IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECTDSAAPP: 03-121326 INC:GENERAL NOTES10. CONTRACTOR BIDCONTRACTOR'S BID SHALL BE BASED ON ALL WORK SHOWN ON THE PLANS AND AS SPECIFIED. IF CONTRACTOR PROPOSES TOSUBSTITUTE FOR EQUIPMENT SPECIFIED, HE SHALL SUBMIT HIS REQUEST FOR CONSIDERATION OF THE OWNER AND ENGINEERPRIOR TO BID IN WRITING. ALL SUBSTITUTIONS MUST BE REVIEWED BY THE ENGINEER IN WRITING. SUCH REVIEW SHALL NOTRELIEVE THE CONTRACTOR COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS, AND THECONTRACTOR SHALL BE RESPONSIBLE AT HIS OWN EXPENSE FOR ANY CHARGES RESULTING FROM HIS PROPOSEDSUBSTITUTIONS WHICH AFFECT OTHER PARTS OF HIS OWN WORK, THE OWNER, ENGINEER OF RECORD OR THE WORK OFOTHER CONTRACTORS.B.DRAWING FILENAME: 20-120E100DRAFTER: CM02MATERIAL AND INSTALLATIONALL WORK AND MATERIAL SHALL CONFORM TO THE LATEST RULES OF THE GOVERNING ELECTRICAL CODE AND INSTALLATIONSHALL BE OF THE LATEST INDUSTRY STANDARDS OF WORKMANSHIP.1.3.4.PANELBOARDSNOT USED.7.8.STRUCTURAL SUPPORTEACH SECTION OF FLOOR MOUNTED SWITCHBOARD, DISTRIBUTION BOARD, MCC, ETC. SHALL BE BOLTED TO THE CONCRETEHOUSEKEEPING PAD USING (6) 3/4"-10 GRADE 2 BOLTS AND CONICAL WASHERS TORQUED TO 70LB-FT. PROVIDE MINIMUM 4000PSI STRENGTH CONCRETE BELOW ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT. TIE THE TOP OF ALL FLOOR MOUNTEDELECTRICAL EQUIPMENT TO THE BUILDING STRUCTURE IN A SEISMICALLY APPROVED MANNER.ELECTRICAL CERTIFICATION"ELECTRICIANS" PERFORMING WORK ON THIS PROJECT SHALL BE CURRENTLY CERTIFIED IN ACCORDANCE WITH THE STATE OFCALIFORNIA AB931 AND THE DIVISION OF APPRENTISHIP STANDARDS SECTION 3099.C.1.DEMOLITIONNOTIFY THE OWNER IMMEDIATELY WHEREVER EXISTING EQUIPMENT IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEWCONSTRUCTION, AND WHICH IS NOT INDICATED ON THE PLANS.2.BEGINNING OF DEMOLITION MEANS CONTRACTOR ACCEPTS EXISTING CONDITIONS.D.1.EXECUTIONCAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHEDSURFACES, LIMIT DAMAGE TO THE CONFINES AS MUCH AS POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACESWHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.2.EQUIPMENT, MATERIALS AND SUPPLIES REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALSDAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY.3.DO ALL DRILLING, CUTTING, CHANNELING AND PATCHING REQUIRED TO INSTALL ELECTRICAL WORK AS INDICATED OR HEREINSPECIFIED. ALL HOLES, CURBS, ETC., IN FLOORS, CEILINGS AND WALLS SHALL BE PATCHED, UNLESS INDICATED OTHERWISE. PAINTALL NEW ELECTRICAL RACEWAYS, CABINETS, ENCLOSURES AND FITTINGS PENETRATING INTO FIRE RATED ENVELOPES, SPACES, ETC.4.ALL CONDUIT RUNS SHALL BE CONCEALED, UNLESS SHOWN OTHERWISE. PROVIDE A PULL WIRE IN ALL EMPTY CONDUITS.5.EXISTING CONDITION SHOWN IS FROM AVAILABLE RECORD DRAWINGS AND VISUAL FIELD SURVEY AND SHOWN FOR REFERENCE ONLY.CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITION AT SITE.6.ALL WORK SHOWN IS NEW UNLESS SPECIALLY INDICATED AS EXISTING (X). ALL ELECTRICAL EQUIPMENT MOUNTING AND ANCHORAGEMUST CONFORM WITH LOCAL AND STATE SEISMIC CODES.ELECTRICAL PANEL SCHEDULEE510FIRE ALARM DETAIL SHEETTTRANSFORMERE500FIRE ALARM GENERAL NOTES, SYMBOLS & ABBREVIATIONE511E50124'X40' MODULAR FIRE ALARM PLAN MODULAR #2 & 3FIRE ALARM RISER DIAGRAM, VOLTAGE DROP, ANDBATTERY CALCULATION CALCULATIONE50236'X40' MODULAR FIRE ALARM PLAN MODULAR #1, 4, 8 & 92.FOR FIRE RATED WALL/CEILING PENETRATION AND/OR MEMBRANE PENETRATION, COMPLETE NRTL CLASSIFICATION SHEETS SHALL BEPROVIDED TO THE INSPECTOR AT THE TIME OF INSPECTION FOR THE LISTED RATED ASSEMBLY.3.PROVIDE SEPARATE SUBMITTAL; OBTAIN ALL REQUIRED PERMITS, INSPECTIONS AND APPROVALS FOR ALL FIRE ALARM SYSTEMINSTALLATIONS AND/OR MODIFICATIONS FROM THE FIRE DEPARTMENT.4.RACEWAY SEALS. CONDUITS OR RACEWAYS THROUGH WHICH MOISTURE MAY CONTACT LIVE PARTS SHALL BE SEALED OR PLUGGED ATEITHER OR BOTH ENDS.5.THE IDENTIFICATION OF EVERY CIRCUIT OF A PANEL BOARD AND SWITCHBOARD SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR,EVIDENT, AND SPECIFIC PURPOSE OR USE AND SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHEDFROM ALL OTHERS. 