Application Guide to CA Title 24A S U P P L E M E N TA L G U I D E TO C O D E R E V I S I O N S I M PAC T I N G L I G H T I N G C O N T R O L

Hubbell Lighting’s Commitment to the CA Title 24 ChallengeHubbell Lightingunderstands the challenge of code compliance and is here to lessen this burden onend-users. As of January 2017, California’s latest Building Energy Efficiency Standards (CA Title 24) went intoeffect. These revised standards improve energy efficiency in non-residential buildings. However, with a goalof Net Zero Energy in non-residential buildings by 2030, navigating the updated lighting code can be timeconsuming and confusing.By breaking down the latest changes to the CA Title 24 by application space, Hubbell Lighting is able tosimplify the complexities of code compliance. On the following pages you will find product solutions for eachcontrols type based on application space and code requirements. These controls solutions range from themost basic solutions to the most advanced. The guidelines are focused on recent code revisions and are notintended to replace the complete CA Title 24 document.The Hubbell AdvantageFor over 128 years Hubbell Lighting has continued to make the ordinary extraordinary as one of the largestlighting fixture manufacturers in North America. Serving a multitude of markets Hubbell Lighting aims to provideinnovative solutions that provide performance, quality, and ease of use regardless of the application. Supportedby a prestigious portfolio of brand names Hubbell Lighting has a full range of indoor and outdoor lightingproducts that supply solutions to commercial, industrial, institutional, and residential markets.TABLE OF CONTENTSONE COMPANY DISTINCT BRANDSAlera Lighting4Hubbell’s Core Capabilities6Classroom / Lecture Hall / Training Room8Conference / Meeting / Multi-Purpose Room10Office 250 Sq. Ft.12Office 250 Sq. Ft.14Corridor16Restroom18Stairwell20Storage Room22NX Distributed Intelligence24CX Commercial Lighting System25Occupancy Sensors26GlossaryArchitectural Area LightingBeacon ProductsColumbia LightingCompassDual-LiteHubbell Control SolutionsHealthcare SolutionsHubbell Industrial LightingHubbell Outdoor LightingKim LightingKurt VersenLitecontrolPrescoliteWhiteway

Hubbell Lighting Core Capabilities - Complete SolutionsStay on the leading edge of technology by selecting from Hubbell Lighting’s portfolioof solid-state lighting products.Complete SolutionsFrom beautiful commercial environments to complex industrial applications, Hubbell Lighting provides highperformance solutions across virtually every industry application.Outdoor SiteCanopyWallRecessedReducing MaintenanceEnergy savings is only part of the story.Solid-state LED solutions from HubbellLighting last up to 3 times longer than MetalHalide or Fluorescent sources and up to 60times longer than incandescent sources,dramatically reducing maintenance costs.IndustrialParking GaragePost TopHubbell Lighting ControlsHaving lights on only when needed, helps in reducing utility costs for energy savings and sustainability objectives.Easy installation, intuitive interfaces and web-based commissioning and monitoring make Hubbell Control Solutions(HCS) the logical choice for lighting control.Energy SavingsHubbell Lighting has broken the technology barriers to create cost effective, high performance LED luminaires thatcan save up to 70% in applications, replacing less efficient technologies such as HID or 1000400-Watt Metal Halide4HUBBELL LIGHTINGFluorescent T5 HOLEDREQUIRED RELAMPSvs. LED1,00060Compact Fluorescent10,0006Metal Halide20,0003Linear Fluorescent20,0003LED60,0000IncandescentControl In ApplicationHubbell LED solutions provide instant restrike performance, that when combinedwith factory integrated HCS, reduce energy usage by as much as 80% inapplication. It’s another innovative way we help meet fast evolving codes.Easy Install, Easy MaintenanceHubbell LED luminaires are designed withinstallation and ease of maintenance inmind. Our products offer simple accessto electrical components that will reduceinstallation time and costs while makingmaintenance quick and efficient.DownlightingLIFE IN HOURSLAMP TYPEElectronic TrackingIn the fast evolving LED space, componentperformance upgrades are ongoing. Toprovide best-in-class field support, we’reintegrating electronic tagging technologyacross our product lines, giving us a recordof all the spec details of your luminaire. Yearsafter installation a quick scan will reveal all ofthe critical specification details our teams willneed to provide superior service and support.Environmentally FriendlyWith no mercury, unlike HID or fluorescenttechnologies, Hubbell Lighting LED luminaries requireno lamp recycling and dramatically reduce CO2emissions when replacing legacy technologies.Rebate Program ApprovedUtility rebate programs, where available, usually requireproducts to be Design Lights Consortium (DLC) or ENERGYSTAR qualified. Hubbell Lighting maintains an extensivecollections of DLC and ENERGY STAR qualified productsavailable to reduce project costs and quicken payback.For a complete listing, visit change

