R4A3 - Home Page For Carrier Air Conditioning, Heating .

Transcription

R4A3Product SpecificationsEFFICIENT 13 SEER AIR CONDITIONERENVIRONMENTALLY BALANCED R 410A REFRIGERANT1 1/2 THRU 5 TONS SPLIT SYSTEM208/230 Volt, 1 phase, 60 HzREFRIGERATION CIRCUITS Scroll compressors on all modelsS Copper tube / aluminum fin coilEASY TO INSTALL AND SERVICES Easy Access service valves on all modelsS External high and low refrigerant service portsS Only two screws to access control panelS Factory charged with R 410A refrigerantBUILT TO LASTS Pre painted cabinet finish over galvanized steelS Models available with coated inlet grille with 2″ (51mm)spacing or with 3/8″ (10mm) spacing for extra protectionLIMITED WARRANTY*S 5 year compressor limited warrantyS 5 year parts limited warranty (including compressor andUse of the AHRI Certified TM Mark indicates amanufacturer’s participation in the program. Forverification of certification for individual products,go to www.ahridirectory.org .coil) With timely registration, an additional 5 year partslimited warranty (including compressor and coil)* For residential applications only. See warrantycertificate for complete details and restrictions, includingwarranty coverage for other Operating Dimensionslength/width(sq.) x heightin. (mm)Ship / OperatingWeight lbs.(kg)2023 1/8 x 24 7/8(587 x 632)124 / 108(56 / 49)14.32523 1/8 x 24 7/8(587 x 632)127 / 107(58 / 49)30,00016.62525 3/4 x 28 11/16( 654 x 729)149 / 126(68 / 57)336,00018.13031 3/16 x 24 7/8(792 x 632)151 / 134(68 / 61)3 1/242,00023.54031 3/16 x 31 11/16(792 x 804)186 / 172(85 / 78)448,00024.34031 3/16 x 35 1/16(792 x 891)205 / 175(93 / 79)560,00034.45031 3/16 x 28 1/4(792 x 718)218 / 203(99 / 92)Size(ton)NominalBTU/hrMin. Circuit Max. FuseAmpacity or Breaker1 1/218,00011.8224,0002 1/2Specifications subject to change without notice.421 65 6002 12 6/10/19

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)Digit Position:12345, 6789101112Example Part Number:R4A324AKH200Product Family4 R 410AA Air ConditionerH Heat Pump3 13 SEERREFRIGERANTTYPENOMINAL EFFICIENCY18 18,000 BTUH 1 1/2 tons24 24,000 BTUH 2 tons30 30,000 BTUH 2 1/2 tons36 36,000 BTUH 3 tons42 42,000 BTUH 3 1/2 tons48 48,000 BTUH 4 tons60 60,000 BTUH 5 tonsNOMINAL CAPACITYA Standard GrilleG Coil Guard GrilleFEATURESK 208/230 1 60VOLTAGESales CodeEngineering RevisionExtra DigitExtra DigitACCESSORIES PART NUMBER IDENTIFICATION GUIDEDigit Position:123456, 78, 910, 11Example Part Number:NASA00101CHN Non BrandedBRANDINGA AccessoryPRODUCT GROUPS Split System (AC & HP)A OriginalB 2nd Generation0 Generic or Not Applicable4 R 410AProduct Identifier NumberPackage QuantityType of Kit (Example: CH Crankcase Heater)2KIT USAGEMAJOR SERIESSpecifications subject to change without notice.REFRIGERANT421 65 6002 12

