GENERAL NOTES: GB Collins Engineering PA Certificate Of .

Transcription

RESTROOMSOutside access to facilities shall be provided for bathers at outdoor pools and if they are notvisible from any portion of the pool deck, signs shall be posted showing directions to thefacilities. These directions shall be legible from any portion of the pool deck and the lettersshall be a minimum of one inch high. Walkways shall be provided between the pool and thesanitary facilities, and shall be constructed of concrete or other nonabsorbant materialhaving a smooth slip resistant finish for the first 15 feet of the walkway measured from thenearest pool water's edge.GB Collins Engineering PASHOWER BEFORE ENTERING POOLFilter:Pump:Feature Pump:Vacuum Pump:Chemical Feeders:DO NOT SWALLOW THE POOL WATERMAX. MAIN POOL LOAD 83 PERSONSNO DIVINGFeeders to be wired with failure proof interlock with the recirculation pump.Valves:Proportional flow, ball globe, or butterfly for return line, main drain, gutterand heater by-pass or approved equal, otherwise gate.Feeders to be wiredwith failure proof interlock with the recirculation pump.Transformers: Area Lighting LG-300 / 12Volt.Leaf Skimmer: LION 1010Vacuum Head: RAINBOW 214Brush: A&B 3004Vacuum Hose: PlastiflexConcrete: 3500 psi, 28 daySteel: ASTM GR40, A615Poles: (3) Jed, 16' StraightHeater: NONEInlets: Hayward SP1425LOCATION MAP NTSADDRESS: 5800 GULF BLVD.Escutcheons: Frost 41661Lights: (8) Pentair Intellibrite 5G white LEDlights 601108, 300watt, 12v and (7)Pentair,Globrite color LED lights 602056, with Guniteniche 620040, Transformer kit 619994Life Ring: (2) 24" W/30' Throw Line, Jim BuoyHook: (2) RAINBOW 153Test Kit: Taylor K-2006Ladder: Smith LFB 36BSCOPE OF WORK:Tread: 6" Maximum from wall, 3" Minimum from wall.Crossed Braced Stainless Steel, Slip Resistant Treads,28" minimum above deck. Must have caps or bumpersthat rest firmly against pool wall.THE EXISTING POOL IS BEING REDUCED IN SIZE FROM 7,889 SQUARE FEET(SF) TO 4,667 SF TO ACCOMMODATE DEVELOPMENT TO THE EAST OF THESITE. THE DEVELOPMENT TO THE EAST IS NOT PART OF THISCONSTRUCTION.SPA POOL750 GallonsNOTE: Pool Rule Letters to be 1" high minimumexcept NO DIVING shall be 4" high minimum.Level (Static) Line Grate:Main Drain: Lawson Aquatics (18"x18")MLD-FDG1818-SECUREmeet ASME/ANSI A112 19-8-2007NSF50, 64E-9Pipe: PVC Schedule 40 NSFpwGutter: Pentair 540063 (2"x4")Flow Meter: Blue White CF 30600PVacuum Fitting: Hayward VAC-LOCKAnchors: Hayward SP1392Capacity:POOL HOURS DAWN a.m. TO DUSK p.m.ST. PETERSBURG, FLORIDAPINELLAS COUNTYPOST SPA RULE SIGNArea:50 Square FeetPerimeter: 25 FeetNO GLASS OR ANIMALS IN THE FENCED POOL AREANO FOOD OR BEVERAGES IN POOL OR ON POOL WET DECKFlow Meter: Blue White CF 30300PLights: Amerlite Series 100w / 12Volt,ground/NEC., Ch. 27, FBC 2007.Transformers: Area LightingLG-100w / 12Volt.Return Inlets: Hayward SP1419ERail: Smith (See Details)Heater: 155,000 BTU HEAT PUMP(Aqua Cal Trupi Cal. T135 or equal)Main Drain: Waterway 640-472-SECUREmeet ASME/ANSI A112 19-8-2007NSF50, 64E-9SHOWER BEFORE ENTERING POOLLevel (Static) Line Grate:DO NOT SWALLOW THE POOL WATERSkimmer: Hayward SP1082W/ SP1078 Equalizer ValveEqualizer Grate: Hayward SP1019Jets: Hayward 1430APPROXIMATELY 