BACnet Protocol - EXHAUSTO

Transcription

3005299-2015-09-29.fmBACnet ProtocolUser ManualEXcon SW vers. 3.19EXHAUSTO A/SOdensevej 76DK-5550 LangeskovTel.: 45 65 66 12 34Fax 45 65 66 11 10exhausto@exhausto.dkwww.exhausto.com

3005299-2015-09-29.fm1. Product information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32. Communication via external BACnet IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52.1 Configuration - BACnet IP. 52.2 Setting up parameters BACnet IP . 63. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73.1 Overview diagram and data points . 73.2 Most used data points . 84. Binary Value DO (R/W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95. Binary Input DI (R) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106. Analogue Input AI (RO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .187. Analogue Value AO (R/W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228. PICS - Protocol Implementation Conformance Statement. . . . . . . . . . . . . . . . . . . .312/36

3005299-2015-09-29.fm1.Product informationThis protocol contains descriptions of all BACnet Object Instances in the EXcon Master.Values in the individual OIs depend on the air handling unit's configuration. For example,the water heating coil return temperature Analogue Input Object Instance 26 will be ableto be read regardless of whether a water heating coil is installed in the actual air handlingunit or not. But the value will only be useful if an associated temperature sensor isinstalled.The BACnet function provides the option for BACnet control and monitoring of acomplete Air Handling Unit (AHU), which is equipped with an EXcon Master controlsystem.BACnet functionality is implemented in EXcon Master using software 2.00 or newer.EXcon Master is a BACnet Application Specific Controller (B-ASC) with supported datalink layer options: BACnet IP. In addition, refer to document "OJ-Air2 EDE" (EngineeringData Exchange). See EXHAUSTO’s website (WWW).CommunicationTCP/IP: 1 x 10/100 Mbit Ethernet, RJ45 connectorEXcon Master,viewed from above1 x RJ12 for hand-heldterminalObject IdentifierObject Identifier is set automatically to the last 5 digits in the EXcon MasterIP address.Example:IP-address 172.21.0.95 172.021.000.095 - Object Identifier 95NB:BACnetInteroperabilityBuilding BlocksSupportedObject Identifier is only set once when the EXcon Master is switched on/restarted.A maximum of 300 values in the COV (Change of Value) can be read at the same time.Data SharingDS-RP-BData Sharing – Read Property – BData SharingDS-WP-BData Sharing-WriteProperty-BDevice ManagementDM-DDB-BDevice Management – Dynamic Device Binding – BDevice ManagementDM-DOB-BDevice Management – Dynamic Object Binding – BDevice ManagementDM-DCC-BDevice Management – Dynamic CommunicationControl – B3/36

3005299-2015-09-29.fmBACnet IP standardobject typesStandard object typessupportedCharacteristicsBinary Value DO (R/W)Object Identifier, Object Name, Object Type, Present Value,Status Flags, Event State, Out Of Service, Priority Array,Relinquish Default.Binary Input DI (R)Object Identifier, Object Name, Object Type, Present Value,Status Flags, Event State, Out Of Service, Priority Array,Analogue Input AI (R)Object Identifier, Object Name, Object Type, Present Value,Status Flags, Event State, Out Of Service, devices,Min Pres Value, Max Pres Value, resolution, reliability,COV IncrementBinary ValueAO (R/W)Object Identifier, Object Name, Object Type, Present Value,Status Flags, Event State, Out Of Service, devices,Priority Array, Relinquish Default, COV Increment.DeviceObject Identifier, Object Name, Object Type, Present Value,Vendor Name, Vendor Identifier, Model Name,Firmware Revision, Aplication Software Version, Location,Description, Protocol Version, Protocol Revision,Protocol Services Supported,Protocol Object Types Supported, Object list,Max APDU Length Accepted, Segmentation Supported,APDU Timeout, Number Of APDU Retries,Device Address Binding, Database Revision.RO Read onlyRW Read/Write4/36

3005299-2015-09-29.fm2.Communication via external BACnet IP2.1 Configuration - BACnet IPProgram for communication set-upand read-out of parametersFor example, QuickMod Modbus Scanner (Freeware)http://www.azeotech.com- orfor example Modbus Pollhttp://www.modbustools.comStandard LAN cableEXcon MasterEXHAUSTO5/36

