ELECTRICAL FIXTURE LEGEND - Faith Enterprises Inc

Transcription

REVISIONELECTRICAL FIXTURE LEGENDDATENOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSEPOEMERGENCY POWER OFFISICE SENSORSNOW SENSORSSJUNCTION BOX FOR WIRING OF INDICATEDEQUIPMENTStoTHERMAL OVERLOAD SWITCH, REQUIRED FORALL 120 VOLT MOTORS AND EQUIPMENT UNLESSNOTED OTHERWISE.1 - 4" SPARE WITH PULL STRINGELECTRIC EQUIPMENT LEGENDSB1FUSED DISCONNECT SWITCH (DISCONNECT SWITCH,COUNT OF TYPE, H 480 VOLT L 208 VOLT, AMPS- 3 30, 6 60, 1 100, 2 200). EC TO PROVIDE THECORRECT FUSES FOR THE EQUPMENT, PANELS, ETC.CONNECTED.D1H1D4L2MTS4" CONDUIT WITH (3) 1" INNERDUCTS, ONEOF WHICH CONTAINS A 12 STRAND SINGLEMODE FIBER OPTIC CABLEMANUAL TRANSFER SWITCHELECTRIC METERHPLP4"øø"4T-14"øMETERLP112"ø4" CONDUIT WITH (3) 1" INNERDUCTS,ONE OF WHICH CONTAINS A 25-PAIRCATEGORY 6 COPPER CABLEPANELBOARD 480 VOLTPANELBOARD 208 VOLTT22" STUBBED OUT INTO THELANDSCAPE AREA FORIRRIGATION CONTROL CABLESHP11SWITCHBOARDtoSBD1H23"ø 3"ø 3"øDRY STEP DOWN TRANSFORMERT2EXISTING COMM VAULT, RUN 3 - 4" CONDUITSFROM VAULT TO NEW IT ROOM. PROPERLYSEAL CONDUITS WHERE THEY ENTER VAULT.THERMAL OVERLOAD SWITCHMS*JUPS1SHUNT TRIP BREAKER, SIZE AND VOLTAGEAS SCHEDULEDELECTRICAL SITE PLAN1/16" 1'-0"Sheet ListJUNCTION BOX FOR WIRING OF INDICATEDEQUIPMENTSheetNumberUNINTERRUPTIBLE POWER SOURCE EQUIPMENTCIRCUITS LEGENDLINE WITH HOOK INDICATES GROUND WIRELONG LINE INDICATES HOT WIRESHORT WIRE INDICATES NEUTRAL WIRENOTE: ISOLATED GROUND CIRCUITS ARE REQUIREDIN THIS PROJECT. THESE ARE INDICATED ONTHE PLANS. IN GENERAL THOSE RECEPTACLECIRCUITS TO PANEL LP13, LP21 AND LP11 ANDFEEDER FROM TRANSFORMER T2 TO LP11.1' - 6"0' - 6"TOPPING AS INDICATEDCONDUIT MARKERBACKFILL1' - 6"INDICATES WIRE IN CONDUIT WITH NUMBER OFGROUNDS, NEUTRALS AND HOTS AS SHOWN,# 12 WIRE IN 3/4" UNLESS NOTED OTHERWISEON THE SCHEDULES OR ON THE PLANSINDICATES HOME RUN CIRCUIT TO PANEL,PANEL NAME AND CIRCUIT NUMBER(S) AREINDICATEDPROJECT:UTILITY TRANSFORMER, 277/480 VOLT,3 PHASE, 4 WIRET-1LP11-1EL11T3EH11MTSSB2DPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGJ1PREPAREDFOR:PIN AND SLEEVE 200 AMP RECEPTACLE153rd AIRLIFT WINGGROUND ROD WITH GROUND WELLWYOMING AIR NATIONAL GUARDGWELECTRICAL SITE PLAN, ELECTRICAL EQUIPMENT,CIRCUIT AND ELECTRICAL FIXTURE LEGEND,TRENCHING DETAILGROUND RODDF.GRDRAWINGTITLE:TRANSIENT VOLTAGE SURGE SUPPRESSORFOR WYOMINGTVSSU.S. PROPERTY & FISCAL OFFICEMAIN GROUND BUSSREF.MGBBNO.DUPLEX RECEPTACLE, TYPE AS SCHEDULEDR1TYPICAL CONDUIT TRENCHINSTALLATION23/4" 1'-0"NUMBER OF CONDUITSAS SHOWN ON 602E-603E-604E-700E-701E-800E-801E-900Sheet NameELECTRICAL SITE PLAN, ELECTRICAL EQUIPMENT, CIRCUIT AND ELECTRICAL FIXTURE LEGEND, TRENCHING DETAILLIGHTING SITE PLAN AND TYPE P INSTALLATION DETAILFIRST FLOOR LIGHTING PLAN, LIGHT FIXTURE AND LIGHTING DEVICE SCHEDULESECOND FLOOR LIGHTING PLAN. LIGHTING LEGEND, DIMMING SYSTEM AND WARNING LIGHT DETAILSFIRST FLOOR POWER PLAN AND SWITHBOARD SB1 SCHEDULESECOND FLOOR POWER PLAN, SWITCHBOARD SCHEDULE SB2, ELEVATOR EQUIPMENT ROOM AND GROUND BUSS DETAILELECTRICAL EQUIPMENT SCHEDULEELECTRICAL ONE LINE AND ELECTRICAL FEEDER SCHEDULEGROUNDING ONELINE & GROUNDING ONELINE FOR SEPARATELY DERIVED SYSTEMS, HP11 