VS2 Intelligent Life Safety System - Reliant Fire And Security

Transcription

Vigilant Catalog ! Small Building Fire Alarm SolutionsVS2 IntelligentLife Safety SystemOverviewFeaturesThe Vigilant VS2 intelligent life safety system offers the speed ofhigh-end intelligent processing in a configuration that delivers anuncomplicated solution for small to mid-sized applications. Withintelligent detection, electronic addressing, automatic devicemapping, optional Ethernet connectivity, and a full line of easilyconfigured option cards and modules, this quick-to-install systemoffers versatility that benefits building owners and contractorsalike. Comes standard with one loop (expandable to two) thatsupports up to 250 (expandable to 500) intelligent devices:each VS2 loop supports up to 125 detectors and up to 125modules.The VS2 provides one Class A or Class B analog device loop thatsupports up to 250 device addresses. A second 250-point loopmay be added to the VS2 to expand total system capacity to upto 500 device addresses. The panel includes four NACs that maybe wired for either Class A or Class B operation. Optional Ethernet port for diagnostics, programming and avariety of system reportsThis life safety system features an attractive contemporary designthat fits with any decor. Its gently curved doorfront offers a distinctive flair with available red or silver finishes. Controls are discreetlyinset behind a striking black bezel.The VS2 supports a wide range of accessories and related equipment, including: Four Class B NACs or two Class A NACs. Form C contacts for alarm and trouble, Form A for supervisory Electronic addressing with automatic device mapping Two programmable switches with LEDs and custom labeling Supports Genesis horn silence over two wires and UL1971-compliant strobe synchronization Supports up to eight serial annunciators, (LCD, LED-only, andgraphic interface). Can use existing wiring for most retrofit applications Supports V-Series single and multisensor detectors Upload/download remotely or locally Intelligent modules, detectors, and bases Two-level maintenance alert reporting R-Series remote annunciators Pre-alarm and alarm verification by point option cards that expand system capacity and extend systemcapabilities. Adjustable detector sensitivityPage 1 of 8 4 x 20 character backlit LCD displayM85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

ApplicationOperationThe VS2 life safety system is an easy-to-use intelligent solution forsmall to mid-sized buildings. Analog technology delivers the benefitsof quick and uncomplicated system installation, while a clean andeasy-to-operatate user interface makes panel operation and systemmaintenance quick and intuitive.The front panel provides an easy-to-use operator’s interface, aswell as all the necessary controls for front panel programming.A large back-lit 80-character LCD displays system status, eventdetails, and programming prompts. Large tactile control buttonsare easy to see in low light conditions, and bright multi-color LEDsoffer at-a-glance status indication.The smart choiceElectronic addressing eliminates the tedium of setting dipswitches,and automatic device mapping ensures that each device resideson the system at its correct location. Meanwhile, innovative programming allows the designer to customize the system to precisely suit the needs of the building nfigurableVersatility built right inTwo fully-programmable front panel switch/LED combinations provide an added measure of simplicity. Their slide-in labels take themystery out of custom applications, and present a clean finishedappearance.Perfect for retrofitsThe VS2 is particularly well-suited to retrofit applications. Allconnections are