VANTRAN SECTION 16 WACO, TEXAS PADMOUNTED

Transcription

VANTRANPAGE 2PADMOUNTED TRANSFORMERSONAN65 C RISEVANPAD I – 125KV-BIL & BELOWBSINGLE PHASESECTION 16WACO, TEXAS60 HZ7-19-12C*N.P.H1X1X3H2X2ASIDE VIEW*DIM ENSIONS INCLUDE COOLERSFRONT VIEW - DOORS REMOVEDWEIGHTS & DIMENSIONSRECOM MENDED MINIMUM PAD SIZE3" TRANSFORMER BASEBASE *51*58*661½"BASE DIMENSIONSETRANSFORMERS CONFORM TO NEMA & ANSISTANDARDS WHERE 4242333340171717105105180TRANSFORMER TESTS PER ANSI C57.12.90ADD 10” TO OVERALL HEIGHT FOR BAYONET FUSES.TRANSFORMERS SUPPLIED WITH STANDARDDISTRIBUTION ACCESSORIES PER ANSI C57.12.REFER TO FACTORY FOR SPECIAL FEATURES.DEAD FRONT SAME DIMENSIONS

VANTRANWACO, TEXASPAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDSINGLE PHASEONAN65 C RISE60 HZSECTION 16PAGE 37-19-12STANDARD ACCESSORIES1. TAMPERPROOF, REMOVABLE, BOLTED-ON CABINET WITH OPEN BOTTOM, REMOVABLELIFTOFF DOORS, STAINLESS STEEL HINGES AND THREE POINT LATCHING MECHANISM.DOORS DESIGNED TO PREVENT ACCESS TO HV COMPARTMENT UNTIL LV COMPARTMENTDOOR IS OPENED.PROVISIONS FOR PADLOCKING ON LV COMPARTMENT DOOR.CAPTIVEPENTA HEAD COMPARTMENT DOOR LOCKING BOLT PROVIDED.2. REMOVABLE COVER (TAMPERPROOF)3. WELDED ON COVER4. BOLTED ON INSPECTION PLATE5. LIFTING LUGS (4EA. REQUIRED)6. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE7. STEEL BARRIER BETWEEN HV & LV COMPARTMENTS8. TWO EACH LV BUSHINGS WITH NEMA 4 HOLE SPADE TERMINALS9. ONE EACH NEUTRAL BUSHING WITH NEMA 4 HOLE SPADE TERMINAL AND REMOVABLEGROUND STRAP (½” – 13 TAP GROUND BOSS)10. TWO EACH HIGH VOLTAGE BUSHINGS WITH EYEBOLT TERMINALS11. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION12. TANK GROUND BOSSES (½” – 13 TAPS) (EACH COMPARTMENT)13. TRANSFORMER BASE WITH PROVISIONS FOR ROLLING14. AUTOMATIC PRESSURE RELIEF VALVE15. DRAIN PLUG16. FILLER PLUG17. EXTERNALLY OPERATED NO-LOAD TAPCHANGER18. PROVISIONS FOR MOUNTING SURGE ARRESTERS19. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN

SECTION 16VANTRANWACO, TEXASLOW PROFILE PAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDSINGLE PHASEOISC65 C RISE60 HZ41761216PAGE 47-19-126185½"X3X395"H1B 29" R7"X124"X1H1A5"13X21115X211"8½"H25"10"12"4"FRONT VIEW WITH LID REMOVED8ARBITRARY POINTRECOMMENDED MINIMUM PAD SIZE3" TRANSFORMER BASE12.5 34"19"H1924"31½"14¾"CONDUIT CABLE OPENING16"16"19"35"ROUTINE TESTS PER ANSI C57.12.90KVAT.W.GAL MERS SUPPLIED WITHSTANDARD ACCESSORIES PERANSI C57.12.25 REFER TO FACTORY FORSPECIAL FEATURES