3,220 SF OF EXISTING SHELL WILL BE ELIMINATED FROMTHE EXISTING POOL. DEMOLISHION OF THE SHELL WILL INCLUDEREMOVAL OF THE TWO (2) ROCK ISLAND FEATURES IN THE CENTER OFTHE POOL. ADDITIONALLY, THE THREE EXISTING EQUIPMENT PACKSSERVICING THE EXISTING POOL WILL BE REMOVED TO ACCOMMODATEONE (1) NEW VACUUM DE FILTER RECIRCULATION SYSTEM.ALSO PART OF THIS CONSTRUCTION, THE "J" GUTTER WILL BE ELIMINATEDAND A NEW ROLL-OUT GUTTER WITH BULLNOSE COPING, AND 6"X6"WATERLINE TILE, AND BULLNOSE TILE WILL BE INSTALLED. THE FOUR (4)SKIMMERS TIED TO THE "J" GUTTER WILL BE REMOVED, AND A NEWPERIMETER GUTTER PLUMBING WILL BE INSTALLED AROUND THE NEWPOOL SHELL.MAX. SPA BATHING LOAD 5 PERSONSNO DIVINGTHE EXISTING MAINS WILL NEED TO BE LOCATED AND TIED TOGETHERAND PLUMBED TO THE NEW EQUIPMENT PACK. ADDITIONALLY, FIFTEEN(15) EXISTING FLOOR RETURNS IN THE SHELL AREA NOT TO BE REMOVEDWILL BE UTILIZED. RETURN LINES TO BE LOCATED AND TIED TOGETHERALONG WITH NEW RETURNS PROPOSED IN THE ZERO-ENTRY AREA ANDPLUMBED TO THE NEW EQUIPMENT PACK. A NEW LEVEL LINE WILL BEINSTALLED. NEW VACUUM FITTINGS AND PLUMBING WILL BE INSTALLEDAND PLUMBED TO THE NEW EQUIPMENT PACK.POOL HOURS DAWN a.m. TO DUSK p.m.NOTE: Pool Rule Letters to be 1" high minimumexcept NO DIVING shall be 4" high minimum.ADDITIONAL SPA RULESCHILDREN UNDER 12 MUST HAVE ADULT SUPERVISIONPREGNANT WOMEN, SMALL CHILDREN, PEOPLE WITH HEALTH PROBLEMSAND PEOPLE USING ALCOHOL, NARCOTICS OR OTHER DRUGS THATCAUSE DROWSINESS SHOULD NOT USE SPA POOLS WITHOUT FIRSTCONSULTING A DOCTOR.MAXIMUM USE 15 MINUTES(A clock shall be visible from the spa to assist the patron in meeting the timerequirement.)THE NEW EQUIPMENT PACK WILL INCORPORATE A NEW FEATURE PUMPFOR THE WATER FEATURE.FINALLY, THE POOL WILL HAVE A NEW 6' WIDE PAVER DECK INSTALLEDAROUND THE PERIMETER.IN ADDITION TO THE POOL MODIFICATION THE EXISTING SPA "A" WILL BEELIMINATED AND ONE NEW 8' DIAMETER SPA WILL BE CONSTRUCTED,WITH NEW EQUIPMENT.MAX. TEMPERATURE 104 DEGREESALARM INDICATES SPA PUMPS OFF. DO NOT USE SPA WHEN ALARMSOUNDS UNTILL ADVISED OTHERWISE.(Only when spa is equipped with optional emergency kill switch.)#Floors: smooth, non-slip, impervious, pitched to floor drains, cove wall to floor, no carpet,duckboard or footbaths. Provide permanent towel, tissue, soap dispensers and wastebaskets. Label doors. Install hose bib w/ vacuum breaker, either in resorts or outside nearby.Water shall be from an approved potable source with air break. Diaper changing tables shallbe provided at facilities that cater to families with small children.NOTE: All units are located within 200 FT walking distance of poolwaters edge.SAMUEL A. LIBERATORE, P.E. #55740Florida Building Code requires that all public pools shall be surrounded by a minimum 48" highfence. The fence shall be continuous around the perimeter of the pool area that is not otherwiseblocked or obstructed by adjacent buildings or structures and shall adjoin with itself or abut to theadjacent members. Access through the barrier other than from doored exits of adjacentbuilding(s) shall be through self-closing, self-latching, lockable gates of 48" minimum height withthe latch located a minimum of 54" from the bottom of the gate or at least 