made over standard wiring – no shielded cablerequired. This means that in most situations existing wiring canbe used to upgrade a legacy control panel to V-Series technologywithout the expense or disruption of rewiring the entire building.Signals with a differenceVS2 NACs are configurable to fully support the advanced signalingcapabilities of Edwards Genesis and Enhanced Integrity notification appliances. These devices offer precision synchronization ofstrobes to UL 1971 standards. For Genesis devices, enabling thisfeature allows connected horns to be silenced while strobes onthe same two-wire circuit continue to flash until the panel is reset.SystemLEDsControl buttonsButtonResetACK/PanelSilenceSignal SilenceDrillClear-cut remote annunciationRemote annunciation is a strong suit of the VS2. Up to eight annunciators can be installed on a single system. Compatible annunciators include a range of LED and LCD models that provide zoneor point annunciation, as well as common control capabilities.RemoteDisconnectThe VS2 also supports graphic annunciation with optional RAGraphic Annunicator interface modules. Each interface providescommon control, indicators, and 32 LEDS. Consult the OrderingInformation section for details.Right arrowLeft arrowUp arrowA complete line of accessoriesThe VS2 life safety system is supported by a complete line ofintelligent detectors, modules and related equipment. Consult theOrdering Information section for details.Down mablebuttonsPage 2 of 8ControlbuttonsDescriptionInitiates a system reset.Silences the panel and remote annunciators duringan active trouble, supervisory, or alarm event andacknowledges new event activations.Alarm mode: Silences active notification appliances.Pressing Signal Silence a second time turns NACs backon.Initiates a drill confirmation. Pressing drill a second timeturns off the drill function.Dialer: Disables or enables dialer.Dialer set to modem only: Disables or enables thecommon alarm relay.Display mode: Moves the cursor to the left.Menu mode: Toggles between programmingselections.Display mode: Moves the cursor to the right.Menu mode: Retrieves a programming option’s submenu and toggles between a programming option’sselections.Display mode: Advances to the previous event.Menu mode: Moves the cursor up.Display mode: Advances to the next event.Menu mode: Moves the cursor down.Display mode: Displays selected event details.Menu mode: Retrieves a programming option’s submenu or jumps to the Save function in the menu.Entry mode: Enters the selected data into the system.Display mode: Exits the detailed information display.Menu mode: Exits the current menu level.Entry mode: Clears the current entry.Display mode: Enters the menu modeMenu mode: Exits menu modeEnters a space, such as a space between words.Entry mode: Pressing a button once enters the numberon the button. Pressing the button twice enters thesecondary value.These buttons can be programmed to control outputs,disable devices or unlatch system outputs. The buttonscan be labeled with a slip-in insert.M85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

System LEDsPanel Operation OptionsLEDDescriptionFire AlarmRed LED. On steady when there is an activealarm.Yellow LED. Flashes when there is a fault on amonitored circuit or system component, or whena circuit is disabled.Yellow LED. On steady when there is an activesupervisory event.Green LED. On when the panel has AC power.Yellow LED. Double-flashes when there is a disabled circuit or alarm relay.Yellow LED. On steady during an active groundfault.Yellow LED. Flashes when performing an audiblewalk test. Steady indicates a silent test.Yellow LED. On steady when there is an activemonitor event.Yellow LED. Indicates