1R4A360AKH100R4A360GKH100Specifications subject to change without notice.18,243036,42,48,60UNIT 4A318AKH100INCH28 11/1628 11/16587.3654.0N 23 1/8N 25 3/4NN24 7/823 1/825 3/431 3/16-587.3654.0792.5-17 7/820 7/1622 /43/43/43/43/4MINIMUM ROOF-TOP MOUNTINGPAD APPLICATION 728.7728.7631.6631.6631.63/4INCH"X"28 1/428 1/435 1/1635 1/1624 7/8MM631.6MINIMUM GROUND MOUNTINGPAD APPLICATION DIMENSIONSY YESN NO792.5N 31 3/16N792.5792.5N 31 3/16N 31 3/16NN792.531 11/16792.5N 31 3/16N 31 3/16N792.5N 31 3/16NN31 11/16792.5N 31 3/16N24 7/8654.0792.5N 25 3/4N 31 3/16NN24 7/824 7/8587.3587.3N 23 1/8N 23 1/8N24 7/8BNMM587.3INCHN 23 ERISTICS208-230-1-60SERIES460-3-60208/230-3-60421 65 6002 9.119.119.119.119.119.1INCH6 9/166 9/166 9/166 9/166 9/166 9/166 9/166 9/164 7/164 7/164 7/164 7/164 7/164 7/16DMMINCH24 11/1624 11/1624 11/1624 11/1624 11/1624 11/1624 11/1624 11/1621 1/421 1/418 1/1618 1/1618 1/1618 9539.9459.0459.0459.0459.0INCH9 1/89 1/89 1/89 1/89 1/89 1/89 1/89 1/89 1/89 1/87 13/167 13/167 13/167 .276.276.2NOTE: ALL DIMENSIONS IN INCH 13.0113.0113.0113.0113.0E161615 3/415 3/4161615 9/1615 9/1612 1/212 1/212 1/212 419.1419.1393.7393.7279.4279.4298.5298.5INCH12 3/412 3/415 5/815 5/813 3/413 3/410 1/410 1/412 1/212 1/2121211 7/811 IPPINGWEIGHT32 3/1632 3/1632 3/1632 3/1632 3/1632 3/1632 3/1632 3/1626 3/426 3/424 1/824 1/824 1/824 9.9612.7612.7612.7612.7SHIPPINGLENGTH / WIDTH(Sq.)INCHMM29 7/829 7/836 11/1636 11/1633 1/433 1/426 7/1626 7/1630 3/830 3/826 7/1626 7/1626 7/1626 7/16INCH.3. SERIES DESIGNATION IS THE 10TH POSITION OF THEUNIT MODEL NUMBER.2. CENTER OF GRAVITYSD5433-4 NEW REV. 2672.1672.1672.1672.1MMSHIPPINGHEIGHT1. ALLOW 24" (609.6) CLEARANCE TO SERVICE SIDE OF UNIT, 48" (1219.2) ABOVE UNIT,6" (152.4) ON ONE SIDE, 12" (304.8) ON REMAINING SIDE, AND 24" (609.6) BETWEENUNITS FOR PROPER AIRFLOW.NOTES:15 1/215 1/216 3/816 3/815 1/215 1/216 1/216 1/215 1/215 1/2111111 3/411 3/4KU.S. ECCN: Not Subject to Regulation 7.5317.5317.5317.5304.8304.8JPRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A33

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3PHYSICAL DATAModel SizeNominal Cooling Capacity (BTU/hr)Nominal SEERPSC Fan Motor HPFan RPM (single speed)Fan CFMCoil Face Area ft2 (m2)Coil Rows fins per inchCircuitsLiquid Line Connection Size in. (mm)Vapor Line Connection Size in. (mm)Recommended Line SetLiquid Tube Diameter in. (mm)Recommended Line SetVapor Tube Diameter in. (mm)1818,00013.01/12110017008.40(.78)1 2033/8 (10)3/4 (19)2424,00013.01/10110022188.40(.78)1 2533/8 (10)3/4 (19)3030,00013.01/101100216911.49(1.07)1 2533/8 (10)3/4 (19)3636,00013.01/51100331012.93(1.20)1 2053/8 (10)7/8 (22)4242,00013.01/51100310017.25(1.60)1 2543/8 (10)7/8 (22)4848,00013.01/41100336519.40(1.80)1 2553/8 (10)7/8 (22)6060,00013.01/41100340015.09(1.40)2 2063/8 (10)7/8 (22)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/8 (10)3/4 (19)*3/4 (19)3/4 (19)* 7/8 (22)* 7/8 (22)*7/8 (22)*1 1/8(29)** Recommended Vapor Tube Line size is for standard installations. These recommendations may not apply to “LongLine” installations. Consult the Long Line Application Guideline document before purchasing/installing line sets.Factory Charge R 410A lbs. (kg)Required Charge R 410A lbs. (kg)(for 15 ft. line set)Required Subcooling F ( C)3.15(1.43)4.20(1.91)14 (7.8)3.15(1.43)4.17(1.89)10 (5.6)4.30(1.95)4.90(2.22)10 (5.6)4.67(2.12)5.36(2.43)11 (6.1)5.84(2.65)5.84(2.65)10 (5.6)7.10(3.22)8.20(3.72)13 (7.2)8.80(3.99)8.80(3.99)10 (5.6)ELECTRICAL DATA (208/230 1 60, voltage range 197V 253V)Model SizeMinimum Circuit Ampacity MCA (amps)Maximum OverCurrentProtective device MOCP (amps)Compressor RLA (Rated Load Amps)LRA (Locked Rotor Amps)Fan Motor FLA (Full Load ions subject to change without notice.421 65 6002 12