2016 C.E.C 408.4 - PROVIDE MORE DETAIL ON PANEL SCHEDULE CIRCUIT DESCRIPTIONS.I.FIRE ALARM SYSTEM1. CONTRACTOR SHALL PROVIDE AND INSTALL A FIRE ALARM SYSTEM FOR THE PROJECT AREA TO INCLUDE:ABBREVIATIONS3/4"C-3#12 & 1#12 GND3/4"C-4#12 & 1#12 GND3/4"C-5#12 & 1#12 GND#10#10#103/4"C-2#10 & 1#10 GND3/4"C-3#10 & 1#10 GND1" CONDUIT MINIMUM IF UNDERGROUND (CONTRACTOR TOPROVIDE DEDICATED NEUTRALS FOR CIRCUITS WHICH DO NOTHAVE COMMON CIRCUIT HANDLE TIES ON BREAKERS FEEDINGTHE CIRCUITS)3/4"C-4#10 & 1#10 GND3/4"C-5#10 & 1#10 GNDSEE KEY NOTE #1 AS INDICATED ON DRAWINGM100A UTILITY METER (OR AS NOTED)200AF150AT3PMOLDED CASE CIRCUIT BREAKER 200 AMP FRAME, 150 AMP TRIP RATING, 3 POLECOLOR CODE FOR CONDUCTORSPROVIDE CONDUCTOR COLOR CODE AS FOLLOWS:120/208VAC,3Ø,4W: BLUE,BLACK,RED FOR PHASE CONDUCTORS AND WHITE FOR NEUTRAL, GREEN FORGROUND.277/480VAC,3Ø,4W: ORANGE,BROWN,YELLOW FOR PHASE CONDUCTORS AND WHITE FOR NEUTRAL, GREEN FORGROUND.APPLICABLE CODES AND STANDARDS1.2019 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODECALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 12.2019 CALIFORNIA BUILDING CODE (CBC)CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 2(2018 INTERNATIONAL BUILDING CODE (IBC) W/CALIFORNIA AMENDMENTS)3.2019 CALIFORNIA ELECTRICAL CODE (CEC)CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 3(2017 NATIONAL ELECTRICAL CODE (NEC) W/CALIFORNIA AMENDMENTS)4.2019 CALIFORNIA ENERGY CODECALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 65.2019 CALIFORNIA FIRE CODE (CFC)CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 9(2018 INTERNATIONAL FIRE CODE (IFC) W/CALIFORNIA AMENDMENTS)6.2019 CALIFORNIA REFERENCED STANDARDS CODECALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 123.CONTRACTOR SHALL BE CAMPUS STANDARD - FCI.4.ALL DEVICES AND EQUIPMENT SHALL BE CALIFORNIA STATE FIRE MARSHALL APPROVED AND CURRENTLY LISTED.5.CONTRACTOR SHALL WARRANTY ALL DEVICES AND SYSTEMS FOR A PERIOD OF TWO YEARS.6.CONTRACTOR SHALL PROVIDE 6 (SIX) HARD COPY SETS OF FIRE ALARM MANUALS FOR ALL SYSTEMS AND DEVICES IN ADDITION TO 6(SIX) HARD COPY SETS OF A SYSTEM OPERATIONAL MANUAL TAILORED FOR THE PROJECT SPACE.7.7.CONTRACTOR SHALL PROVIDE AN INDIVIDUALLY ADDRESSABLE TOTALLY SUPERVISED SYSTEM WITH BATTERY BACK-UP FOR 24 HOURSOF MONITORING INITIATING CIRCUITS PLUS 30 MINUTES OF ALARM WITH DUAL RATE BATTERY CHARGER.AMERICANS WITH DISABILITIES ACT (ADA)TITLE II - ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAG)1990 STATE FIRE MARSHAL REGULATIONS AND AMENDMENTS TO-DATE8.8.CONTRACTOR SHALL PROVIDE A SATISFACTORY SYSTEM TEST IN THE PRESENCE OF THE OWNER, FIRE PREVENTION BUREAU ANDCONSULTING ENGINEER.CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, CALIFORNIA STATE ACCESSIBILITY STANDARDSCALIFORNIA CODE OF REGULATIONS (CCR) TITLE 199.2019 CALIFORNIA GREEN BUILDING STANDARDS CODE(CAL GREEN), PART II, TITLE 24 C.C.R.9.CONTRACTOR SHALL PROVIDE ALL CONNECTION TO POWER PANELS, CONDUIT AND WIRE AND CONNECTIONS REQUIRED TO PROVIDEAN OPERATIONAL FIRE ALARM SYSTEM.10. UNIQUELY LABEL ALL ADDRESSABLE DEVICES TO MATCH FIRE ALARM PROGRAMMING & AS BUILTS, EACH DEVICE TO BE UNIQUELYLABELED.11. CONTRACTOR TO LABEL AS ASM/E3 CLGCOCTV(CU)CWDISDSDWGECDEMEMTEOREPREVCSAMPERESAMP FRAME/AMP FUSEAVAILABLE FAULT CURRENTABOVE FINISHED FLOORAMP INTERRUPTING