that detector needs servicing.Yellow LED. On steady indicates that NAC circuits are turned off but the panel is still in alarm.Yellow LED. On steady indicates that the dialeris disabled or that the alarm relay is enabled ordisabled when the dialer is set to modem only.Yellow LED. Indicates that the panel is in drill.Yellow LED. Indicates that the panel is resetting.Yellow LED. Indicates that the panel has beensilenced during an active trouble, supervisory, oralarm event and indicates that new event activations have been acknowledged.Yellow LED. Programmable.SupvAC User keysProgrammingZone resoundReset inhibit afterNACs turn onAuto signalsilenceDay startNight startDateSounder BaseMappingLCD bannerEvent notificationDimensionsV-Series panels are simple to set up, quick to program, and easyto maintain. The auto programming feature quickly gets the paneloperational using factory default settings. Basic zone and pointsettings can be programmed easily through the front panel interface, so the system is up and running in no time.Among the many innovations of the VS2 control panel is theoptional network card. This module provides a standard 10/100Base T Ethernet network connection that permits access tothe control panel from any remote location with the correctcommunications protocols. The connection can be used todownload to the panel from the VS-CU, or upload and viewsystem reports using the VS-CU.Page 3 of 8 ()* ,-./01)23425/617.8! !# ,- 1?/@436A11*/,33,-6.A ,- 1?/@436/A11*/,2A3*40/*425/,33,-6.A!:For more advanced system configuration and correlation groupsprogramming, V-Series panels interface to a PC running compatible VS-CU software. This option offers full system configurationin the familiar Windows operating environment. Connection istypically made to a laptop through the panel’s optional RS-232communications port, which can also be used to connect a system printer.Available system reports include: Correlation groups Device maintenance Internal status System status DialerEnglish or FrenchU.S. or CanadaOff: Off-premise notification of an AC power failureis immediate.1 to 15 hours: Delays the off-premise notification ofan AC power failure by the time period selected.On: NACs resound each time a device in the zonegoes into alarm even if they were silencedOff: Inhibits the NACs from turning on again (afterthey were silenced) when a second device in thezone goes into alarm.Off: Panel reset is operational immediately.1 minute: Panel reset is inhibited for one minute.Off: Allows immediate silencing of signals from anoff-normal condition using the Signal Silence button5 to 30 minutes: Delays the silencing of signalsfrom an off-normal condition by disabling the SignalSilence button for the time period selected.Start time for daytime sensitivityStart time for nighttime sensitivityMM/DD/YYYY, DD/MM/YYYYSix configuration settingsDisabled: Device mapping is not availableEnabled: Device mapping is availableBanner text for line one and line two. Each line iscapable of up to 20 characters.Zone: When a device is a member of a zone, onlythe zone information is sent to the LCD display,LEDs, printer, and dialer.Zone/device: Zone information is sent to the LCDdisplay and LEDs. Device information is sent to theprinter and dialer.Device: Only device information is reported.!"!%(.04 7)86/01)23425/617.8TroubleLanguageMarketplaceAC fail delay!9()* ,-./01)23425/617.8!'!;!;!&!Backbox and backbox with "3.9"71.1cm9.8cm22.8cm 55.8cm 40.0cm 26.0cm9.9cm* Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.D8D928.2"71.6cm2.7"6.8cmDevice detailsHistorySystem configurationWalk testM85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