3005299-2015-09-29.fm2.2 Setting up parameters BACnet IP1 Start "DAQFactory QuickMod" Modbus scanner2 Click on "Modbus TCP over Ethernet"3 Click on "Configure"4 Read/Set communication parameters in EXcon hand-held terminal5 Set communication parameters in "DAQFactory QuickMod Modbus scanner"6 Set IP-Address as read/set in EXcon hand-held terminal7 Set Port Always Port 5028 Set "Timeout" 10009 Click on "Save"2396786/36

2,11,2T2TE21FanIO2P1, P2T1,T2T1TE122 PP2M1 PP1FAN/FXECEFLightMRHX2MEXconER3ECSFLight7/365M2 PP1 PP2FAN/FX4FanIO1P1, mOverview3.1 Overview diagram and data points

3005299-2015-09-29.fm3.2 Most used data pointsPos. no. onoverviewdiagramLocationData points-For the whole airhandling unitCurrent operating modeManual operating functionSetting temperature regulation modeOperation ON/OFFExtended low speed activeExtended high speed activeA-alarm activeB-alarm activeAlarm resetAI; OI, 0AV; OI, 0AV; OI, 133BI; OI, 0BI; OI, 3BI; OI, 4BI; OI, 30BI; OI, 31BV; OI, 01Exhaust airCurrent exhaust air temperatureCurrent airflowMotor signal setpointSetpoint low speedSetpoint high speedAI; OI, 22AI; OI, 7AI; OI, 60AI; OI, 12AI; OI, 132Outdoor airCurrent outdoor air temperatureSupply air filter pressureAlarm limit supply air filterAI; OI, 20AI; OI, 27AI; OI, 313RecoveryHeat recovery setpointAI; OI, 684Extract airCurrent extract air temperatureExtract air filter pressureAlarm limit extract air filterTemperature setpoint for current regulationmodeCurrent duct pressure extract airSetpoint duct pressure low speed extract airSetpoint duct pressure high speed extract airAI; OI, 18AI; OI, 28AI; OI, 32AV; OI, 134AI; OI, 3AV; OI, 6AV; OI, 75Supply airCurrent supply air temperatureCurrent airflowMotor signal setpointSupply air setpoint low speedSupply air setpoint high speedTemperature setpoint for current regulationmodeCurrent duct pressure supply airSetpoint duct pressure low speed supply airSetpoint duct pressure high speed supply airAI; OI, 16AI; OI, 5AI; OI, 51AV; OI, 10AV; OI, 11AV; OI, 134AV; OI, 1AV; OI, 2AV; OI, 36Heating coilHeating levelHeating relay 1Electric heating coil high temperatureFrost-free temperatureAI; OI, 36BI; OI, 26BI; OI, 34AI; OI, 267Cooling coilCooling levelCooling relay 1AI; OI, 38BI; OI, 278TemperaturesensorRoom temperatureTemperature setpoint for current regulationmodeAI; OI, 21AV; OI, 1348/36

3005299-2015-09-29.fm4.Binary Value DO (R/W)NAMEUNITADDRESSMIN.MAX.NOTESAlr Reset001Alarm reset-signal (changes automatically to zero)CoolRecovFunc101Cold recovery ON/OFFSN Func201Summer night cooling ON/OFFSWTC Func301Summer/Winter temperature compensation; ON/OFFFlwTmpCmpFunc401Airflow temperature/outdoor air temperature; ON/OFFRecircFunc501Recirculation function; ON/OFFCoolFlwForceFc601Forced airflow with cooling requirement; ON/OFFTimeSw-SumFunc701Automatic summer time/winter time;ON/OFFExtDrfHiPeriod801Input for forced high speedExtDrfPeriodON901Run-on time on forced high speed activeManZeroCali1001Start manual "0" calibration (can be used at the samewith automatic "0"calibration)Resets automatically to "0" (OFF) when the calibrationis completedAutoZeroCali1101Automatic "0" calibration function ON/OFF1Filter, dynamic alarm function - ON/OFFOFF - Static alarm limit (Constant)ON - Dynamic alarm limit(Dynamic limit in relation to airflow)FiltDynAlrFunc120FiltCalibrate1301Start filter calibration Changes automatically to "0"(OFF) when the calibration is completedUsed only when the filter monitoring is set to"DYNAMIC"FiltCaliDone1401Filter calibration executed (valid filter data)Used only when the filter monitoring is set to"DYNAMIC"MBTOutd Act1501Activation of outdoor sensor via BMSMBTRoom1 Act1601Activation of room sensor via BMS9/36