Classroom / Lecture Hall / Training RoomHUBBELL CONTROL SOLUTIONSCodeProvisionMinimumControl TypeRequirementBasic (Choice of)IntermediateAdvanced NX Room Control CX Panel Controls NX Distributed System(Choice of)130.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor DLC7 Daylighting Harvesting Sensor NX Room Control CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. NX Room Control CX Panel Controls NX Distributed SystemON/OFF CONTROLS130.1(b)LIGHT LEVELCONTROLADDITIONALCONTROL130.1(e)NOTE: Areas where no change has been made:On/Off ControlProgrammable Timeclock, Vacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlReceptacle Control6HUBBELL LIGHTINGHUBBELL LIGHTING7

Conference / Meeting / Multi-Purpose RoomHUBBELL CONTROL SOLUTIONSCodeProvisionMinimumControl TypeBasic (Choice of)Intermediate(Choice of)Advanced130.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. NX Room Control CX Panel Controls NX Distributed SystemReceptacle ControlAutomatically turn OFF at least 50% ofthe receptacles in the space. This caneither be achieved by switching everyalternate receptacle within 6 feed or eachuncontrolled receptacle or 50% of theoutlets in each receptacle. NX Room Control CX Panel Controls NX Distributed SystemON/OFF CONTROLS130.1(b)LIGHT 0.5(d)NOTE: Areas where no change has been made:On/Off ControlProgrammable Timeclock, Vacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlN/A8HUBBELL LIGHTINGHUBBELL LIGHTING9

Office 250 Sq. Ft.HUBBELL CONTROL SOLUTIONSCodeProvisionMinimumControl TypeBasic (Choice of)Intermediate(Choice of)Advanced130.1(a)Local switchReadily accessible device(s) to controllighting within an enclosed space. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch LightHAWK2 Wall Switch Sensor NX Room Control CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. NX Room Control CX Panel Controls NX Distributed SystemReceptacle ControlAutomatically turn OFF at least 50% ofthe receptacles in the space. This caneither be achieved by switching everyalternate receptacle within 6 feed or eachuncontrolled receptacle or 50% of theoutlets in each receptacle. NX Room Control CX Panel Controls NX Distributed SystemON/OFF CONTROLS130.1(b)LIGHT 0.5(d)NOTE: Areas where no change has been made:On/Off ControlProgrammable Timeclock, Vacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlN/A10HUBBELL LIGHTINGHUBBELL LIGHTING11

