan Corp. 00.TAP.1040 R7 8-2018 RGPrepared to SupportGreen Building Efforts

Tonnage 25 (2,500 cfm) 85 40 (4,000 cfm) 45 (4,500 cfm) 70 (7,000 cfm) (8,500 cfm) 120 (12,000 cfm) Nominal Airflow. 4 Standard and Optional Features . Outdoor/Exhaust Airflow Monitor Roof Curbs Room Dehumidistat Room Humidity Sensor Room Temperature Sensor Room Thermostat