Wiring & ConfigurationNotification appliance circuits (TB2)Device loopV-Series control panels come equipped with two notificationappliance circuits. Each circuit can be individually configured forcontinuous, temporal, synchronized, latching, and coded output.The control panel provides one device loop circuit that can support 125 detectors and 125 module addresses. The loop circuit issupervised for opens, shorts, and grounds.Circuit specificationsCircuit Type 4 Class B or 2 Class A, 2.5 amps eachVoltage24 VFWRCurrent6.0 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz5.0 A total at 230VAC 50 Hz2.5 A max. per circuitImpedance 26 Ω total, 0.35 µF maxEOLR15 K Ω, ½ WCircuit specificationsDevice loops1 loop, expandable to 2, Class A or B, each loopsupporting up to 250 device addressesCommunicationMaximum 20 V peak-to-peakline voltageCircuit current0.5 A maxCircuit66Ω total, 0.5 µF, maximpedanceIsolators64 maximumClass B wiringNAC1 NAC1 NAC2 NAC2 Class B Wiring - - - -Loop 1 SECEOLRLoop 1 PRITB2NAC3 NAC3 NAC4 NAC4 Class A wiringNAC1 NAC1 NAC2 NAC2 Data Line - ----LoopdeviceLoopdeviceLoopdeviceLoopdeviceLoop cardTB6 - -Class A Wiring-EOLRMarking indicatesoutput signal polaritywhen the circuit is active. Polarity reverseswhen the circuit is notactive. Wire notificationappliances accordingly.Notification appliancepolarity shown in active state.TB2Annunciator loop (TB4)The control panel provides a connection for up to eight seriallydriven and supervised remote annunciators.Circuit specificationsDevice loopsClass B (Style Y) or Class A (Style Z)Circuit voltage2.55 VCircuit current30 mA maxCircuitUp to 8 annunciators or 4000 feetimpedanceClass BClass A&hanne'() &hanne'(*&hanne'() &hanne'(*"!"!"!! Data Line"# %# %.//u/0123o4.//u/0123o4TB6&H)( !,(I-&H)( !,(I-&H1 (-) I-CH1 (-) I-&H*( !,(I-&H*( !,(I-Auxiliary & Smoke power outputs (TB3)The control panel provides two auxiliary power outputs which canbe used for powering ancillary equipment such as remote annunciators and two wire smoke detectors. Aux 2 can be softwareselected to operate continuous. The circuit is supervised for shortsand grounds.Note: For a complete list of devices that can be connected to thiscircuit, refer to the VS Series Compatibility List.Circuit specificationsCircuit voltage range 21.9 to 28.3 VResettable circuit24 VDC nominal at 500 mA(Aux power 2)Continuous circuit24 VDC nominal at 500 mA. Use this circuit for(Aux power 1)powering two-wire smoke detectors.Note: Any current above 0.5 amp connected to both Aux 1 and 2 will reduce the totalavailable NAC power by that amount.Page 4 of 8 &H2 (-) I-&H* (-) IN!!Alarm, trouble, and supervisory relay (TB3)The trouble relay is normally-open, held closed, and opens on anytrouble event or when the panel is de-energized. The supervisoryrelay is normally-open, and closes on any supervisory event. Thealarm relay changes over on any alarm event.Relay specificationsAlarmTypeVoltageForm C24 VDC at 1 A resistiveTroubleSupervisoryForm A24 VDC at 1 A resistiveRelay circuits can only be connected to power-limited sources.M85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

Option CardsV-Series panels are supported by a complete line of modules andrelated equipment that enhance performance and extend systemcapabilities. Option cards are easy to install and set up. Theysimply plug directly into the control panel main circuit board or areconnected to it with a ribbon cable. After installation, terminalsremain easily accessible for quick connection of field wiring. Thecabinet provides ample room for wire routing, keeping wiring neatand easy to service at all times.SA-ETH Ethernet Interface CardSA-ETH wiringThe SA-ETH card provides aTo networkconnection standard 10/100 Base T EthernetNetwork cablenetwork connection for connecting to an intranet, a local network, or the Internet. The cardcan be used to downloadconfiguration programming fromthe VS-CU to the panel over thenetwork.SMK Smoke Power ConverterThe SMK Smoke Power" -./0Converter Module pro1234554167 -89:;6,vides a regulated power 9 -6;?; 1@5;Asource for two-wire smokecircuits connected to aSignature data circuit. TheSMK monitors the operatCDEing power from the powersupply. When power begins to degrade, the SMKprovides the necessaryoperating voltage to the!wo"# %&'()* &,&-&.