CURRENTARCHITECTAMP SWITCHAMERICAN SOCIETY OFTESTING MATERIAL(S)AMP TRIPAUTOMATIC TRANSFER SWITCHAMERICAN WIRE GAGEBACKBOARDCONDUIT OR CEILINGCIRCUIT BREAKERCONTINUATIONCIRCUITCEILINGCONDUIT ONLYCABLE TELEVISIONCOPPERCOLD WATER PIPEDISCONNECTDISCONNECT SWITCHDRAWINGELECTRICAL CONTRACTOREMERGENCY LIGHT/FEEDERELECTRICAL METAL TUBINGENGINEER OF RECORDETHYLENE PROPYLENE RUBBERELECTRIC VEHICLE LOW FLOOR BOXFEETGENERAL CONTRACTORGROUND FAULT ATE DISTRIBUTIONFRAMEISOLATED GROUNDJUNCTION BOXKILOKILO VOLT AMPS 1000VALIGHTING CONTACTORLONG CONTINUOUS LOADLOW VOLTAGEMETERMETAL CLADMAIN DISTRIBUTION FRAMEMINIMUMMOUNTEDMAIN TELEPHONE BACKBOARDMOUNTINGMEDIUM VOLTAGEMAN HOLEMANUFACTURERNATIONAL ELECTRICAL CODENEWNOT IN CONTRACTNIGHT LIGHTNORMALLY LUONUNSWVVAVDWWPW/(X)ɸNORMALLY CLOSEDOVERHEADPOWER OR POLEPROVIDED BY OTHERSPANELPHOTO VOLTAICREMOVEDRIGID GALVANIZED STEELCONDUITROOMSYSTEM NEUTRALSURGE PROTECTION DEVICETIME CLOCKSTELEPHONE TERMINAL BOARDTELEPHONE TERMINAL CABINETTRANSFORMERTRANSIENT VOLTAGE SURGESUPPRESSORTYPICALUNDERGROUNDUNDERWRITERS LABORATORYUNLESS OTHERWISE NOTEDUNSWITCHEDVOLTS/VOLTAGEVOLT AMPSVOLTAGE DROPWATTS/WATTAGE OR WIREWEATHERPROOFWITHEXISTINGPHASE10. 2019 CALIFORNIA MECHANICAL CODE (CMC)CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 4(2018 UNIFORM MECHANICAL CODE (UMC) W/CALIFORNIA AMENDMENTS)11. 2019 CALIFORNIA PLUMBING CODE (CPC)CALIFORNIA CODE OF REGULATIONS (CCR) TITLE 24, PART 5(2018 UNIFORM PLUMBING CODE (UPC) W/CALIFORNIA AMENDMENTS)13. 2016 NFPA 72 NATIONAL FIRE ALARM CODE(a) MORE THAN THREE CURRENT-CARRYING CONDUCTORS IN A RACEWAY OR CABLE. WHERE THE NUMBER OF CURRENT-CARRYINGCONDUCTORS IN A RACEWAY OR CABLE EXCEEDS THREE, THE ALLOWABLE AMPACITIES SHALL BE REDUCED AS SHOWN IN THEFOLLOWING TABLE:4 THROUGH 67 THROUGH 910 THROUGH 2021 THROUGH 3031 THROUGH 4041 AND ABOVEPERCENT OF VALUES IN TABLES AS ADJUSTEDFOR AMBIENT TEMPERATURE IF NECESSARY8070504540352'0" MAX2'-6" CLRTOPWHERE SINGLE CONDUCTORS OR MULTICONDUCTOR CABLES ARE STACKED OR BUNDLED LONGER THAN 24 INCHES (610 mm) WITHOUTMAINTAINING SPACING AND ARE NOT INSTALLED IN RACEWAYS, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED ASSHOWN IN THE ABOVE TABLE.EXCEPTION NO. 1: WHERE CONDUCTORS OF DIFFERENT SYSTEMS, AS PROVIDED IN SECTION 300-3, ARE INSTALLED IN A COMMONRACEWAY OR CABLE, THE DERATING FACTORS SHOWN ABOVE SHALL APPLY TO THE NUMBER OF POWER AND LIGHTING (ARTICLES 210, 215,220, AND 230) CONDUCTORS ONLY.EXCEPTION NO. 2: FOR CONDUCTORS INSTALLED IN CABLE TRAYS, THE PROVISIONS OF SECTION 318-11 SHALL APPLY.EXCEPTION NO. 3: DERATING FACTORS SHALL NOT APPLY TO CONDUCTORS IN NIPPLES HAVING A LENGTH NOT EXCEEDING 24 INCHES(610mm).EXCEPTION NO. 4: DERATING FACTORS SHALL NOT APPLY TO UNDERGROUND CONDUCTORS ENTERING OR LEAVING AN OUTDOOR TRENCHIF THOSE CONDUCTORS HAVE PHYSICAL PROTECTION IN THE FORM OF RIGID METAL CONDUIT, INTERMEDIATE METAL CONDUIT, OR RIGIDNONMETALLIC CONDUIT HAVING A LENGTH NOT EXCEEDING 10 FEET (3.05m) ABOVE GRADE AND THE NUMBER OF CONDUCTORS DOES NOTEXCEED FOUR.EXCEPTION NO. 5: FOR OTHER LOADING CONDITIONS, ADJUSTMENT FACTORS AND AMPACITIES SHALL BE PERMITTED TO BE CALCULATEDUNDER SECTION 310-15(b)(FNC): SEE APPENDIX B, TABLE B-310-11 FOR ADJUSTMENT FACTORS FOR MORE THAN THREE CURRENT-CARRYING CONDUCTORS IN ARACEWAY OR CABLE WITH LOAD DIVERSITY.(b) MORE THAN ONE CONDUIT, TUBE, OR RACEWAY. SPACING BETWEEN CONDUITS, TUBING, OR RACEWAYS SHALL BE MAINTAINED.PROJECT AREA(NEW MODULARS)TOP OF THERMOSTAT,SWITCH, OUTLET, CONTROLCLTHERMOSTAT, SWITCH,OUTLET, CONTROLFAX (805) 389-6519PROJECT AREA(ADMINISTRATION BUILDING)NEC #310-8 ADJUSTMENT FACTORSNUMBER OF CURRENT-CARRYINGCONDUCTORSNo. E 8340Exp. 09/30/2022EAT L E C T R I CAREOF C A L I FOSITE/AREA MAP12. 