PANEL SCHEDULE, BRANCH CIRCUITS LARGER THAN # 12FIRST FLOOR HVAC POWER PLAN AND MECHANICAL EQUIPMENT SCHEDULESECOND FLOOR HVAC POWER PLANLIGHTNING PROTECTION PLAN GROUND LEVELLIGHTNING PROTECTION ROOF PLAN, OBSTRUCTION LIGHTS INFORMATION AND LIGHTNING PROTECTION 3DGUTTER HEATER ROOF PLANFIRST AND SECOND FLOOR SECURITY PLAN, SECURITY DEVICE SCHEDULE AND SECURITY LEGENDSECURITY SYSTEM INSTALLATION DETAILSFIRST FLOOR TELE/DATA FLOOR PLAN, DATA DEVICE, CABLE TRAY & UNDER FLOOR RACEWAY SCHEDULES, TELE/DATA & CABLE TRAY & UNDER FLOOR RACEWAY LEGENDSSECOND FLOOR TELE/DATA FLOOR PLAN, TV DEVICE SCHEDULE AND DATA OUTLET CONFIGURATION DETAILCOMM ROOM CALLOUT, DETAILS AND RENDERINGSRACK SECTION, DATA EQUIPMENT SCHEDULE AND PATCH PANEL DETAILDATA PANEL SCHEDULESFIRST FLOOR FIRE ALARM AND MASS NOTIFICATION PLAN, FIRE ALARM DEVICE SCHEDULE AND FIRE ALARM AND MASS NOTIFICATION LEGENDSSECOND FLOOR FIRE ALARM AND MASS NOTIFICATION PLANPANELBOARDS LP11, LP12 , EH11 AND EL11 SCHEDULESPANELBOARDS LP13, LP21 AND LP22 SCHEDULES3D VIEWSp.c.engineeringplanningsurveyingPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 2013DRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017DRAWINGNO.E-100

DATELPCPROJECT:lv6 BOLLARD LIGHTS AND ALL WIRINGFOR THE LIGHTS SHALL BE A BIDOPTION153rd AIRLIFT WINGWYOMING AIR NATIONAL GUARDDRAWINGTITLE:LDPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGPREPAREDFOR:REF.DF.LLIGHTING SITE PLAN AND TYPE P INSTALLATIONDETAILLFOR WYOMINGCONNECT FIRSTTHROUGHCONTACTOR (CON HP11 - 12), THEN TO PANELLU.S. PROPERTY & FISCAL OFFICENO.REVISIONNOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSCON1LLCON2LPCONNECT FIRSTTHROUGHCONTACTOR (CON 2),THEN TO PANEL HP11 - 1PPPCONNECT FIRSTTHROUGHCONTACTOR (CON 1),THEN TO PANEL HP11 - 1Op.c.OTYPE P FIXTURE3' - 6 1/2"P4 ANCHOR BOLTS PER MANUFACTURERREQUIREMENTSGRADEPEDISTALS99' - 6"CONDUIT3' - 6"SIGN LIGHTS AND WIRINGFOR SIGN LIGHTS TO BEA BID OPTION2' - 0"2E-1012PHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 20131' - 0"PengineeringplanningsurveyingTYPE P INSTALLATION INFORMATION1/4" 1'-0"CONCRETE FOUNDATIONFOR MOUNTING FIXTUREDRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017SITE LIGHTING11/8" 1'-0"DRAWINGNO.E-101

LIGHTING FIXTURE SCHEDULES2OSlvF (a)ES2 (a)AlvlvJON AT ALL TIMESBH (b)J (a)CORRIDOR LIGHTSSHALL BE CONTROLLEDBY POWER PAK RELAYMODULE IN TYPE MARK"JRM" JUNCTION BOX.THERE WILL BE NODEDICATED WALLSWITCHDEEOSOSEJlvlvJ (a)DH (b)J (b)S2J (b)lvJHP11 - 4CDEEBlvTO UPPER LEVEL FIXTURES (SEE SECONDFLOOR LIGHTING PLAN)S2DJ (a)H (b)JRMH (a)EEH (b)H (a)ECW (c)CD (b)EOS2S2 S2S2 S2OSDDlvH (a)D (a)BS4 (c)S4 (b)lvlvCD (b)H (b) EWJOSOSD (a)LP12H (b)JBJCD (b)A (d) CD (b)PCJOSAJJOS1S1AH.E. 1013Finelite Inc.DUAL LITEDUAL 0NI03LEO3DUAL LITEEVOEWFFE1101DUAL LITEHE WILLIAMSHE 1-54T5H-WG-73141-EB2-277-EMGH1218HE WILLIAMSHE SOVERHUBBELLNO22CROUSE HINDSKim LightingP6KIM 0S16-SSL-12-2T5HO-DC-91W-OPEN-277-AC- SUSPENDED LINEAR PENDANT 12' NOMINAL LENGTHEE-C4-1.0XCHWM3-LED-WT LED 48 450-NW-UE-BLK LED EXTERIOR WALL SCONCENVX15GHGA-NVBAWALL MOUNTED VAPOR-TIGHT FIXTURE, TOSHIBA8A19/27F-UP LED LAMP, 120 VOLT43961-116-GRROOF MOUNTED, TWO HEAD, AIRCRAFT WARNING LIGHTCFL1-27L3KUV-BLLED FLOODLIGHT