Form#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1HHR1000UL300A Exhaust HoodsFeatures & BenefitsThe HHR1000 hoods are the first fullyintegrated, pre-engineered fire suppressionrange hood systems introduced to the market.Using many components found in a fullcommercial hood, The HHR1000 hoods fulfillall of the theory and intent behind a Type Icommercial hood with fire suppression, in aproduct designed for use over a residentialgrade appliance. Our hoods incorporate asuppression system that is proven effectiveby using a mechanical system, a wet chemicalagent, hardwired disconnect options and alarmcontacts. They’re easy to install and are an idealoption for any cooking space using a residentialstyle range. HMI touchscreen display Stainless Steel finish Wall mounted Ability to store multiple passwords formultiple users Multiple power disconnect options May be used as a standalone option or inconjunction with our hood systemsApplications Institutional & Limited CommercialInstallations Common Kitchen Areas Colleges & Universities Day Care Centers Schools Elderly Communities Managed CareFacilities Group Homes Churches Fire Houses EMS Facilities Military HousingAny cooking space using a residential stylerange in a not for profit applicationHHR1000UL300A Exhaust Hoods1

Fully Integrated Fire Suppression System Roof & Wall Venting Options 30 Inch Wide or 36 Inch Wide Inline Fan ETL Tested, UL300A & UL507 Compliance Variable Speed Motorized Impeller Options available to meet NFPA101 LifeSafety Code. NFPA101 Compliant Tank Pressure Gauge Optional Sealed Unit - National SanitaryFoundation (NSF) Approved Option High Pitch Audible Buzzer (90 dB) Stages of Pre-Suppression (2) Gas, Electric, DED, DRD Fuel SourceDisconnects NFPA101 Compliance National Sanitation Foundation (NSF) Mechanical “Fail-Safe” Actuation LED Visual Annunciation Fuel Source Disconnect Interlock Plenum Nozzle Low pH Suppressant Agent (Amerex 660) Programmable Logic Controllers (PLC) 304 Stainless Steel Hood Number of Nozzles (4/5***) Optional Manual Pull Station Number of Fusible Links (3) Grease Baffle (NFPA 96 & 17A) Number of Alarm Contacts (3) Optional ADA Switch Compatible withhandicap accesible controls Optional Gloss White FInish* Option of Power Coat Finish in CustomColors Standard Warranty Period (3 Years) ClockBox Compatible Front Recirculating & Rear Ventilation*Upon Request (additional charge)*** HHR1036 4, HHR1030 5The TimerboxThe TIMERBOX helps prevent unauthorizedcooking and reduces the risk of unattendedcooking. It works by disconnecting power to therange until the operator unlocks the system fora pre-set amount of time simply by entering apasscode. In addition to being used as a standalone product, the TIMERBOX can be usedwith the HHR1000 as part of Halton’s NFPA101upgrade and would allow for 120 minutes of useat one time. Whether or not a facility is requiredto monitor the use of the ranges within, theTIMERBOX is an excellent additional source ofprotection.TimerboxTimerbox ProHHR1000UL300A Exhaust Hoods2Form#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1Features

How to Build A Hood System1. Select Model – What core model is required – HHR1030 or HHR10362. Select Fan Type – What type of fan is required – Recirculating, Rear Venting, Ducted or NFPA?3. Select a Disconnect – What type of disconnect is required – Electric (E), Gas (G), or DualElement (DED)?4. Select Options – Do they need an Extended Warranty, Manual Pull Kit, ClockBox or ADA, etc.?HHR10XX-D-RF-G-CLBX-ADA-MPK-EXCore ModelOptional ComponentsHHR1030 30 Inch HHR1000HHR1036 36 Inch HHR1000ADA Handicap Accessible Fan & Light ControlsCLBX TimerboxCLBX Pro Timerbox ProCC Custom Color or FinishEX Extended WarrantyMPK Manual Pull StationNFPA NFPA101 Compliance UpgradeNFPA-PRO NFPA101 Compliance Upgrade withupgrade to Timerbox ProLSC Limiting Speed ControlFBO Fan By OthersMACM Make-Up Air or Damper Control ModuleStrobe Strobe Light & AlarmCFCS Common Fan UseBPFC Control Multiple FansVentilationD Top Vented DuctedF Front RecirculatingR Rear VentedExternal Fan TypeFuel Source DisconnectIF Inline FanRF External Roof Mounted FanWF External Wall Mounted FanHHR1000UL300A Exhaust HoodsE Electric Disconnect †G Solenoid Gas Valve DisconnectDED Dual Element Disconnect †DRD Dual Receptacle Disconnect †† NEMA selection required3Form#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1Product Model Code

HHR1000 StandardHHR1000 NFPA (Option)HHR1030 30 Inch HHR1000HHR1036 36 Inch .HHR1000UL300A Exhaust HoodsIF Inline FanRF External Roof Mounted FanWF External Wall Mounted FanF Front RecirculatingR Rear VentedD Top Vented DuctedHHR1030-F StandardHHR1030-F NFPAHHR1030-R StandardHHR1030-R NFPAHHR1030-D-IF StandardHHR1030-D-IF NFPAHHR1030-D-RF StandardHHR1030-D-RF NFPAHHR1030-D-WF StandardHHR1030-D-WF NFPAHHR1036-F StandardHHR1036-F NFPAHHR1036-R StandardHHR1036-R NFPAHHR1036-D-IF StandardHHR1036-D-IF NFPAHHR1036-D-RF StandardHHR1036-D-RF NFPAHHR1036-D-WF StandardHHR1036-D-WF NFPAForm#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1Product Model CodeWALLMOUNTINGHEIGHT(in)MIN: 24MAX: 30MOUNTINGHEIGHT(in)MIN: 30MAX: 8.856.878.810.556.819.38(B)DEPTH(in)19.38