VANTRANWACO, TEXASLOW PROFILE PAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDSINGLE PHASEOISC65 C RISE60 HZSECTION 16PAGE 57-19-1215 KV & BELOWSTANDARD ACCESSORIES1. TWO EACH DEAD FRONT LOADBREAK SAFETY PLUG HIGH VOLTAGE BUSHINGS OR BUSHINGWELLS AS REQUIRED2. THREE EACH 5/8” EPOXY STUD LOW VOLTAGE BUSHINGS (EXTERNALLY MOUNTED)3. LOW VOLTAGE NEUTRAL STUD GROUNDED TO TANK WITH DETACHABLE STRAP4. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE5. TANK GROUND BOSS (½” – 13 TAP)6. HINGED FRONT COVER SUITABLE FOR REMOVING IN OPEN POSITION7. BOTTOM OPEN FOR CONDUIT CABLE ENTRANCE8. REMOVABLE FRONT SILL9. LIFTING LUGS REMOVABLE10. FRONT COMPARTMENT LIFTING HANDLE (RECESSED) PROVISION FOR PADLOCKING (7/16”PADLOCK)11. ½” DRAIN PLUG12. ONE INCH FILLING PLUG13. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN14. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION15. 2” ACCESS HOLE WITH COVER IN SIDE OF SILL16. AUTOMATIC PRESSURE RELIEF VALVE17. LOADBREAK EXTERNALLY REMOVABLE BAYONET FUSE ASSEMBLY WITH INTERNAL FAULTSENSING ISOLATION LINK18. HIGH VOLTAGE FUSE OIL DRIP SHIELD19. HIGH VOLTAGE PARKING STAND

SECTION 16VANTRANWACO, TEXASLOW PROFILE PAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDSINGLE PHASEOISC65 C RISE60 HZ41761216PAGE 67-19-12618199"9X3X36"H1B 29" R7"30"X1H1AX16"13X211X21511"9"H25"10"FRONT VIEW WITH LID REMOVED12"4"8ARBITRARY POINTRECOMMENDED MINIMUM PAD SIZE3" TRANSFORMER BASE12.5 H19C30"AD14¾"CONDUIT CABLE OPENING16"16"ABROUTINE TESTS PER ANSI C57.12.90KVAT.W.GAL FORMERS SUPPLIED WITHSTANDARD ACCESSORIES PERANSI C57.12.25 REFER TO FACTORYFOR SPECIAL FEATURES

VANTRANWACO, TEXASLOW PROFILE PAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDSINGLE PHASEOISC65 C RISE60 HZSECTION 16PAGE 77-19-1215 KV & BELOWSTANDARD ACCESSORIES1. TWO EACH DEAD FRONT LOADBREAK SAFETY PLUG HIGH VOLTAGE BUSHINGS OR BUSHINGWELLS AS REQUIRED2. THREE EACH 1” EPOXY STUD LOW VOLTAGE BUSHINGS (EXTERNALLY MOUNTED)3. LOW VOLTAGE NEUTRAL STUD GROUNDED TO TANK WITH DETACHABLE STRAP4. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE5. TANK GROUND BOSS (½” – 13 TAP)6. HINGED FRONT COVER SUITABLE FOR REMOVING IN OPEN POSITION7. BOTTOM OPEN FOR CONDUIT CABLE ENTRANCE8. REMOVABLE FRONT SILL9. LIFTING LUGS REMOVABLE10. FRONT COMPARTMENT LIFTING HANDLE (RECESSED) PROVISION FOR PADLOCKING (7/16”PADLOCK)11. ½” DRAIN PLUG12. ONE INCH FILLING PLUG13. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN14. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION15. 2” ACCESS HOLE WITH COVER IN SIDE OF SILL16. AUTOMATIC PRESSURE RELIEF VALVE17. LOADBREAK EXTERNALLY REMOVABLE BAYONET FUSE ASSEMBLY WITH INTERNAL FAULTSENSING ISOLATION LINK18. HIGH VOLTAGE FUSE OIL DRIP SHIELD19. COOLING FINS (167 KVA ONLY)20. HIGH VOLTAGE PARKING STAND