-*%stwo-wire smoke detectioncircuits.B9:;6-92 # " !!& !% ! !# !"#" !" !! !* )FB!( ' & % # " !-/1 1-4 The Ethernet card is installed onthe plastic assembly and connects to the main circuit boardvia a ribbon cable.Ethernet card( ' & % B9:;6-4 !wo"# %&'()* &,&-&.-*%s!& !% ! !# !"#" !" !! !* )FB!SA-ETH specificationsEthernet10/100 Base TOperating environmentTemperature 32 to 120 F (0 to 49 C)Humidity 0 to 93% RH, noncondensing at 90 F(32 C)( ' & % G;6H4 1 ;96- 9- ;3 ID # " !/1 1-92 SMK specificationsV-SLC Loop Expander CardThe V-SLC Loop Expander Card provides an additional deviceloop on the control panel. The card expands the control panel’sdevice capacity to 500 total device addresses, 250 per loop. Thecard is compatible with Class B or Class A wiring. It is compatiblewith VS2 control panels only.The loop expander card connects to connector J7 on the maincircuit board.Class B WiringClass A WiringLoop 1 SECLoop 1 PRI - ----LoopdeviceLoopdeviceLoopdeviceLoopdeviceV-SLC specificationsDevice addresses on loopWiringOperating voltageOperating currentCircuit impedanceTerminal ratingOperating environmentTemperatureHumidityPage 5 of 821.9 to 28.3 VDC (not resettable)Output voltage24 VDC nom. at 200 mA, max., specialapplications10 k ohmGround faultimpedanceOperating environmentTemperatureHumidityStorage temperatureCompatible electricalboxesWire sizeData Line Loop cardInput voltageData Line 32 to 120 F (0 to 49 C)0 to 93% RH, noncondensing at 90 F (32 C)–4 to 140 F (–20 to 60 C)North American 4 inch square x 2-1/2 in.(64 mm) deep 2 gang box or Standard 4 in.square box 1-1/2 in. (38 mm) deep14, 16, or 18 AWG wire (1.5, 1.0, or 0.75 sq.mm) (Sizes 16 and 18 AWG are preferred)125 detectors and 125 modulesClass B (Style Y) or Class A (Style Z)20 V peak-to-peak0.5 A total66 Ω, 0.5 µF, max12 to 18 AWG (0.75 to 2.5 sq mm)32 to 120 F (0 to 49 C)0 to 93% RH, noncondensing at 90 F(32 C)M85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

SA-DACT DialerThe SA-DACT provides communications between the controlpanel and the central station over a telephone line system. Ittransmits system status changes (events) to a compatible digitalalarm communicator receiver over the public switched telephonenetwork. The dialer is capable of single, dual, or split reportingof events to two different account and telephone numbers. Themodem feature of the SA-DACT can also be used for uploadingand downloading panel configuration, history, and current statusto a PC running the VS-CU.SA-DACTwiringPhone line 1Phone line 2Phone cables(supplied)To wallphone jackRJ31 jacksThe dialer phone lines connectto connectors on the dialer’smain circuit board. Phone line 1connects to connector J4 andphone line 2 connects toconnector J1.SA-232 RS-232 interfaceThe SA-232 card provides an RS-232interface with VS2 panels. It can beused for connecting a printer to thecontrol panel to print system events. Thecard also can be used for connecting acomputer to download a configurationprogram from the VS-CU to the controlpanel.SA-232 wiringGND (black wire)TXD (white wire)RXD (red wire)The SA-DACT queues messages and transmits them based onpriority (alarm, supervisory, trouble, and monitor). Activations aretransmitted before