VentilationGuideIndoor air quality solutions for residentialand commercial environments

Tableof contentsIntroduction3Five reasons4Decision guide6Legislation and standards8Unit construction210

Clean air is a basicrequirement of life. Thequality of air inside homesand commercial buildingswhere people spend a largepart of their life is an essentialdeterminant of healthy lifeand people’s well-being.Daikin offers a variety of solutions from small energy recoveryventilation to large air handling units for the provisionof fresh air ventilation to residential and commercial buildings.Ventilation solutionsControl of fresh air temperatureDaikin offers state-of-the-art ventilation solutions that caneasily be integrated into any project:›› Wide ventilation portfolio, unique among ACmanufacturers›› High-quality solutions complying with the highestlegislative standards›› Seamless integration of all products to provide the bestindoor environment quality›› All Daikin products connected to a single front endcontroller for complete control of the HVAC system.Daikin offers a range of inverter condensing units and chillers which canbe used in combination with Daikin Air Handling Units (AHUs) for theultimate in control over fresh air.There are four control possibilities when combining AHUs and Daikinoutdoor units, offering all the required flexibility for any installation.Multiple indoor units can be combined with the same outdoor unitto reduce the installation costs. For false-ceiling installations wherespace is a constraint, the VKM can fit perfectly, delivering fresh air at acomfortable temperature and with optional humidification.Energy Recovery VentilationOur energy recovery units recover sensible energy (ModularL Pro / Modular L Smart) or total (sensible latent) energy(VAM/VKM), substantially reducing the load on the airconditioning system up to 40%.Five components of indoor air quality:›› Ventilation: ensures the provision of fresh air›› Energy recovery: saves energy by transferring heat and moisturebetween airflows›› Air processing: delivers the right supply temperature to decrease theindoor unit load›› Humidification: ensures relative indoor humidity levels are respected›› Filtration: separates pollen, dust and pollution harmful to ficationFiltration 3

Five reasons why Daikin’sventilation range isunique in the market1Market leading controls& connectivity›› Interlocking ventilation and air conditioning system: Control ERV/HRV and air conditioning from the same controller Aligns the operation mode between the systems to save energy›› Easy integration in the total solution: Online control and monitoring via the Daikin Cloud Service Full portfolio integration in the intelligent Touch Manager,Daikin's cost-effective mini BMS›› User-friendly controller with premium design: Intuitive touch button control2Unique installation benefits›› Integrates seamlessly within the Daikin total solution,ensuring a single point of contact›› Total fresh air solution with Daikin supplying both theVAM/Modular L Smart and the electrical heater›› Daikin AHU and condensing unit connect Plug & Play thanks to samepipe diameters, factory mounted controls, expansion valves, etc.421 C

3High energy efficiency›› Energy recovery of up to 92%, reducing running costs›› Free night-time cooling using fresh outside air›› Higher Efficency EC Fans›› ErP compliant4Up to92%energyrecoveryBest comfort›› Wide range of units to control fresh air for comfort cooling applications›› Wide range of optional filters to suit the application available up to ePM1 80% (F9)›› Special paper heat exchanger recovers heat and moisture from extracted airto warm up and humidify fresh air to comfortable levels (VAM, VKM)›› Aluminum plate heat exchanger, eliminating the risk of cross contaminationbetween air flows (Modular L & Modular P)5Total reliability›› Most extensive testing before new units leave the factory›› Widest support network and after sales service›› All spare parts available in EuropeErPCOMPLIANT 5

Indoor air qualitydecision guideFull fresh AirTempered air -(i.e supplied at room temperature)Heat Recovery Ventilation (HRV)Decentralised systems150 - 200Pa (i.e by floor, medium ESP)VAM-FC9 / VAM-J6VKM-GB(M)MODULAR L (SMART) (ALB)Ventilation with heat recovery asstandardWith DX coil for post-treatedfresh airHigh efficiency counterflow heatexchanger›› 0.04-0.56 m3/s›› @ 90Pa›› 80% Efficiency›› SA: ePMCoarse 50%›› RA: ePMCoarse 50%›› 0.04-0.56 m3/s›› @ 90Pa›› 80% Efficiency›› SA: ePMCoarse 50%›› RA: ePMCoarse 50%›› 0.08-0.75 m3/s›› @ 150Pa›› 90% Efficiency›› SA: ePM1 50%›› RA: ePM10 75%