3005299-2015-09-29.fm5.Binary Input DI (R)ADDRESSMIN.MAX.NOTESOperation001Current operating modeExtStop101External stopExtHiSpeed201External high speedExtDrfLoSpeed301Extended low speed - activeExtDrfHiSpeed401Extended high speed - activeElBattPowerRed501Energy for electric heating coil reduced due to lowairflow.SN Drift601Summer night cooling is activeSN Reset701Reset parameters for summer night cooling(new calculation is started)SWTC WintComp801Winter temperature compensation is activeSWTC SumComp901Summer temperature compensation is activeSW Status1001Summer/winter current status (SW Mode 1.3)OFF – Winter operation ("0")ON – Summer operation ("1")RecircStatus1101Recirculation statusEXC Exercise1201Motioning of heat exchanger - activeExhaustPowRed1301Signal for crossflow heat exchanger reduced (frostprotection)SupDuctMinFlow1401Supply air duct pressure regulator, adjusted for min.airflowSupDuctMaxFlow1501Supply air duct pressure regulator, adjusted for max.airflowExtDuctMinFlow1601Extract air duct pressure regulator, adjusted for min.airflowExtDuctMaxFlow1701Extract air duct pressure regulator, adjusted for max.airflowCoolRecovery1801Cold recovery - StatusHW FrosrReg1901Circulation pump on heating coilFrost regulation - activeHW PumpExer2001Circulation pump on heating coil;Pump motioning - activeCW PumpExer2101Circulation pump on cooling coil;Pump motioning - activeHeat FlwDnReg2201Signal for heating coil reduced(for low airflow) - active1"1" when min. supply air temperature regulation isactive.Only active when "TempRegMode" is 1 or 2 Sup2401"1" when max. supply air temperature regulation isactive.Only active when "TempRegMode" is 1 or 2 (Roomregulation)BattEXC Exer2501Circulation pump on recovery section; Pump motioning activeHeat RE12601Heating relay 1Cool RE12701Cooling relay 110/36

3005299-2015-09-29.fmADDRESSMIN.MAX.NOTESBattEXC PumpRE2801Circulation pump on recovery section;Pump - operatingAlrActive2901At least one active alarmAlr RE13001Alarm relay 1 (A-Alarm)Alr RE23101Alarm relay 2 (B-Alarm)Alr FireSignal3201Fire, alarm signal (Room sensor)Alr SmokeSig3301Smoke/fire, alarm signal (Sensor in duct)ElBattOverHeat3401Electric heating coil, High temperature alarm signalFiltSupalarm3501Filter alarm for supply air filter(Pressure drop above set limit)FiltExtalarm3601Filter alarm for extract air filter(Pressure drop above set limit)SupTempSensErr3701Supply air temperature sensor - sensor faultExtTempSensErr3801Extract air temperature sensor - sensor faultOutDoorSensErr3901Outdoor air temperature sensor - sensor faultRoomSensErr4001Room temperature sensor - sensor faultExhaustSensErr4101Exhaust air temperature sensor - sensor faultHW SensErr4201Water heating coil temperature sensor - sensor faultNAMEUNITBattEXC SensEr4301Heat exchanger temperature sensor - sensor faultHW FrostAlr4401Water heating coil - frost alarmCool Sumalarm4501Cooling common alarmCool DI1 alarm4601Cooling digital alarm-1 InputCool DI2 alarm4701Cooling digital alarm-2 InputCool DI3 alarm4801Cooling digital alarm-3 InputCool DI4 alarm4901Cooling digital alarm-4 InputSupmotorON5001Supply air motor ON/OFFSupmotoralarm5101Alarm from supply air motor ON/OFFFCsupMtrAlrVlo5201Supply air motor voltage low alarm(only with OJ-FC)FCsupMtrAlrVHi5301Supply air motor high voltage limit alarm(only with OJ-FC)FCsupMtrAlrIHi5401Supply air motor high current alarm(only with OJ-FC), motor protectionFCsupMtrAlrTmp5501Supply air motor temperature alarm(only with OJ-FC)FCsupMtrAlrPhs5601Supply air motor phase error alarm(only with OJ-FC)FCsupMtrAlrRip5701Supply air motor ripple voltage alarm(only with OJ-FC)FCsupMtrIHiLim5801Supply air motor high current limit; short-circuitprotection (only with OJ-FC)ExtmotorON5901Extract air motor ON/OFF(only with OJ-FC)Extmotoralarm6001Extract air motor alarm ON/OFF(only with OJ-FC)FCextMtrAlrVlo6101Extract air motor alarm for low voltage(only with OJ-FC)FCextMtrAlrVHi6201Extract air motor high voltage limit alarm(only with OJ-FC)11/36

