Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerRosemount Flow Computer “EZ Setup”- Guided Setup for First TimeUsers Liquid, Gas, Steam, Mass Flow, Heat Flow,and Corrected Volume Equations NX19 Gas Equations, Stacked DPTransmitters Isolated Pulse and Analog Outputs Standard RS-232 Port Standard, RS-485 OptionalWindows Setup Software Internal Data Logging Remote Metering by Modem Available Wall Mount Enclosures Available Applications-Utility Metering / Billing-Compensated Mass Flow-Energy Mass BalanceContentIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7www.rosemount.com

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerExpand the Capability of Flow Measurement TechnologyExpand CapabilitiesSteam Mass FlowThe Rosemount Flow Computer satisfies theinstrument requirements for a variety of flowmetertypes in liquid, gas, steam and heat applications.Multiple flow equations are available in a singleinstrument with many advanced features.Flow ComputerEasy To UseThe alphanumeric display offers measuredparameters in an easy to understand format. Manualaccess to measurements and display scrolling issupported.VersatileFlowmeterThe versatility of the Flow Computer permits a widemeasure of capabilities within the instrumentpackage. The various hardware inputs and outputscan be “soft” assigned to meet a variety of commonapplication needs. The user “soft selects” the usageof each input/output while configuring the erSteam Net HeatFlow ComputerWaterAdaptabilityThe isolated analog output can be chosen to followthe volume flow, corrected volume flow, mass flow,heat flow, temperature, pressure, or density bymeans of a menu selection. Most hardware featuresare assignable by this method.SteamFlowThe user can assign the standard RS-232 Serial Portfor external data logging, transaction printing, or forconnection to a modem for remote meter reading.Simplified VerificationA Service or Test mode is provided to assist the userduring start-up system check out by monitoringinputs and exercising outputs. The system setup canalso be printed.FlowmeterPressureTemperatureTransmitter TransmitterLiquid Delta HeatT2TemperatureTransmitterWarmFlow tter

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerSPECIFICATIONSEnvironmentalCurrent Loop BrokenOperating Temperature: -4 to 131 FCalibration: Operator assisted learn modeStorage Temperature: -40 to 85 C (-40 to 185 F)Extended calibration: Learns Zero and Full Scale of each rangeHumidity: 0-95% Non-condensingFault Protection:Materials: UL, CSA, VDE approvedFast Transient: 500 V Protection (capacitive clamp)Reverse Polarity: No ill effectsDisplayOver-Voltage Limit: 50 VDC Over voltage protectionType: 2 lines of 20 charactersOver-Current Protection: Internally current limited protected to24VDCTypes: Backlit LCDCharacter Size: 0.3” nominalUser selectable label descriptors and units of measurePulse Inputs:Number of Flow Inputs: oneKeypadInput Impedance: 10 k Ohms nominalKeypad Type: Membrane KeypadTrigger Level: (menu selectable)Keypad Rating: Sealed to NEMA 4High Level InputNumber of keys: 16Logic On: 2.5 to 30 VDCLogic Off: 0 to 2 VDCEnclosureEnclosure Options: Panel, Wall Mount NEMA 4, Wall Mount NEMA12/13Size: See Dimensional Drawings on page 8Depth behind panel: 6.5” including mating connectorType: DINLow Level Input (mag pickup)Selectable sensitivity: 10 mV and 100 mVMinimum Count Speed: 0.25 Hz (to maintain rate display)Maximum Count Speed: Selectable: 0 to 50 kHzOvervoltage Protection: 50 VDCMaterials: Plastic, UL94V-0, Flame retardantTemperature, Pressure, Density InputsBezel: Textured per matte finishThe compensation inputs usage are menu selectable fortemperature, temperature ( temp) 2, pressure, density, or notused.Power InputThe factory equipped power option is internally fused. An internalline to line filter capacitor is provided for added transientsuppression. MOV protection for surge transient is also supported.Universal AC Power: 85 to 276 Vrms, 50/60 HzDC Power Option: 24 VDC (16 to 48 VDC)Power ConsumptionAC Power: 6.5 V/A (6.5W)DC Power: 300 mA max.Flow Meter Types:Linear: Vortex, Turbine, Positive Displacement, Magnetic andothersSquare Law: Orifice, Venturi, Nozzle, Wedge, Averaging Pitot,Target and othersMulti-Point Linearization: May be used with all flowmeter types.Including: 16 point, dynamic compensationCalibration: Operator assisted learn modeOperation: RatiometricAccuracy: 0.02% FS at 20 CBasic Measurement Resolution: 16 bitUpdate Rate: 2 updates/sec minimumAutomatic Fault detection:Signal Over-range/under-rangeCurrent Loop BrokenRTD shortRTD openReverse Polarity: No ill effectsOver-Current Limit (current input) Internally limited to protectinput to 24 VDCAvailable Input RangesCurrent: 4-20 mA, 0-20 mAResistance: 100 Ohms DIN RTD100 Ohm DIN RTD (DIN 43-760, BS 1904):Flow Inputs:Analog Input:Accuracy: 0.02% FS at 20 CRangesVoltage: 0-10 VDC, 0-5 VDC, 1-5 VDCCurrent: 4-20 mA, 0-20 mA,4-20 mA stacked, 0-20 mA stackedBasic Measurement Resolution: 16 bitUpdate Rate: 4 updates/secAutomatic Fault detection: Signal over/under range,Three Wire Lead CompensationInternal RTD linearization learns ice point resistance1 mA Excitation current with reverse polarity protectionTemperature Resolution: 0.1 CTemperature Accuracy: 0.25 CStored Information (ROM)Steam Tables (saturated & superheated),Fluid Properties: Water, Air, Natural Gas, A Variety of UserEntered Industrial Fluids or Generic User Entry3

