catalog C-BLzM-0710a h e a d o f t h e f lo w CPVC BlazeMasterFire Protection Fittings

www.nibco.comAHEADOF THE FLOW Revised 6/9/20107/1/2010CPVC Threaded Fire Protection FittingsAdapters .15-16Crosses . 17Elbows . 17Tees . 18Test Plugs . 19CPVC Transition FittingsIPS to CTS Transition Fittings. 19BlazeMaster is a registered trademark of The Lubrizol Corporation.14NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.com

www.nibco.comAHEADOF THE FLOW Revised 6/9/20107/1/2010BlazeMaster Fire Protection Fittings – THREADEDADAPTERS5003-BIFemale Adapters with Metal Thread InsertUNIV.FIG. ROX.NET WT./LBS.0.280.631.021.261.98DIM. SXFNPTSXFNPTSpigot Female Adapters with Metal Thread InsertUNIV.FIG. 1/2"2"NOM.SIZE3/4"1"APPROX.NET WT./LBS.0.280.61DIM. AINCHES2.002.72JOINTSPGXFNPTSPGXFNPTMale Adapters with Metal Thread InsertUNIV.FIG. 1"1-1/4"1-1/2"2"APPROX.NET WT./LBS.0.220.460.741.061.80DIM. SxMNPTSxMNPTBlazeMaster is a registered trademark of The Lubrizol Corporation.NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.com15

www.nibco.comAHEADOF THE FLOW RevisedRevised9/22/20107/1/2010BlazeMaster Fire Protection Fittings – THREADEDADAPTERS5003-S-BIFemale Sprinkler Head Adapterswith Metal Thread InsertUNIV.FIG. T WT./LBS.0.160.180.18DIM. 2"3/4"x1/2"APPROX.NET WT./LBS.0.160.15DIM. AINCHES1.841.53JOINTSPGXFNPTSPGXFNPTBRASTIC Female Sprinkler Head Adapterswith Metal Starter ThreadUNIV.FIG. NO.5003-S-BT5003-S-BTNOM.SIZE1" x 1/2"3/4" x 1/2"APPROX.NET WT./LBS.0.170.15DIM. AINCHES.75.75BlazeMaster is a registered trademark of The Lubrizol Corporation.16JOINTSpigot Female Sprinkler Head Adapterswith Metal Thread InsertUNIV.FIG. "1"x1/2"1"x3/4"NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.comJOINTS x FNPTS x FNPT

www.nibco.comAHEADOF THE FLOW RevisedRevised6/17/20107/1/2010BlazeMaster Fire Protection Fittings – THREADEDCROSSES5035-3-S-BI-S5035-3-S-BI-LSprinkler Head Back To Back Crosseswith Metal Thread InsertsUNIV.FIG. NO.NOM.SIZEAPPROX.DIM. ANET WT./LBS. INCHESDIM. BINCHESDIM. CINCHESDIM. DINCHESJOINT5035-3-S-BI-S 1x1"x1/2"x1/2"3-3/8" Take Out0.461.691.690.620.62SXSXFNPTXFNPT5035-3-S-BI-L 1x1"x1/2"x1/2"3-5/8" Take -BISprinkler Head 90 with Metal Thread InsertUNIV.FIG. .SIZE3/4"x1/2"1"x1/2"1"x3/4"1-1/4"x1/2"APPROX.NET WT./LBS.0.220.270.260.30DIM. AINCHES0.560.500.590.48DIM. PTBlazeMaster is a registered trademark of The Lubrizol Corporation.NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.com17

www.nibco.comAHEADOFTHEFLOW Revised 6/9/2010BlazeMaster Fire Protection Fittings – I5012R-S-BI5014R-S-BIBack To Back Tees with Metal Thread InsertsUNIV.FIG. NO.NOM.SIZEAPPROX.DIM. ANET WT./LBS. INCHES5011-3-3-S-BI-S1/2”x1/2"x1"3-3/8" Take Out0.445011-3-3-S-BI-L1/2"x1/2"x1"3-5/8" Take Out0.46DIM. BINCHESDIM. FNPTXSSprinkler Head Tees with Metal Thread InsertUNIV.FIG. .APPROX.DIM. ASIZENET WT./LBS. /2"x1/2"0.580.48DIM. SXSXFNPTSXSXFNPTSXSXFNPTSXSXFNPTSprinkler Head Tees with Metal Thread InsertUNIV.FIG. NO.5014R-S-BINOM.SIZE1"x1/2"x1"APPROX.NET WT./LBS.0.30DIM. AINCHES0.71DIM. BINCHES1.74BlazeMaster is a registered trademark of The Lubrizol Corporation.18DIM. CO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.comDIM. CINCHES1.90JOINTSXFNPTXS

