I-Line Combo Panelboard - Steven Engineering

Transcription

I-Line Combo PanelboardDistribution PanelboardsCatalog2110CT13012013Class 2110ContentsDescriptionPageProduct Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Enclosure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . .Main Circuit Breaker Panelboards . . . . . . . . . . . . . . . . . .Main Lugs-only Panelboards . . . . . . . . . . . . . . . . . . . . . .Solid Neutral. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Branch Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . .22345555DescriptionPageFeatures and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Accessories and Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Available Ready-to-Install Kits. . . . . . . . . . . . . . . . . . . . . 8Available Factory Installed Options . . . . . . . . . . . . . . . . . 8Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9General and Application Information . . . . . . . . . . . . . . . . 10Enclosure Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com

I-Line Combo PanelboardProduct DescriptionProduct DescriptionThe I-Line Combo Panelboard combines an NQ or NF lighting section withan I-Line power distribution section in a single panelboard. This is anindustry-exclusive addition to the Schneider Electric Square D brandI-Line Power Distribution Panelboard offer, designed for use in both AC andDC systems. It is available in single or duplex configurations, whichdetermine the number of included lighting sections. All main circuit breakerpanelboards rated 800 A or less are suitable for use as service entrance.I-Line Combo panelboards are available as 225–800 A main lugs only and70–1200 A main circuit breakers. The I-Line Combo panelboards aredesigned to accept the following circuit breakers: FA, FH, FI, FY, HD, HG,HJ, HL, HR, JD, JG, JJ, JL, JR, LA, LD, LG, LH, LI, LJ, LL, LR, MG, MJ, PG,PJ, PK, PL, Q4, QB, QG, QJ, EDB, EGB, EJB, QO and QOB.StandardsSingle I-LineCombo PanelboardI-Line Combo panelboards are designed, manufactured, and tested tocomply with the following standards:StandardDescriptionUL 50Standard for electrical equipment enclosuresUL 67Standard for panelboardsCSA C22.2, Nos.29 and 94-1989Standard for panelboards, includingenclosed panelboardsNFPA 70National Electrical Code (NEC)CSA C22.1Canadian Electrical Code (CEC)NEMA PB 1Standard for panelboardsW-P 115C Type 1 Class 1Specification for circuit breaker panelboards2000 IBCUS standard for seismic requirements1995 NBCCCanadian standard for seismic requirementsDuplex I-LineCombo Panelboard208/2013 2013 Schneider ElectricAll Rights ReservedCourtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com

I-Line Combo PanelboardProduct DescriptionServiceThe I-Line Combo distribution panelboards can be used on the followingsystem umAmperage18 in. (457 mm)60022.5 in. (572 mm)22.5 in. (572 mm)31.5 in. (800 mm)Lighting SectionCircuit CountSection 2HeightWidthDepth30—86 (2184)26 (660)9.5 (241)42—86 (2184)26 (660)9.5 (241)30—73 (1854)32 (813)9.5 (241)42—91 (2311)32 (813)9.5 (241)424291 (2311)32 (813)9.5 (241)543091 (2311)32 (813)9.5 (241)424286 (2184)44 (1118)9.5 (241)543086 (2184)44 (1118)9.5 (241)30Optional MountingSpace 286 (2184)44 (1118)9.5 (241)42Optional MountingSpace 286 (2184)44 (1118)9.5 (241)54 3Optional MountingSpace 286 (2184)44 (1118)9.5 (241)600800NEMA 1Dimension in Inches (mm)Section 1600MLODuplexThe DC rating of the entire panelboard is limited due to the 48 Vdc rating of QO circuit breakersused in the NQ section of the I-Line Combo panelboard.MCB12001Only available in the NQ lighting panelboard.2Optional mounting space is only available on 800 A interiors, not 1200 A.3The 54 circuit with an optional mounting space is available for 800 A, but can only be used with 1, 2, or 3 lighting contactors. 2013 Schneider ElectricAll Rights Reserved Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com08/20133