WITH ADJUSTABLE BARN DOORLOUVERS (BD-CFL/BL), ON STANCHION MOUNT (SM18BL),8" ABOVE GROUNDGEM1C-36L3K277-LG-NG-CPERFORMANCE BOLLARD MOUNTED ON CONCRETESHAFT. TO BE BURIED 3' 6"AFAPCAWAAS2lvlvS1 (b)B116JLP13lvlvS1 (a)CW (c) D (a) EEH (a)OSJS3DCW (c)HP11 - 4AAJJ (a)OSBCDLEOE-602S2 (a)DIRECT/INDIRECT 2 LAMP RECESSED FIXTURE, DUALLEVEL SWITCHINGDIRECT/INDIRECT 1 LAMP RECESSED FIXTURE6" RECESSED LED CAN WITH LUTRON SERIES A LEDDRIVER AND 2000 LUMEN LED MODULE6" RECESSED LED CAN WITH 1000 LUMEN OUTPUT6" RECESSED LED CAN CONFIGURED TO WALL WASHWITH LUTRON SERIES A DRIVERWALL MOUNTED LINEARCEILING MOUNTED EXIT SIGN, 277 VOLTEMERGENCY LED WALLPACK, NICKEL CADMIUMBATTERY, 6 VOLT,TWO LED OUTDOOR REMOTE EMERGENCY LIGHTINGHEADSWALL MOUNTED EXIT SIGN, 277 VOLTSINGLE LAMP STRIP FIXTURE WITH WIRE GUARDSINGLE LAMP STRIP FIXTURE WITH WIRE GUARD ANDBATTERY BACKUPDUAL LAMP STRIP FIXTURE WITH WIRE GUARD3 LAMP WALL MOUNTED CORNER LIGHT WITH CLEARACRYLIC LENSSUSPENDED LINEAR PENDANT 8' NOMINAL LENGTHGrand total: 151JGEEOSMA (d)S1ALL SWITCHES IN RECEPTION AREASHALL BE CONFIGURED TO RESPONDTO AREA OCCUPANCY SENSOR (OS)S2 (d)S2 (d)GlvlvUP TO LIGHTSABOVEGS1S1SWITCH FORUPPER LIGHTSEPROJECT:S1 (e)GCL (e)153rd AIRLIFT WINGH 5K-WHWTB24WYOMING AIR NATIONAL GUARDH (b)H.E. WilliamsFIRST FLOOR LIGHTING PLAN, LIGHT FIXTURE ANDLIGHTING DEVICE SCHEDULEH (a)15DRAWINGTITLE:EEAFOR WYOMINGF (a)H (b)DescriptionU.S. PROPERTY & FISCAL OFFICEF (b)ModelNO.OSS2 (b)OSH (a)TypeMark Count ManufacturerF (a)PREPAREDFOR:F (b)DPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGF (a)F (b)DATEREVISIONNOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSEH11 - 2EOCON1CON2EL11EEHP11 - 3T3GG EH11EH11 - 6LP11 T2SB2 IRST FLOOR LIGHTING PLAN1/8" 1'-0"LIGHTING DEVICE SCHEDULEType Mark Count S3S4S5Grand total: UBBELLLutron Electronics1221MRF2-6ANS-277-**HUBBELLLutron on4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELL4 CONTACT CONTACTOR FOR LIGHTING CIRCUITS WITH ON/OFF/AUTO SWITCH AND REMOTE PHOTOCELLPULL BOX FOR LIGHTING SYSTEM WITH POWPAK RELAY MODULECEILING-MOUNT WIRELESS OCCUPACY SENSOR WITH SURFACE OR RECESSED MOUNTING HARDWARE AS REQUIRED FOR LOCATIONS INSTALLEDPULL BOX FOR LIGHTING SYSTEM, TYPICAL, FOR REFERENCE ONLY, MORE BOXES MAY BE REQUIREDPHOTOCELL FOR USE WITH SITE LIGHTING CIRCUITSPHOTO CELL FOR AIRCRAFT WARNING LIGHTSHEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATEWIRELESS SWITCH. WHEN DUAL LEVEL SWITCHING IS USED, ENSURE THAT BOTH SWITCHES ARE CONFIGURED TO RESPOND TO WIRELESS OCCUPANCYSENSOR (OS) IN AREA.HEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR GARBAGE DISPOSER CONTROL, WIRE TO RECEPTACLEWIRELESS DIMMERHEAVY DUTY 120/277 VOLT SINGLE POLE SNAP SWITCH WITH FACE PLATE FOR CONTROL OF EXHAUST FANPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 2013DRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017DRAWINGNO.E-200

DATEREVISIONNOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSEJEXTERIOR REMOTE EXIT LIGHTS1DEES2BH (c)S2 (c)OSS1DJDCDlv"A"DDB ElvJFOSA(a)S2S24'0" STRIP LIGHT WITH WIRE GUARDEElvLIGHT ON AT ALL TIMES**SEE ROOF LIGHTENINGPROTECTION PLAN FORROOF AIRCRAFT WARNINGLIGHTING**EEEGGJOSDAAFEOSGlvlvAS5 S2S2S2S2DEVICE TYPEDEVICE TYPE WITH SWITCHING INFORMATIONJDJCORRIDOR LIGHTSSHALL BE CONTROLLEDBY POWER PAK RELAYMODULE IN TYPE MARK"JRM" JUNCTION BOX.THERE WILL BE NODEDICATED WALLSWITCH3 LAMP WALL MOUNTED CORNER FIXTUREEXTERIOR WALL SCONCEWALKWAY BOLLARDLFFLOODLIGHTJlvlvJOSFIXTURE TYPE WITH SWITCHING INFORMATIONOSDS1EH11 - 4FIXTURE TYPEEEOSDLOW VOLTAGE SWITCH6" RECECCED CAN DOWNLIGHTEJ"S1""S1(a)"S2BSINGLE POLE 120/277 VOLT SNAP SWITCHDIRECT/INDIRECT WALL FLUORESCENT FIXTURELIGHTS ON ATALL TIMESlvlvlvJROOF MOUNTED OBSTRUCTION LIGHTAEH11 - 6PENDANT FLUORESCENT STRIPLP22S1LIGHTS SWITCHED FROMSNAP SWITCH ON 1STFLOORGHP11 - 2GPROJECT:LGTOBA NLL EXTAS DT/ IMDR MIV INGER.SECOND FLOOR LIGHTING PLAN1/8" 1'-0"120 VOLTBLACKORANGEWHITERWARNING LIGHTSON TOP OF BUILDING1 POLE PHOTO CELLCONTROLRCEILING MOUNTEDWIRELESS ningsurveyingDIMMING DRIVERDIMMING DRIVERWARNING LIGHT WIRING DETAILDRAWNBY:MHG / RCW/ RCWCHECKEDBY:MHGRRAUGUST 1, 2013DESIGNEDMHGBY:BLACKWARNING LIGHTSON TOP OF BUILDINGPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:NEUTRALGREEN1153rd AIRLIFT WINGBBWYOMING AIR NATIONAL GUARDOSBWALL MOUNTED LED EXIT SIGNFSECOND FLOOR LIGHTING PLAN. LIGHTINGLEGEND, DIMMING SYSTEM AND WARNING LIGHTDETAILSElvlvDRAWINGTITLE:S2lvlvFOR WYOMINGS2 S2CEILING MOUNTED LED EXIT SIGNPREPAREDFOR:EE2X4 RECESSED DIRECT/INDIRECT CEILING FIXTURElvlvU.S. PROPERTY & FISCAL OFFICEKH (c)S2S2JRMKS2DPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGFROM LOWER LEVELLIGHTING FIXTURES (SEEFIRST FLOOR LIGHTING PLAN)OSNO.OSLIGHTING LEGENDKOSWIRELESS DIMMERCONTROL SWITCHJOBNO.:DPEZ 089017GROUNDTYPICAL DIMMING SYSTEMDRAWINGNO.E-201

REVISIONDATENOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSSwitchboard: SB1R2Location:Supply From:Mounting:Enclosure:JLP13 13R2R2WST SIM MAINT PARTSSTORMECHANICAL/FIRE.T-1PADNEMA 1Volts: 480/277 WyePhases: 3Wires: 4A.I.C. Rating: 42000Mains Type:Mains Rating: 800 AMCB Rating: 800 ANO.Notes:114VAVCPR2R1LP12 - 8SGBBLP11 13,15,17MSALP12 7,9LP12D1HCB1R1R1R1R10R10LP13 - 9103EL11 10EL11 17R2R2SITE MGR (CONTRACT)PO/QAR STOR108107R10STAIRTGBB110R1R2R2140856 VATotal Conn. Load: 142126 VATotal Amps:514 A141796 VA512 A140856 VA509 ARemarksLegend:Load PowerReceptacleSpareNotes:Connected Load63282 VA113779 VA11200 VA11157 VA78700 VA25554 VA7800 VA51010 VA64830 VADemand 0.00%59.80%100.00%Estimated Demand63282 VA113779 VA11200 VA13946 VA84078 VA25554 VA7800 VA30505 VA64830 VAPanel TotalsTotal Conn. Load:Total Est. Demand:Total Conn.:Total Est. Demand:427312 VA414974 VA514 A499 ALP13 - 5R1R2R2141796 VAINSTRUCTORS SUITER1R10142126 VATrip Rating800 AR5VAVCPLP12 11,13105R6STAIR104EPONOTE: ALL CIRCUITS RUN TO PANEL LP13LP11 SHALL HAVE AN ISOLATED GROUND AS20,22,24WELL AS AN EQUIPMENT GROUNDMSPDUWOMENSGBBSB2 - 3112MSS-1 R4Vac 1,3,5LP13 - 8LP12 - 3P1WST COMPUTORUPSROOM-1LP12 - 5LP12 CORRDATA STORAGEMSS-1R7MSUPS1,3106113- 1,3,5LP11 UPSR2R2R2R214,16,18LP13 R4EL11 10,12,14R8LP13 - 6MSUPS14MENLP12 - 2MSSD - 2LP13 10R164,6 16,18,20R15RECEPTIONLP12 - 9 R1R1Frame Size800 AR15PO/QARR2 (GOV'T)109R2R2R2R2J1J1LP11 23R21R2J1R2R2E-602JR10LP13 - 4LP13 - 7VAVCPR6R2 R2R2R13COMMLOBBYWIRETO PITLIGHT101& SWITCHR6ELEVEL11 -117EL11 R22523R2R2102R1J2MECHANICAL/FIREPROTECTIONEL11 - 4100R1R1J2FCHP11 - 6118HP11 - 5EL11LP11 25LP11R17T2LP11 21HP11 EH11MTSMGBBSB2 SB1METERD1H2TVSSS/PFIRST FLOOR POWER11/8" 1'-0"GHCPGHSCPR6T3R6EL11 34VESTIBULER1SPACE FOR FUTURE ROOFSOLAR COLLECTOR EQUIPMENTLP13 - 1R1EL11 - R119EL11 21LP13 - 3PROJECT:NOTE: ALL CIRCUITS RUN FROM ROOM 117TO PANEL EL11 SHALL HAVE AN ISOLATEDGROUND AS WELL AS AN EQUIPMENT GROUND153rd AIRLIFT WINGWST HIGH BAYLP13 15# of Poles3CWYOMING AIR NATIONAL GUARDtoMSAWStoM2R2Circuit DescriptionSB2BFIRST FLOOR POWER PLAN AND SWITHBOARD SB1SCHEDULEMSVACEMMPROVIDE A LIMIT SWITCH (WITH NC CONTACTS)ON THE CRANE RAIL AT THE PARKED POSITION.PROVIDE WIRING IN CONDUIT FROM LIMIT SWITCHBACK TO THE MOTION CONROL CABINET. FIELDLOCATE PARKED POSITION.R2CKT123456ADRAWINGTITLE:R1DUCT RUN116UNDERNEATHSIMULATORDISCONNECT FOR BRIDGE POWERLP13 11R2MSEMMR6R2 115FOR WYOMINGLP13 15R1PREPAREDFOR:R1DPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGR1U.S. PROPERTY & FISCAL OFFICEMAINT SUPVINSTALL 2" CONDUIT UNDERGROUND ANDEXTEND UP INTO MECHANICAL ROOMFOR IRRIGATION CONDUCTORS.p.c.engineeringplanningsurveyingPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 2013DRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017DRAWINGNO.E-202

REVISIONDATENOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSSwitchboard: SB2.25"4"Location:Supply From:Mounting:Enclosure:R2R2 R5LP21 - 5CLASSROOMR15210 R2R2R2211R5JR2R2R2R2CLASSROOMR2R5LP21 - 3R15R15212R2R2R2R2LP21 - 7R2LP21 - 4R2NOTE: ALL CIRCUITS RUN TO PANEL LP21SHALL HAVE AN ISOLATED GROUND ASWELL AS AN EQUIPMENT GROUNDUNIT STORAGESGBBR1LP21 - 6213R1R4R1R1?LP22 - 5 R7205R2R2CC208215R4R2R15R2R2R15R5R2R21Load PowerReceptacleSpareNotes:Connected Load63282 VA113779 VA11200 VA11157 VA78700 VA25554 VA7800 VA51010 VA64830 VADemand 0.00%59.80%100.00%Estimated Demand63282 VA113779 VA11200 VA13946 VA84078 VA25554 VA7800 VA30505 VA64830 VAPanel TotalsTotal Conn. Load:Total Est. Demand:Total Conn.:Total Est. Demand:427312 VA414974 VA514 A499 AE-602R2JR1GPBLP22 - 7GPBCLASSROOMLP21 - 1WOMENJ203148918 VA538 ALegend:CORRIDORSTAIRS149028 VA538 A200 A200 A200 A200 A?LP21 - 2LP22 13Total Conn. Load: 148544 VATotal Amps:536 ARemarks214?209D9H317976 VA7834 VA19214 VA0 VA30594 VA32267 VA20633 VA20400 VALP21 R11MENHP11 20,22,24JR1JAN.?LP22 - 9D1H1GPB16273 VA7834 VA19214 VA0 VA31306 VA33368 VA20633 VA20400 VAJ153rd AIRLIFT WINGR2CLASSROOM333314054 VA7834 VA19214 VA0 VA34862 VA31546 VA20633 VA20400 VATrip Rating200 A40 A100 A60 A175 A200 A125 A100 AWYOMING AIR NATIONAL GUARDR2SPACESPACESPACESPACEFrame Size200 A60 A100 A60 A200 A200 A200 A100 ASECOND FLOOR POWER PLAN, SWITCHBOARDSCHEDULE SB2, ELEVATOR EQUIPMENT ROOM ANDGROUND BUSS DETAILR2R2R2# of Poles33333333CDRAWINGTITLE:LOCATE AT WIRING "WATERFALL"ON TOWERCircuit DescriptionHP11HCB1MSEMMTVSST2MTSACC-1D1H1BFOR AU.S. PROPERTY & FISCAL OFFICEGPBNotes:PROJECT:GPBA.I.C. Rating: 30000Mains Type:Mains Rating: 800 AMCB Rating:PREPAREDFOR:JVolts: 480/277 WyePhases: 3Wires: 4DPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGGROUND BUSS - MGBB,TGBB OR SGBBMECHANICAL/FIRE.SB1PADNEMA 1NO."23LOBBY201R1LP22 6,8R1LP22 - 8R9R9 R9 R9GALLY & VENDINGR1BREAK AREA?206R12LP22 - 2LP22 1,3207R12 R12LP22?R1p.c.LP22 2,4JStoeJGPBStoeJJR111SECOND FLOOR POWER1/8" 1'-0"GPBSWITCHES TO BE USEDFOR ELEVATOR 120 VOLTEQUIPMENT AND LIGHTING FEHJS1D1L1HSPT1PHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:EL11 20,22,24S216EL11 12EL11 16to toEQUIPMENT PLATFORMengineeringplanningsurveyingAUGUST 1, 2013DRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:ELEVATOR LEVEL, POWER, LIGHTING,DATA AND FIRE ALARM31/8" 1'-0"DPEZ 089017DRAWINGNO.E-203