VANTRANTHREE PHASEPADMOUNTED TRANSFORMERSOISC65 C RISEVANPAD III – 125KV-BIL & BELOWBH2SECTION 18PAGE 260 HZ7-19-12CX3X1H1WACO, TEXASH3XOX2AFRONT VIEW - DOORS REMOVEDRECOM MENDED MINIMUM PAD SIZEKVA304575112½1503" TRANSFORMER BASEWEIGHTS & 13042260012542B5757575757BASE DIMENSIONSDFCONDUITCABLEOPENING1½"ETRANSFORMERS CONFORM TO NEMA & ANSISTANDARDS WHERE APPLICABLE.TRANSFORMER TESTS PER ANSI C57.12.90ADD 10” TO OVERALL HEIGHT FOR BAYONET FUSES.TRANSFORMERS SUPPLIED WITH STANDARDDISTRIBUTION ACCESSORIES PER ANSI C57.12.26REFER TO FACTORY FOR SPECIAL FEATURES.LIVE FRONT SAME DIMENSIONSKVA304575112½150C3737394141BASE DIMENSIONSDE34503450365038503850F1818181818

VANTRANWACO, TEXASPAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDTHREE PHASEOISC65 C RISE60 HZSECTION 18PAGE 37-19-12VANPAD III – 125KV-BIL & BELOWSTANDARD ACCESSORIES1. FOUR LIFTING HOOKS2. PER ASTM D-3487 TYPE II MINERAL OIL FILLED WITH LESS THAN 1 P.P.M. OF P.C.B. AT TIME OFMANUFACTURE3. JACKING PADS4. ONE INCH DRAIN VALVE5. TANK GROUNDING PADS (½” – 13 TAP) (EACH COMPARTMENT)6. TRANSFORMER BASE DESIGNED FOR ROLLING7. THREE LOW VOLTAGE BUSHINGS WITH NEMA 4 HOLE SPADE TERMINALS8. ONE LV NEUTRAL BUSHING WITH NEMA 4 HOLE SPADE TERMINAL AND EXTERNALGROUNDING STRAP ( IF LOW VOLTAGE IS “Y” OR W/CENTER TAP)9. NEUTRAL GROUND PAD (½” – 13 TAP)10. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE11. TAMPERPROOF, REMOVABLE, BOLTED ON CABINET WITH OPEN BOTTOM. REMOVABLE LIFTOFF DOORS, STAINLESS STEEL HINGES AND THREE POINT LATCHING MECHANISM. DOORSDESIGNED TO PREVENT ACCESS TO HV COMPARTMENT UNTIL LV COMPARTMENT DOOR ISOPENED. PROVISIONS FOR PADLOCKING ON LV COMPARTMENT DOOR. CAPTIVE PENTAHEAD COMPARTMENT DOOR LOCKING BOLT PROVIDED12. THREE EACH DEAD FRONT HIGH VOLTAGE BUSHING WELLS ARRANGED FOR RADIAL FEEDWITH PARKING STANDS13. FULL LENGTH STEEL BARRIER BETWEEN HIGH VOLTAGE AND LOW VOLTAGECOMPARTMENTS14. TAMPERPROOF, REMOVABLE COVER FOR ACCESS TO INSPECTION PLATE15. TANK COVER WELDED ON16. ONE INCH FILLING PLUG17. BOLTED ON INSPECTION PLATE18. AUTOMATIC PRESSURE RELIEF VALVE19. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION20. EXTERNAL NO-LOAD TAPCHANGER21. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN

VANTRANTHREE PHASEPADMOUNTED TRANSFORMERSOISC65 C RISEVANPAD III – 125KV-BIL & BELOWBH2SECTION 18PAGE 460 HZ7-19-12C*X3X1H1WACO, TEXASH3XOX2ASIDE VIEWFRONT VIEW - DOORS REMOVED*DIM ENSIONS INCLUDE COOLERSRECOM MENDED MINIMUM PAD SIZE3" TRANSFORMER BASEBASE DIMENSIONSDFCONDUITCABLEOPENINGWEIGHTS & 08250002400084082ABOVE 5000 KVA REFER TO FACTORYB6464646567738282829298BASE 3000*9156703750*9160805000*996286ABOVE 5000 KVA REFER TO FACTORYF18182020202020222224241½"ETRANSFORMERS CONFORM TO NEMA & ANSISTANDARDS WHERE APPLICABLE.TRANSFORMER TESTS PER ANSI C57.12.90ADD 10” TO OVERALL HEIGHT FOR BAYONET FUSES.TRANSFORMERS SUPPLIED WITH STANDARDDISTRIBUTION ACCESSORIES PER ANSI C57.12.26REFER TO FACTORY FOR SPECIAL FEATURES.LIVE FRONT SAME DIMENSIONS

