ADEMCOVISTA-128FB/V128FB-24Commercial Fire and Partitioned Alarm PlatformDesigned to integrate seamlessly with CCTV, accessaddressable V-Plex technologies. A diverse line ofcontrol and Honeywell’s full range of fire and burglaryHoneywell initiating devices, notification circuits, digitalcomponents, the VISTA-128FB provides the ultimatedialers, keypads, RF receivers and relays support thisprotection of life and property. The UL listedextremely powerful control platform. The VISTA-128FBCommercial Fire and Burglary Control Platform controlshas been designed to mount quickly and easilyup to eight partitions, and supports up toin an attack resistant cabinet, and is available in128 zones/points using hardwired, wireless and12V and 24V models.F E AT U R E S Supports addressable V-Plexaccess control points usingVistaKey (1 to 8 doors) Supports up to 15 doors ofaccess control using VistaGateway Module (VGM)* Supports CCTV applications withthe new VistaView-100 CCTVswitcher module Identifies the point or zone of a fireor alarm, using the new FSA-8/FSA-24 Fire system annunciator Stores up to 512 events and canaccommodate 150 user codes Can control eight separate areasindependently (8 partitions) New E2 software simplifiesprogramming Two on-board notification (bell)circuits delivering 2.3A @ 12V or3.4 amp @ 24V Easily programmed andmaintained with newly upgradedCompass Downloader software Eight hardwired zones standard,expandableto 120 V-Plexaddressable points/zonesor 128 wireless points/zones Automatic smoke detectorsensitivity maintenance testing* Connects to Honeywell’s Passpoint AccessControl Systems. Maximum 32 doors.

ADEMCO VISTA-128FB/V128FB-24Commercial Fire and Partitioned Alarm PlatformS P E C I F I C AT I O N SCabinet dimensions 18"H X 14.5"W X 4.3"DEnvironmental Storage temp: -10 C to 70 C Operating temp: 0 C to 50 C Humidity: 85% RHEMIMeets or exceeds the followingrequirements:— FCC Part 15, Class B Device— FCC Part 68— IEC EMC DirectiveAgency ListingsBurglary UL609 Grade A Local MercantilePremises and Mercantile Safe and Vault UL611/1610 Grades A, AA,Central Station UL365 Grades A, AA PoliceConnectFire UL864/NFPA72 Local, CentralStation and Remote Station Factory Mutual California State Fire Marshal MEA UL9859500SNGlassbreak SensorAdditional Features Notification Appliance Circuits(two)— Programmable— Temporal code compliant— Individually silenceable Programmable on-board auxiliaryrelay SIA false alarm reductionfeatures:— Exit Error Logic— Exit Delay Reset— Cross Zoning— Call Waiting Defeat— Recent Close Report Supports commercial hardwired,addressable V-Plex polling loopand wireless zones Hardwired zones:— Provides nine style Bhardwired zones— EOLR supervised for Fire andUL burglary installations— Supports N.0 or N.C. sensors— Individually assignable to oneor all eight partitions— Up to 16 two-wire smokedetectors each zone 1 and 2(32 total)4101SNRelay Module4208UEight-ZoneExpansionModule— Up to 50 two-wire glass breakdetectors on zone eight Patented addressable V-Plexpolling loopV-Plex technology:— Supports up to 120 two-wirezones/points— Global polling technology forfaster processing— Increased current drawcapacity (128mA)— Supervised by panel— Individually assignable topartitions, notification circuit(bell) output or aux relay— 4,000 ft capability without theuse of shielded cable— Extender/Isolation bus module— Two-wire smoke detectorzone/group expansion moduleadds two or four zones— Eight zone - Class A and BExtender Module— One zone supervised ContactMonitor