ELECTRICAL EQUIPMENT YesT31NoT-1UPSGrand total: 481148NoNoNoNoWIRE SHUNT TRIP INTO EPO SWITCHWIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWNWIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWNWIRE SHUNT TRIP INTO BUILDING FIRE ALARM SYSTEM FOR SHUT DOWN153rd AIRLIFT WING1111WYOMING AIR NATIONAL GUARDD1L1D1L3D1L6D2H3ELECTRICAL EQUIPMENT SCHEDULENoDRAWINGTITLE:1FOR WYOMINGD1H6OVERHEAD CRANE CONNECTION POINT, PROVIDED BY GC, WIRED BY EC. FIELD LOCATE EXACT CONNECTION POINT100 AMP, 277/480 VOLT, 3 PHASE, 4 WIRE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, FUSED,NEMA 3R DISCONNECT30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED60 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED100 AMP, 208 VOLT, 3 PHASE, FUSED FOR ELEVATOR MOTOR, FUSE TO MATCH MOTOR REQUIREMENTS30 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.60 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 208 VOLT, 1 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC. LOCATE MC PROVIDED STARTERABOVE AND WIRE AS REQUIRED30 AMP, 480 VOLT, 3 PHASE, NEMA 3R FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC.30 AMP, 480 VOLT, 3 PHASE, FUSED DISCONNECT, PROVIDED, INSTALLED AND WIRED BY EC., LOCATE NEXT TO CRANE POWERCONNECTION POINT, FIELD LOCATE277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1, 200 AMP MAIN BREAKER120/208 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1, 30 SPACEELECTRIC MOTION CABINET TO BE PROVIDED BY LOCKHEEDFUSE CABINET BY EC TO STORE SPARE FUSES277/480V GUTTER HEAT CONTROL PANEL WITH 50A BREAKER277/480V GUTTER HEAT SATELLITE CONTROL PANEL WITH 50A BREAKER CONNECTED TO MASTER CONTROL PANEL USING 12 AWG3-WIRE CABLE277/480 VOLT, 3-PHASE, 4 WIRE, 40 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPENPOSITION277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP, NEMA 1120/208 VOLT, 3-PHASE, 4 WIRE, 400 AMP, 400 AMP MAIN PANELBOARD120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARD120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, MAIN LUG ONLY PANELBOARDNEW METER120/208 VOLT, 3-PHASE, 4 WIRE, 50 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPENPOSITION120 VOLT, 20 AMP, 1 PHASE, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THE OPEN POSITION277/480 VOLT, 3-PHASE, 4 WIRE, 100 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCK DEVICE TO ENABLE PADLOCK IN THE OPENPOSITION120/208 VOLT, 3-PHASE, 4 WIRE, 100 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THEOPEN POSITION120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THEOPEN POSITION120 VOLT, 1-PHASE, 2 WIRE, 20 AMP, SHUNT TRIP BREAKER120/208 VOLT, 3-PHASE, 4 WIRE, 200 AMP, SHUNT TRIP BREAKER, WITH FRONT LOCKING DEVICE TO ENABLE PADLOCK IN THEOPEN POSITION120 VOLT, 1-PHASE, 2 WIRE, 20 AMP, SHUNT TRIP BREAKER