2013 TITLE 19 CALIFORNIA CODE OF REGULATIONS (CCR)PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONSDERATING TABLEFESSPRO W IONALD ETH . LNLA3/4"C-2#12 & 1#12 GND(805) 389-6520PROVIDE F.A. PLANS FOR 9 NEW MODULAR BUILDINGS PER SITE PLAN & 2 WAY COMMUNICATIONS TO ADMINISTRATIONBUILDING.2LA 1-3-5,7NIINDICATES A HOMERUN TO PNL 2LA, CKTS 1-3-5 WITH SHARED NEUTRAL &CKT 7 WITH DEDICATED NEUTRAL.1H. ADDITIONAL NOTES1. THE ISSUANCE OF A PERMIT SHALL NOT PREVENT THE BUILDING OFFICIAL FROM REQUIRING THE CORRECTION OF ERRORS ON THESEPLANS OR FROM PREVENTING ANY VIOLATION OF THE CODES ADOPTED BY THE CITY, RELEVANT LAWS, ORDINANCES, RULES AND/ORREGULATIONS.SCOPE OF WORKCAMARILLO, CA 93012-8094WHERE NO NUMBER IS INDICATED, THE CONDUCTORS ARE#12AWG(MIN.) CONDUIT SIZE IS AS REQUIRED BY ELECTRICAL CODE.(3/4" CONDUIT MINIMUM).7. CONTRACTOR SHALL EXAMINE PLANS AND VERIFY IN FIELD LOCATIONS OF ALL FIRE RATED WALLS, CEILINGS AND FLOORS.CONTRACTOR SHALL SEAL ALL ELECTRICAL SYSTEM PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS AND FLOORS WITH U.L.LISTED MATERIAL APPROVED BY THE AUTHORITY HAVING JURISDICTION.8. PANEL CIRCUIT DIRECTORY SHALL COMPLY WITH CEC 408.4.HASH MARKS INDICATE QUANTITY OF #12 CONDUCTORS. NO HASHMARKS INDICATE (2)#12AWG. (PROVIDE GROUND CONDUCTOR IN ALLCONDUITS.)3251 CORTE MALPASO, #511#10CONSULTING ELECTRICAL ENGINEERSFLEXIBLE CONDUIT (WITH GROUND CONDUCTOR, PROVIDE LIQUID TIGHT CONDUIT IN ALLEXPOSED AREAS)#10SWITCHES AND RECEPTACLESNOT USED.6.E2006. ALL ELECTRICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING, MAINTAINING ANDREPAIRING. ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. EXPOSED CONDUIT SHALL BE IN STRAIGHT LINES PARALLEL WITH,OR AT RIGHT ANGLES TO, COLUMN LINES OR BEAMS AND SEPARATED BY AT LEAST THREE (3) INCHES FROM WATER LINES WHENEVERTHEY RUN LONG SIDE OR ACROSS SUCH LINES. CONDUIT SHALL NOT BE RUN BELOW CABLE TRAYS OR LIGHT FIXTURES WITHOUTSPECIFIC APPROVAL OF THE OWNERS REPRESENTATIVE. HANGERS SHALL BE FASTENED TO STEEL, CONCRETE OR MASONRY, BUT NOTTO PIPING. HANGERS AND SUPPORT SYSTEMS ARE AN INTEGRAL PART OF THE VISUAL ENVIRONMENT. ALL HANGERS AND SUPPORTSEXPOSED TO PUBLIC VIEW MUST BE SHOWN IN DETAIL ON PLANS SUBMITTED TO ENGINEER FOR APPROVAL OF APPEARANCE. ALLHANGERS MUST BE UNIFORMLY SPACED AND NEATLY INSTALLED WITH NO EXCESS MATERIAL BEYOND WHAT IS REQUIRED FOR THESUPPORT FUNCTION. CONTRACTOR SHALL SELECT ACCESSORIES AND HARDWARE WITH A SMOOTH, NEAT FINISHED APPEARANCE ANDPAINT ALL EXPOSED CONDUIT HANGERS TO MATCH THE ADJACENT FINISHES.CONTRACTOR SHALL SUBMIT FOR THE OWNERS SIGNED APPROVAL, APPROVED FIRE DEPARTMENT FIRE ALARM DRAWINGS FOR THEPROJECT SPACE.LIGHTING FIXTURESNOT USED.36'X40' MODULAR FIRE ALARM PLAN MODULAR #5 & RESTROOMCONDUIT RUN CONCEALED BELOW FLOOR OR UNDERGROUND5. SIZE OUTLET BOXES IN CONFORMITY WITH CODE FOR NUMBER AND GAUGE OF CONDUCTORS THEREIN, EXCEPT WHERE NOTED TO BELARGER. MINIMUM BOX SIZE SHALL BE 4" SQUARE BY 1-1/2" DEEP.2.5.E5044. DO NOT RUN ANY CONDUIT IN SLAB IF ITS OUTSIDE DIAMETER EXCEEDS 1/3 THE THICKNESS OF THE SLAB. LOCATE CONDUITS WITHINTHE MIDDLE OF THE SLAB. WHERE CONDUITS ARE GROUPED IN PARALLEL RUNS, SPACE THEM 3" OR MORE APART. WHERE CONDUITSCROSS EACH OTHER, THICKEN SLAB PROPORTIONATELY OVER A HORIZONTAL AREA EQUAL TO TEN TIMES THE DIAMETER OF THELARGEST CONDUIT. REFER ALSO TO DETAILS SHOWN.CONDUITSCONDUIT SHALL BE EMT, PVC, IMC, RIGID OR FLEXIBLE STEEL TYPE. CONDUIT SHALL BE MANUFACTURED IN ACCORDANCE WITHUL-1. A GROUND WIRE IS REQUIRED IN ALL FLEXIBLE CONDUIT AND UNDERGROUND CONDUIT. BUSHINGS SHALL BE INSTALLEDON ALL COMMUNICATION, TELEPHONE & SPEAKER CONDUITS. PROVIDE 3/16" NYLON PULL STRING IN ALL EMPTY