restorations.The SA-DACT is installed on the plastic assembly and connects tothe main circuit board via a ribbon cable.SA-DACT specificationsPhone line typeOne or two loop-start lines on a public,switched networkPhone line connectorRJ-31/38X (C31/38X)Communication formatsContact ID (SIA DC-05)Operating environmentTemperature 32 to 120 F (0 to 49 C)Humidity 0 to 93% RH, noncondensing at 90 F(32 C)Compatible ent KnightSur-GardModels685CP220OH 2000D66009800SG-MLR1, MLR2FormatsContact IDContact IDContact IDContact IDContact IDContact IDThe RS-232 card is installed on the plastic assembly and connects to the main circuit board via a ribbon cable.SA-232 specificationsOperating voltageTerminal ratingOperating environmentTemperatureHumidityStandard EIA-23212 to18 AWG (0.75 to 2.5 sq mm)32 to 120 F (0 to 49 C)0 to 93% RH, noncondensing at 90 F (32 C)SpecificationsDevice loopsNAC circuitsPower supplyNAC OperatingvoltageSLC Loop circuitoperating voltagePrimary powerAux Power 1(Continuous circuit)Aux Power 2(Resettable circuit)Auxiliary outputBase panelcurrent drawPage 6 of 81 loop, expandable to 2, Class A or B, each loopsupporting up to 250 device addresses4 Class B or 2 Class A, 2.5 amps each6.0 A total, 2.5 A max. per circuit at 120/230 VAC60 Hz5.0 A total at 230VAC 50 Hz, 2.5 A max. percircuit0.5 amps aux power24 VDC. NAC minimum voltage: 19.5 VDC @20.4 V battery voltage20 V peak-to-peak120 VAC, 60 Hz, 230 VAC 50-60 Hz24 VDC nominal at 500 mA. A SMK module isrequired when using the GSA-UM module tosupport two-wire smoke detectors.24 VDC nominal at 500 mA.19 to 25.7 VDCStandby: 172 mAAlarm: 267 mABattery placementBatteriesLoop circuitGSA-UM/GSA-MABCompatibility IDAlarm contactTrouble contactSupervisory contactEnvironmentalTerminal ratingSerialcommunicationsRemote annunciatorInput zonesAgency ListingVS2 cabinets accommodate up to 18 A/H batteries.Use a external cabinet for larger battery sizes.Batteries must be sealed lead acid type only.Maximum charging capacity 26 Ah.Maximum loop resistance: 66 Ω. Maximum loopcapacitance: 0.5 µF. Style 4, 6, and 7 wiring. 64isolators maximum.1.5 mA (see the UL and ULC compatibility list forfor the maximum quantity of detectors per circuit)100Form C 24 VDC @ 1 A (resistive load)Form C 24 VDC @ 1 A (resistive load)Form A 24 VDC @ 1 A (resistive load)Temperature: 0 to 49 C (32 to 120 F).Humidity: 0 to 93% RH, noncondensing.All terminals rated for 12 to 18 AWG (0.75 to 2.5mm²)Voltage: 2.55 V. Current: 30 mA max8 drops max, RS-485 Class A or B32 max.UL, CSFM and ULCM85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

Ordering InformationPartDescriptionVS2 Intelligent Multi-Loop Systems, 500 analog point capacityVS2-R1 Loop System, 4 NACs, Red door. Surface mount enclosure, 115 Vac, English.VS2-RD1 Loop System, two-line dialer, 4 NACs, Red door. Surface mount enclosure, 115 Vac, English.VS2-G1 Loop System, 4 NACs, Silver door. Surface mount enclosure, 115 Vac, English.VS2-GD1 Loop System, two-line dialer, 4 NACs, Silver door. Surface mount enclosure, 115 Vac, English.VS2-GC (1)1 Loop System, 4 NACs, 16 zone LED display, Silver door. Surface mount enclosure, 115 Vac, English.VS2-G-F (1)1 Loop System, 4 NACs, 16 zone LED display, Silver door. Surface mount enclosure, 115 Vac, French.VS2-G-2 (2)1 Loop System, 4 NACs, Silver door. Surface mount enclosure, 230 Vac, English.VS2-R-2 (2)1 Loop System, 4 NACs, Red door. Surface mount enclosure, 230 Vac, English.VS2-G-SP (2)1 Loop System, 500 point capacity, 4 NACs, silver door. Surface mount enclosure, 115 Vac, SpanishVS2-G-2-SP (2) 1 Loop System, 500 point capacity, 4 NACs, silver door. Surface mount enclosure, 230 Vac, SpanishVS2-G-PG (2)1 Loop System, 500 point capacity, 4 NACs, silver