Office 250 Sq. Ft.HUBBELL CONTROL SOLUTIONSCodeProvisionReadily accessible device(s) to controllighting within an enclosed space.130.1(c)1ProgrammableTimeclockScheduled time-of-day operated control thatturns lighting off at specified times whentypically unoccupied. Occupancy sensorsor other building system signals that turn Offlights during vacancy also comply. Maximum2 hour manual override.130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less.Basic (Choice of)(Choice of)Advanced NX Distributed System NX Room Control CX Panel Controls NX Distributed System OMNI Ceiling Sensor & OverrideSwitch NX Room Control CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. OMNI Ceiling Sensor & OverrideSwitch NX Room Control CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch NX Room Control CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch NX Room Control CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. NX Room Control CX Panel Controls NX Distributed SystemReceptacle ControlAutomatically turn OFF at least 50% ofthe receptacles in the space. This caneither be achieved by switching everyalternate receptacle within 6 feed or eachuncontrolled receptacle or 50% of theoutlets in each receptacle. NX Room Control CX Panel Controls NX Distributed SystemLIGHT LEVELCONTROL130.1(e)CONTROL130.5(d) OMNI Ceiling Sensor & OverrideSwitchIntermediate NX Room Control CX Panel Controls130.1(b)ADDITIONALRequirementLocal switch130.1(a)ON/OFF CONTROLSMinimumControl TypeNOTE: Areas where no change has been made:On/Off ControlVacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlN/A12HUBBELL LIGHTINGHUBBELL LIGHTING13

CorridorHUBBELL CONTROL SOLUTIONSCodeProvision130.1(a)MinimumControl TypeLocal switchRequirementMay use a manual control not accessible tounauthorized personnelON/OFF CONTROLSBasic (Choice of)IntermediateAdvanced OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System TD300 Wall Switch Timer Switch CX Panel Controls NX Distributed SystemAutomatic PartialOFFAutomatically reduces lighting power in anyone controlled zone by at least 50% aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch TD300 Wall Switch Timer CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. CX Panel Controls NX Distributed System130.1(c)5130.1(b)LIGHT LEVELCONTROLADDITIONALCONTROL130.1(e)NOTE: Areas where no change has been made:On/Off ControlVacancy Sensor (Manual On - Auto Off): Automatic Full OffLight Level ControlN/AAdditional ControlReceptacle Control14HUBBELL LIGHTINGHUBBELL LIGHTING15

RestroomHUBBELL CONTROL SOLUTIONSCodeProvisionBasic (Choice of)IntermediateAdvancedMay use a manual control not accessible tounauthorized personnel OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.1(c)1ProgrammableTimeclockScheduled time-of-day operated control thatturns lighting off at specified times whentypically unoccupied. Occupancy sensors orother building system signals that turn OFFlights during vacancy also comply. Maximum2 hour manual override. TD300 Wall Switch Timer Switch CX Panel Controls NX Distributed System130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.1(b)Multi-level lightingcontrolsShall have at least one control step between30-70 percent of full rated power. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch TD300 Wall Switch Timer CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. CX Panel Controls NX Distributed SystemLIGHT LEVELCONTROLRequirementLocal switch130.1(a)ON/OFF CONTROLSMinimumControl TypeADDITIONALCONTROL130.1(e)NOTE: Areas where no change has been made:On/Off ControlVacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlReceptacle Control16HUBBELL LIGHTINGHUBBELL LIGHTING17

StairwellHUBBELL CONTROL SOLUTIONSCodeProvisionMinimumControl TypeRequirementBasic (Choice of)IntermediateAdvanced130.1(a)Local switchMay use a manual control not accessible tounauthorized personnel. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed System130.1(c)6 & 7Automatic PartialOffAutomatically reduces lighting power in anyone controlled zone by at least 50% aftervacancy of 30 minutes or less. OMNI Ceiling Sensor & OverrideSwitch CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. WASP2 Sensor CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. WASP2 Sensor CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. OMNI Ceiling Sensor & OverrideSwitch WASP2 Sensor CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. CX Panel Controls NX Distributed SystemON/OFF CONTROLS130.1(b)LIGHT LEVELCONTROLADDITIONALCONTROL130.1(e)NOTE: Areas where no change has been made:On/Off ControlVacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlReceptacle Control18HUBBELL LIGHTINGHUBBELL LIGHTING19