3" below the top of thegate on pool side. Gates shall open outward away from the pool area.NO FOOD OR BEVERAGES IN POOL OR ON POOL WET DECKFor: CORAL REEF RESORTFENCE:NO GLASS OR ANIMALS IN THE FENCED POOL AREANotes and SpecificationsCapacity:131,000 Gallons (NEW)Area: 4,667 Square Feet (NEW)Perimeter: 465 Feet (NEW)Flow Rate: 416 GPM (NEW)Swimming Pool Modification1. Structure suitable when empty for ground water not higher than 6" above main drain.2. Permanent Tile depth markers, minimum 4" high with contrasting color, slip resistant flush ondeck or top of beam not more than 2 feet from water edge and inside back of gutter (glazed)minimum 4" high.3. Permanent Red International NO DIVE Tiles, non-slip flush minimum 4" high, on top of thedeck not more than 2 feet from water edge every 25 feet of perimeter maximum see detail.4. All equipment shall have NSF, UL, or appropriate approval.5. All electrical, grounding, wiring & bonding to comply with Chapter 42, Florida building codeFBC2011, Chapter 42 Electrical, NEC Section 680.26(C). No overhead power within 10 feet.Electrician must certify compliance to engineer. NEC 680.26(C) requires that all parts specifiedin 680.26(B) shall be connected to an equipotential bonding grid with solid copper conductor,insulated, covered. or bare, not smaller than 8 AWG or rigid metal conduit of brass or otheridentified corrosion-resistant metal conduit. Connection shall be made by exothermic weldingor by listed pressure connectors suitable for the purpose and are of stainless steel, brass,copper, or copper alloy.6. Pool make-up water is from an approved source with air gap.7. No direct connections between water and sanitary systems, minimum 3" gap.8. Vacuum breakers on all hose bibs in pool area.9. Minimum 7' vertical clearance above deck and pool water10. No food or drink services to be within 12 feet of inner edge pool deck.11. Walkways between pool and sanitary facilities shall be impervious, slip resistant for the first15 feet from pool water edge.12. If night swimming is allowed, overhead lighting shall provide at least 3 foot candles ofilluminations at the water and wet deck level.13. Overhead illumination of 30 foot candles at floor level in equipment room.14. Owner to provide storage of chemicals under roof, protected from access by unauthorizedpersons.15. Owner to provide traffic barriers at deck if needed.16. Main drain(s) to meet ASME/ANSI A112 19-8-2007, NSF50, 64E-9 and comply with VirginiaGraeme Baker Act.17. Feeders to be interlocked with recirculation pump.18. Pipe: PVC schedule 40 NSFpw19. Gauges: 2" minimum; 0-60 psi.20. Test Kit: Taylor 2006 or Equal21. All electric and ground to meet NEC or local code.22. This pool is not classified as a Title II or Title III pool and doesnot require ADA lift or ramp.23. The equipment area or collector tank or chemical containers shall not be accessible tounauthorized individuals.24. Install new equipment and plumbing per manufacturers instructions.25. Plastic pipe subject to a period of prolonged sunlight exposure must be coated to protect itfrom ultraviolet light degradation26. ALL EQUIPMENT MUST BE LABELED AND EASILY READ, THIS INCLUDES THEFLOWMETER.27. All equipment (pumps, motors, pressure