www.nibco.comAHEADOF THE FLOW RevisedRevised9/22/20105/7/2010Review – Do's & Don'tsDo’sDon’ts Installation should be made only by a qualified installeror contractor in accordance with all applicable codes andrequirements. Do not use edible oils as a gasket lubricant. Read and follow the installation instructions. Do not use any glycol-based solutions as an anti-freeze. Follow recommended safe work practices. Do not contaminate the CPVC system with cutting oils orcompressor oils. Make certain that thread sealants, gasket lubricants, or firestopmaterials are compatible with CPVC. Keep pipe and fittings in original packaging until needed. Cover pipe and fittings with an opaque tarp if stored outdoors. Follow proper handling procedures. Do not use petroleum or solvent-based sealants, lubricants, orfire stop materials. Do not mix glycerin and water solutions in contaminatedcontainers. Do not use solvent cement that exceeds its shelf life or hasbecome discolored or jellied. Use tools specifically designed for use with plastic pipe andfittings. Do not allow solvent cement to plug the sprinkler head orifice. Use the proper solvent cement and follow applicationinstructions. Do not thread or groove CPVC pipe. Do not connect rigid metal couplers to CPVC grooved adapters. Use a drop cloth to protect interior finishes. Do not use solvent cement near sources of heat, open flame, orwhen smoking. Cut the pipe ends square. Do not pressure test with air. Deburr and bevel the pipe end with a chamfering tool. Do not pressure test until recommended cure times are met. Rotate the pipe 1/4 turn when bottoming pipe in fitting socket. Do not exceed proper pressure for testing. Make certain no solvent cement is on sprinkler head andadapter threads. Do not use ratchet cutters below 50 F. Make certain that solvent cement does not run and plug thesprinkler head orifice. Do not use CPVC pipe that has been stored outdoors,unprotected and is faded in color. Do not allow threaded rod to come in contact with the pipe. Follow the manufacturer’s recommended cure times prior topressure testing. Do not install NIBCO BlazeMaster CPVC Fire SprinklerProducts in cold weather without allowing for expansion. Fill lines slowly and only at a proper pressure. Do not install NIBCO BlazeMaster CPVC Fire SprinklerProducts in dry systems. Bleed the air from the system prior to pressure testing. Support sprinkler head properly to prevent lift up of the headthrough the ceiling when activated. Do not allow puddling of cement in fittings and pipe. Do not use dull or broken cutting tool blades when cutting pipe. Keep threaded rod within 1/16” of the pipe or use a surgearrestor. Install NIBCO BlazeMaster CPVC Fire Sprinkler Products inwet systems only. Use only insulation and/or glycerin and water solutions forfreeze protection. Allow for movement due to expansion and contraction. Ensure installers have been properly trained per the NIBCOBlazeMaster CPVC Fire Sprinkler System Installation andDesign Manual and renew your training every three years at aminimum.BlazeMaster is a registered trademark of The Lubrizol Corporation.NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.com25

www.nibco.comAHEADOF THE FLOW RevisedRevised10/1/20095/7/2010NIBCO LIMITED WARRANTYApplicable to NIBCO INC. CPVC FIRE PROTECTION Plastic FittingsNIBCO INC. warrants each NIBCO BlazeMaster Fire Protection CPVC plastic fitting to be free from defects in materials andworkmanship under normal use and service for a period of ten (10) years from the date of purchase.In the event any defect occurs which the owner believes is covered by this Warranty, the owner should immediately contact NIBCOINC., Technical Services, either in writing or by telephone call, (888) 446-4226 or (574) 295-3000. The owner will be instructed toreturn said fitting or valve, at the owner’s expense, to NIBCO INC. or an authorized NIBCO INC. representative for inspection. In theevent said inspection discloses to NIBCO INC.’s satisfaction that said fitting or valve is defective, a replacement shall be mailed freeof charge to the owner, and NIBCO INC. shall further pay the installing contractor the sum of ten ( 10.00) dollars to apply on the costof installation of said replacement fitting.TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY SPECIFICALLY EXCLUDES INCIDENTAL AND CONSEQUENTIALDAMAGES OF EVERY TYPE AND DESCRIPTION RESULTING FROM ANY CLAIMED DEFECT IN MATERIAL ORWORKMANSHIP, INCLUDING BUT NOT LIMITED TO, PERSONAL INJURIES AND PROPERTY DAMAGES. Some statesdo not allow the exclusion or limitations of incidental or consequential damages, so these limitations may not apply to you. ToTHE EXTENT PERMITTED BY LAW, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULARPURPOSE ARE LIMITED IN DURATION.This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.NIBCO INC. World Headquarters 1516 Middlebury St. Elkhart, IN 46516-4740 USA www.nibco.comhow to orderNIBCO sells its products through select stockingdistributors. Our distributors are knowledgeable aboutplastics fittings as well as the complete line of NIBCO FireProtection Systems.Please visit www.nibco.com for a complete listing ofauthorized NIBCO distributors in your area.NIBCO INC. Customer ServiceWorld Headquarters1516 Middlebury StreetP.O. Box 1167Elkhart, IN 46515-1167USAPhone: 800.234.0227Fax:800.234.0557To the best of our knowledge the information contained in this publication is accurate. However, NIBCO does not assume any liability whatsoever forthe accuracy or completeness of such information. Final determinations of the suitability of any information or product for the use to be contemplated isthe sole responsibility of the user. The manner of that use, and whether there is any infringement of patents, is also the sole responsibility of the user.30NIBCO INC. WORLD HEADQUARTERS 1516 MIDDLEBURY ST. ELKHART, IN 46516-4740 USA PH: 1.800.234.0227TECH SERVICES PH: 1.888.446.4226 FAX: 1.888.336.4226 INTERNATIONAL OFFICE PH: 1/574.295.3327 FAX: 1/574.295.3455www.nibco.com

Do not use CPVC pipe that has been stored outdoors, unprotected and is faded in color. Do not allow threaded rod to come in contact with the pipe. Do not install NIBCO BlazeMaster CPVC Fire Sprinkler Products in cold weather without allowing for expansion. Do not install NIBCO BlazeMaster CPVC Fire Sprinkler Products in dry .