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerUser Entered Stored Information(EEPROM /Nonvolatile RAM)Transmitter Ranges, Signal TypesFluid Properties(reference density, expansion factor, specific heat, viscosity,isentropic exponent, combustion heating value, Z factor)Units Selections (English/Metric)Excitation Voltage24 VDC @ 100 mA (fault protected with self resetting fuse)Data LoggingThe data logger captures print list information to internal storagefor approximately 5000 transactions. This information can be usedfor later uploading or printing. Storage format is selectable forComma-Carriage Return or Printer formats.Isolated Pulse outputThe isolated pulse output is menu assignable to UncompensatedVolume Total, Compensated Volume Total, Heat Total or MassTotal.Pulse Output Form (menu selectable): Open CollectorRelay OutputsNPN or 24 VDC voltage pulseThe relay outputs usage is menu assignable to (Individually foreach relay) Hi/Lo Rate Alarm, Hi/Lo Temperature Alarm, Hi/LoPressure Alarm, Pulse Output (pulse options), Wet Steam orGeneral purpose warning (security).Nominal On Voltage: 24 VDCNumber of relays: 2 (3 optional)Saturation Voltage: 0.4 VDCContact Style: Form C contacts (Form A with 3 Relay option)Pulse Duration: User selectableContact Ratings: 240 V, 5 ampPulse output buffer: 8 bitAnalog OutputsThe analog outputs are menu assignable to correspond to theUncompensated Volume Rate, Corrected Volume Rate, MassRate, Heat Rate, Temperature, Density, or Pressure.Number of Outputs: 2Type: Isolated Current Sourcing (shared common)Available Ranges: 0-20 mA, 4-20 mA (menu selectable)Resolution: 16 bitAccuracy: 0.05% FS at 20 CUpdate Rate: 5 updates/secTemperature Drift: Less than 200 ppm/ CMaximum Load: 1000 ohmsCompliance Effect: Less than .05% Span60 Hz rejection: 40 dB minimumEMI: No effect at 3 V/MCalibration: Operator assisted Learn ModeAveraging: User entry of DSP Averaging constant to cause asmooth control actionListing: CE Compliant, UL/C-UL PendingSerial CommunicationThe serial port can be used for printing, datalogging, modemconnection, two way paging and communication with a computer.RS-232:Device ID: 01-99Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200Parity: None, Odd, EvenHandshaking: None, Software, HardwarePrint Setup: Configurable print list and formattingRS-485: (optional 2nd COM port)Device ID: 01-247Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200Parity: None, Odd, EvenProtocol: Modbus RTU (Half Duplex)4Maximum Sink Current: 25 mAMaximum Source Current: 25 mAMaximum Off Voltage: 30 VDCFault ProtectionReverse polarity: Shunt DiodesOver-current ProtectedOver-voltage ProtectedReal Time ClockThe Flow Computer is equipped with a nonvolatile real time clockwith display of time and date.Format:24 hour format for timeDay, Month, Year for date

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerDIMENSIONAL DRAWINGSFIGURE 1. Panel Mount DimensionsFIGURE 3. Wall Mount (NEMA 12/13) Dimensions5.67 (144)9.4 (238)RATE147.43 GPMTOTAL 267395.749 GAL2.83(72)6.18 (157)7.3 (184)RATE147.43 GPMTOTAL 267395.749 9PRINT5TIME0–CLEARMENUHELP ENTERSecurityTagProvisions0.385(9.8)8.4 (213)Dotted Line Shows Optional Bezel Kit0.59(9.8)0.5(13)6.15 (156)0.28 (7.2)0.625-in. 0.75-in. 5 places4.72 (120)3.43(87)4.13 (105)2.33 (59)0.75-in. ConduitKnockouts (5 Places)1.06 1.10 1.10 1.10 1.10(27) (28) (28) (28) (28)1.10 1.10 1.10 1.10(28) (28) (28) (28)0.4 (10)7.8 (198)5.43 (138)FIGURE 4. Standard Terminal Layout2.68(68)PanelCutoutRS-232RS-485Phone1 2 3 41 25 4 3 2 19 8 7 6FIGURE 2. Terminal Designations12345678910111213141516DC OUTPUTPRESSURERTD EXCIT ( )(TEMP 2)RTD SENS ( )INIin ( )RTD SENS (-)PULSE OUTPUT ( )PULSE OUTPUT (-)ANALOG OUTPUT 1 ( )ANALOG OUTPUT 2 ( )ANALOG OUTPUT COMMON (-)171819202122NOCOM RLY1NCNCCOM RLY2NODC OUTPUTPULSE IN---------COMMONRTD EXCIT ( )RTD SENS ( )RTD SENS (-)23 AC LINE24 AC LINEVin ( )Iin ( )1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24FLOWINTEMPERATUREINIin ( )FIGURE 5. RS-232 DB-9 Pinout5 4 3 2 19 8 7 61. Handshake Line (cd in)2. Transmit (tx)3. Receive (rx)4. Do Not Use5. Ground6. Do Not Use7. RTS Out8. Do Not Use9. DC Power Out*DC ( )DC (-)POWER IN*8 VDC Power supplied on Pin 9 to power modem5