gauges, valves, auto and manual fills, piping, filters,flow indicators and flow meters ) must be operating properly before calling thisoffice and/or the Health Department for inspection.28. Lighting certification is not part of this submittal. Contact a Lighting or Electrical engineer forcertification.29. Direct access to equipment is required.30. Pool and Bathhouse electrical outlets to be GFCI with trip points 10mA or less with cover.31. Pool chemicals to be stored away from other materials in a cool, dry , ventilated area withrestricted access.32. Pool to have Shepherd's Hook, Straight Pole, Ring Buoy for safety equipment.333. The deck must not have pits and crevices more than 16" deep.34. A flow meter shall be provided with properly located and proper clearances upstream anddown stream.35. A gate to the equipment area must be provide within 10' of the equipment area.36. The equipment room area must provide clearances for all equipment as prescribed by themanufacturer to allow normal maintenance and removal.37. All equipment meets NSF/ANSI Standards 50-2007.38, Recirculation pump must havea hair and lint strainer.39. All exposed PVC piping will be painted for UV protection.40. The plans meet FBC 2014, 5th Edition.POST ZERO ENTRY POOL RULE SIGNSamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netMAIN POOLCertificate of Authorization 27934GENERAL NOTES:Sheet 1 of 8TABLE OF CONTENT:NOTES AND SPECIFICATIONSSITE PLAN - EXISTING CONDITIONSSITE PLAN - PROPOSED CONDITIONSZERO ENTRY POOL PLUMBING PLANZERO ENTRY POOL PROFILES AND DETAILSZERO ENTRY POOL EQUIPMENT DETAILSNEW SPA PLANNEW SPA EQUIPMENT PLAN12345678RevisionDescriptionDateJuly 21, 2015Date:Drawn by:SAL

BUILDING #3EXISTING SPA "B" TO REMAIN(SPA TO BE MODIFIED FOR VGB COMPLIANCE ANDNEW EQUIPMENT PACK TO BE INSTALLED - REFERTO MODIFICATION PLANS BY OTHERS)EXISTING POOL SHELL AREATO BE DEMOLISHED(3,220 SF)ISLANDISLANDISLAND TO BE DEMOLISHEDSAMUEL A. LIBERATORE, P.E. #55740SPA "A"Site Plan- Existing ConditionSPA "B"EXISTING POOL SHELL AREATO BE MODIFIED FOR NEWROLLOUT GUTTER - ISLANDTO BE REMOVED.Swimming Pool ModificationWALK OVERBRIDGE TOREMAINSamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netEXISTING POOL SHELL AREATO BE REMAIN4,667 SF)Certificate of Authorization 27934GB Collins Engineering PAEXISTINGCONVERATIONALPOOLBUILDING #2For: CORAL REEF RESORTSPA "C"EXISTING SPA "C" TO REMAIN(SPA TO BE MODIFIED FORVGB COMPLIANCE ANDCOLLECTOR TANKINSTALLATION - REFER TOMODIFICATION PLANS BYOTHERS)EXISTING CONVERSATIONALPOOL TO REMAIN(POOL TO BE MODIFIED FORVGB COMPLIANCE ANDCOLLECTOR TANKINSTALLATION - REFER TOMODIFICATION PLANS BYOTHERS)EXISTING SPA TO BEDEMOLISHED#RevisionDescriptionDateDECK AREA TO BE MODIFIEDTO ACCOMMODATEZERO-ENTRYSheet 2 of 8EXISTING POOL INFORMATION:AREA: 7,888 SFPERIMETER: 703 LFGALLONS: 207,000 GALLONSSITE PLANSCALE: 81" 1'NJuly 21, 2015Date:Drawn by:SAL

For: CORAL REEF RESORTEXISTINGCONVERATIONALPOOLEXISTINGSPA "B"TOTAL AREA 4,667 SFTOTAL VOLUME 131,000 GALLONSTOTAL FLOW RATE (5.25 HOUR TURNOVER) 416 GPMHANDICAP STAIRSSAMUEL A. LIBERATORE, P.E. #55740WATER FEATURE - TO BE INSTALLED ON WALLRAIL TO REMAIN (4' MINIMUM DECK CLEARANCE)NEWSPA "A"WITH SPILLOVERFEATURE#Sheet 3 of 8SITE PLANSCALE: 81" 1'NSite Plan- Proposed ConditionHC LIFTSwimming Pool ModificationBUILDING #3Samuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netBUILDING #2Certificate of Authorization 27934GB Collins Engineering PAEXISTINGSPA "C"RevisionDescriptionDateJuly 21, 2015Date:Drawn by:SAL