CONDUITS. NOMC, BX OR AC90 SHALL BE PERMITTED. FLEXIBLE STEEL CONDUIT RUNS SHALL BE LIMITED TO A MAXIMUM LENGTH OF 6 FOOT.ALL CONNECTIONS SHALL BE COMPRESSION & NOT SCREW TYPE.CONDUCTORSDELIVER ALL CONDUCTORS TO THE JOB SITE IN ORIGINAL UNBROKEN CARTON OR REEL, PROPERLY TAGGED WITH U.L. LABEL,SIZE, TYPE, MANUFACTURER, TRADE NAME AND THE DATE OF MANUFACTURE. (MUST BE MANUFACTURED WITHIN 6 MONTHS)PROVIDE COPPER CONDUCTORS #12 AWG MINIMUM UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. PROVIDESTRANDED COPPER CONDUCTORS FOR ALL WIRING. USE CONDUCTORS WITH 90 C THHN/THWN 600 VOLTS INSULATION, UNLESSOTHERWISE NOTED. CONDUCTOR SIZE NO.1 AWG AND SMALLER WITH 90 DEGREE C INSULATION ARE TO USE THE 60 DEGREECOLUMN OF THE CODE, TABLE 310-16, TO DETERMINE AMPACITY. CONDUCTORS #1/0 AWG AND LARGER WITH 75 DEGREE AND90 DEGREE INSULATION ARE TO USE THE 75 DEGREE COLUMN OF CODE, TABLE 310-16, TO DETERMINE AMPACITY. (110.14C)WHERE THE NUMBER OF CONDUCTORS IN A RACEWAY OR CABLE EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACHCONDUCTOR SHALL BE REDUCED PER TABLE 310.15(B)(3)(a).PARTIAL SITE PLANJUNCTION BOX (WALL MTD.) SIZE PER TABLE AND NEC ARTICLE 370CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS,3. DETERMINE EXACT ROUTING OF CONCEALED FEEDERS AND BRANCH HOMERUNS IN COOPERATION WITH OTHER TRADES TO SIMPLIFYINSTALLATION WHEREVER POSSIBLE BUT SUBJECT TO APPROVAL OF ARCHITECT FOR VISUAL AND STRUCTURAL REASONS.SMOKE DETECTORS IN ALL REQUIRED AREASHEAT DETECTORS IN ALL REQUIRED AREASDUCT DETECTORS IN ALL REQUIRED SPACESSTROBES/SPEAKERS IN ALL REQUIRED AREASPULL STATIONS AT ALL LEGAL FIRE EXITSFEEDERS AND BRANCH CIRCUITS IDENTIFICATIONIDENTIFY FEEDERS WITH THE CORRESPONDING CIRCUIT DESIGNATION AT THE OVER-CURRENT DEVICE, LOAD END, AND IN PULLBOXES WITH E-Z CODE OR OTHER APPROVED WIRE MARKER. IDENTIFY BRANCH CIRCUITS WITH I.D. MARKERS, THECORRESPONDING CIRCUIT DESIGNATION AT THE OVER-CURRENT DEVICE, AT ALL SPLICES, IN JUNCTION BOXES, AND INOUTLETS. USE PLASTIC COATED SELF-STICKING MARKERS SUCH AS THOMAS & BETTS E-Z CODE FOR IDENTIFICATION OFCONDUCTORS. IDENTIFY SIGNAL & COMMUNICATION CABLES AT TERMINAL AND OUTLET UNIQUELY WITH PERMANENTLABELING.E140J2. PROCURE ALL PERMITS FROM LEGALLY CONSTITUTED AUTHORITIES, ARRANGE FOR ALL INSPECTIONS AND PAY ALL COSTS FOR FEESAND TESTS IN CONNECTION THEREWITH. COMPLY WITH CODES: NOTHING IN THESE PLANS AUTHORIZES DEVIATION FROMAPPLICABLE CODES.A)B)C)D)E)ALL INSTALLED MATERIALS AND EQUIPMENT SHALL BE LISTED U.L., NRTL OR LISTED AND APPROVED BY AN APPROVED TESTINGLABORATORY.2.Drafter:CM02 Paper Size: 12,9Drawing:G:\20\120\EL\Sheets\20-120E100.dwgApr 19, 2021, 12:17pmAttached XREFS:XREF:G:\20\120\EL\Xrefs\20-120TB.dwgXREF: G:\20\120\AR\Xrefs\24x36 - TB - NO STAMP Oxnard College.DWGSHOP DRAWINGSSUBMIT SHOP DRAWINGS AND MATERIAL LIST FOR REVIEW PRIOR TO COMMENCING ANY WORK. ALL EQUIPMENT TO BEAR U.L.LABEL OR THAT OF ANOTHER ACCEPTABLE TESTING LABORATORY. SHOP DRAWINGS MUST BE STAMPED BY THE CONTRACTORFOR CONFORMANCE PRIOR TO SUBMITTAL. SUBMIT THREE HARD COPY SETS OF SHOP DRAWINGS FOR REVIEW PRIOR TOPURCHASING ALL BREAKER MOUNTING HARDWARE, DISCONNECT SWITCHES, FUSES, CONTROLLERS, LIGHTING FIXTURES, LIGHTSWITCHES, RECEPTACLES, ETC.36'X40' MODULAR FIRE ALARM PLAN MODULAR #6 & 7 DATE: 19 April 2021PATHNAME: G:\20\120\EL\Sheets9.GUARANTEECONTRACTOR SHALL UNCONDITIONALLY GUARANTEE ALL LABOR AND MATERIALS ON ALL WORK AGAINST DEFECTS INWORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR.E503ST8.AS BUILTPROVIDE RECORD DRAWINGS IN ACAD TO THE OWNER WITH ALL CHANGES NOTED THEREON AT THE COMPLETION OF THEPROJECT. RECORD DRAWINGS SHALL BE SIGNED AND DATED BY CONTRACTOR PRIOR TO RELEASE OF FINAL RETENTION OF