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3METERING DEVICEREQUIRED SUBCOOLING F ( C)13 (7.22)10 (5.56)12 (6.67)11 (6.11)11 (6.11)11 (6.11)13 (7.22)INDOOORUNIT SIZE18243036424860TXV** TXV must be ordered separately when indoor coil is not equipped with a TXV. TXV must be hard–shutoff type.REFRIGERANT CHARGE ADJUSTMENTSLiquid Line SizeR-410A Charge oz/ft0.60(Factory charge for lineset 9 oz)0.400.273/85/161/4Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line*. The factory charge for 3/8” lineset 9 oz. When using other length ordiameter liquid lines, charge adjustments are required per the chart above.Charging Formula:[(Lineset oz/ft x total length) – (factory charge for lineset)] charge adjustmentExample 1: System has 15 ft of line set* using existing 1/4“ liquid line. What charge adjustment is required?Formula:(.27 oz/ft x 15ft) – (9 oz) (-4.95) oz.Net result is to remove 4.95 oz of refrigerant from the systemExample 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?Formula:(.40 oz/ft. x 45ft) – (9 oz.) 9 oz.Net result is to add 9 oz of refrigerant to the systemNOTE: Conditions must be favorable for charging by subcooling method. Indoor temperatures must be 70 F to 80 F (21.1 C to 26.7C), and outdoor temperature must be 70 F to 100 F (21.2 C to 37.8 C). If outside these conditions, adjust charge for long line setsby weigh in method.* When applicable. Refer to Physical Data Table in this Specification and to the Installation Instructions for more information.LONG LINE APPLICATIONSAn application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintainacceptable refrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories.Defining a system as long line depends on the liquid line diameter, actual length of the tubing, and vertical separation between theindoor and outdoor units.For Air Conditioner systems, the charts below shows when an application requires a TXV and long line accessories due to linesetlength.AC with R 410A Refrigerant Long Line Description ft (m) Beyond these lengths, a TXV is requiredTotal LengthTXV required beyond 50 ft. (15.2 m)Outdoor Unit Above or Below Indoor UnitTXV required beyond 20 ft. (6.1 m)AC with R 410A Refrigerant Long Line Description ft (m) (Beyond these lengths, long line accessories are required)Liquid Line Size1/4 TXV5/16 TXV3/8 TXVUnits On Same LevelNo accessories needed within al lowed lengths120 (36.6)80 (24.4)Outdoor Below IndoorNo accessories needed withinallowed lengths50 (15.2) vertical or 120 (36.6) total35 (10.7) vertical or 80 (24.4) totalOutdoor Above Indoor175 (53.3)120 (36.6)80 (24.4)Note: See Long Line Guideline for details421 65 6002 12Specifications subject to change without notice.5

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3R4A3 SOUND RATINGSA Weighted Sound Power Level Without Sound ShieldTypical Octave Band Spectrum (dBA without pure toneStandard12525050010002000Rating (dBA)Unit 7957.567.072.075.072.5Note: Tested in accordance with AHRI Standard 270 2008 (not listed in AHRI).A Weighted Sound Power Level With Sound ShieldTypical Octave Band Spectrum (dBA without pure toneStandard12525050010002000Rating (dBA)Unit .568.072.574.572.5Note: Tested in accordance with AHRI Standard 270 2008 (not listed in .060.5R 410A COOLING CAPACITY LOSS FOR VARIOUS LINE LENGTHS & TUBE DIAMETERSModelSizeLiquidLinein.(mm)AcceptableVapor LineSizesin. (mm)3/8 (10)1/2 (13)5/8 (16)3/4 (19)5/8 (16)3/4 (19)7/8 (22)5/8 (16)3/4 (19)7/8 (22)5/8 (16)3/4 (19)7/8 (22)3/4 (19)7/8 (22)1 1/8 (29)3/4 (19)7/8 (22)1 1/8 (29)3/4 (19)7/8 (22)1 1/8(29)18243036424860Cooling Capacity Loss (%) at Total Equivalent Line Length, feet (m)Refer to Long Line Application Guideline to calculate equivalent lengthStandard 210420Long Line Application (Requires �(76.2)123162193113426318411262Consult the Long Line Application Guideline document before purchasing/installing line sets.Applications in shaded area may have height restrictions that limit allowable total equivalent length when outdoor unit is below indoorunit.6Specifications subject to change without notice.421 65 6002 12

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3COOLING PERFORMANCE FOR COMBINATION RATINGS Indoor ModelsFor complete ratings information, use the AHRI website directory search: www.AHRIdirectory.org.New ratings may be listed online before Specification Sheets are updated.Model Size18243036424860INDOOR 57,500AHRI STANDARD RATINGSCooling 95 F (35 C 0011.0011.0011.0011.0011.0011.00*Tested CombinationEER – Energy Efficiency RatioSEER – Seasonal Energy Efficiency RatioTDR - Time delay RelayTXV – Thermostatic Expansion ValveRatings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinationsare determined under DOE computer simulation procedures.Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace literature.TESTED AHRI COMBINATION RATINGS*NOTE: Ratings contained in this document are subject to change at any time.Or scan this QR code:For AHRI ratings certificates, please refer to the AHRI directory. www.ahridirectory.orgAdditional ratings and system combinations can be accessed via the Maratherm .aspx?Brand Maratherm421 65 6002 12Specifications subject to change without notice.7