VentilationAirconditioningwith % Fresh air (i.e. re-circulation)Centralised systems200-400Pa (i.e. plant room,high ESP)MODULAR P (ADT)MODULAR R (ADT)High efficiency aluminiumplate heat exchangerRotary heat exchanger (sorptionand sensible technology)›› 0.41-5.83 m3/s›› @ 250Pa›› 80% Efficiency›› SA: ePMCoarse 60%/ePM1 50%›› RA: ePMCoarse 60%›› 0.5-5.28 m3/s›› @ 250Pa›› 80% Efficiency›› SA: ePM Coarse 60%/ePM1 50%›› RA: ePMCoarse 60%Centralised systems250-500Pa (i.e. plant room, high ESP)AHU by OthersOEM Approach› If DX coil consider Daikinexpansion valve (EXEXV) andcondenser (ERQ/VRV)› If chilled water coil considerDaikin chiller options 2kW to2mW.Rooftop UATYQ›› 1.38-7.2 m3/s›› 19.5-107kW›› @ 300Pa›› SA: ePM Coarse 60%Note:SA - Supply AirRA - Return Air 7

Legislation andstandardsVentilation RatesPart FRoomExtract ratesRooms containing printers and photocopiers in substantial use(greater than 30 minutes per hour)Air extract rate of 20I/s per machine during use. Note that, if the operators are in theroom continuously, use the greater of the extract and whole building ventilation ratesOffice sanitary accomodation and washroomsIntermitent air extract rate of:15I/s per shower/bath6I/s per WC/urinalFood and beverage preparation areas(not commercial kitchens)Intermitent air extract rate of:15I/s with microwave and beverages only30I/s adjacent to the hob with cooker(s)60I/s elsewhere with cooker(s)All to operate while food and beverage preperation is in progressSpecialist buildings/spaces (e.g. commercial kitchens, sports centres)See table 6.3Table 6.1b Whole building ventilation rate for air supply to officesAir supply rateTotal outdoor air supply rate for office(no smoking and no significant pollutant sources)10I/s/personCIBSE - Guide BCIBSE Guide B Section2.3.52.3.24.22.3.88Calculation ExamplesBuilding sectorRecommendationBroadcasting studios6–10 ACHCall centres4–6 ACHCommunal residential building0.5–1 ACH2.3.24.4Darkrooms (photographic)6–8 ACH2.3.24.5Dealing roomsAs offices for ventilation2.3.10Dwellings (inc. high-rise dwellings)0.5–1 ACH2.3.12High-rise (non-domestic) buildings4–6 ACH for office areas up to 10 ACH formeeting spaces2.3.14Hotels10–15 ACH minimum for guest roomswith en-suite bathrooms2.3.16Laboratories6–15 ACH (allowance must be made forfume cupboards)2.3.19Schools and educational buildingsSee Table 2.262.3.20Shops and retail premises5–8 I/s per person2.3.22ToiletsBuilding Regulations apply: mechanicalventilation at 6 I/s per WC or 3 CHminimum for non-domestic buildings3ach on 1m3 volume1m3 x 3ach 3m3/hrOr3m3/hr 3600 0.0008m3/sOr3m3/hr 3.6 0.833l/s1m31mOccupancy (No. of people)16 people at 10l/s/person16people x 10l/s 160l/sOr160l/s 1000 0.16m3/sOr0.16m3/s*3600 576m3/hr