ALLMONIES.GENERAL NOTES, ABBREVIATIONS, SYMBOLS & DRAWING LISTINEERENG ICUC7.SERVICE CONTINUITYUNINTERRUPTED EXISTING ELECTRICAL POWER SHALL BE MAINTAINED TO OTHER TRADES FOR TEMPORARY POWER AREAS OFTHE SITE DURING CONSTRUCTION. PROVIDE ANY TEMPORARY SERVICES AS MAY BE REQUIRED. IDENTIFY AT BID TIME, ALLWORK TO BE DONE ON PREMIUM TIME AND THE TOTAL OVERTIME MAN-HOURS REQUIRED FOR COMPLETION.E100REGISTERKEN E6.COORDINATIONCOORDINATE ALL WORK WITH OTHER TRADES. OBTAIN ALL DRAWINGS THAT WILL REQUIRE COORDINATION AND PROVIDE ALLELECTRICAL CONNECTION REQUIRED WHETHER SHOWN ON ELECTRICAL DRAWINGS OR NOT. ELECTRICAL EQUIPMENTLOCATIONS INDICATED ARE SHOWN DIAGRAMMATICALLY, EXACT LOCATION SHALL BE VERIFIED. SCALING OFF OF DRAWINGSSHALL BE DONE AT CONTRACTORS RISK. DO NOT SCALE DEVICES, LIGHTING FIXTURES OR ANY EQUIPMENT FROM PLANS.LIGHTING FIXTURE QUANTITIES AND LENGTHS SHALL BE CONTRACTORS RESPONSIBILITY. FIXTURES ARE SHOWN FORCIRCUITING ONLY. CONTRACTOR TO VERIFY SIZES & QUANTITIES PRIOR TO BID.DESCRIPTIONJUNCTION BOX (CEILING MTD.) SIZE PER TABLE AND NEC ARTICLE 370BRANCH CIRCUIT PANELBOARD - 240/120V, 1Ø, 3W OR 3Ø, 3W, 240VAC OR 120/208VAC, 3Ø, 4W.05/03/2021DATE:JG. INSTALLATION1. IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT A COMPLETE AND WORKABLE ELECTRICAL INSTALLATION BE PROVIDEDFOR ALL THE EQUIPMENT DESCRIBED OR SHOWN AS BEING IN THIS CONTRACT. TOWARD THIS END FURNISH ALL LABOR AND TOOLSNECESSARY AND FURNISH AND INSTALL ALL APPARATUS, MATERIALS AND EQUIPMENT IN A FASHION COMPLYING WITH ALL APPLICABLECODES, INCLUDING ITEMS REQUIRED BUT NOT NORMALLY SHOWN, SUCH AS LAMPS, COUPLINGS, HANGERS, BRACKETS, CLAMPS, BOXES,CONNECTORS AND HARDWARE. REFER ALSO TO WRITTEN SPECIFICATIONS FOR GENERAL, MECHANICAL AND ELECTRICAL SECTIONS.DIVISIONARCHITECT THE STATE FLS OFACSGENERAL NOTES, SYMBOLS,5.VERIFYING EXISTING CONDITIONSBEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR WITH ACTUAL EXISTING CONDITIONS AT THE BUILDING. THEINTENT OF THE WORK IS SHOWN ON THE DRAWINGS AND DESCRIBED HEREINAFTER. BY THE ACT OF SUBMITTING A BIDPROPOSAL FOR THE WORK, THE CONTRACTOR SHALL BE DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION AND TOACCEPT ALL CONDITIONS PRESENT AT THE SITE. NO REQUEST FOR ADDITIONAL PAYMENT WILL BE CONSIDERED AS VALID, DUETO FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST.SS DEPARTMENT OF GENERAL SERVICES TIME: 12:17 pm4.REGULATIONS AND CODESPROVIDE AND INSTALL ALL MATERIALS IN CONFORMANCE WITH THE 2019 C.E.C., CALIFORNIA ADMINISTRATIVE CODE TITLE 8,AND OTHER CODES AND REGULATIONS HAVING JURISDICTION. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THEREQUIREMENTS OF THE INSPECTING AUTHORITY AND THE MANUFACTURERS RECOMMENDATIONS.GROUNDING & BONDINGFURNISH AND INSTALL COMPLETE BONDING AND GROUNDING SYSTEM AS REQUIRED BY CODES. CONTINUITY OF GROUNDING SHALL BEMAINTAINED MECHANICALLY AND ELECTRICALLY THROUGHOUT THE SYSTEM. A GREEN GROUNDING CODE SIZED CONDUCTOR SHALL BECARRIED IN ALL CONDUITS.SHEETDESCRIPTION4'0" MAX3.PERMITS AND CHARGESOBTAIN AND PAY FOR ALL NECESSARY CONSTRUCTION PERMITS, INSPECTION FEES, AND OTHER CHARGES BY AGENCIES HAVINGJURISDICTION.F.SHEETSPECIAL OUTLET, TYPE AS REQUIRED BY EQUIPMENT.3'10" MAX2.SCOPETHE DRAWINGS AND THESE GENERAL NOTES DESCRIBE THE SCOPE OF WORK AND SYSTEMS. THE MATERIAL REQUIRED FOR THEWORK SHALL BE CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED, UNLESS SPECIFICALLY NOTED OTHERWISE. THEWORK INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING PRINCIPAL SYSTEMS AND EQUIPMENT. ALL ITEMS NOTED ON THEPLAN WHICH ARE NOT EXPLICITLY STATED AS EXISTING SHALL BE NEW.TELEPHONE SYSTEMSNOT USED.2'10" MAX1.E.LIST OF DRAWINGSSYMBOLSNA. GENERALREVIEWED FORE100Copyright Lucci and Associates Consulting Electrical Engineers. Deviations from this drawing will not be made without their expressed written permission. L.A.I.# 20-120PAPER SIZE 36"x24"