Storage RoomHUBBELL CONTROL SOLUTIONSCodeProvisionRequirementBasic (Choice of)IntermediateAdvancedLocal switchReadily accessible device(s) to controllighting within an enclosed space. LightHAWK2 Wall Switch Sensor TD300 Wall Switch Timer CX Panel Controls NX Distributed System130.1(c)1ProgrammableTimeclockScheduled time-of-day operated control thatturns lighting off at specified times whentypically unoccupied. Occupancy sensors orother building system signals that turn OFFlights during vacancy also comply. Maximum2 hour manual override. TD300 Wall Switch Timer CX Panel Controls NX Distributed System130.1(c)5Vacancy sensor(Manual On - AutoOff): Partial On (5070% On - Full Off)Automatically shuts off lighting power aftervacancy of 30 minutes or less. LightHAWK2 Wall Switch Sensor CX Panel Controls NX Distributed SystemMulti-level lightingcontrolsAt least one multi-level lighting controldevice (manual or automatic) in enclosedareas 100 sq. ft. or larger. Light levelrequirements are defined in Table 130.1-A.Note, the majority of lighting types requiremultiple control steps. LightHAWK2 Wall Switch Sensor CX Panel Controls NX Distributed System130.1(d) and140.6(d)Multi-level daylightcontrolSensor to reduce lighting in responseto available daylight. Daylighting zonesdefined in Section 130.1(d)1. Primary daylightzones must be controlled separately fromsecondary zones. Refer to Table 130.1-A forlighting-level requirements. LightHAWK2 Wall Switch Sensor CX Panel Controls NX Distributed System130.4Acceptance testing(functional testing)Testing shall ensure that control hardwareand sofware are calibrated, programmed,and functioning properly. LightHAWK2 Wall Switch Sensor TD300 Wall Switch Timer CX Panel Controls NX Distributed SystemDemand ResponseAutomatic lighting reduction by a minimumof 15% of total installed lighting power inresponse to a Demand Response Signal.Required for new buildings larger than10,000 sq. ft. or luminare alterations thatincrease the lighting power in the enclosedspace. CX Panel Controls NX Distributed System130.1(a)ON/OFF CONTROLSMinimumControl Type130.1(b)LIGHT LEVELCONTROLADDITIONALCONTROL130.1(e)NOTE: Areas where no change has been made:On/Off ControlVacancy Sensor (Manual On - Auto Off): Automatic Partial-offLight Level ControlN/AAdditional ControlReceptacle Control20HUBBELL LIGHTINGHUBBELL LIGHTING21