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3EXPANDED COOLING PERFORMANCE RATINGS For Outdoor / Indoor ModelsFor complete ratings information, use the AHRI website directory search: www.AHRIdirectory.org.New ratings may be listed online before Specification Sheets are updated.018 Size Outdoor Section With EN(A,D)4X24L14** Indoor yMBtuhCONDENSER ENTERING AIR TEMPERATURES deg XPANDED COOLING PERFORMANCE RATINGS For Outdoor / Indoor ModelsFor complete ratings information, use the AHRI website directory search: www.AHRIdirectory.org.New ratings may be listed online before Specification Sheets are updated.024 Size Outdoor Section With EN(A,D)4X24L14** Indoor CoolingCONDENSER ENTERING AIR TEMPERATURES F ( C)EVAPAIR75 (23.9)CapacityMBtuhCFM70080090085 (29.4)95 (35)CapacityMBtuh105 tmSystmSystmTotal SensTotal SensTotalKWKWKW115 (46.1)CapacityMBtuhTotalSystmSensTotalKW125 SensKWEWBTotalSens72 (22.2)27.3014.671.7526.11 14.221.9524.85 13.752.1723.44 13.242.4121.98 12.712.6820.45 12.162.9867 (19.4)24.9718.161.7423.88 17.711.9322.68 17.222.1521.41 16.702.3920.05 16.162.6618.65 15.592.9763 (17.2)††23.2717.501.7322.23 17.041.9221.10 16.542.1419.90 16.012.3818.64 15.462.6517.31 14.892.9662 (16.7)23.0121.601.7322.03 21.121.9220.96 20.572.1419.90 19.902.3818.86 18.862.6517.76 17.762.9657 (13.9)22.6022.601.7321.76 21.761.9220.85 20.852.1419.88 19.882.3818.84 18.842.6517.73 17.732.9672 (22.2)27.6915.401.7926.45 14.941.9925.15 14.472.2123.70 13.952.4522.19 13.422.7220.61 12.863.0367 (19.4)25.3619.351.7824.23 18.901.9723.00 18.402.1921.68 17.872.4320.30 17.312.7018.85 16.733.0163 (17.2)††23.6518.611.7722.57 18.141.9721.41 17.632.1820.18 17.102.4218.88 16.532.6917.52 15.943.0062 (16.7)23.5623.151.7722.67 22.351.9721.62 21.622.1820.59 20.592.4219.48 19.482.7018.31 18.313.0057 (13.9)23.4423.441.7722.56 22.561.9721.60 21.602.1820.56 20.562.4219.46 19.462.6918.28 18.283.0072 (22.2)27.9616.091.8326.68 15.632.0325.34 15.152.2523.87 14.632.4922.32 14.092.7620.71 13.533.0767 (19.4)25.6520.491.8224.48 20.022.0223.23 19.522.2321.88 18.982.4720.48 18.402.7419.02 17.793.0563 (17.2)††23.9519.671.8122.84 19.182.0121.64 18.672.2220.38 18.122.4619.06 17.532.7317.70 16.903.0462 (16.7)24.1724.171.8123.25 23.252.0122.22 22.222.2221.13 21.132.4719.97 19.972.7418.74 18.743.0557 (13.9)24.1424.141.8123.22 23.222.0122.20 22.202.2221.11 21.112.4719.95 19.952.7418.72 18.723.05†† - At TVA rating indoor condition (75 F db / 63 F wb). All other indoor air temperatures are at 80 F db.Total sensible capacities are based on net capacities. Blower heat has been subtracted.Sensible capacities shown are based on 800 F (270 C) entering air at the indoor coil. For sensible capacities at other than 800 F (270 C), deduct 835 Btuh(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 800 F (270 C), or add 835 Btuh 245 kW) per 1000 CFM (480 L/S) of indoor coilair per degree above 800 F (270 C).Detailed cooling and heating capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240 -2008. If additional tubinglength is required and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.System kw is total of indoor and outdoor unit kilowatts.8Specifications subject to change without notice.421 65 6002 12

PRODUCT SPECIFICATIONSSplit System Air Conditioner: R4A3EXPANDED COOLING PERFORMANCE RATINGS For Outdoor / Indoor ModelsFor complete ratings information, use the AHRI website directory search: www.AHRIdirectory.org.New ratings may be listed online before

PRODUCT SPECIFICATIONS Split System Air Conditioner: R4A3 4 Specifications subject to change without notice. 421 65 6002 12 PHYSICAL DATA Model Size 18 24 30 36 42 48 60 Nominal Cooling Capacity (BTU/hr) 18,000 24,000 30,000 36,000 42,000 48,000 60,000 Nominal SEER 13.0 13.0 13.0 13.0 13.0