door. Surface mount enclosure, 115 Vac, PortugueseVS2-G-2-PG (2) 1 Loop System, 500 point capacity, 4 NACs, silver door. Surface mount enclosure, 230 Vac, PortugueseSA-TRIM2Flush mount trim, blackReplacement Electronics500elec-VSReplacement Base electronics, Vigilant, 500pt system, includes main board, base plate, User interface and 1 loop.500elec-VS-FR(1) Replacement Base electronics, Vigilant, 500pt system, includes main board, base plate, User interface and 1 loop, French500elec-VS-SP(2) Replacement Base electronics, Vigilant, 500pt system, includes main board, base plate, User interface and 1 loop, Spanish500elec-VS-PG(2) Replacement Base electronics, Vigilant, 500pt system, includes main board, base plate, User interface and 1 loop, PortugueseOption CardsSA-DACTSA-232SA-ETHV-SLCD16L-VSDual Line Dialer/Modem, supports 4/2 and Contact ID, mounts in cabinet on base plate.Serial Port (RS-232), for connection to printers & computers, mounts in cabinet to base plateEthernet Port, Slave, mounts in cabinet on base plateSLC Loop Expansion Module. Adds second loop to VS2 systems, 250 point capacity. Mounts in cabinet on main board.LED Annunciator Module, 16 groups, 2 LEDs per group with insertable labeling. Mounts in cabinet on VS2 systems.Remote Annunciators (refer to Data Sheet 85005-0128)LCD Remote Annunciators (mount to standard 4” square electrical box)RLCDRemote Annunciator, 4X20 LCD & Common Indicators for displaying system status. Off-white housing.RLCD-RRemote Annunciator, 4X20 LCD & Common Indicators for displaying system status. Red housing.RLCD-CRemote Annunciator, 4X20 LCD. Common controls and status indicators. Off-white housing.RLCD-CRRemote Annunciator, 4X20 LCD. Common controls and status indicators. Red housing.RLCDF (1)Remote Annunciator, 4X20 LCD & Common Indicators for displaying system status. Off-white housing.RLCD-CF (1)Remote Annunciator, 4X20 LCD. Common controls and status indicators. Off-white housing.RLCD-SP (2)Remote Annunciator, 4X20 LCD. Common system status indicators. Off-white housing. Spanish.RLCD-PG (2)Remote Annunciator, 4X20 LCD. Common system status indicators. Off-white housing. Portuguese.RLCD-C-SP (2) Remote Annunciator, 4X20 LCD. Common controls and status indicators. Off-white housing. Spanish.RLCD-C-PG (2) Remote Annunciator, 4X20 LCD. Common controls and status indicators. Off-white housing. Portuguese.LED Remote Annunciators & Expander (mount to standard 4” square electrical box)RLED-CRemote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Off-white housing.RLED-CRRemote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Red housing.RLED-CF (1)Remote Annunciator. Common controls and status indicators with 16 X 2-LED groups for zone display. Off-white housing, French.RLED-C-SP (2)Remote Annunciator, common controls and status indicators. 16 groups w/2 LEDs each for zone display. Off-white housing. Spanish.RLED-C-PG (2)Remote Annunciator, common controls and status indicators. 16 groups w/2 LEDs each for zone display. Off-white housing. Portuguese.RLED24Remote Annunciator Zone expander. 24 X 2-LED groups with custom label areas for display of alarm and trouble. Off-white housing.RLED24RRemote Annunciator Zone expander. 