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerFIGURE 6. Wall Mount (NEMA 4) Dimensions11.85 (301)(4) Each #10-32 Brass Inserts &Plated Carbon Steel Screws1.75 (44)ABB13.73(349)5.35 (136)6.00 (152)6.75 (171)7.21 (183)A(4) .34 dia.(8.74)8.31 (211)9.01 (229)BACK VIEWSECTION A-A11.20 (285)9.85 (250)Closed Cell Neoprene GasketS. St’L. Hinge(2) S. St’L. Lockable SnapLatch & Keeper PlateHinged Front Panelshown Alum. - .09 Th’k(4) S. St’L.Mounting Feet13.08 11.72(332) (298)11.50(292)(4) Each #10-32 Brass Inserts &Plated Carbon Steel ScrewsSECTION B-B9.5 (241).47 (11.9) TYPFRONT VIEW WITH LID REMOVEDFIGURE 7. NEMA 12/13 Terminal DesignationsRATE147.43 GPMTOTAL 267395.749 GALTOTAL1RATE2PRE 13TEMP4GRAND6SCROLL7PRE 6DC OUTPUTPULSE IN---------COMMONRTD EXCIT ( )RTD SENS ( )RTD SENS (-)Vin ( )*Iin ( )FLOWINTEMPERATUREINIin ( )DC OUTPUTPRESSURERTD EXCIT ( )(TEMP 2)RTD SENS ( )INIin ( )RTD SENS (-)PULSE OUTPUT ( )PULSE OUTPUT (-)ANALOG OUTPUT 1 ( )ANALOG OUTPUT 2 ( )ANALOG OUTPUT COMMON (-)NO RLY1COM RLY1NC RLY1NC RLY2COM RLY2NO RLY2AC LINEAC LINE171819202122DC ( )DC (-)NO RLY1COM RLY1NO RLY2COM RLY2NO RLY3COM RLY3POWER IN3 Relay NUHELP ENTERRS-485 Phone681234129 10 11 12 13 14 15 1617 18 19 20 21 22 23 24

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerORDERING INFORMATION Available- Not AvailableRosemount Part NumberDescriptionPanelNEMA 408800-0800-xxxxFlow Computer NEMA 12/13 13AC (85 to 275 V)DC (24 V) 01NoneRS-485 012PanelNEMA 4 Wall MountNEMA 12/13 Wall Mount - - 012No Additional Option(1)3 RelaysInternal Modem(2) Input Type (Power Supply)Network CardMountingOptionsTypical Part Number: 08800-0800-1000(1) Note: Peak Demand, AGA NX 19, Stacked DP, Data Logging, Manifold Flowmeter Control, Modem Power, and Extended Temp Display are Standard.(2) Note: Internal Modem cannot be ordered in combination with RS-485 Card for NEMA 12/13 Mounting.7

Product Data Sheet00813-0100-4005, Rev BAOctober 2009Rosemount Flow ComputerStandard Terms and Conditions of Sale can be found at www.rosemount.com/terms of saleThe Emerson logo is a trade mark and service mark of Emerson Electric Co.Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.All other marks are the property of their respective owners. 2009 Rosemount, Inc. All rights reserved.Emerson ProcessManagementRosemount Measurement8200 Market BoulevardChanhassen, MN 55317 USAT (U.S.) 1-800-999-9307T (International) (952) 906-8888F (952) 949-700100813-0100-4005 Rev BA, 10/09Emerson Process Management FlowNeonstraat 16718 WX EdeThe NetherlandsT 31 (0)318 495555F 31 (0)318 495556Emerson Process ManagementAsia Pacific Private Limited1 Pandan CrescentSingapore 128461T (65) 6777 8211F (65) 6777 0947Enquiries@AP.EmersonProcess.com

Handshaking: None, Software, Hardware Print Setup: Configurable print list and formatting RS-485: (optional 2nd COM port) Device ID: 01-247 Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200 Parity: None, Odd, Even Protocol: Modbus RTU (Half Duplex) Data Logging The data logger captures print list information to internal storage