Module UL Listed wireless expansion— Supports up to 128 wirelesszones using 5881 ReceiverVPlex Loop4293SNV-Plex Adapter4208SNFEight-ZoneExpansionModuleWith Two Class A5881ENHCZonesWirelessCommercialReceiver5192 SeriesSmokeDetectorsV-PLEX Loop6160CRCustom AlphaConsoleVistaView-100CCTVSwitcherVistaKey V-PlexAccess ControlModuleNAC (Bell) Circuit4204CF4204RelayModuleNotification Appliances}Eight Class B Hardware Zones4146KeySwitchOption5140 LEDCommunicatorStatus n Appliances6220S PrinterPhone Line to Central Station7720ULF LongRange Radio7845C Cellular

— Supervised by control forcheck-in signals— Tamper protection fortransmitters— Individually assignable up toeight partitions— Supports UL864/NFPAapproved wireless smokedetectorsAccess control integration— Full integration with PassPointAccess Control SystemComplete Gateway in accessfunctionsEvent reportingLocal printer of access or VISTArelated eventScheduled uploading of events tocentral stationStored events for one call retrievalCommunication— Phone mapping by zoneresponse type— Supports VIP Interactive PhoneVoice Module— Panel operation duringdownload— Uploading equipment list tocentral station— Communication to PassPointvia Vista Gateway Module(VGM)ApplicationsSupported by a diverse line ofHoneywell initiating devices, thepowerful VISTA-128FB is the idealintegrated fire and burglary controlfor applications where a higherlevel of security is necessaryincluding medical and professionalbuildings, supermarkets, churchesand synagogues, office buildings,schools, universities, strip malls,larger residences and factory orwarehouse environments.InstallationThe VISTA-128FB alarm system hasbeen designed to mount bothquickly and easily in an attackresistant cabinet. It meets allapplicable requirements for ULcommercial burglary installations.Electrical:Primary power:— 18 VAC@ 72 VA No. 1451Quiescent current draw:— 300mABackup battery 12VDC, 12AH min to 34AAH max Lead acid battery (gel type)Alarm power 12VDC, 1.7A max for eachnotification (bell) circuit outputAux. standby power 12VDC, 1A maxTotal power 2.3A at 12VDC, 3.4A at 24VDCfrom all sourcesStandby time 24 hours with 1A standby load or60 hours with 205mA maxstandby load using 34AAHbatteryFusing Battery input, aux. and notification(bell) circuit outputs are protectedusing PTC circuit protectors. Alloutputs are power limited.Main dialer Line seize:— Double PoleManual Pull Stations5140MPS - 1*5140MPS - 2*4278EX Quad PIRECP Bus4193SNSerial InterfaceModuleQ2260SN MultiplexDUAL TEC Motion Detector4190SNV-Plex Two-ZoneExpander4944SNAddressableRecessed MountContactTamper Switch*Flow Switch*Low Temp Switch*5881Wireless Receiver(Max Two)5808LSTSmokeDetectors6139R32 CharacterRed-AlphaKeypad5890Wireless PIR5800 Door/WindowMiniatureTransmitter4209UGroup ZoningModule5808LSTSmokeDetectorsSupports Up To 16Conventional Two-WireSmoke p SwitchSupports Up To 64Conventional Two-WireSmoke Detectors5817CBWirelessCommercialTransmitterVGM (PTVGM)VistaGatewayModulePassPoint