WITH FRONT LOCKING DEVICE TO PADLOCK IN THE OPEN POSITION277/480 VOLT, 3 PHASE, 4 WIRE, 200 AMP MANUAL TRANSFER SWITCHWST POWER CABINET BY LOCKEED.120/208 VOLT, 3 PHASE, 100 AMP PANEL BY OTHERS, WIRED TO MSPDU BY OTHERS277/480 VOLT, 3 PHASE, 4 WIRE, 800 AMP MAIN BREAKER, CT SPACE FOR CLF&P METERINGDISTRIBUTION SECTION, 277/480 VOLT, 3 PHASE, 4 WIRE , 800 AMP480 VOLT, DELTA PRIMARY - 120/208 VOLT WYE SECONDARY, 112.5 KVA DRY TYPE STEP DOWN TRANSFORMER, K4 RATING,SHIELDED, 3% IMPEDANCE480 VOLT, DELTA PRIMARY - 120/208 VOLT WYE SECONDARY, 75 KVA DRY TYPE STEP DOWN TRANSFORMER, K4 RATING, SHIELDED,3% IMPEDANCETRANSFORMER BY CLF&P75 KVA RATED AT ALTITUDE UPS, TO BE PROVIDED AND INSTALLED BY ECU.S. PROPERTY & FISCAL 2D1H3DescriptionDPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGCountPROJECT:Type MarkHAS ISOLATEDGROUND BUSDATEREVISIONNOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION REQUIREMENTSWIRE SHUNT TRIP INTO EPO SWITCHWIRE SHUNT TRIP INTO EPO SWITCHWIRE SHUNT TRIP INTO EPO SWITCHMAIN SWITCH AND CT SECTION OF MAIN SWITCHBOARDDISTRIBUTION SECTION OF MAIN SWITCHBOARDp.c.engineeringplanningsurveyingPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 2013DRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017DRAWINGNO.E-204

YZ4ZUPSQCRAC-1WST COMPUTER ROOM FLOOR1" CONDUIT FOR METER WIRINGMSPDUZ1WPUMSS-1MSUSPNO.TVSS2PDUP1DATEUPON COMPLETION OF PROJECT THE FOLLOWING MEASUREMENTS SHALL BE MADE OVER A PERIOD OF SEVERAL DAYS (THE RESULTS TO BE SENT TO CAE FOR ANALYSIS)PREFERABLY WHEN THE AREA OF INTEREST AND ANY NEAR-BY AREAS HAVE THEIR FULL COMPLEMENT OF ELECTRICAL EQUIPMENT INSTALLED AND OPERATED:MAIN INPUT VOLTAGE VARIATIONS, SAGS AND SURGES (ALL PHASES AND NEUTRAL)FREQUENCY VARIATIONSTRANSIENTS MAGNITUDE EXCEEDING 1.5 TIMES THE NOMINAL VOLTAGETRANSIENTS DURATION EXCEEDING 1/2 POWER CYCLENUMBER AND DURATION OF POWER OUTAGESLP21LP22HCB1REVISIONNOTE: ALL 3D AND SECTION VIEWS ARE SHOWN TO HELP CONTRACTORINTERPRET DESIGN. THESE VIEWS SHALL NOT BE USED AS A MODELFOR CONSTRUCTION. REFER TO THE ARCHITECTURAL DRAWINGS FORALL BUILDING CONSTRUCTION TY TRANSFORMER277/480V, 3PH, 4WMSALP11SB2TVSSXS/PMTST-1FGT3TIHT-2VMNKEMMD1FIRST FLOORLPREPAREDFOR:EL11153rd AIRLIFT WINGZ2DWYOMING AIR NATIONAL GUARDELECTRIC METERFOR WYOMINGWST COMPUTER ROOM LOWERED FLOORU.S. PROPERTY & FISCAL SPDUGrand total: 29Circuit 3,5Load LP12LP21LP22MSUPSMSALP13CRAC-1D1 HVAC WST HIGH BAY 124UPSEMMTVSS2MSS-1P1SB2MSPDUPDUWire Size3 runs of 3-#300, 1-#300, 1-#1/03-#3/0, 1-#3/0, 1-#63-#3/0, 1-#3/0, 1-#63-#3/0, 1-#3/0, 1-#63-#3/0, 1-#3/0, 1-#63-#3, 1-#3, 1-#63-#3/0, 1-#3/0, 1-#63-#8, 1-#8, 1-#103-#6, 1-#6, 1-#103-#3/0, 1-#3/0, 1-#63-#2/0, 1-#2/0, 1-#62 runs of 3-#3/0, 1-#3/0, 1-#33-#3, 1-#3, 1-#83-#1/0, 1-#1/0, 1-#63-#1/0, 1-#1/0, 1-#63-#1/0, 1-#1/0, 1-#63-#3/0, 1-#3/0, 1-#63-#6, 1-#6, 1-#103-#1/0, 1-#1/0, 1-#63-#8, 1-#8, 1-#103-#6, 1-#6, 1-#103-#3/0, 1-#3/0, 1-#63-#3, 1-#3, 1-#83-#10, 1-#10, 1-#103-#3/0, 1-#3/0, 1-#63-#3/0, 1-#3/0, 1-#63 runs of 3-#300, 1-#300, 1-#1/03-#3, 1-#3, 1-#83-#3, 1-#3, 1-#8ConduitSize WhenLarger Than1/2"Voltage3 - 3"2"2"2"2"1 1/4"2"1 1/4"1"2"2"2 - 2"1 1/4"2"2"2"2"1"2"1 1/4"1"2"1 1/4"1/2"2"2"1 1/4"1 1/4"480 V480 V480 V480 V480 V480 