I-Line Combo PanelboardProduct DescriptionEnclosure ProtectionEnclosureProtects From These Environments:Type 1Indoor contact with the enclosed equipmentType3R1Type 4/4XOutdoor falling rain and sleet, iceStainless1Corrosion, hose-directed water, dustType 51Indoor settling dust, falling dirt, dripping liquidsType 121Indoor circulating dust, falling dirt, dripping liquidsFrontsSurface and flush trims available as four-piececonstruction, standard (door not included). An optionalfour-piece trim with door is also available.Finished with gray-baked enamel electrodeposited overcleaned phosphatized steel (ANSI 49).Type 1EnclosuresBoxesGalvanized steel in 26, 32, and 44-inch (660, 813, and1118 mm) widths.Removable endwalls without knockouts.NEMA Type 1EnclosureGasketed door with vault handle and directory card holderThree-point latchingType 3R, 5,and 12EnclosuresEnd and side gutter trimNo knockoutsRemovable drain screw for Type 3RFinished with gray-baked enamel electrodeposited over cleanedphosphatized steel (ANSI 49)NEMA Type 3REnclosure1408/2013Only available in 26 in. (660 mm) and 44 in. (1118 mm) width configurations. 2013 Schneider ElectricAll Rights ReservedCourtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com

I-Line Combo PanelboardProduct DescriptionMain Circuit Breaker Panelboards Powerpact P-Frame 1200 A Main(the maximum size circuit breaker for theI-Line Combo panelboard) Accepts up to 1200 A main circuit breaker 2Available factory-assembled up to 1200 A or ready-to-installup to 800 A 2Cable entry can be top or bottom feed 3Suitable for use as service entrance equipment up to 800 A in the USAccepts plug-on I-Line main circuit breakers: LA/LH-frame, PowerPact L-frame, M-frame, and P-frameAvailable with a short circuit current rating (SCCR) up to200 kA maximumAvailable with tin plated copper bus, silver plated copper bus,or tin plated aluminum bus 4Solid neutral is mounted at the top of the panelboard, as standardAvailable with compression lugs for I-Line circuit breakers; consultonline Digest for details about compression lugs available for each circuitbreaker type.Main Lugs-only Panelboards Powerpact L-Frame 250 A Main Available factory-assembled or ready-to-install up to 800 AAccepts plug-on I-Line main lug kits 5Available with a short circuit current rating (SCCR) up to200 kA maximumAvailable with tin plated copper bus, silver plated copper bus, or tin platedaluminum bus 4Cable entry can be top or bottom feed 3Solid neutral is mounted at the top of the panelboard, as standardAvailable with compression lugs for I-Line circuit breakers; consultonline Digest for details about compression lugs available for each circuitbreaker type.Solid Neutral Mounts in main compartment above the lighting sectionsDoes not take up interior circuit breaker mounting spaceUL/CSA Listed for use with aluminum or copper conductorsCopper or aluminum neutral available200% rated neutral available as a factory-assembled option up to 800 ABranch Circuit Breakers 2013 Schneider ElectricAll Rights ReservedNQ lighting sections accept QO and QOB circuit breakers, which areavailable from 10–150 ANF lighting sections accept E-frame circuit breakers, which are availablefrom 15 –110 AI-Line sections with 18 in. (457 mm), 22.5 in. (572 mm), or 31.5 in.(800 mm) of mounting space will accept thermal magnetic/basic electronicor electronic with ammeter or energy trip unit I-Line circuit breakers 621200 A main circuit breaker is allowed in US and Mexico only.3I-Line section is required to reside at the bottom of the panelboard.4Tin-plated aluminum bussing is only available on 225 A and 250 A configurations.5Plug-on lug kits include catalog numbers SL400, SL800, and S33931. Please refer to the mostcurrent Digest to determine which one is required.6Available with compression lugs for I-Line circuit breakers. Consult online Digest for detailsabout compression lugs available for each circuit breaker type. Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com08/20135

I-Line Combo PanelboardFeatures and BenefitsFeatures and BenefitsListed below are some of the benefits of the I-Line Combo panelboard.Ease of InstallationThe I-Line Combo panelboard provides a simple, quick installation due tothe minimal amount of materials needed and the benefit of only having toinstall a single panelboard.Reduced FootprintBy combining a power panel with up to two lighting panels in a singleenclosure, the I-Line Combo panelboard saves significant space at any site.Industry Exclusive DesignThe innovative, hard-bussed connection between the NQ or NF lightingsections and the I-Line power section are friction-stir welded to ensure areliable connection.Simple to RetrofitI-Line Combo panelboard enclosures fit into the same footprint on siteswhere an existing I-Line power panelboard resides, providing easyupgrades of electrical equipment.Flexible Circuit Breaker ConfigurationDue to the I-Line Combo panelboard's ability to house I-Line molded casecircuit breakers as well as cost effective miniature circuit breakers, itprovides not only a more economical solution but an adaptable solutiontailored to each customer.Classic SolutionI-Line Combo Panelboard SolutionNQ or NFPanelboardNQ or NFI-Line26 in. (660 mm), 32 in. (813 mm),or 44 in. (1118 mm) widthI-Line Panelboard400 A–1200 A MLO/MCB608/201326 in. (660 mm), 32 in. (813 mm),or 44 in. (1118 mm) widthI-Line Combo Panelboard 60 in. (1524 mm) width 2013 Schneider ElectricAll Rights ReservedCourtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com