APOOL PLUMBING PLANSCALE: 3/16" 1'SAMUEL A. LIBERATORE, P.E. #55740A#Sheet 4 of 8RevisionDescriptionZero Entry Pool Plumbing PlanSwimming Pool ModificationBFor: CORAL REEF RESORTSamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netCertificate of Authorization 27934GB Collins Engineering PALEGENDBDateJuly 21, 2015Date:Drawn by:SAL

ÆLadder DetailÆGutter,Wall and Floor DetailFor: CORAL REEF RESORTMain Drain DetailTransverse Pool Section, Deep PortionSAMUEL A. LIBERATORE, P.E. #557403HR-7-049 CUSTOMZero Entry Pool Profiles and DetailsLadder Custom: S.R.Smith Custom, Stainless SteelTread: 6" Maximum from wall, 3" Minimum from wall.Cross Braced, Slip Resistant Treads, 28" minimum / 36" max above deck.Frame, 1.9" OD x .065", Type 304 Stainless Steel, with white rubber bumpers.Steps, acrylic plastic and have a slip resistant top surface.Escutcheon, (p/n EP-100F), stainless steel.Anchor Assembly: AS-100B (see spec sheet for SRS-908)Transverse Main Pool Section, Shallow PortionSwimming Pool ModificationLFB-30-3BSamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netFLOOR RETURN DETAILCertificate of Authorization 27934GB Collins Engineering PABack of gutter drain shall be within ¾ inchof back vertical wall of gutter wall wheregutter is deepest, and flush or recessedno more than 3/8 inchFeature Wall DetailDEPTH MARKER DETAILS#RevisionDescriptionDatePool Step and Rail Detail #118"18"DEPTH MARKER DETAILSBench DetailGutter Beam Modification DetailSheet 5 of 8July 21, 2015Date:Drawn by:SAL

60"80TDH44 "36 "70AIR GAPCYENCI42"60FIEFSIDEWALL VENTEFFICIENCYNSPHRBHP203" PUMP SUCTION36 "44 "20604" PVC TO WASTEDISPOSAL SYSTEM(TYP BOTH SIDES)8018"WASTE LINEAIR GAP DETAIL1" x 1" STEEL FRAME72"8" FEATURE DRAIN30FIELD CAST 6" THICK, 2500 PSICONCRETE FOOTING UNDERSTEEL FRAME & COVER402060"BHP00100200300FEATURES COLLECTOR TANKPLAN VIEWEQUIPMENT VAULTSIDE ELEVATION20RHNPSSHIM FRAME ON BRICKSAS NEEDEDFILTER EQUIPMENT LIST10400500132.000700600RECIRCULATION PUMPPENTAIR EQK1000, 10 HP, 416 GPM @ 50' TDH. INCLUDESBASKET STRAINERVACUUM PUMPPENTAIR MAX-E-PRO P6E6E-206L, 1 HP WITH INTEGRAL BASKET,STRAINER, 60 GPM @ 60' TDH, 230V, 1ØFEATURE PUMP (2)PENTAIR MAX-E-PRO P6E6H-209L, 3 HP WITH INTEGRAL BASKET,STRAINER, 230V, 1ØFILTER TANK SIZEAT600, 600 GALLON CAPACITYFEATURE TANK SIZEAT215, 215 GALLON CAPACITYDE FILTER ELEMENTS(48) - 13.5" x 24" ELEMENTS, 4.5 SQ FT EACH, 216 SQ FT TOTALWATER LEVEL CONTROLAQUATEK HYDRAULIC VALVE W/ MANUAL FILL VALVE & RESERVOIRCHLORINE FEEDERSTENNER 45M5, 50 GPD CAPACITY, 110VCHLORINE RESERVOIR TANK30 GALLON WITH LOCKABLE LIDpH FEEDERSTENNER 45M5, 50 GPD CAPACITY, 110VpH RESERVOIR TANK30 GALLON WITH LOCKABLE LIDSEPARATOR TANK(S)(3) - HAYWARD 9002SEP , 80 SQ FT EA, 240 SQ FT TOTALFLOWMETER6" BLUE/WHITE F-30600P, 250 TO 1050 GPM RANGETHERMOMETERPRECISION INSTRUMENT CO B2B1-K WITH 1/2" NPT THERMOWELL30 TO 240 F RANGEVACUUM GAUGEWIKA, 0-30 IN HG, LIQUID FILLED, 1/4" NPT, 