Submittalsis reached, the tension on the actuator paddlereleases pushing down on the actuator of thesuppression tank; expelling the wet chemicalagent from the pre-charged tank, a signal is sentto shut OFF power to the range and a local and(when connected) building fire alarm will beactivated.Submit product data and shop drawings on packagedexhaust hood.General Hood system shall be installed as 300A compliant NFPA 101 compliance is an available option on theHalton HHR1000. The hood shall be operating at a minimum of 500CFM when NFPA101 compliant.Tank pressure shall be monitored using tankpressure switch and a fault will cause the systemalarm to beep and the LED status light willsimultaneously flash 4 times.All fire suppression and control components mustbe easily accessible by dropping the hood intoa service position to allow for service withoutremoving the hood from the wall. Thumb screwsshall be utilized to hold the hood into place fornormal operation. No latches are acceptable.Standards of ConstructionA. Hood shall be constructed of 18 gauge minimum,300 Series stainless steel outer shell. Hoodshall be either 30 in. long (to cover 30 in. range)or 36 in. long (to cover 36 in.range). Hood shellshall be manufactured and assembled with novisible outer welds or weld marks. All internalseams shall be sealed with NSF-approved caulk,standard. A metal baffle filter shall be provided.One (1) 60W Incandescent Shatterproof orequivalent LED hood light shall provide lighting onthe range below.D. Hood system shall include either an electric orgas shut off device that shall be field connecteddirectly to the hood via factory-provided plug andplay cables. Prior to fire suppression release, theshut off device shall be responsible for disablingthe range upon detecting a high temperature.Gas disconnect (if provided) shall include a 3/4in. gas valve supplied with plug and play cable,and a 120VAC control receptacle is available uponrequest. Other electric disconnect receptacletypes are also available upon request.B. Kitchen ventilation hood shall be recirculatingor exhaust only, and cover a domestic rangein commercial environments used for lightduty cooking purposes only. The hood shall beICC evaluated and certified as compliant withInternational Mechanical Code (IMC), InternationalFire Code (IFC), and Uniform Mechanical Code(UMC). If provided with a fan, the fan shall be UL507 listed or equivalent. Hood fire suppressionshall be listed by ETL to the standards of the ULSubject 300A. Hood shall be configured as wallstyle (supplied with wall mounting bracket).E. Hood system with NFPA 101 compliance, mustinclude: a minimum of 500 CFM fan, locked(password protected) appliance disconnect withtimed-automatic range deactivation, and manualpull station.1.C. Hood shall include factory-installed UL Subject300A fire suppression system, includingenvironmental monitoring, wire rope, failsafe fusible links, and mechanical actuation.No electronic detection or actuation shall beaccepted. Fire suppression shall be a fail-safemethod and consist of three fusible links (212 for 30”, 280 for 36”), temperature switches thatmonitor the cooking surface and upon reachingthe first set-point, send a signal to turn the fanON, at the second set point sends a signal tomaintain the fan ON, while also sending a signalto shut OFF power to the range and sounding alocal alarm. When the set point of the fusible linksHHR1000UL300A Exhaust HoodsPull station shall be a mechanical pullstation. Electronic pull station is notacceptable.2. Password protected access will be mountedremotely. Hood mounted password accessis not acceptable.F.5User controls shall be provided to control fan,and lights. A hood mounted touchscreen is notacceptable. The status LED and audible alarmmay be used to determine any faults within thesystem. All hood controls must be accessed byswitches and potentiometers on the hood itselfunless supplied with an ADA Switch with factoryprovided plug and play cable or controlled inconjunction with a touchscreen that is mountedremotely.Form#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1Specification

Form#: SS205 HHR1000-UL300A Exhaust HoodDate: 03-2021 - Rev1G. The hood system shall be configured with eithera factory-supplied integral fan, factory-suppliedexternal fan, or fan by others. Integral fan optionsinclude either front recirculating or rear discharge.Front recirculating style shall include an easilyaccessible charcoal filter and opening in the frontof the hood for filtering the exhaust air beforedischarging back into the space. Rear dischargeshall direct the air to exit the back of the hood, todischarge through a wall to the outside. Externalfan options include either a factory-providedinline fan (with plug and play cable), wall mountfan, roof fan or fan by others option with a topdischarge hood configuration. Top dischargeshall direct the air to exit the top of the hood, todischarge through a roof or wall to the outside.All factory provided fan options shall be listed toUL507 standards.H. Dry contacts are provided standard for integrationto building alarm systems.I.Check, Test and Balance:1.The kitchen exhaust system shall beinspected, tested and balanced by a qualifiedcontractor. The contractor shall ensureproper and satisfactory operation of thekitchen exhaust system and shall provide awritten and detailed report of this check, testand startup to the Engineer and Owner.ExecutionThe entire packaged kitchen exhaust hood shallbe installed by qualified contractors meeting anylicensing criteria in the jurisdiction they are installing.The company has a policy of continuous product development,For more information, please contact your nearest Haltontherefore we reserve the right to modify design andagency. To find it: www.halton.comspecifications without notice.6HHR1000UL300A Exhaust HoodsHalton Company101 Industrial DriveScottsville, KY 42164 USATel: 270-237-5600 Fax: 270-237-5700Halton Indoor Climate Systems1021 Brevik PlaceMississauga, ON L4W 3R7, CanadaTel: 905-624-0301 Fax: 905-624-5547

integrated, pre-engineered fire suppression range hood systems introduced to the market. Using many components found in a full commercial hood, The HHR1000 hoods fulfill all of the theory and intent behind a Type I commercial hood with fire suppression, in a product designed for use over a residential grade appliance. Our hoods incorporate a