NX DISTRIBUTED INTELLIGENCENX plaform is capable of scaling from standalone fixture and room control applications tonetworked enterprise deployments. NX operates using wired, wireless and hybrid connectivitywith native BACnet support.Device Setup AppIn-Fixture ControlsIn-Fixture Control Modules On / Off control and/or twochannel dimmingSuitable for indoor andoutdoor applicationsWireless programmingIn-Fixture Sensor Modules Luminaire-integrated designreduces complexity and designtime Out-of-the-box operation to meetcode and simplify installation Bluetooth enabled sensorsavailable in five versions toaddress occupancy and daylightdimmingNX Radio Modules Provide HubbNETTM wirelessnetwork communication Robust and reliable IEEE802.15.4 2.4GHz radio Remote, in-fixture andon-fixture mounting optionsThe NX Device Setup App provides Bluetooth wireless setup and configuration of NX RoomControl devices and luminaires equipped withan NX In-Fixture module with smart sensor. Themobile App is available in Android and iOS versions for free download from Google Play orApple stores.Accessories Provide dual RJ45 ports forCAT5 daisy-chain connections Offer dual, mini SmartPORT connections for In-Fixturemodules Simple attachment to luminairesIntelliscopeTMIntelliscope provides a unique and powerfultool for calibrating and testing NX In-Fixturesmart sensors. Motion captured by the sensoris displayed in real time relative to the currentsensitivity setting making precise calibrationpossible without the need for repetitive “testmode” trial and error calibration.Room ControlsWall Switch StationsRoom ControllersOccupancy Sensors Intelligent auto-configurationwith devices Automatic code compliance Cat5 plug and play connectivity Embedded IntelliDAPT self-adaptive technology Passive Infrared, Ultrasonic andDual Technology versions Occupancy or vacancy modewith up to 2000 sq. ft. coverageareaDaylight Sensors Open-loop daylighting controls Supports up to 6 lightingzones per room Simple setup using the NXmobile AppSingle and multi-button wall switch stationsare available in specialty pre-configured andprogrammable smart versions. Both offer a selfconfiguration feature that automatically configuresthe wall switch stations to perform the logicalcontrol and code compliant sequence of operation.All NX wall switch stations can be used with RoomControllers, Panels, or In-Fixture Modules in eitherstandalone or networked applications.Interfaces Allow third party interfaces Support A/V, Dry Contacts andHVAC options Mounts to standard junction boxor DIN railEnterprise / Building ControlsArea ControllerArea Controllers Central component forenterprise solutions Real-time programming andmonitoring Native BACnet supportNetwork BridgeNetwork AccessoriesLighting Control Panels Connect Room Controllers toHubbNET network Provide communication link forArea Controllers CAT5 plug and play connectivity Enable connection of additionalNX devices Provide network connectionsand power to NX accessories Mount to standard DIN rail Provides programmableswitching and dimming oflighting circuits Can be used exclusively or aspart of a network solution Available in 8, 16, 24, 32 and 48relay versionsThese are the key components. For a full list of NX products please visit www.hubbellcontrolsolutions.com.22HUBBELL LIGHTINGThe NX Area Controller is the central componentin an enterprise or building networked system. Theinterface is web browser based and does not requirethe installation of any software. A native BACnet interface facilitates a standard TCP/IP connectionproviding monitoring and control of lighting by theBuilding Automation System.These are the key components. For a full list of NX products please visit www.hubbellcontrolsolutions.com.HUBBELL LIGHTING23

WASP2 AND DIMMING WASP Indoor and outdoor occupancy and photocell sensors for on/off or preset dimmedWASP2 Occupancy and Photocell Sensor Digital Passive Infrared (PIR) sensorMultiple (single and dual) output versionsUnique Smart Cycling for improved fluorescent lamp lifeInterchangeable high/low mount detection lens optionsLow voltage and line voltage models availableFactory Installed & Field Installed Options AvailableDimming WASP Outdoor Motion and Photocell SensorCX COMMERCIAL LIGHTING SYSTEMFeature rich, cost effective lighting control system for switching and 0-10V dimming.CX 8 RELAY MASTER PANEL WITH DIMMING CARD 8 dimming channels 8 - 20AMP relays with 4 relay options - 20A/1P, N/O, 20A/2P, N/O, N/C (14K SSCR)and 30A/1P latching (18K SCCR) Color LCD user interface with keypad 365 day programming with 64 schedules Astronomical and real time clock Programmable inputs accept low voltage switches, photocells, or motion sensorsOMNI CEILING MOUNT OCCUPANCY SENSOR Low voltage Form C contacts availableDigital dual-technology (ultrasonic [US] and passive infrared [PIR]) sensorIntelliDAPT self-adaptive technologyUp to 2,000 square-foot coverage areaNon-volatile memory for sensor settings—no manual adjustment required Mounting heights: high mount lens: 30 ft outdoors; 45 ft indoors:low mount lens: 16 ft indoors/outdoors Controls 0-10V, 2-wire dimmable ballasts User controlled dimming with high/low area detection options Low temperature /water-tight/indoor-outdoor Factory Installed & Field Installed Options AvailableLOW VOLTAGE SENSORSWall switch vacancy & occupancy sensorsLightHAWK 2 Wall Switch Sensor IntelliDAPT self-adaptive technology - no manual adjustment requiredAvailable in Passive Infrared, Ultraso

effect. These revised standards improve energy efficiency in non-residential buildings. However, with a goal of Net Zero Energy in non-residential buildings by 2030, navigating the updated lighting code can be time consuming and confusing. By breaking down the latest changes to the CA Title 24 by applic