ADEMCO VISTA-128FB/V128FB-24Commercial Fire and Partitioned Alarm PlatformS P E C I F I C AT I O N SRinger equiv.— 0.713Formats:— ADEMCO Low Speed, ADEMCO4 2 Express, ADEMCO HighSpeed, ADEMCO Contact ID,Sescoa and RadionicsAuxiliary devices 6160CR Alpha KeypadCommercial Fire 6139R - Red AlphaKeypad/Annunciator FSA-8 & FSA-24 Fire SystemAnnunciator 4204 - Relay Module, four form Ccontacts 4204CF - Two supervised outputcircuits 6220S - System printer used with4100SM Serial Interface Module 5140DLM, FSA-8, FSA-24,FSAKSM Fire AnnunciatorTwo-wire and four-wire smokedetectors conventional: System Sensor smoke detectorsHorn/Strobes System Sensor notificationappliancesManual pull stations: 5140MPS-1 5140MPS-2V-Plex (addressable) devices: 4101SN Single Relay/ZoneModule 4190SN Remote Point Module two zones 4190WH Two Point Multiplex RPM 4193SN Two Zone Serial InterfaceModule 4208U Loop Expansion Module eight zones 4208SNF Class A/13 ExpanderModule 4209U Group Zoning Module two/four zones 4293SN One Zone Serial InterfaceModule 4297 Isolation/Extender ModuleV-Plex (addressable) smokedetectors 5192SD 5192SDTPassive infrared detectors 998MX 4275EX-SN 4278EX-SN Quest 2260SNV-Plex (addressable) contacts 4939SN-WH 4944SN-WH 4959SNGlassbreak detectors 9500SNVISTA Interactive Phone Module 4286 Voice ModuleOptional 24V power supply PS24 - 24V power supply - 3.4ALong range radio Long range radio 7720ULF-XX,7845C, 7835CFPKUpgraded software Upgraded Compass DownloaderWindows compatibleWireless devices 5804 - Wireless Key 5804BD - Bi-Directional Key 5804BDV - Bi-Directional withvoice 5816 - Door/Window Transmitter 5819 - Shock Sensor 5827BD - Bi-Directional Keypad 5849 - Glassbreak Detector 5881 Series - RF Receiversupporting 5800 wirelessdetectors 5890 - PIRAccess control VistaKey V-Plex (addressable)Access Control VistaKey-SK Starter Kit VistaKey-EX Expansion Kit VGM Vista Gateway Module toPassPoint Access Control(Honeywell Access Systems)CCTV VistaView-100-CCTV SwitchModuleCommercial wireless devices 5869 - Hold up Transmitter 5817CB - Wireless CommercialTransmitter 5881ENHC - CommercialFire/Burg Receiver 5808LST - Wireless SmokeDetector 5809 - Wireless Heat DetectorORDERINGVISTA-128FBV128FB-24Commercial Fire and Partitioned Burglary Alarm Platform 12V ModelCommercial Fire and Partitioned Burglary Alarm Platform 24V ModelHoneywell Security & Custom Electronics165 Eileen Way, Syosset, NY 11791www.ademco.comCopyright 2004 Honeywell International Inc. L/VIS128FB/D 1/04

ADEMCO VISTA-128FB/V128FB-24Commercial Fire and Partitioned Alarm PlatformS P E C I F I C AT I O N SCabinet dimensions 18"H X 14.5"W X 4.3"DEnvironmental Storage temp: -10 C to 70 C Operating temp: 0 C to 50 C Humidity: 85% RHEMIMeets or exceeds the followingrequirements:— FCC Part 15, Class B Device— FCC Part 68— IEC EMC DirectiveAgency ListingsBurglary UL609 Grade A Local MercantilePremises and Mercantile Safe and Vault UL611/1610 Grades A, AA,Central Station UL365 Grades A, AA PoliceConnectFire UL864/NFPA72 Local, CentralStation and Remote Station Factory Mutual California State Fire Marshal MEA UL985Additional Features Notification Appliance Circuits(two)— Programmable— Temporal code compliant— Individually silenceable Programmable on-board auxiliaryrelay SIA false alarm reductionfeatures:— Exit Error Logic— Exit Delay Reset— Cross Zoning— Call Waiting Defeat— Recent Close Report Supports commercial hardwired,addressable V-Plex polling loopand wireless zones Hardwired zones:— Provides nine style Bhardwired zones— EOLR supervised for Fire andUL burglary installations— Supports N.0 or N.C. sensors— Individually assignable to oneor all eight partitions— Up to 16 two-wire smokedetectors each zone 1 and 2(32 total)— Up to 50 two-wire glass breakdetectors on zone eight Patented addressable V-Plexpolling loopV-Plex technology:— Supports up to 120 two-wirezones/points— Global polling technology forfaster processing— Increased current drawcapacity (128mA)— Supervised by panel— Individually assignable topartitions, notification circuit(bell) output