lrIHi6301Extract air motor high current limit alarm(only with OJ-FC)FCextMtrAlrTmp6401Extract air motor temperature alarm(only with OJ-FC)FCextMtrAlrPhs6501Extract air motor alarm for phase error(only with OJ-FC)FCextMtrAlrRip6601Extract air motor ripple voltage alarm(only with OJ-FC)FCextMtrIHiLim6701Extract air motor high current limit(only with OJ-FC)EXC ON6801Rotary heat exchanger; Motor regulation ON/OFF(only with OJ-RHX2M)EXC Reset6901Rotary heat exchanger; Reset signal(only with OJ-RHX2M)EXC Direction7001Rotary heat exchanger; direction of rotation(only with OJ-RHX2M)EXC Rotalarm7101Rotary heat exchanger; Rotation alarm(only with OJ-RHX2M)EXC Vloalarm7201Rotary heat exchanger; Alarm for undervoltage(only with OJ-RHX2M)EXC VHialarm7301Rotary heat exchanger; Alarm for overvoltage(only with OJ-RHX2M)EXC IHialarm7401Rotary heat exchanger; Alarm for high current(only with OJ-RHX2M)EXC Tempalarm7501Rotary heat exchanger; Temperature alarm(only with OJ-RHX2M)EXC RotSignal7601Rotary heat exchanger; Rotation signal(only with OJ-RHX2M)EXC Overload7701Rotary heat exchanger; Torque overload(only with OJ-RHX2M)ExtBrandStop7801External fireman's stop input, statusAddOnTSens1Err7901Supplementary sensor 1, sensor faultAddOnTSens2Err8001Supplementary sensor 2, sensor faultAddOnTSens3Err8101Supplementary sensor 3, sensor faultAddOnTSens4Err8201Supplementary sensor 4, sensor faultAlrFrostLuft8301Frost alarm from frost thermostat; Digital inputHW2 FrostReg8401Water heating coil 2;Frost regulation - activeHW2 PumpExer8501Water heating coil 2;Pump motioning - activeHW2 SensErr8601Water heating coil 2 - return sensor; Sensor faultHW2 FrostAlr8701Water heating coil 2; Frost alarmPHFreezeAlarm8801Pre-heating coil; Frost alarmPHFrostRegAct8901Pre-heating coil; Frost regulation activeNAMEUNIT12/36

r9001Pre-heating coil; Pump motioningPHHeatRelay9101Pre-heating coil; Heating relay activePH OverHeat9201Preheating coil; Overheating faultPH PowReduc9301Pre-heating coil; Power reduction, low airflow (onlyelectric heating coil)PH HWBSensErr9401Preheating coil - Return sensor; sensor faultAlrEXCEffToLow9501Alarm efficiency on heat exchanger is too lowAlrAtvSupComm9601Alarm ATV FC supply air; no communication to ATVfrequency converterAlrAtvExtComm9701Alarm ATV FC extract air; no communication to ATVfrequency converterAlrAtvSupFC9801Alarm ATV FC supply air; common alarm from ATVfrequency converterAlrAtvExtFC9901Alarm ATV FC extract air; common alarm from ATVfrequency converterAlrFrzBattEXC10001Frost alarm; liquid connected heat exchanger (BattEXC)AlrDeIceCont10101Ice protection pre-heating coil - Contactor stuck (onlyelectric heating coil)AlrDeIceOverh10201Ice protection pre-heating coil - Overheating fault (onlyelectric heating coil)AlrDeIceReduc10301Ice protection; preheating coil - Power reduction, lowairflow (only electric heating coil)AlrNoREXCali10401Pressure transmitter over rotary heat exchanger;Extract air, not calibratedAlrSensREXNC10501Pressure transmitter over rotary heat exchanger;Extract air, no connectionNO CRecovStat10601Cold recovery recirculation activeNO CStpRoomAct10701Cold blocking; Room temperature stopHP CoolingActv10801Heating pump; Cooling operation activeHP De-icingAct10901Heating pump; De-icing activeAlrRexFrozen11001Alarm, rotary exchanger iced upAlrRexDusty11101Alarm, rotary exchanger soiledHt2FlowChgAct11201Airflow changed because Heating 2 is activeHt2DelayStatus11301Status timer Heating 2Ht2DelLimBlkNo11401Limiting for Heating 2 is not activeHt2RecBlkAct11501Blocking of Heating 2 with recirculation ActiveIntRecFlowStat11601Status, low airflow at 100% recirculationRecClosDmpAct11701Recirculation damper is closedHW1RiFaActiv11801Max. increase/fall time is activatedNAMEUNIT13/36

