PLUMBING GENERAL NOTES : PLUMBING FIXTURE SIZING SCHEDULE

Transcription

P-#PLUMBING FIXTURESANVENTCWP-1TANK TYPE WATER CLOSET3''2''1-1/4''P-1ATANK TYPE WATER CLOSET - ADA3''2''1-1/4''P-2COUNTER TOP LAVATORY - SENSOR - ADA1-1/2''1-1/2''1/2''P-3URINAL - SENSOR BATTERY2''1-1/2''3/4''P-3AURINAL - SENSOR BATTERY - ADA2''1-1/2''3/4''P-41 COMPARTMENT SINK - UNDERMOUNT - BREAK ROOM1-1/2''1-1/2''1/2''1/2''P-4A1 COMPARTMENT SINK - UNDERMOUNT - CONFERENCE ROOM 1011-1/2''1-1/2''1/2''1/2''P-5ELECTRIC WATER COOLER - 2 STATION - BOTTLE FILLER2''1-1/2''1/2''P-6COLD WATER CONNECTION BOXFD-1FLOOR DRAIN - TOILET ROOM - TRAP GUARD4''2''FD-2FLOOR DRAIN - MECHANICAL ROOM - TRAP GUARD3''1-1/2''RD-1ROOF DRAIN - 4"4''RD-2ROOF DRAIN - 6"6''ORD-1OVERFLOW ROOF DRAIN - 4"4''ORD-2OVERFLOW ROOF DRAIN - 6"6''OSD-1OVERFLOW SPOUT NOZZLE - 6"6"DBC-1DOWNSPOUT BOOT CONNECTOR - 6"6"DC-1DOWNSPOUT CONNECTOR - 6"6"MINIMUM 2'' SANITARY WASTE UNDERSLAB. ALL PIPING TO BE SIZED ACCORDINGTO CHART UNLESS OTHERWISE NOTED ON FLOOR PLANS.1/2''HW1/2''A. COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, GASOUTLETS, ETC., WITH ALL CASEWORK EQUIPMENT,MECHANICAL ROOM EQUIPMENT, ETC., PRIOR TO COMMENCINGINSTALLATION. WORK NOT SO COORDINATED SHALL BEREMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THECONTRACTOR.B. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THECOURSE OF THEIR WORK SO AS TO INSURE THAT THEY DO NOTINTERRUPT ANY EXISTING SERVICE. FOR SAFETY PURPOSES,PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVETO NATURAL GAS AND ELECTRICAL LINES. VERIFY THELOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OROVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED INACCORD WITH ALL FEDERAL, STATE AND/OR LOCAL RULES,REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.UTILITIES SHALL BE INSTALLED IN ACCORD WITH THEAPPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS.IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALLAPPLY.C. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTEROR GYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BERESPONSIBLE FOR REMOVAL AND REINSTALLATION (ORREPLACEMENT, IF DAMAGED) OF ALL CEILING OR TILE ANDGRID MEMBERS NECESSARY TO PERFORM HIS WORK. NEWTILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALLPATCHING WORK SHALL MATCH ADJACENT SURFACES.D. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROMTHE WORK OF OTHER TRADES, WHETHER EXISTING OR NEW.E. COORDINATE ALL WORK WITH PROJECT PHASINGREQUIREMENTS.F. PATCH, REPAIR AND PAINT OR PROVIDE WALL COVERING FOR(TO OWNER'S STANDARDS) EXISTING WALLS, CEILINGS, ETC.,THAT ARE TO REMAIN IF DAMAGED DURING CONSTRUCTION.REPAIRS SHALL MATCH ADJACENT SURFACES TO THESATISFACTION OF THE ARCHITECT AND OWNER.G. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONSTHAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.(CITY, COUNTY, LOCAL, FEDERAL, MUNICIPALITY, UTILITYCOMPANY, COMMONWEALTH OF KENTUCKY, ETC.)H. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING WORKDURING DEMOLITION. IF ITEMS ARE UNCOVERED DURINGDEMOLITION THEN FIELD VERIFY THE USE OF THE ITEMS ANDPLAN AN ALTERNATE ROUTE TO RUN THESE ITEMS. THENCONTACT THE ENGINEERS TO REVIEW THE ROUTING.I. IF AREA OF CONSTRUCTION HAS A POST TENSION FLOOR SLAB.CONTRACTOR SHALL USE ULTRA SOUND OR OTHER APPROVEDMETHODS TO SURVEY THE EXISTING FLOOR STRUCTUREBEFORE MAKING ANY AND ALL FLOOR PENETRATIONS.J. WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTUREALL EXISTING CONDUITS, WATER, HYDRONIC, STEAM, CHILLEDWATER, FIRE PROTECTION LINES, MED GAS, ETC. SHALL BELOWERED TO BE BELOW FULL THICKNESS OF FIRE PROOFINGWITH NO INTERFERENCE.K. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIESSHALL BE APPROPRIATELY FIRE STOPPED PER AN APPROVEDU.L. LISTED STANDARD. CONTRACTOR SHALL PAY PARTICULARATTENTION TO INSULATED PIPING PENETRATIONS.L. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THEBUILDING SHALL BE SCHEDULED 2 WEEKS IN ADVANCE, ANDSHALL COMPLY WITH INTERIM LIFE SAFETY MEASURES.M. ALL PIPING IN ROOMS WITH CEILINGS SHALL BE ABOVE CEILINGEXCEPT AS NOTED.N. IN ACCORDANCE WITH K.R.S. ALL PLUMBING WORK SHALL BECONSTRUCTED IN COMPLIANCE WITH PLANS APPROVED BYAND BEARING THE APPROVAL STAMP OF THE KENTUCKYDIVISION OF PLUMBING AND/OR THE DIVISION OF WATER. THECONTRACTOR SHALL NOT BEGIN WORK UNTIL HE HASRECEIVED SUCH APPROVED PLANS.O. LOCATIONS OF PIPING AND EQUIPMENT ARE APPROXIMATE ANDSUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. DO NOTSCALE THE DRAWINGS.P. ALL OFFSETS IN PIPING ARE NOT NECESSARILY SHOWN.PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.Q. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANYFEES OR OTHER COSTS THAT ANY UTILITY COMPANY MAYREQUIRE TO COMPLETE THEIR WORK. (GAS, SEWER, WATER,ETC.).R. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE INCONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THEENGINEERS BEFORE INSTALLATION. REFER ALSO TOARCHITECTURAL WALL INTERIOR AND EXTERIOR WALLELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OF THESEDOCUMENTS.S. DOUBLE WIDTH TURNING VANES SHALL BE INSTALLED IN ALLSUPPLY, RETURN, AND EXHAUST DUCTWORK ELBOWS.TURNING VANES NOT REQUIRED FOR KITCHEN EXHAUSTS.T. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTIONPRODUCING EQUIPMENT SHALL BE ISOLATED FROMSURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY ORSTRUCTURALLY DAMAGING INSTALLATIONS SHALL BESATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLINGCONTRACTOR'S EXPENSE. THE FINAL DECISION ON THESUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITYSHALL BE THAT OF THE ENGINEER.U. DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOREQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BETHE RESPONSIBILITY OF THE PURCHASER OF THATEQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE ADEVIATION, WHETHER APPROVED BY THE ENGINEERS OR NOT,SHALL BE