I-Line Combo PanelboardFeatures and BenefitsA. I-Line Como panelboards are available as Type 1, 3R, 4/4X, 5, and 12enclosures in 26 in. (660 mm), 32 in. (813 mm), or 44 in. (1118 mm) boxwidths. Placing the lighting sections and I-Line power section in thesame box reduces the total footprint on a project site. All enclosuresoffer either high-quality galvanized or stainless steel, providing extraprotection for the panelboard's interior components.AB. Schneider Electric NQ or NF lighting sections are hard bussed to theI-Line power section. With the lighting sections and power section in thesame enclosure, cost-conscious customers will benefit from flexiblecircuit breaker configurations.FEC. The I-Line power section is mounted horizontally and available in18 in. (457 mm), 22.5 in. (572 mm), or 31.5 in. (800 mm) mountingspace configurations. The stacked bus structure offers unrestrictedcircuit breaker placement options. Due to the circuit breaker’s “plug-on”type connection, the jaws on each circuit breaker create a firm grip onthe bus bar during high-level short circuit conditions. The only toolneeded for installing an I-Line circuit breaker is a screwdriver, making itthe industry’s quickest and easiest installation.BD. Wireway in the I-Line Combo panelboard offers ample room for wirebending, utilizing standard installation practices. This enclosure's designis installer friendly.CE. The I-Line Combo panelboard duplex configuration, with optionalmounting space (pictured at left), provides the capability for future sitegrowth. Ready-to-install kits are available as cable-fed field installableoptions that are mounted in the available space. This allows forindividual shut down of the right section instead of discontinuing powerto the entire panelboard.The additional mounting space can be utilizedfor many applications including:DReady-to-Install KitsDuplex I-Line Combo Panelboardwith Optional Mounting Space—Dual 18 circuit section assembly—Single 18 circuit section with contactor mounting assembly—Additional 42 circuit section assembly—Contactor mounting kit for up to three contactorsFactory Assembled Options7—Powerlink lighting section in 42 or 54 circuit configurations8F. The solid neutral in the I-Line Combo panelboard is includedas standard. 2013 Schneider ElectricAll Rights Reserved7Options listed above for ready-to-install configurations can be ordered as cable fed factoryassembled configurations.8Powerlink sections will be available only on the left side of the I-Line Combo panelboard. Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com08/20137

I-Line Combo PanelboardAccessories and KitsAccessories and KitsAvailable Ready-to-Install KitsTo provide future job site growth, ready-to-install 42 circuit NQ or NF lightingsections make it possible to install additional circuits in the field.Ready-to-install dual 18 circuit assemblies are also available as fieldinstallable accessories.Lighting SectionTypeCircuit CountAmperageCatalog Number18 (with contactor kit)125NFICRT418C1CDual 600Y/347 Vac Max)4218 (with contactor kit)Dual 18NQ(240/120 Vac Max)4242 Circuit NQ Ready-to-Install g SectionTypeCatalog NumberContactor Adaptor Kit1NQINFI8903KIT1See the most updated version of the Digest for contactor assemblies.Available Factory Installed OptionsAll available options that may be installed on the lighting section mountingpan can be ordered factory assembled. Powerlink lighting sections c

NEMA PB 1 Standard for panelboards W-P 115C Type 1 Class 1 Specification for circuit breaker panelboards 2000 IBC US standard for seismic requirements 1995 NBCC Canadian standard for seismic requirements Single I-Line Combo Panelboard Duplex I-Line Combo Panelboard Courtesy of Steven Engineering, Inc. - (800) 258-9200 - sales@steveneng.com - www.stevenengineering.com . I-Line