or aux relay— 4,000 ft capability without theuse of shielded cable— Extender/Isolation bus module— Two-wire smoke detectorzone/group expansion moduleadds two or four zones— Eight zone - Class A and BExtender Module— One zone supervised ContactMonitor Module UL Listed wireless expansion— Supports up to 128 wirelesszones using 5881 Receiver — Supervised by control forcheck-in signals— Tamper protection fortransmitters— Individually assignable up toeight partitions— Supports UL864/NFPAapproved wireless smokedetectorsAccess control integration— Full integration with PassPointAccess Control SystemComplete Gateway in accessfunctionsEvent reportingLocal printer of access or VISTArelated eventScheduled uploading of events tocentral stationStored events for one call retrievalCommunication— Phone mapping by zoneresponse type— Supports VIP Interactive PhoneVoice Module— Panel operation duringdownload— Uploading equipment list tocentral station— Communication to PassPointvia Vista Gateway Module(VGM)ApplicationsSupported by a diverse line ofHoneywell initiating devices, thepowerful VISTA-128FB is the idealintegrated fire and burglary controlfor applications where a higherlevel of security is necessaryincluding medical and professionalbuildings, supermarkets, churchesand synagogues, office buildings,schools, universities, strip malls,larger residences and factory orwarehouse environments.InstallationThe VISTA-128FB alarm system hasbeen designed to mount bothquickly and easily in an attackresistant cabinet. It meets allapplicable requirements for ULcommercial burglary installations.Electrical:Primary power:— 18 VAC@ 72 VA No. 1451Quiescent current draw:— 300mABackup battery 12VDC, 12AH min to 34AAH max Lead acid battery (gel type)Alarm power 12VDC, 1.7A max for eachnotification (bell) circuit outputAux. standby power 12VDC, 1A maxTotal power 2.3A at 12VDC, 3.4A at 24VDCfrom all sourcesStandby time 24 hours with 1A standby load or60 hours with 205mA maxstandby load using 34AAHbatteryFusing Battery input, aux. and notification(bell) circuit outputs are protectedusing PTC circuit protectors. Alloutputs are power limited.Main dialer Line seize:— Double PoleVPlex LoopManual Pull Stations5140MPS - 1*5140MPS - 2*9500SNGlassbreak Sensor4101SNRelay Module4208UEight-ZoneExpansionModule4293SNV-Plex Adapter4208SNFEight-ZoneExpansionModuleWith Two Class A5881ENHCZonesWirelessCommercialReceiver5192 SeriesSmokeDetectorsV-PLEX Loop4278EX Quad PIRECP Bus4193SNSerial InterfaceModuleQ2260SN MultiplexDUAL TEC Motion Detector4190SNV-Plex Two-ZoneExpander4944SNAddressableRecessed MountContactTamper Switch*Flow Switch*Low Temp Switch*5881Wireless Receiver(Max Two)6160CRCustom AlphaConsoleVistaView-100CCTVSwitcherVistaKey V-PlexAccess ControlModuleNAC (Bell) Circuit4204CF4204RelayModuleNotification Appliances}Eight Class B Hardware Zones4146KeySwitchOptionNotification Appliances6220S PrinterPhone Line to Central Station7720ULF LongRange Radio7845C Cellular5890Wireless PIR5800 Door/WindowMiniatureTransmitter4209UGroup ZoningModule5808LSTSmokeDetectorsSupports Up To 16Conventional Two-WireSmoke p Switch5140 LEDCommunicatorStatus eDetectors6139R32 CharacterRed-AlphaKeypadSupports Up To 64Conventional Two-WireSmoke Detectors5817CBWirelessCommercialTransmitterVGM (PTVGM)VistaGatewayModulePassPoint

* Connects to Honeywell’s Passpoint Access Control Systems. Maximum 32 doors. Commercial Fire and Partitioned Alarm Platform ADEMCO VISTA-128FB/V128FB-24 Cabinet dimensions 18"H X 14.5"W X 4.3"D Environmental