THE RESPONSIBILITY OF THE PURCHASER.V. VALVES, BALANCING DAMPERS OR ANYMECHANICAL/ELECTRICAL ITEM REQUIRING ACCESS SHALL NOTBE LOCATED ABOVE A HARD CEILING. IF THIS IS NOT POSSIBLE,THEN AN APPROPRIATELY SIZED ACCESS DOOR SHALL BEPLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE ANDADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BELOCATED AN UNREASONABLE DISTANCE ABOVE THE CEILINGS.IN GENERAL ALL SUCH ITEMS UNLESS INDICATED OTHERWISESHALL BE MOUNTED SIX TO TWELVE INCHES ABOVE THECEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TOINSTALLING.W. ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUNDSTRUCTURES SHALL HAVE THE TOP ELEVATION SET FLUSHWITH FINISHED GRADE UNLESS SPECIFICALLY NOTEDOTHERWISE.X. WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR INTHE ZONE OF INFLUENCE THE PIPING SHALL BE BACKFILLEDWITH CEMENTITIOUS FLOWABLE FILL PER SPECIFICATIONS.WHENEVER POSSIBLE, LOCATE PIPING OUTSIDE OF THE ZONEOF INFLUENCE. THE ZONE OF INFLUENCE IS THE AREA UNDERTHE FOOTER WITHIN A 45 DEGREE ANGLE PROJECTING DOWNFROM THE BOTTOM EDGE OF THE FOOTER OF ALL SIDES OFTHE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BEHELD AWAY FROM BUILDING WALLS FAR ENOUGH TO BEOUTSIDE OF THE ZONE OF INFLUENCE.Y. WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITHTHE OWNER'S SAFETY POLICY REQUIREMENTS.Z. THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009IECC.AA. THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, ANDASHRAE 90.1-2007.AFFABOVE FINISHED FLOORPOINT OF CONNECTIONAFRABOVE FINISHED ROOFPIPE ELBOW TURNING UP/TURNING DOWNBFFBELOW FINISHED FLOORPIPE TEE TURNING UP/TURNING DOWNBFPBACK FLOW PREVENTERC.I.CAST IRONORLCOCLEAN OUTPDPUMPED DISCHARGE PIPINGCWDOMESTIC COLD WATERRLROOF LEADER PIPINGDNDOWNFPCMTA Office BuildingFIRE PROTECTION LINEOVERFLOW ROOF LEADER PIPINGLouisvilleKentuckyPlumbing LegendSANSANITARY WASTE PIPINGECOEXTERIOR CLEAN OUTSSSTORM SEWER PIPINGFFEFINISHED FLOOR ELEVATIONVTVENT PIPINGFPWHFREEZE PROOF WALL HYDRANTE(NAME)EXISTING PIPING (THIN LINE)HBHOSE BIBBDOMESTIC COLD WATER PIPINGHWDOMESTIC HOT WATERDOMESTIC HOT WATER SUPPLYHWRDOMESTIC RECIRCULATING HOT WATERDOMESTIC RECIRCULATING HOT WATERIAWIN ACCORDANCE WITHRevisionsCLEANOUT IN CEILING SPACECOIDINSIDE DIMENSIONFLOOR CLEANOUTCOIEINVERT ELEVATIONEXTERIOR CLEANOUTECOKwKILOWATTBALANCING VALVEMHMANHOLEBALL VALVENTSNOT TO SCALESAFETY RELIEF VALVENICNOT IN CONTRACTSAFETY RELIEF VALVENONORMALLY OPENOS&Y (GATE) VALVENCNORMALLY CLOSEDPRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)ODOUTSIDE DIMENSIONSTRAINEROFCIOWNER FURNISHED, CONTRACTOR INSTALLEDCHECK VALVEOFOIOWNER FURNISHED, OWNER INSTALLEDDOUBLE CHECK VALVE ASSEMBLYCFCICONTRACTOR FURNISHED, CONTRACTOR INSTALLEDPIPING UNIONPRICING SET NOT FORCONSTRUCTIONFSOROPEN RECEPTACLEFLOW SWITCHORLOVERFLOW ROOF LEADEROSDOVERFLOW SPOUT NOZZLETAMPER SWITCHPUMPED DISCHARGETHERMOMETERPSPRESSURE SWTICHTSPDPRVPRESSURE REDUCING VALVE (STEAM, WATER, OR GAS)VACUUM BREAKERPSIPOUNDS PER SQUARE INCHLIMITED AREA SPRINKLER HEADRLROOF LEADERPETE'S PLUGVSANSANITARY PIPINGDC-#DOWNSPOUT ONNECTOR DESIGNATORSRSANITARY RISERDBC-#DOWNSPOUT BOOT CONNECTOR DESIGNATORT&PTEMPERATURE & PRESSUREFD-#FLOOR DRAIN DESIGNATORSSSTORM SEWEROSD-#OVERFLOW ROOF DRAIN SPOUT NOZZLE DESIGNATORTBTHRUST BLOCKFD-#TETOP ELEVATIONORD-#OVERFLOW ROOF DRAIN DESIGNATORTPTRAP PRIMEROSD-#OVERFLOW ROOF DRAIN SPOUT NOZZLE DESIGNATORTYPTYPICALUONUNLESS OTHERWISE NOTEDVTRVENT THRU ROOFW/WITHRD-#XXP-#XFLOOR DRAIN DESIGNATORS2IROOF DRAIN DESIGNATORSTRUCTURAL SERVICES, INC.PLUMBING FIXTURE DESIGNATORPost Office Box 485Goshen, KY 40026(502) 292-2100www.structuralservices.comEQUIPMENT TAG DESIGNATORXTAGGED NOTE DESIGNATORXREVISION DESIGNATORTSTEMPERATURE SENSOR DESIGNATORHOSE BIB DESIGNATORIndianaKentucky3211 Grant Line Road Suite 30 819 West Main Street, Suite 400New Albany, Indiana 47150Louisville, Kentucky 40202[p] 812.944.2222[p] 502.581.0570[f] 812.944.1122[f] 502.581.0670A r c h i t e c t u r eD e s i g nP l a n n i n gPLUMBING FIXTURE SIZING SCHEDULESYMBOLS & ABBREVIATIONSA R C H I T E C T U R EPLUMBING GENERAL NOTES:Project NumberVCOB17DateJuly 27, 2017Sheet NumberP1.0

1"REFER TO FLOOR PLANFOR CONTINUATIONCMTA Office BuildingLouisville3THERMOMETER1"DPRECIRCULATING WATER PUMP DP-1BELL & GOSSETT MODEL NBF-22OR EQUAL. 2.5 GPM @ 13.5FT TDH, 120 V.PROVIDE W/ BELL & GOSSETTAQUASTAT MODEL AQ-1/2.11"EXPANSION TANKWATTS #PLT-54"WATER HEATERHEAT TRAP (TYP)WHALL-THREADROD1T&P RELIEF VALVEDRAIN LINE112" TALLDRAIN PAN1" DRAIN LINEPlumbing Details &ElevationsRevisionsUNION (TYP)WALLKentuckySYMBOLWH-1MANUFACTURER &MODELA.O. SMITHDEL 6 (OR EQUAL)TYPEELECTRIC, GLASSLINED TANKGALLONS STORAGE6VOLTS/PHASE/HERTZ208/3/60Kw3ASHRAE 90A -1980COMPLIANCEYESASME RATED/ULLISTEDYESSPILL T&P RELIEFAND DRAIN TO FLOORDRAIN.PRICING SET NOT FORCONSTRUCTIONWATER HEATER TO BE MOUNTEDON SHELF APPROXIMATELY 7'-0" A.F.F.SHELF SHALL BE CONSTRUCTED OF1/4"x21-1/2"x1-1/2" ANGLE IRON, FASTENEDTO WALL, AND SUPPORTED FROM STRUCTUREABOVE WITH ALL-THREAD ROD.WATER HEATER PIPING SCHEMATICNOT TO SCALE3.642" VT PIPE FROM FD-21 1/2" CW TO BUILDINGLOAD1" CW THROUGH WALL FORIRRIGATION PIPING ONNORTH WALLCHECK VALVE (TYP)2" BFP-1 DRAINBALL VALVE (TYP.)1" VALVED, CAPPED CHECK VALVEFOR HVAC MAKE-UP WATER.BALL VALVE WITH HOSE THREADS2"x4" INCREASER (TYP.)AIR GAPFINISHED FLOOR4" SAN. TO MAINBUILDING DRAIN1 1/2" BFP-1 EQUAL TO WATTS LF909FPWH (REFER TO SPECIFICATIONS)S2IDOWNSPOUT BOOT CONNECTOR (DBC-1)FLOOR DRAIN (FD-2)STRUCTURAL SERVICES, INC.Post Office Box 485Goshen, KY 40026(502) 292-2100www.structuralservices.com1 1 /4" CW OUT TO SITE, CAPPEDBEYOND SIDEWALK FOR IRRIGATIONSTORM PIPING BY CIVIL. REFER TO CIVILDRAWINGS FOR ACTUAL DRAIN LOCATIONAND MORE INFORMATION.1 1/2" DOMESTIC WATER SERVICEIndianaKentucky3211 Grant Line Road Suite 30 819 West Main Street, Suite 400New Albany, Indiana 47150Louisville, Kentucky 40202[p] 812.944.2222[p] 502.581.0570[f] 812.944.1122[f] 502.581.0670A r c h i t e c t u r eD e s i g nP l a n n i n gA R C H I T E C T U R EMechanical Room Domestic Water ServiceEntry11/4" 1'-0"Project NumberVCOB17DateJuly 27, 2017Sheet NumberP1.1