hiLim11901EC 2 Supply air motor high current limit; short-circuitprotectionEC2supMtAlrVlo12001EC 2 Supply air motor low voltage, alarmEC2supMtAlrVhi12101EC 2 Supply air motor high voltage, alarmEC2supMtAlrIhi12201EC 2 Supply air motor high current limit; alarmEC2supMtAlrTmp12301EC 2 Supply air motor temperature, alarmEC2supMtAlrPhs12401EC 2 Supply air motor, alarm for phase errorEC2sup I Rip12501EC 2 Supply air motor, alarm for high rippleEC2supRoBlok12601EC 2 Supply air motor, alarm for blocked rotorEC2extMtIhiLim12701EC 2 Extract air motor high current limit; short-circuitprotectionEC2extMtAlrVlo12801EC 2 Extract air motor voltage low, alarmEC2extMtAlrVhi12901EC 2 Extract air motor voltage high, alarmEC2extMtAlrIhi13001EC 2 Extract air motor high current limit; alarmEC2extMtAlrTmp13101EC 2 Extract air motor temperature, alarmEC2extMtAlrPhs13201EC 2 Extract air motor, alarm for phase errorEC2ext I Rip13301EC2 Extract air motor, alarm for high rippleEC2extRoBlok13401EC 2 Extract air motor, alarm for blocked rotorEC-Sup2-Comm13501EC 2 Supply air motor, alarm for communication failureEC-Ext2-Comm13601EC 2 Extract air motor, alarm for communication failureECsupMtIhiLim13701EC Supply air motor high current limit; short-circuitprotectionECsupMtAlrVlo13801EC Supply air motor voltage low, alarmECsupMtAlrVhi13901EC Supply air motor voltage high, alarmECsupMtAlrIhi14001EC Supply air motor high current limit; alarmECsupMtAlrTmp14101EC Supply air motor temperature, alarmECsupMtAlrPhs14201EC Supply air motor, alarm for phase errorECsup I Rip14301EC Supply air motor, alarm for high rippleECsupRotBlok14401EC Supply air motor, alarm for blocked rotorECextMtIhiLim14501EC Extract air motor high current limit; short-circuitprotectionECextMtAlrVlo14601EC Extract air motor voltage low, alarmECextMtAlrVhi14701EC Extract air motor voltage high, alarmNAMEUNIT14/36