SHEET NOTES:ADMINISTRATION FRONT DESK (EXISTING)1.(EXISTING IDF)2.ALL SITE ELECTRICAL WORK TO BE COMPLETED UNDER SEPARATEPERMIT (EXCEPT FIRE ALARM).CBEXISTING CONDUIT PATHWAY (2)2"CREVIEWED FORSS 3.SE200ALL LIGHTING & POWER IN MODULAR BUILDINGS TO BE PROVIDEDBY MODULAR COMPANY AND APPROVED BY DSA UNDER SEPARATEPERMIT.DSAAPP: 03-121326 INC:MODULAR BUILDING TO BE PROVIDED BY MODULAR COMPANY.S2IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECTDIVISIONARCHITECT THE STATE FLS OFACSDEPARTMENT OF GENERAL SERVICES05/03/2021DATE:2COM ROOM (X)PROVIDE NEW WEST PENN AQ 245 (2 PAIR #16 UTP AQUASEAL) FROM NEW MODULARBUILDING #1 (FA) SYSTEM (E3) TO ADMINISTRATION BUILDING (E3) FOR 2-WAYCOMMUNICATIONS.TIME: 12:17 pm(X) COM PULLBOX1M2FAX (805) 389-65192(805) 389-6520CEXISTING (9) 4"C.O. COM.CAMARILLO, CA 93012-8094(X) COM PULLBOXC13251 CORTE MALPASO, #5112CONSULTING ELECTRICAL ENGINEERS1KEY NOTES:2(2)2" C- EXISTINGREGISTERKEN E1NIASTES-4LANo. E 8340Exp. 09/30/2022ELATE E C T R I C RO F C A L I FOSDATE: 19 April 2021INEERENG ICUCFESSPRO W IONALD ETH . LN2MSUBUBUBM1PATHNAME: G:\20\120\EL\SheetsS122UBUB(X)COM PULLBOXSDRAWING FILENAME: 20-120E140SV1ES-12" C (EXISTING)21E200IDF (EXISTING)UB& SEE E500 SERIESDRAFTER: CM02MPARTIAL SITE PLAN2NEWNEWNEW123SEE NEW6789SEE E503SEE E503SEE E502SEE E502S060120PARTIAL SITE PLAN1SCALE:- E140-1" 60'-0"SNDrafter:CM02 Paper Size: 12,9Drawing:G:\20\120\EL\Sheets\20-120E140.dwgApr 19, 2021, 12:17pmAttached XREFS:XREF:G:\20\120\EL\Xrefs\20-120TB.dwgXREF: G:\20\120\AR\Xrefs\24x36 - TB - NO STAMP Oxnard College.DWGXREF:G:\20\120\AR\Xrefs\Arts Classrooms CONST DOCS.dwgSSCALE: 1" 60'SSEE E502SSNEWSEE E504 SS SE140Copyright Lucci and Associates Consulting Electrical Engineers. Deviations from this drawing will not be made without their expressed written permission. L.A.I.# 20-120PAPER SIZE 36"x24"

KEY .SPACE.SPACEFIRE ALARM100ADMINISTRATION FRONT DESKTOTALSL.C.L. VOLT AMPS:TOTAL VOLT AMPS:7360PHASE A.201CKT PHASE CKTA 1415161718192021222324540.LCL10OUTLETS4WP GFCI1OUTLETS3SPACE.SPACE.SPACE.SPACE.SPACE.FUTURE SOLAR PV ELECTRICAL.2LITESPACE.40RCPTLIGHTING A1801620PHASE BB7207460.CIRCUIT DESCRIPTIONMISCFUTURE SOLAR PV ELECTRICAL1260TOTALS.17700PHASE A8980PHASE B8720.73.75PHASE A74.8PHASE B72.6.FESSPRO W IONALD ETH . LNNo. E 8340Exp. 09/30/2022ELATE E C T R I C RO F C A L I FOAST1INEERENG ICUCTOTAL AMPS:2.SPACEPROVIDE LOCK 0N DEVICE & NEW RED BREAKERAMP7360HVAC UNITBRKRBRKRPOLEFLUSH MOUNTINGFAX (805) 389-6519LOAD(VA)CIRCUIT DESCRIPTION125BUS AMPERE RATING(805) 389-6520LITE125MAIN CIRCUIT BREAKERLALCLRCPTWIRE 305/03/2021DATE:COPPER BUSSNIPANEL LOCATION INSIDE UNIT (SEE E501)MISC1NEMA 1A.I.C. 10,000DBSOURCEPHASEDIVISIONARCHITECT THE STATE FLS OFACSCAMARILLO, CA 93012-8094CONNECT TO DEDICATED 120VAC, 20A, DEDICATED CIRCUIT BREAKERWITH RED HANDLE & LOCK ON DEVICE.VOLTAGE 120/240SS DEPARTMENT OF GENERAL SERVICES3251 CORTE MALPASO, #511PANEL NUMBER AHVAC UNITTIME: 12:17 pmREVIEWED FORTYPICAL PANEL IN EACH MODULESEE E500 SERIES FOR EQUIPMENTAND RISER DIAGRAMDATE: 19 April 2021DSAAPP: 03-121326 INC:CONSULTING ELECTRICAL ENGINEERS2NEW FCI E3 FIRE ALARM STATION (FOR 2-WAY COMMUNICATIONS) WITH:xAOM TELFxASM-16xINI VGE UTPxINI 7100 UTPxVOICE PAGING MICROPHONE ASSEMBLYxLCD NGA ANNUNCIATORxFIRE FIGHTERS HANDSETREGISTERKEN E1IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECT2NEW CONDUIT PATHWAY(1"C & (1) AQUASEAL AQ245)BEXISTING TO REMAINSNEWNEWSEE E502SEEE501NEWNEWSSEEE501NEWSEE E504SEE E502DRAFTER: CM02SNEWS20'-0"MINIMUMNEWNEWNEWSSSEE E503SEE E503SEE E502SEE E502ENLARGED MODULAR PLANSCALE: 1" 40'04080SCALE:1" 40'-0"1E140 E200-NDrafter:CM02 Paper Size: 12,9Drawing:G:\20\120\EL\Sheets\20-120E200.dwgApr 19, 2021, 12:17pmAttached XREFS:XREF:G:\20\120\EL\Xrefs\20-120TB.dwgXREF: G:\20\120\AR\Xrefs\24x36 - TB - NO STAMP Oxnard College.DWGXREF:G:\20\120\AR\Xrefs\Arts Classrooms CONST DOCS.dwgSE200Copyright Lucci and Associates Consulting Electrical Engineers. Deviations from this drawing will not be made without their expressed written permission. L.A.I.