V208 V480 V480 V480 V480 V208 V480 V208 V208 V208 V208 V208 V208 V480 V208 V208 V480 V208 V208 V208 V480 V208 V208 VASCI AtLoad2873924268LESS THAN 10000LESS THAN 100002276920728LESS THAN 100004561194822717225064LESS THAN 100007373LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 10000LESS THAN 1000028739LESS THAN 10000CommentsGROUND WIRES (# 1/0) NOT REQUIRED FOR THESE GTITLE:ELECTRICAL FEEDER SCHEDULEDPEZ 089017C-130 FLIGHT SIMULATOR TRAINING FACILITYCHEYENNE, WYOMINGELECTRICAL ONE LINEELECTRICAL ONE LINE AND ELECTRICAL FEEDERSCHEDULESREQUIRES AND ADDITIONAL # 3 ISOLATED GROUND WIRE IN EACH CONDUITREQUIRES AND ADDITIONAL # 6 ISOLATED GROUND WIRE IN CONDUITp.c.REQUIRES AND ADDITIONAL # 6 ISOLATED GROUND WIRE IN CONDUITWIRING FROM BREAKER TO EQUIPMENT NOT REQUIRED IN THIS CONTRACTWIRING FROM BREAKER TO EQUIPMENT NOT REQUIRED IN THIS CONTRACTengineeringplanningsurveyingPHONE (307) 637-60171103 OLD TOWN LANE, SUITE101CHEYENNE, WY 82009AVI@AVIPC.COMDATE:AUGUST 1, 2013WIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACTBUSSING BETWEEN SB1 AND SB2 TO EQUAL SIZE OF FEEDERS SHOWNWIRING FROM BREAKER TO EQUPMENT NOT REQUIRED IN THIS CONTRACTDRAWNBY:MHG / RCWDESIGNEDMHGBY:/ RCWCHECKEDBY:MHGJOBNO.:DPEZ 089017DRAWINGNO.E-205

ELECTRIC CIRCUIT SCHEDULE, BRANCH CIRCUITS LARGER THAN # 12HP1153/4"HP1163/4"SB27SB28Grand total: 181 1/2"1 1/4"277 V4V1.5177661-#6, 1-#6, 1-#10277 V3V0.9210891-#6, 1-#6, 1-#10277 V0V0.0848161-#6, 1-#6, 1-#10277 V0V0.1338193-#1, 1-#63-#3, 1-#3, 1-#8480 V480 V1V0V0.1168240Branch Panel: HP11GB2Location:Supply From:Mounting:Enclosure:ISOLATED GROUND480 DELTA/120/208 YXFRMEQUIPMENT GROUNDTYPICAL# 4 COPPER (1/0 FOR 150 KVATRANSFORMEREQUIPMENT GROUNDNEUTRAL (TYPICAL)480 VOLT CONDUIT120/208 VOLTCONDUIT, (TYPICAL)BONDING CONDUCTORGROUNDING ONELINE FOR SEPARATELYDERIVED SYSTEMSBOND TO EVERY FOURTH RISER OFRAISED COMPUTER ROOM FLOORWITH #62/0SGBBLOCATED WITHIN 78"OF P1 CABINETAT WIRING "WATER FALL"FIRE ALARM &GENERATOR MASS NOTIFICATIONDISCONNECTPANEL(S)SGBBMAIN SERVICESWITCHBOND TO CABLE SUPPORTWITH # 6RADIO ANTENNA FORFIRE ALARM AND MASSNOTIFICATION SYSTEMAT EMMIN COMM RMNEUTRAL Notes:MGBBGROUND BUSSA.I.C. Rating: 30000Mains Type:Mains Rating: 225 AMCB Rating:480/277 Wye34NoCircuit DescriptionLighting - SiteRoom 101, 105, 108, 109, 106, 111, 107, 100, 11.GHSCP (GUTTER AND DOWNSPOUT SpareSpareSpaceSpaceSpaceSpaceTrip20 A20 A50 APolesABCPoles1698 VA 2789.113172. 2592.113000. 4500.12018. 2018.2018. 2018.20 A332018. 2018.797 VA 797 VA20 A33797 VA 797 VA797 VA 797 VA3718. 1933.3718. 1933.20 A333718. 1933.20 A10 VA0 VA120 A10 VA0 VA120 A10 VA0 VA120 A10 VA0 VA120 A10 VA0 VA1--0 VA0 VA---0 VA0 VA---0 VA0 VA---0 VA0 VA-Total Load:14768 VA17045 VA18781 VATotal Amps:53 A63 A69 ATrip20 A20 A50 ACircuit DescriptionRoom 212, 211, 210, 205, 214, 213, 215, 209, 20.Room 116GHCP (GUTTER AND DOWNSPOUT HEAT)20 AD3H3/PCWP-120 AD5H3/DCP-220 ADNH320 A20 A20 A20 A20 A

n 2 crouse hinds 43961-116-gr roof mounted, two head, aircraft warning light o 2 kim lighting cfl1-27l3kuv-bl led floodlight with adjustable barn door louvers (bd-cfl/bl), on stanchion mount (sm18bl), 8" above ground p 6 kim lighting gem1c-36l3k277-lg-ng-c performance bollard mount