2" FACE DIAMETERFLOW RATE IN U.S. GPMFILTER TANK COVERTOP VIEWRECIRCULATION PUMP CURVE60.0064"54 "1620" E"6" FLOWMETER3" FEATURE RETURNFEATURE PUMPVACUUM PUMPTHERMOMETERCHLORINE FEEDER1518" "3" FEATURE PUMP SUCTION60W SERVICE LIGHT3" x 2" PVC ECCENTRIC REDUCER (TYP OF 2)3" FEATURE PUMP SUCTION3" FEATURE RETURNFEATURE PUMPpH FEEDER6" FILTER RETURNPIPE AND VALVES CHARTLINE FUNCTIONFILTER TANKTANK FRONT ELEVATIONFILTER TANKLEFT SIDE ELEVATIONELECTRICAL PANEL6" RECIRCULATION PUMP SUCTION2" FROM HEATER2" TANK DRAINV.G.6"4"2" TO WASTEDE SEPARATION TANK (TYP OF 3)2" TANK DRAIN2" VACUUM2" TO HEATER6" SUCTION2" VACUUM TO FILTER4" PRECOATRECIRCULATION PUMP3"SIZEMAIN DRAIN10GUTTER/SKIMMER10"STATIC LINE2"RECIRCULATION PUMP SUCTION6"RECIRCULATION PUMP DISCHARGE6"RECIRCULATION RETURN6"TANK DRAIN2"VACUUM LINE TO POOL2"VACUUM TO FILTER2"VACUUM TO WASTE2"FILTER PRECOAT4"OVERFLOW2"TO HEATER2"FROM HEATER2"FRESH WATER FILL1"FEATURE TANK MAIN DRAIN8"FEATURE PUMP SUCTION (2)3"FEATURE PUMP RETURN (2)3"DE FILTER ELEMENTS1" AUTOFILL2" VACUUM TO FILTER4" PRECOAT LINE10" DRAIN VALVE (TYP)LEVEL SENSORTANK OVERFLOW WITHCHECK VALVESAMUEL A. LIBERATORE, P.E. #55740EQUIPMENT VAULTCOMPONENTS IDZero Entry Pool Equipment Details16 "EQUIPMENT COVERPLAN VIEWSwimming Pool ModificationUSAFor: CORAL REEF RESORTTOTAL HEADWASTE LINE FROMPOOL FILTERCOUPLING100Samuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.net1201. PLUMBING - ALL PIPE & FITTINGS SHALL BE SCHEDULE 40 PVC PER ASTM D1785 AND N.S.F. APPROVED AND STAMPED FORPOTABLE WATER APPLICATIONS. JOINTS TO BE SOLVENT WELDED PER ASTM D2855. ALL PLUMBING AND MATERIALS TO CONFORMTO FLORIDA BUILDING CODE 2010 - SECTION 424.2. ELECTRICAL - ALL ELECTRICAL EQUIPMENT WIRING, INSTALLATION AND GROUNDING OF POOL COMPONENTS SHALL CONFORM TONATIONAL FIRE PROTECTION ASSOC. 70, NATIONAL ELECTRICAL CODE (N.E.C.) LATEST EDITION AND ALL APPLICABLE LOCAL CODES.CHEMICAL FEED PUMPS TO BE INTERLOCKED WITH THE RECIRCULATION PUMP.3. EQUIPMENT - ALL PUMPS, FILTERS AND DISINFECTION EQUIPMENT SHALL BE TESTED AND APPROVED BY THE PERTINENTMANUFACTURER USING THE NSF/ANSI STANDARD 50 AND LISTED AS APPROVED BY THE NSF.4. THE FILTER ROOM FLOOR IS SLIP RESISTANT AND SLOPED TO FLOOR DRAINS5. ALL PLASTIC PIPING SUBJECT TO PROLONGED SUNLIGHT EXPOSURE MUST BE COATED TO PROTECT IF FROM ULTRAVIOLETLIGHT DEGRADATION.6. EACH WASTE LINE SHALL HAVE A UNIQUE AIR GAP. WASTE LINES FROM DIFFERENT SOURCES (E.G. POOL, SPA, OVERFLOW,SUMP PUMP) SHALL NOT BE TIED TOGETHER BUT MAY DISCHARGE INTO A COMMON SUMP OR RECEPTACLE.7. THE WASTE LINE MUST BE CONNECTED TO AN APPROVED WASTE DISPOSAL SYSTEM ACCORDING TO LOCAL OR STATE CODES.8. ALL COLLECTOR TANKS SHALL HAVE COVED INTERSECTIONS AND SLOPE TO THE TANK DRAIN.9. AN AUTOMATIC AND MANUAL WATER MAKEUP CONTROL MUST BE PROVIDED TO MAINTAIN THE WATER LEVEL AT THE LIP OF THEOVERFLOW GUTTER OR AT THE MOUTH OF THE RECESSED AUTOMATIC SKIMMERS AND MUST DISCHARGE THROUGH AN AIR GAPINTO A FILL PIPE OR COLLECTOR TANK. OVER THE RIM FILL SPOUTS ARE PROHIBITED.10. A RATE OF FLOW INDICATOR, READING IN GPM, SHALL BE INSTALLED ON THE FILTER RETURN LINE. THE RATE OF FLOWINDICATOR SHALL BE PROPERLY SIZED FOR THE DESIGN FLOW RATE AND SHALL BE CAPABLE OF MEASURING FROM ONE