rIhi14801EC Extract air motor high current limit; alarmECextMtAlrTmp14901EC Extract air motor temperature, alarmECextMtAlrPhs15001EC Extract air motor, alarm for phase errorECext I Rip15101EC Extract air motor, alarm for high rippleECextRotBlok15201EC Extract air motor, alarm for blocked rotorEC-Sup-Comm15301EC Supply air motor, alarm for communication failureEC-Ext-Comm15401EC Extract air motor, alarm for communication failureTTH6202ComAlr15501TTH-6202 communication failureBELDampSmokeComErr15601Alarm for communication failure Belimo smokeevacuation damperAlrBDDampSmokePos15701Alarm for position fault Belimo smoke evacuationdamperAlrExtIO1 Comm15801Extension IO-Module no. 1 - communication failureAlrExtIO2 Comm15901Extension IO-Module no. 2 - communication failureAlrExtIO3 Comm16001Extension IO-Module no. 3 - communication failureAlrExtIO4 Comm16101Extension IO-Module no. 4 - communication failureAlrExtIO5 Comm16201Extension IO-Module no. 5 - communication failureAlrExtIO6 Comm16301Extension IO-Module no. 6 - communication failureAlrExtIO7 Comm16401Extension IO-Module no. 7 - communication failureAlrExtIO8 Comm16501Extension IO-Module no. 8 - communication failureAlrSupTemp216601Customer specificAlrAddOnSens116701Supplementary sensor 1 - sensor faultAlrAddOnSens216801Supplementary sensor 2 - sensor faultAlrAddOnSens316901Supplementary sensor 3 - sensor faultAlrAddOnSens417001Supplementary sensor 4 - sensor faultAlrSupMtr17101Alarm supply air motorAlrExtMtr17201Alarm extract air motorCmb2CoolRel17301Combi coil; Cooling relay no. 2 activeHW1RIFaActRH17401Customer specificCmbEnCtrlMB17501Combi coil - release Modbus controlCmbEnHeatMB17601Combi coil - heating stateCmbEnCoolMB17701Combi coil - cooling stateNAMEUNIT15/36

3005299-2015-09-29.fmADDRESSMIN.MAX.NOTESECsupEEP Err17801EC Supply air motor, alarm for EEPROM faultEC2supEEP Err17901EC Supply air motor 2, alarm for EEPROM faultECextEEP Err18001EC Extract air motor, alarm for EEPROM faultEC2extEEP Err18101EC Extract air motor 2, alarm for EEPROM faultTTH6040ComAlr18201TTH-6040 (room sensor) communication failureLowOilDXHPAlr18301Alarm - low oil level in cooling compressorAlrComWBPump18401Alarm 27AlrComSupFan18501Common alarm - supply air fanAlrComExtFan18601Common alarm - exhaust air fanAlrComSupFlDu18701Common alarm - supply air pressure/airflowAlrComExtFlDu18801Common alarm - exhaust air pressure/airflowAlrComEXC18901Common alarm - heat exchangerAlrComFreeze19001Common alarm - frostAlrComElHeat19101Common alarm - electric heating coilAlrComTemp19201Common alarm - temperature high/lowAlrComSFilt19301Common alarm - supply air filterAlrComEFilt19401Common alarm - extract air filterAlrComTmpSens19501Common alarm - temperature sensorAlrComCool19601Common alarm - coolingAlrComBDamp19701Common alarm - Belimo damperAlrComIntern19801Common alarm - internal modbus errorBMS InpState19901Input for activation of BMS control - activeExternLowState20001Input for activation of External low - activeAlr MBTOutds20301Alarm - BMS outdoor sensor out of range for more than10 seconds.Alr MBTRoom120401Alarm - BMS room sensor out of range for more than 10seconds.AlrFireManstop20501Alarm - Air handling unit stopped by "Fireman's stop"AlrSmokEvac20601Smoke evacuation activeAlrSmokEvaFan20701Alarm, smoke evacuation fanStatInleRel20801Output for recirculation damper - activeStatSupRel20901Output for recirculation damper - activeNAMEUNIT16/36

l21001Output for recirculation damper - activeExOutDSensErr21101External outdoor sensor - sensor faultPHTempSensErr21201Temperature sensor pre-heating coil - sensor faultCW TSensErr21301Cooling water supply - sensor faultHeat RE2121401Relay 1 on heating coil 2 activatedHeat RE2221501Relay 2 on heating coil 2 activatedHeat RE2321601Relay 3 on heating coil 2 activatedHeat RE2421701Relay 4 on heating coil 2 activatedHeat RE2521801Relay 5 on heating coil 2 activatedHeat RE2621901Relay 6 on heating coil 2 activatedCombi PumpRE22001Pump relay combi coil activatedNAMEUNIT17/36