24 X 2-LED groups with custom label areas for display of alarm and trouble. Red housing.Remote Annunciator Cabinets & AccessoriesRA-ENC1Remote Annunciator Enclosure, key locked with plexiglass window for one RLCD(C) or RLED(C).RA-ENC2Remote Annunciator Enclosure, key locked with plexiglass window with space for 2 of either RLCDx, RLEDx or RLED24.RA-ENC3Remote Annunciator Enclosure, key locked with plexiglass window with space for 3 of either RLCDx, RLEDx or RLED25.RKEYKeyswitch, single gang, provides key operated enable or disable of common controls on RLCD or RLED units.LSRA-SBSurface Mount Box - for R Series single units.Graphic Annunciator Drivers (comes with a snap track for mounting in custom graphic enclosures)GCIProvides outputs for common indicators and 32 alarm/supv zones as well as inputs for common switches.Programming ToolsVS-CUVigilant VS Series configuration and diagnostics utility.260097RS232 cable, 4 conductor, DB9 PC interfaceNotes:(1)Available in Canada only.Page 7 of 8(2)Available in international markets only.M85005-0130D ATA S H E E TNot to be used for installation purposes. Issue 4

Ordering InformationPartNumberDetection & alarm since 1872U.S.T 888 378 2329F 866 503 3996CanadaChubb EdwardsT 519 376 2430F 519 376 7258Southeast AsiaT : 65 6391 9300F : 65 6391 9306IndiaT : 91 80 4344 2000F : 91 80 4344 2050EuropeT 32 2 725 11 20F 32 2 721 86 13Latin AmericaT 305 593 4301F 305 593 4300utcfireandsecurity.com 2010 UTC Fire & Security.All rights reserved.DescriptionShip wt.Analog Addressable Detectors and BasesV-PHSV-PSIntelligent Analog Optical/Fixed Temperature DetectorIntelligent Analog Optical Smoke Detector0.25 (0.11)0.25 (0.11)V-HRDV-HFDIntelligent Analog Rate-of-Rise Heat DetectorIntelligent Analog Fixed Temperature Heat Detector0.25 (0.11)0.25 (0.11)GSA-SDB4UIntelligent Analog Duct DetectorStandard Base2.4 (1.1)0.11 (0.05)RB4UIB4URelay Detector BaseIsolator Detector Base0.11 (0.05)0.11 (0.05)SB4UAB4G-SBAudible (Sounder) Detector BaseSurface Box for Audible Base0.11 (0.05)1.0 (0.45)RLEDRemote alarm LED, use with standard base only0.2 (.09)System AccessoriesCTMCity Tie Module. Mounts in 2-gang electric box. Provides connection toa local energy fire alarm box.BC-1Battery Cabinet. 14.0" x 18.25" x 7.25" Free-standing cabinet with keylock. Supports up to 40 Ah batteries. Holds up to 2 12V24A batteries.BC-1RBattery Cabinet - Red. 14.0" x 18.25" x 7.25" Free standing cabinetwith key lock. Supports up to 40 Ah batteries. Holds up to 2 12V24Abatteries.IOP3AIsolator Module - RS232. For use with short haul modems.RPMReverse Polarity ModuleMFC-AMultifunction Fire Cabinet, 8" x 14" x 3.5" - RED.MIR-PRT/SSystem Printer - Desktop style.Analog Addressable ModulesGSA-CC1Single Input Signal Module (Standard Mount)GSA-MCC1 Single Input Signal Module (UIO Mount)GSA-CC1S Synchronization Output Module (Standard Mount)GSA-MCC1S Synchronization Output Module (UIO Mount)GSA-CC2Dual Input Signal Module (Standard Mount)GSA-MCC2 Dual Input Signal Module (UIO Mount)GSA-CRControl Relay Module (Standard Mount)GSA-MCRControl Relay Module (UIO Mount)GSA-CRRPolarity Reversal Relay Module (Standard Mount)GSA-MCRR Polarity Reversal Relay Module (UIO Mount)GSA-RM1Riser Monitor Module (Standard Mount)GSA-MRM1 Riser Monitor Module (Plug-in)GSA-IOInput/Output Module (Standard Mount)GSA-MIOInput/Output Module (Plug-in)GSA-CT1Single Input ModuleGSA-CT2Dual Input ModuleGSA-MCT2 Dual Input Plug-in (UIO) ModuleGSA-IMFault Isolator ModuleGSA-MM1Monitor ModuleGSA-WTMWaterflow/Tamper ModuleSMKSmoke Power Converter Module50.0 (22.7)50.0 (22.7)1.61 (0.7)3.0 (1.36)20.6 (9.4)36.6 (16.6)0.5 (0.23)0.18 (0.08)0.5 (0.23)0.18 (0.08)0.5 (0.23)0.18 (0.08)0.4 (0.15)0.18 (0.08)0.4 (0.15)0.18 (0.08)0.5 (0.23)0.18 (0.08)0.34 (0.15)0.22 (0.10)0.4 (0.15)0.4 (0.15)0.1 (0.05)0.5 (0.23)0.4 (0.15)0.4 (0.15)0.4 (0.15)M85005-0130D ATA S H E E TNot to be used for in

Signal Silence Alarm mode: Silences active notification appliances. Pressing Signal Silence a second time turns NACs back on. Drill Initiates a drill confirmation. Pressing drill a second time turns off the drill function. Remote Disconnect Dialer: Disables or enables dialer. Dialer set to modem only: Disables or enables the common alarm relay.