HALF TOAT LEAST ONE-AND-ONE-HALF TIMES THE DESIGN FLOW RATE. THE CLEARANCES UPSTREAM AND DOWNSTREAM FROM THERATE OF FLOW INDICATOR SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS.11. THESE PLANS HAVE BEEN PREPARED IN COMPLIANCE WITH THE 2010 FLORIDA BUILDING CODE - SECTION 424Certificate of Authorization 27934GB Collins Engineering PANOTES:PENTAIR EQ SERIES PERFORMANCE CURVEEQ1000AT600 COLLECTOR TANKWITH LOCKABLE COVERFILTER TANKCOMPONENTS ID73 "54 "42 "3" PUMP SUCTION(TYP OF 2)12 "USA104350 66th STREET NORTHPINELLAS PARK, FL 33782(888) 426-85111/2" 1'-0"7-18-15ENGINEER OF RECORDREV DATEAQT-2195416 GPM VACUUM DE FILTERWITH (2) 3 HP FEATURE PUMPSRevisionDescriptionDateFEATURES COLLECTOR TANKSIDE ELEVATIONREVISION DESCRIPTIONBYJ.J.B.J. J. B.S. D. H.REVISION NUMBER#6"FEATURES COLLECTOR TANKFRONT ELEVATIONJOB NAMELOCATIONTHIS SPACE FOR STATE APPROVAL STAMPSNOTESSheet 6 of 8July 21, 2015Date:Drawn by:SAL

112"DIA6" DIAMAIN DRAIN2 1/2" DIAJETSTO BEYOND DECKELBOW DOWN ANDPAINT2" DIA AIRSPA PLUMBING PLANSCALE: 1' 1 2"SPA SECTIONNTS'#Sheet 7 of 8RevisionDescriptionNew Spa "A" Plan11 2"DIADETAIL18"17"SAMUEL A. LIBERATORE, P.E. #557402" DIALEVEL11DI 2 "ASamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netCertificate of Authorization 27934GB Collins Engineering PA2"DIALEGENDSwimming Pool Modification11 2"DIA112"DIAFor: CORAL REEF RESORT112"DIA112"DIA1121 1 DIA "DI 2 "A112"DIA112"DIA11DI 2 "A112"DIA112"DIA1 2"1 IAD1 1/2" DIASKIMMERTIE TO 112" DIAAT FILTER2" DIA INLETSDate&July 21, 2015Date:Drawn by:SAL

Recirculation Pump1 H.P. Sta-Rite P2RA5E (52.5 G.P.M. @ 60' T.D.H.)Self Primming Throttled to 50 G.P.M.Therapy Pump2 H.P. Sta-Rite P6E6GL (100 G.P.M. @ 60' T.D.H.)Cartridge FilterSta-Rite PLM150 Pressure Cartridge (150 S.F.,56 GPM Max)Automated ControllerCHEMTROL CH 250 Digital pH/ORP ControllerChlorine Feeder PumpStenner 45M5 (50 G.P.D.)Chlorine Reservoir Tank25 Gallon with Lockable LidpH Feeder PumpStenner 45M2 (10 G.P.D.)pH Reservoir Tank5 Gallon with Lockable LidFlow MeterBlue White F-30 -1 1/2" (20-100 gpm)ThermometerGeneral Instruments (32 to 248 F)Pressure Gauges (2)2" Ø Face ( 0 to 60 PSI)Collector Tank65 Gal. Usefull ValumeEQUIPMENT PLANPIPE AND VALVE CHART:NOTES:1. ALL PLASTIC PIPE SUBJECT TO PERIOD OFPROLONGED SUNLIGHT EXPOSURE MUST BE COATED TOPROTECT IT FROM ULTRAVIOLET LIGHT DEGRADATION.WASTE LINEAIR GAP DETAIL2. EACH WASTE LINE SHALL HAVE A UNIQUE AIR GAP.WASTE LINES FROM DIFFERENT SORCES (e.g. POOL, SPA,0VERFLOW, SUMP PUMP) SHALL NOT BE TIEDTOGETHER, BUTMAY DISCHARGE INTO A COMMONSUMP OR RECEPTACLE AFTER THE AIR GAP.3. THE WASTE LINE MUST BE CONNECTED TO A WASTEDISPOSAL SYSTEM ACCORDING TO LOCAL OR STATECODES.2" OVERFLOW LINE6"Recirculation Suction Pipe2"Skimmer Suction Pipe2"Filtered Return Pipe1 1/2"Therapy Suction Pipe4"Therapy Return Pipe3"Heater Inlet Pipe1 1/2"Heater Outlet Pipe1 1/2"Waste Pipe1 1/2"THERAPYSUCTION LINETHESE PLANS HAVE BEEN PREPAREDIN COMPLIANCE WITH THE 2007 FLORIDABUILDING CODES WITH 2009 AMENDMENTS.1" MIN. AUTO FILLSTATIC WATER LINECOLLECTOR TANKTOTAL CAPACITY - 65 GALLONSDFEEDER & CIRCUIT SCHEDULE:CBETOP VIEWLOCKABLEACCESSHAUTO FILL VALVE ANDHOSE BIBB WITHVACUUM BREAKERMARK3F5A52 -#121 - #121/2"UL SEALTITE32 -#121 - #121/2"UL