# 20-120Drafter: CM01: G:\20\120\EL\Sheets\20-120E200.dwg: DATE: APR 15, 2021 TIME: 10:58 AM - E200-1" 10'-0"ELECTRICAL PANEL SCHEDULESSCALE: DRAWING FILENAME: 20-120E20020S102S0ENLARGED AREA ADMIN FRONT DESKSSCALE: 1" 10'NPATHNAME: G:\20\120\EL\SheetsIDF #1.3PAPER SIZE 36"x24"

FIRE ALARM INPUTSREGISTERKEN EModularNo. E 8340Exp. 09/30/2022ELATE E C T R I C RO F C A L I FOCopyright Lucci and Associates Consulting Electrical Engineers. Deviations from this drawing will not be made without their expressed written permission. L.A.I.# 20-120LAWIRE CHARTNIAOM TELFASM-16INI VGE UTPINI 7100 UTPVOICE PAGING MICROPHONE ASSEMBLYLCD NGA ANNUNCIATORFIRE FIGHTERS HANDSETFAX (805) 389-6519SV(805) 389-6520CAMARILLO, CA 93012-80943251 CORTE MALPASO, #511CONSULTING ELECTRICAL ENGINEERSDATE: REQUIRED FIRE SAFETY CONTROLFIRE ALARM GENERAL NOTES,SYMBOLS & ABBREVIATIONFIRE ALARM OUTPUTS NOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOTIFICATIONSYSTEM WILL BE 100% OPERATIONAL ON BATTERY BACK UPNOT USEDACTIVATE MANUAL OVER RIDE OF SPEAKERS "ALL CALL"NOT USEDACTIVATE INTELLIGENT VOICE EVACUATIONACTIVATE 120VAC SPRINKLER BELLTRANSMIT CARBON MONOXIDE DETECTOR SUPERVISORY SIGNALCONTROL UNIT ANNUNCIATIONTRANSMIT TROUBLE SIGNAL TO SUPERVISING STATIONTRANSMIT SUPERVISORY SIGNAL TO SUPERVISING STATIONTRANSMIT FIRE ALARM SIGNAL TO SUPERVISING STATIONDISPLAY MESSAGE ON LCD DISPLAYDISPLAY CHANGE OF STATUS MESSAGE ON LCD DISPLAYACTUATE COMMON TROUBLE SIGNALACTUATE COMMON TROUBLE SIGNAL INDICATORPROJECT DATAACTUATE COMMON SUPERVISORY SIGNALTIME: 12:18 pmSCOPE OF WORKACTUATE COMMON SUPERVISORY SIGNAL INDICATORDATE: 19 April 2021* INCLUDES:xxxxxxxACTUATE AUDIBLE ALARM SIGNALPATHNAME: G:\20\120\EL\SheetsSProvide two way voice communication between a new E3 fire alarm station handset in AdministrationBuilding at main desk and new E3 Fire Alarm master panel in Building 1, plus provide at both new E3Fire Alarm panels (Administration and new Modulars) the ability to provide paging over the newmodular building speakers on interior and exterior of project buildings as a portion of this scope ofwork.ACTUATE COMMON ALARM SIGNAL INDICATORDRAWING FILENAME: 20-120E500SS FESSPRO W IONALD ETH . LNINEERENG ICUCDRAFTER: CM02AdminASTDrafter:CM02 Paper Size: 20-120E500.dwgApr 19, 2021, 12:18pmAttached XREFS:XREF:G:\20\120\EL\Xrefs\20-120TB.dwgXREF: G:\20\120\AR\Xrefs\24x36 - TB - NO STAMP Oxnard College.DWGIDENTIFICATION STAMPDIV. OF THE STATE ARCHITECTAPP: 03-121326 INC:REVIEWED FORDEPARTMENT OF GENERAL SERVICESDSADIVISIONARCHITECT THE STATE FLS OFACS05/03/2021EVACS LEGENDPDSA REQUIRED NOTESE500PAPER SIZE 36"x24"

SYMBOL LEGEND:IDENTIFICATION STAMPDIV. OF THE STATE ARCHITECTKEYED NOTES:DSAAPP: 03-121326 INC:REVIEWED FOR1SYMBOLS:ABOVE CEILING HEAT DETECTOR. TYPICALSS DIVISIONARCHITECT THE STATE FLS OFACSDEPARTMENT OF GENERAL SERVICES0

california code of regulations (ccr) title 24, part 6 5. 2019 california fire code (cfc) california code of regulations (ccr) title 24, part 9 (2018 international fire code (ifc) w/california amendments) 6. 2019 california referenced standards code california code of regulations (ccr) title 24, part 12 7. americans with disabilities act (ada)