SCMTA Office BuildingWDELPHINIUM STREETP.B. 53, PG. 450' R/WLouisvilleSite Plan - PlumbingWATAGGED NOTESTBCDEFGHP24 TERMINATE 2" PD PIPE TO GRADE.P25 REFER TO SHEET P2.1 FOR PIPING CONTINUATION.P33 3/4" CW CAPPED BELOW GRADE. REFER TO SITE DRAWINGSON SHEET P2.0 FOR MORE INFORMATION. COORDINATE EXACTLOCATION AND BURY DEPTH WITH PLANTER AND IRRIGATIONCONTRACTOR.P36 1 1/4" CW CAPPED BELOW GRADE. COORDINATE EXACTLOCATION AND BURY DEPTH WITH IRRIGATION CONTRACTORAND SIDEWALK.P37 3/4" CW UP IN WALL TO FIXTURES.P38 REFER TO SHEET FP2.1 FOR PIPING CONTINUATION.P39 REFER TO SHEET P2.2 FOR PIPING CONTINUATION.P60 PROVIDE DOWNSPOUT BOOT CONNECTION (DBC-1), TO BEMINIMUM 24", CAST IRON, MANUFACTURED BY ZURN, NEENAHOR EQUIVALENT. CONNECTION TO DOWNSPOUT SHALL BEUNGROUTED. COORDINATE EXACT SIZE AND LOCATION WITHDOWNSPOUT AND DOWNSPOUT CONTRACTOR.E.2W1P33P33P39 P37P37 P39WRevisionsPRICING SET NOT FORCONSTRUCTIONFFE - 688.001P1.12Kentucky571ANORTON COMMONSSECTION B, PHASE 5P.B. 52, PG. 233FFE - 688.00ECO8" SSP25I.E.3' 8" B.F.F.MASTERCRA FT TH IEN EMAN HOMESLLC D.B. 10838, PG. 385DNP38P394P604" FS1 1/2" CWP60P601 1/4" CWP36WEXISTING SANITARYCONNECTION.I.E. - 678.90 (9' 1-3/16" B.F.F.)WP25P274" SASTP24I.E.4' 0" B.F.F.NS2IECOECOSTRUCTURAL SERVICES, INC.FFE - 688.00Post Office Box 485Goshen, KY 40026(502) 292-2100www.structuralservices.comS584/WR'05 4.GYPAW 53,IC .B.VCI PSIndianaKentucky3211 Grant Line Road Suite 30 819 West Main Street, Suite 400New Albany, Indiana 47150Louisville, Kentucky 40202[p] 812.944.2222[p] 502.581.0570[f] 812.944.1122[f] 502.581.0670A r c h i t e c t u r eD e s i g nP l a n n i n gA R C H I T E C T U R EWProject NumberVCOB17576DateJuly 27, 20171Plumbing & Fire Protection - Site1/8" 1'-0"Sheet NumberP2.0

CMTA Office BuildingTAGGED 12" SAN UP.2" VT UP.2" CW UP.REFER TO SITE DRAWINGS ON SHEET P2.0 FORCONTINUATION OF PIPING.2" PD PIPE DOWN TO ELEVATOR SUMP PUMP. COORDINATEEXACT LOCATION WITH STRUCTURAL MEMBERS ANDELECTRICAL CONTRACTOR.4" SAN UP.2" PD UP.1 1/4" CW OUT TO IRRIGATION PIPING. CAP PIPE BEYONDSIDEWALK FOR IRRIGATION CONTRACTROR. REFER TO SITEPIPING DRAWINGS ON SHEET P2.0 FOR MORE INFORMATION.3/4" CW CAPPED BELOW GRADE. REFER TO SITE DRAWINGSON SHEET P2.0 FOR MORE INFORMATION. COORDINATE EXACTLOCATION AND BURY DEPTH WITH PLANTER AND IRRIGATIONCONTRACTOR.1 1/4"

plumbing fixture sizing schedule plumbing fixture counter top lavatory - sensor - ada to chart unless otherwise noted on floor plans. minimum 2'' sanitary waste underslab. all piping to be sized according 1 compartment sink - undermount - break room p-2 p-4 tank type water closet urinal - sensor battery - ada urinal - sensor battery p-1a p-3a p .