VANTRANWACO, TEXASPAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDTHREE PHASEOISC65 C RISE60 HZSECTION 18PAGE 57-19-12VANPAD III – 125KV-BIL & BELOWSTANDARD ACCESSORIES1. FOUR LIFTING HOOKS2. PER ASTM D-3487 TYPE II MINERAL OIL FILLED WITH LESS THAN 1 P.P.M. OF P.C.B. AT TIME OFMANUFACTURE3. JACKING PADS4. ONE INCH DRAIN VALVE5. TANK GROUNDING PADS (½” – 13 TAP) (EACH COMPARTMENT)6. THREE LOW VOLTAGE BUSHINGS WITH NEMA 4 OR 6 HOLE SPADE TERMINALS7. ONE LV NEUTRAL BUSHING WITH NEMA 4 OR 6 HOLE SPADE TERMINAL AND EXTERNALGROUNDING STRAP ( IF LOW VOLTAGE IS “Y” OR W/CENTER TAP)8. NEUTRAL GROUND PAD (½” – 13 TAP)9. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE10. FULL LENGTH STEEL BARRIER BETWEEN HIGH VOLTAGE AND LOW VOLTAGECOMPARTMENTS11. THREE EACH DEAD FRONT HIGH VOLTAGE BUSHING WELLS ARRANGED FOR RADIAL FEEDWITH PARKING STANDS12. TAMPERPROOF, REMOVABLE, BOLTED ON CABINET WITH OPEN BOTTOM. REMOVABLE LIFTOFF DOORS, STAINLESS STEEL HINGES AND THREE POINT LATCHING MECHANISM. DOORSDESIGNED TO PREVENT ACCESS TO HV COMPARTMENT UNTIL LV COMPARTMENT DOOR ISOPENED. PROVISIONS FOR PADLOCKING ON LV COMPARTMENT DOOR. CAPTIVE PENTAHEAD COMPARTMENT DOOR LOCKING BOLT PROVIDED13. TAMPERPROOF, REMOVABLE COVER FOR ACCESS TO INSPECTION PLATE14. TRANSFORMER BASE DESIGNED FOR ROLLING15. TANK COVER WELDED ON16. ONE INCH FILLING PLUG17. BOLTED ON INSPECTION UNDER COVER PLATE18. AUTOMATIC PRESSURE RELIEF DEVICE19. RADIATORS (FLEXOPLATE) (AS REQUIRED)20. EXTERNAL NO-LOAD TAPCHANGER PADLOCKABLE IN ANY POSITION21. OIL LEVEL GAUGE (750 KVA AND LARGER)22. PROVISIONS FOR DIAL TYPE THERMOMETER (750 KVA AND LARGER)23. PROVISIONS FOR PRESSURE VACUUM GAUGE (750 KVA AND LARGER)24. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION25. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN

VANTRANTHREE PHASEWACO, TEXASPADMOUNTED TRANSFORMERSOISC65 C RISEVANPAD III – 125KV-BIL & BELOWBSECTION 18PAGE 660 HZ7-19-12C*ASIDE VIEW*DIM ENSIONS INCLUDE COOLERSFRONT VIEW - DOORS REMOVEDRECOM MENDED MINIMUM PAD SIZE3" TRANSFORMER BASEBASE DIMENSIONSDFCONDUITCABLEOPENING1½"ETRANSFORMERS CONFORM TO NEMA & ANSISTANDARDS WHERE APPLICABLE.TRANSFORMER TESTS PER ANSI C57.12.90ADD 10” TO OVERALL HEIGHT FOR BAYONET FUSES.TRANSFORMERS SUPPLIED WITH STANDARDDISTRIBUTION ACCESSORIES PER ANSI C57.12.26REFER TO FACTORY FOR SPECIAL FEATURES.LIVE FRONT SAME DIMENSIONSWEIGHTS & 50200007508250002400084082ABOVE 5000 KVA REFER TO FACTORYBASE 156703750*9160805000*996286ABOVE 5000 KVA REFER TO 81818202020202022222424

VANTRANWACO, TEXASPAD MOUNTED TRANSFORMERS – MINERAL OIL FILLEDTHREE PHASEOISC65 C RISE60 HZSECTION 18PAGE 77-19-12VANPAD III – 125KV-BIL & BELOWSTANDARD ACCESSORIES1. FOUR LIFTING HOOKS2. PER ASTM D-3487 TYPE II MINERAL OIL FILLED WITH LESS THAN 1 P.P.M. OF P.C.B. AT TIME OFMANUFACTURE3. JACKING PADS4. ONE INCH DRAIN VALVE5. TANK GROUNDING PADS (½” – 13 TAP) (EACH COMPARTMENT)6. THREE LOW VOLTAGE BUSHINGS WITH NEMA 4 OR 6 HOLE SPADE TERMINALS7. ONE LV NEUTRAL BUSHING WITH NEMA 4 OR 6 HOLE SPADE TERMINAL AND EXTERNALGROUNDING STRAP ( IF LOW VOLTAGE IS “Y” OR W/CENTER TAP)8. NEUTRAL GROUND PAD (½” – 13 TAP)9. DIAGRAMMATIC CORROSION RESISTANT NAMEPLATE10. FULL LENGTH STEEL BARRIER BETWEEN HIGH VOLTAGE AND LOW VOLTAGECOMPARTMENTS11. SIX EACH DEAD FRONT HIGH VOLTAGE BUSHING WELLS ARRANGED FOR LOOP FEED WITHPARKING STANDS12. TAMPERPROOF, REMOVABLE, BOLTED ON CABINET WITH OPEN BOTTOM. REMOVABLE LIFTOFF DOORS, STAINLESS STEEL HINGES AND THREE POINT LATCHING MECHANISM. DOORSDESIGNED TO PREVENT ACCESS TO HV COMPARTMENT UNTIL LV COMPARTMENT DOOR ISOPENED. PROVISIONS FOR PADLOCKING ON LV COMPARTMENT DOOR. CAPTIVE PENTAHEAD COMPARTMENT DOOR LOCKING BOLT PROVIDED13. TAMPERPROOF, REMOVABLE COVER FOR ACCESS TO INSPECTION PLATE14. TRANSFORMER BASE DESIGNED FOR ROLLING15. TANK COVER WELDED ON16. ONE INCH FILLING PLUG17. BOLTED ON INSPECTION UNDER COVER PLATE18. AUTOMATIC PRESSURE RELIEF DEVICE19. RADIATORS (FLEXOPLATE) (AS REQUIRED)20. EXTERNAL NO-LOAD TAPCHANGER PADLOCKABLE IN ANY POSITION21. OIL LEVEL GAUGE (750 KVA AND LARGER)22. PROVISIONS FOR DIAL TYPE THERMOMETER (750 KVA AND LARGER)23. PROVISIONS FOR PRESSURE VACUUM GAUGE (750 KVA AND LARGER)24. BOTTOM OF TRANSFORMER UNDERCOATED TO PREVENT CORROSION25. PAINT COLOR MUNSELL 7.0 GY 3.29/1.5 BELL GREEN

routine tests per ansi c57.12.90 kva t.w. gal oil transformers supplied with standard accessories per ansi c57.12.25 refer to factory for special features 15 800 57 25 825 55 37½ 900 53 50 1000 51 75 1100 49 6 6 9 12 15 16 conduit cable opening 3" transformer base recommended minimum pad si