SEALTITE41 -#121 - #121 - #121/2"SEALTITE TO LIGHT51 -#121 - #121 - #121/2"SEALTITE TO PANEL61 -#121 - #121 - #121/2"SEALTITE TO PANELCONDUCTORS AND CONDUIT INSTALLED BY OTHERS7FIXTURE SCHEDULE:1" FRESH WATER LINEMARKNEW 1" MIN. AUTO FILLSTATIC WATER LINECT-65PANEL SCHEDULE:MANUFACTURER & MODEL NO.1 PHASE, 3 WIRE, 120/240 VAC, INSULATED/BONDABLE SPLIT NEUTRALMAIN LUG BREAKER PANEL120/240V(10 SPACES / 20 POLES)EATON, BR1020B100RFPCIRCUITPOLETRIPLOAD1230ASPA RECIRC. PUMP W/ (2) INTERLOCKED CHEM. FEEDS19.4BGFCI115VPASS & SEYMOUR2220ATHERAPY PUMP11.2C100W SERVICE LIGHT115VINTERMATIC, VPXG11GCI 100W3115ASERVICE LIGHT4220AGFCIA6" MAIN DRAIN LINEREMARKS2SHUTOFF VALVE2" TANK OVERFLOWW/CHECK VALVECONDUITPANEL FEED625CONDUCTORSNEUTRAL GROUND14GPHASEDESCRIPTIONVOLTAGE115/230VSTA-RITE, MAX-E-PRO, P6E6E-206LTHERAPY PUMP230VSTA-RITE, MAX-E-PRO, P6E6G-208LFCHEMICALCONTROLLER115VCHEMTROL 250GCHLORINE FEEDER PUMP115VSTENNER, 45M5HACID FEEDER PUMP115VSTENNER, 45M2DRECIRCULATION PUMPEAMPS1.515.0TOTAL MAXIMUM LOADSUCTION LINESSEE ABOVECOLLECTOR TANKTOTAL CAPACITY - 65 GALLONSCOLLECTOR TANKFRONT ELEVATIONSIDE ELEVATIONAQUAWORXATFS6SPA/50 EQUIPMENT CABINET (50 G.P.M.)SAMUEL A. LIBERATORE, P.E. #55740REC. SUCTION LINE,CONNECT TO EXISTINGREC. SUCTION LINE FROMREC. PUMPSwimming Pool ModificationFor: CORAL REEF RESORT4. ALL COLLECTOR TANKS HAVE COVEDINTERSECTIONS AND SLOPE TO THE TANK DRAIN.6" MAIN DRAIN LINESLOPE CONTINUOUSLY UPTO THE COLLECTOR TANK1" FRESH WATER LINEMain Drain Pipe (Gravity)New Spa "A" Equipment Details1. PLUMBING - ALL PIPE AND FITTINGS SHALL BE SCHEDULE 40 PVC PER ASTM D1785 AND N.S.F. APPROVED ANDSTAMPED FOR POTABLE WATER APPLICATIONS. JOINTS TO BE SOLVENT WELDED JOINTS PER ASTM D2855. ALLPLUMBING EQUIPMENT AND MATERIALS SHALL CONFORM TO THE FLORIDA BUILDING CODE, PLUMBING (2007 WITH2009 SUPPLEMENTS).2. ELECTRICAL SYSTEM - ALL ELECTRICAL EQUIPMENT WIRING, INSTALLATION AND GROUNDING OF POOLCOMPONENTS SHALL CONFORM WITH NATIONAL FIRE PROTECTION ASSOC. 70, NATIONAL ELECTRICAL CODE(N.E.C.), 2008 EDITION, AND ALL APPLICABLE LOCAL CODES AND SHALL BE CERTIFIED AS SUCH BY THE ELECTRICALCONTRACTOR. CHEMICAL PUMPS TO BE ELECTRICALLY INTERLOCKLED WITH RECIRCULATION PUMP.3. EQUIPMENT - ALL PUMPS, FILTERS, AND DISINFECTION EQUIPMENT MUST BE TESTED AND APPROVED USING THENSF/ANSI STANDARD 50-2007 AND LISTED APPROVED BY NSF.4. THE FILTER ROOM FLOOR IS SLIP-RESISTANT AND SLOPED TO FLOOR DRAINSSamuel A. Liberatore PE 557401268 Rogers StreetPhone: (727) 442-8443Clearwater, FL 33756Fax.: (727) 442-6988gb collins@verizon.netSPA FILTER EQUIPMENT LIST: 50 G.P.M.Certificate of Authorization 27934GB Collins Engineering PANOTES:47.1USA10430 66th STEETST. PETERSBURG, FL 33782(727)329-8845JOB NAMELOCATIONUSA10430 66th STREETST PETERSBURG, FL 33782(888) 426-8511N.T.S.M.C.M.02.14.14S. D. H.#ATFSS6-55ERevisionDescriptionDateATFSS6/5.5 ELECTRICAL55 GPM EQUIPMENT CABINETSheet 8 of 8July21, 2015Date:Drawn by:SAL

Lights: (8) Pentair Intellibrite 5G white LED lights 601108, 300watt, 12v and (7)Pentair, Globrite color LED lights 602056, with Gunite niche 620040, Transformer kit 619994 Ladder: Smith LFB 36B Tread: 6" Maximum from wall, 3" Minimum from wall. Crossed Braced Stainless Steel, Slip Resistant