Part L Guidelines (NDBCG)Recommended minimum dry heat recovery efficiency for heat exchangersHeat exchanger typeDry heat recoveryPlate Heat Exchanger50%Thermal Wheel60%Maximum specific fan power in air distribution system in new and existing buildingNew BuildSFP (W/I.s))Existing BuildCentral balance mechanical ventilation with heating and cooling1.62.2Central balance mechanical ventilation withheating only1.51.8All other central balanced mechanical ventilation systems1.11.6Zonal supply and extract ventilation units, such as ceiling or roofunits serving a single room or zone with heating and heat recovery1.91.9Local balanced supply and extract ventilation units, such as ceiling orroof units serving a single area with heating and heat recovery1.61.6Air Distribution System TypeModularP&RVAM/VKMModular LExtending specific fan power for additional components in new and existing buildingsComponentSFP (W/(I.s))Additional return filter for heat recovery 0.1HEPA filter 1.0Heat recovery - Thermal Wheel 0.3Heat recovery - other systems 0.3Humidifier/dehumidifier (airconditioning system) 0.1Note: SFP Specific Fan PowerFiltration StandardEN 779 2012Filter ClassGrossMedFineEN ISO 16890 (July 2018)Coarse 10µmePM100.3 to 10µmePM2,50.3 to 2.5µmePM10.3 to 1µmG1----G230% - 50%---G345% - 65%---G460% - 85%---M580% - 95%40% - 70%10% - 45%5% - 35%M6 90%60% - 80%20% - 50%10% - 40%F7 95%80% - 90%65% - 75%60% - 85%F8 95%90% - 100%75% - 95%60% - 85%F9 95%90% - 100%85% - 95%80% - 90%Note:Classification is based on achieving a min of 50% efficiencyEfficiency value of filter is rounded down to nearest 5% for classification purposes 9

Unit constructionDX COIL MODULEThermal WheelPlate Heat Exchanger›› Reduces unit length›› Low pressure drops›› High sensible efficiency›› 3% carry over (ie: cross contamination)›› Larger unit›› High dry efficiency›› No risk of cross contaminationFeatureSystem TypeControlsDetailVAM/VKMModular L SmartModular L ns MT3STDMixing BoxEC FanDampersFrost CoilFiltersSTDüüSTDSTDOPTOPTSTDSTDSTDSTDExhaust Air TDSTDOPTOPTSTDSTDSTDLPHWPanelSTDBagCross Flow (Paper)Heat RecoveryModular RFresh Air inletElectricSTDModular PPlate (Aluminium)STDThermal WheelCooling CoilHeating CoilAttenuatorsSTDDX Heat Pump Atmosphere SideOPT1OPT1OPTRoom SideOPT1OPT1OPTOPTOPT3OPT3Before Cooling CoilOPTOPTAfter Cooling CoilOPTOPTNotes:1. Optional module, supplied loose for field installation2. 'Factory Special', contact Applied Department3. Includes supply and fitting of Steam Distributor(s) and loose supply of Carel HumiSteam Basic immersed electrode humidifier(s).10OPTChilled WaterHumidifier SectionEmpty SectionOPT

HEAT RECOVERYWHEEL AND FILTERDAMPER AND EC FANAccessory ListMandatoryRecommendedüLifting BracketFlat Roofü1üüüLamp Wired To External SwitchLED Lamp Wired To External SwitchPort HoleRain HoodLouvreü1ü1üFlexible ConnectionüüüCircular SpigotFlexible Connection - VDI ClassNoise Reduction Laminar StraightenerScreen DoorüüMicroswitchFrost Protection Thermostatü2üüüüüü'U' Tube ManometerMinihelic GaugeCO2 SensorRoom ThermostatRemote InterfaceHumidity SensorBACNET ModuleMODBUS ModuleOptionalüSpare Filterü3üNotes:1. For units mounted outdoors2. For units fitted with electric frost coil3. For integration with ITM frontend 11

FSCDaikin Airconditioning UK Limited The Heights Brooklands Weybridge Surrey KT13 0NY Tel 01932 879000 daikin.co.ukUKEPLEN20-1126 / 08.20 / Copyright 2020 DaikinThe present leaflet is drawn up by way of information only and does not constitute an offer binding upon DaikinUK. Daikin UK has compiled the content of this leaflet to the best of its knowledge. No express or implied warrantyis given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the productsand services presented therein. Specifications are subject to change without prior notice. Daikin UK explicitlyrejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin UK.