3005299-2015-09-29.fm6.Analogue Input AI (RO)lNAMEUNITOperation ModeOBJECTMIN.INSTANCEMAX.NOTES00500Current Operating Mode000-099:Air Handling Unit stop100-199:Air Handling Unit Low speed200-299:Air Handling Unit High speed300-399:Air Handling Unit Spec RegModeSupDuctPaPa102000Current duct pressure supply airSupDuctPaRgSetPa202000Setpoint for duct pressure supply airExtDuctPaPa302000Current duct pressure extract air [Pa]ExtDuctPaRgSetPa402000Setpoint duct pressure extract airSupFlowl/s5030000Current supply airflowSupFlowRegSetl/s625030000Setpoint supply airflowExtFlowl/s7030000Current extract airflowExtFlowRegSetl/s8030000Setpoint for extract airflowCO2 ppmMeasppm9010000CO2 sensor measuringMtrFanSupVinV100100-10 VDC signal for supply air motorMtrFanExtVinV110100-10 VDC signal for extract air motorFAN SupPrcMeas%120100Voltage on Fan Optimiser input; Supply air signalFAN ExtPrcMeas%130100Voltage on Fan Optimiser input; Extract air signalSupFC MaxFlowl/s1410030000Supply air FC - Max. airflow [m3/h]ExtFC MaxFlowl/s1510030000Extract air FC - Max. airflow [m3/h]SupTemp C16-40100Current supply air temperatureSupTempRegSet C17040Setpoint for supply air temperatureExtTemp C18-40100Current extract air temperatureExtTempRegSet C19040Setpoint for extract air temperatureOutDoorTemp C20-40100Current outdoor air temperatureRoomTemp C21-40100Current room temperatureExhaustTemp C22-40100Current exhaust air temperatureTempRegMeas C23-40100Temp. measuring for current regulation choiceTempRegVal C24040Regulation value for current regulation choiceBattEXC Temp C25-40100Water heating coil temperature after heat exchangerHW BattTemp C26-40100Current temperature, water heating coilSupFiltPaAvrPa2702000Supply air filter pressureExtFiltPaAvrPa2802000Extract air filter pressureSupMotorSet%29010000Setpoint for motor signal, supply airExtMotorSet%30010000Setpoint for motor signal, extract airFiltSupAlrPaPa310100Supply air filter monitoring max. alarm limitUsed only when the filter monitoring is set to"DYNAMIC"FiltExtAlrPaPa320100Extract air filter monitoring max. alarm limitUsed only when the filter monitoring is set to"DYNAMIC"FlwTmpCmpOut%33-40100Temperature corrected airflow setpointSWTC ActSetOfs C34-1010Summer/winter temperature compensation of currentsetpoint, offset18/36

.NOTESHeatEXCPower%350100Heat exchanger regulator heating powerHeatPower%360100Current heating powerCoolPower%370100Cooling regulator powerCoolActPower%380100Current cooling powerCoolFlwForcePw%390100Forced cooling airflow powerCoolVin1Alarm%400100Cooling alarm 1 transmitter signalCoolVin2Alarm%410100Cooling alarm 2 transmitter signalCoolVin3Alarm%420100Cooling alarm 3 transmitter signalCoolVin4Alarm%430100Cooling alarm 4 transmitter signalC LoPress1BarBar440100Current low pressure transmitter - 1 Bar [1/100 Bar]C HiPress1BarBar450100Current high pressure transmitter - 1 Bar [1/100 Bar]C LoPress2BarBar460100Current low pressure transmitter - 2 Bar [1/100 Bar]C HiPress2BarBar470100Current high pressure transmitter - 2 Bar [1/100 Bar]FCsupMtrType480256Supply air motor type (only OJ-FC)FCsupMtrFC SW49Supply air motor software vers. (only OJ-FC)FCsupMtrIO SW50Supply air IO card software vers. (only OJ-FC)FCsupMtrPrcOut%510100Supply air motor output, percent (only OJ-FC)FCsupMtrHzOutHz52010000Supply air motor output, frequency [1/100 Hz] (only OJFC)FCsupMtrIoutmA53030000Supply air motor output, current current (only OJ-FC)FCsupMtrPowOutWatt5406000Supply air motor output, current power (only OJ-FC)FCsupMtrPrcSet%550100Supply air motor setpointSupSFPJ/m356010000Supply air specific fan power (SFP) [Ws/m3 J/m3](only OJ-FC)FCextMtrType570256Extract air motor type (only OJ-FC)FCextMtrFC SW58Extract air motor software vers. (only OJ-FC)FCextMtrIO SW59Extract air IO card software vers. (only OJ-FC)FCextMtrPrcOut%600100Extract air motor output, percent (only OJ-FC)FCextMtrHzOutHz61010000Extract air motor output, frequency [1/100 Hz] (only OJFC)FCextMtrIoutmA62030000Extract air motor output, current current (only OJ-FC)FCextMtrPowOutWatt6306000Extract air motor output, current power (only OJ-FC)FCextMtrPrcSet%640100Extract air motor output, setpointExtSFPJ/m365010000Extract air specific fan power (SFP) [Ws/m3 J/m3](only OJ-FC)EXC Type6603Rotary heat exchanger, motor type (only OJ RHX2M)EXC Software67Rotary heat exchanger, software vers.(only OJ RHX2M)EXC PrcOut%680100Rotary heat exchanger, percentEXC RpmOutrpm690200Rotary heat exchanger, rpm output19/36

.NOTESEXC IoutmA70010000Rotary heat exchanger, current output(only OJ RHX2M)EXC PowerWatt71010000Rotary heat exchanger; output power(only OJ RHX2M)EXC DriftDaysDay72032000Rotary heat exchanger; total number operating days(only OJ RHX2M)EXC PrcSet%730100Rotary heat exchanger; setpoint(only OJ RHX2M)EXTM1 SW Ver74Extension Module 1 software vers. [1/100]EXTM2 SW Ver75Extension Module 2 software vers. [1/100]TimeSw-WeekDay7606Current weekday (0-Mon.6-Sun)ExtDrfDaysLeftDay7706Extended operation remaining total number daysExtDrfMinLeftMin7801439Extended operation remaining total number minutesAlr Released00790300Stack for active alarms(0 indicates end of stack)Alr Released01800300Stack for active alarms(0 indicates end of stack)Alr Released02810300Stack for active alarms(0 indicates end of stack)Alr Released03820300Stack for active alarms(0 indicates end of stack)Alr Released04830300Stack for active alarms(0 indicates end of stack)Alr Released05840300Stack for active alarms(0 indicates end of stack)Alr Released06850300Stack for active alarms(0 indicates end of stack)Alr Released07860300Stack for active alarms(0 indicates end of stack)Alr Released08870300Stack for active alarms(0 indicates end of stack)Alr Released09880300Stack for active alarms(0 indicates end of stack)Alr Released10890300Stack for active alarms(0 indicates end of stack)Alr Released11900300Stack for active alarms(0 indicates end of stack)Alr Released12910300Stack for active alarms(0 indicates end of stack)Alr Released13920300Stack for active alarms(0 indicates end of stack)Alr Released14930300Stack for active alarms(0 indicates end of stack)Alr Released15940300Stack for active alarms(0 indicates end of stack)MasterSW Ver95DisplaySW VerMaster software vers.96Display software vers.AddOnTSensor1 C97-40100Supplementary sensor 1AddOnTSensor2 C98-40100Supplementary sensor 2AddOnTSensor3 C99-40100Supplementary sensor 3AddOnTSensor4 C100-40100Supplementary sensor 420/36

.NOTESMtrFanSupVinV1010100-10 VDC signal for supply air motorMtrFanExtVinV1020100-10 VDC signal for extract air motorHeat2Power%1030100Heating 2 regulator powerPHeatPower%1040100Current power, pre-heating coilPHeatTempAir%1050100Current temperature, pre-heating coil106030000Supply air ATV, frequency converter, Current FC TypeAtvSupFCTypAtvExtFCTyp107030000Extract air ATV frequency converter, Current FC TypeEXCActualEff%1080100Current heat exchanger efficiencyHW12 VDCOutV109010Heating 12; VDC signalHP CoilPaMeasPa11002000Pressure drop across heat pump outdoor part11102Current status of recirculation Latest change of airflow:0 No cha

1 Start "DAQFactory QuickMod" Modbus scanner 2 Click on "Modbus TCP over Ethernet" 3 Click on "Configure" 4 Read/Set communication parameters in EXcon hand-held terminal 5 Set communication parameters in "DAQFactory QuickMod Modbus scanner" 6 Set IP-Address as read/set in EXcon hand-held terminal 7 Set Port Always Port 502 8 Set "Timeout" 1000